This document is an existing conditions summary and architectural assessment of the St. Clair County Health Department facility, comprising a main building and two annex buildings. The comprehensive report details the architectural, mechanical, electrical, plumbing, and accessibility characteristics of the entire facility, including the main building, North Annex, and South Annex (WIC Suite). The analysis evaluates the buildings' structural integrity, mechanical systems, electrical infrastructure, and compliance with Americans with Disabilities Act (ADA) standards, noting that the facilities have been generally maintained over the years with periodic updates.
The report highlights several critical findings, including potential asbestos in insulation and floor tiles, aging mechanical and electrical systems nearing the end of their expected life cycles, and significant accessibility limitations. Mechanical systems like HVAC units are approximately 15-20 years old, with multizone rooftop units in the main building and different heating systems in the annexes. Plumbing and electrical systems show signs of wear, with some components exceeding their typical life expectancy. The buildings have multiple accessibility challenges, including restricted circulation between buildings and levels, non-compliant restrooms, and outdated door hardware. The report recommends testing for asbestos, updating mechanical and electrical systems, and making comprehensive accessibility improvements to meet current ADA guidelines.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| HD - Exhibit A.pdf | ||
| RFP-AD-1025-603.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4-24
4. EXISTING CONDITIONS SUMMARY
The existing St. Clair County Health Department, and two annex buildings are detailed in the following existing conditions summary. The split-level main building, and attached annexes are described and analyzed for architectural and engineering integrity, as well as aspects of accessibility, Americans with Disabilities Act (ADA) and life safety.
The main building and annexes have generally been maintained over the years, with architectural and engineering updates performed as needed to keep the building serviceable. The following report will detail some needed architectural finish upgrades, ongoing maintenance issues, and some older mechanical and electrical systems in need of various upgrades. It also identifies some instances of environmental concerns related to possible asbestos composition in insulation, pipe wrap and floor tiles, with testing recommended to confirm materiality.
Accessibility is another existing building condition that is detailed in the report, noting that public and staff circulation between buildings and levels is somewhat restricted.
Going in and out of buildings is required to maintain an accessible route. The majority of the toilet rooms in the main building and the annexes are not accessible and cannot accommodate wheelchairs. All of these restrooms will be noted as needing updates to meet ADA, when any renovations would be performed in the future. Some door hardware will also need updates to meet current ADA guidelines.
Existing original construction drawings were available for review and no destructive testing or investigations were undertaken.
The following analysis is broken down by discipline, and details the Site, Main Building, North Annex, and South Annex.
Civil/Site:
Drives and Parking:
o 172 standard parking spaces.
o 9 accessible parking spaces with none specifically designated as Van-accessible spaces.
o Drives, parking areas appear to be in serviceable condition.
Sidewalks:
o An accessible concrete ramp connects the closest accessible parking with the public entrance.
o A sidewalk that once connected the S Annex entry from 28th Street has been modified to provide access to a recently installed storage shed and the original entry has been removed and new siding has been installed however the eave canopy and concrete stoop remain.
4-25 o The accessible concrete sidewalk connects to the egress door from the North Annex and is in relatively good condition on the North side of the North Annex
Landscaping:
o Turf grass throughout the site appears healthy, o Shrubs along the East side of the South Annex also appear healthy o As the site walkthrough took place during the late winter season, the condition of the existing planting beds is unknown, but the raised concrete planting beds with at grade drainage look to be in good condition.
Architectural:
Exterior:
Main Building:
The exterior walls of the main building appear to be constructed as follows:
o Masonry load-bearing with concrete masonry units on the inner wythe and face brick veneer on the majority of the exterior.
o The extent of cavity insulation is documented as 2� rigid insulation.
o The finished face at the staff and public entrance of the west side of the main building appears to consist of painted cement board paneling.
o Both exterior finishes generally appear to be in relatively good condition.
Windows appear to consist of the following:
o Non-operable aluminum frame (thermal break undeterminable).
o Single pane glazing and no detectable low-e or reflective coatings
Existing exterior doors consist of the following:
o Painted hollow metal frames.
o Painted hollow metal doors.
o Doors and frames generally appear to be in poor condition.
The roof is a ballasted built-up membrane system over 2� rigid insulation over 1-1/2� metal deck on steel joists, according to existing drawings.
o Though partially snow-covered during inspection, it appears in relatively good condition for its age (approximately 20 years).
o Metal flashings at parapet walls are in generally good condition with the exception of missing some caulking in places. (See photo below) o The membrane flashings underneath the metal are showing signs of age with visible cracking in the material. (See photo below) o The caulking around various roof penetrations has deteriorated, with staining on interior ceiling tiles showing signs of the leaks (see photo below).
Expansion joints between the three building segments appear weathertight, with no reported leaks to the interior.
North Annex:
The exterior walls consist of the following:
4-26 o Prefabricated metal building with metal/vinyl siding system with interior finish consisting of vinyl wall panels o The wall system generally appears to be in good condition.
The extent of cavity insulation is unknown.
Windows appear to consist of the following:
o Non-operable aluminum frame (thermal break undeterminable).
o Single pane glazing and no detectable low-e or reflective coatings.
Existing exterior doors consist of the following;
o Painted hollow metal frames.
o Painted hollow metal doors.
o Doors and frames appear to generally be in good condition.
Gutters appear to be in working order and relatively good condition.
The roof consists of prefabricated metal roof panels which appear to be in good condition.
The flat roofed connector to the Main Building reportedly had a leak at the Main Building face that has since been corrected.
South Annex (WIC Suite):
The South Annex appears to be constructed as follows:
o Masonry load bearing CMU on the inner with a wainscoting of face brick with vertical vinyl siding above on the East elevation.
o Full height vinyl siding on the remaining elevations.
o The South wall of the South Annex is missing a small portion of the vinyl siding (See photos below) o The general condition of the siding is poor.
The extent of cavity insulation is unknown.
Windows appear to consist of the following:
o Single hung dark bronze anodized aluminum frames (thermal break undeterminable).
o Single pane glazing with no detectable low-e or reflective coatings.
Existing exterior doors consist of painted hollow metal doors in painted hollow metal frames in good condition.
The roof appears to consist of a ballasted built-up membrane roof.
o Though snow-covered during the inspection, the roof�s condition is assumed to be in relatively good condition for its age as staff and maintenance have not complained of leaks or other issues.
Interior:
Main Building:
Flooring throughout the building consists mainly as follows:
o Commercial carpet tile.
o Carpet is generally in good condition with minimal wear most commonly in areas of high traffic.
Limited areas of the building have the following flooring:
o Vinyl Composite Tile flooring.
4-27 o Tile generally appears to be in good condition.
Still other areas contain what looks to be 9x9 vinyl floor tile.
o Tile generally appears to be in good condition.
o Tile is suspected to likely contain asbestos.
The toilet facilities consist of the following flooring:
o Ceramic floor tile and base o Tile generally appears to be in fair condition.
Structural load bearing walls in the central and core spaces consist of the following:
o Painted masonry CMU from floor to underside of structure above.
o Walls generally appear to be in good condition with minimal areas of wear in need of touch-up paint.
The typical non-rated wall partitions appear to be constructed as follows:
o Vinyl wall panels with rubber base on the public side and painted gypsum board with rubber base on the private side of metal studs from floor to the underside of the acoustic ceiling system above.
o Walls generally appear to be in good condition with minimal areas of wear in need of touch-up paint or replacement of the vinyl panel system.
Typical doors and frames throughout the building are as follows:
o Non-rated painted hollow metal frames.
o Non-rated solid core wood veneered doors o The doors range from solid panels to various lite sizes.
The central core contains two sets of store front aluminum door and side-lite systems.
o The store front systems are non-rated.
o They are full lite tempered glazing.
o Installed from floor to the underside of acoustic ceiling system above.
o The systems are generally in good condition.
Door hardware generally consisting of hinges, closers, latches, knobs, and kickplates, are mostly in good condition.
o Knob hardware does not meet ADA guidelines.
o Panic devices where provided seem to be in working order.
o Keypad security hardware is functional if not dated.
The stairways throughout the building consist of the following:
o Steel stringers with steel covered sheet vinyl treads and risers.
o The stairs appear in relatively good condition.
o The handrails consist of a molded rubber or vinyl material attached to wall with steel supports at equally spaced intervals. (See photo below) o The handrail material is in poor condition, sagging between the wall support anchors.
Where casework exists it generally consists of the following:
o Plastic laminate countertops.
o Veneered or Laminate base and wall cabinets to match.
o Casework appears to be in fair condition if not for dated finishes.
The ceiling throughout generally consists of the following:
o 2x4 acoustic ceiling systems.
4-28 o The grid and tiles are in poor condition.
o Painted gypsum board headers and soffits.
o Where painted gypsum board headers and ceiling soffits are provided, they are in generally good condition.
There are accessible routes into each of the annex buildings, but there are stairs between the annexes and the main building. There is an accessible route into the main building. Once in the building, accessibility is provided by the use of an elevator in each wing.
o Elevators appear to be in working order if not dated.
o The bi-level nature of the building does not allow access from the north side of the building to the south side without ascending or descending the elevators, crossing the main level and ascending or descending the corresponding elevator.
o An accessible route from each of the annex buildings into the main building is only possible by existing each annex and re-entering the main building.
North Annex:
Flooring throughout the open emergency coordination center consists of the following:
o Vinyl Composite Tile (VCT) flooring.
o Vinyl flooring in generally in good condition.
Flooring throughout the offices and circulation spaces within the annex consist of the following:
o Commercial carpet tile.
o Carpet is generally in good condition with minimal wear most commonly in areas of high traffic.
The toilet facilities consist of the following flooring:
o Ceramic floor tile and base o Tile generally appears to be in fair condition.
Entry from the main building tunnel into the North Annex contains quarry tile flooring in good condition.
The typical non-rated wall partitions appear to be constructed as follows:
o Vinyl wall panels with rubber base both sides of metal studs from floor to the underside of the prefabricated metal building structure above o Walls generally appear to be in good condition.
Typical doors and frames throughout the building are as follows:
o Non-rated painted hollow metal frames.
o Non-rated solid core wood veneered doors o The doors range from solid panels to various lite sizes.
Door hardware generally consisting of hinges, closers, latches, knobs, and kickplates, are mostly in good condition.
o Knob hardware does not meet ADA guidelines.
o Panic devices where provided seem to be in working order.
o Keypad security hardware is functional if not dated.
Where casework exists it generally consists of the following:
4-29 o Plastic laminate countertops.
o Veneered or Laminate base and wall cabinets to match.
o Casework appears to be in fair o condition if not for dated finishes.
The ceiling throughout generally consists of the following:
o 2x4 acoustic ceiling systems.
The grid and tiles are in good condition.
o Painted gypsum board headers and soffits.
Where painted gypsum board headers and ceiling soffits are provided, they are in generally good condition.
Flooring throughout the annex consists mainly of vinyl composite tile flooring.
o Flooring is generally in good condition with minimal wear most commonly in areas of high traffic.
Entry from the main building tunnel into the North Annex contains the following:
o 9x9 Vinyl floor tile.
Tile is generally in good condition.
Tile is suspected to likely contain asbestos.
Structural load bearing walls in central and core spaces consist of the following:
o Painted masonry CMU from floor to underside of structure above.
o Walls generally appear to be in good condition with minimal areas of wear in need of touch-up paint.
The typical non-rated wall partitions appear to be constructed as follows:
o Painted gypsum board with rubber base both sides of metal studs from floor to the underside of the structure above.
o Walls generally appear to be in good condition with minimal areas of wear in need of touch-up paint.
Typical doors and frames throughout the building are as follows:
o Non-rated painted hollow metal frames.
o Non-rated solid core wood veneered doors o The doors range from solid panels to various lite sizes.
Door hardware generally consisting of hinges, closers, latches, knobs, and kickplates, are mostly in good condition.
o Knob hardware does not meet ADA guidelines.
o Panic devices where provided seem to be in working order.
o Keypad security hardware is functional if not dated.
Where casework exists it generally consists of the following:
o Plastic laminate countertops.
o Veneered or Laminate base and wall cabinets to match.
o Casework appears to be in fair condition if not for dated finishes.
The ceiling throughout generally consists of 2x4 acoustic ceiling systems with painted gypsum board headers and soffits.
o The grid and tiles are in poor condition.
o Where painted gypsum board headers and ceiling soffits are provided, they are in generally good condition.
St. Clair County Health Department Existing Building Interior Photo Reference:
Main Building – Corridor Finishes
Main Building Stair – Sagging Handrails
Main Building – Typical Casework Finishes
Main Building - Typical Toilet Room Finishes
Rooms are non-conforming with ADA standards
Existing Building Interior Photo Reference:
North Annex – Casework
South Annex (WIC) – Exam Room
North Annex – South Wall
South Annex (WIC) – Exam Room
Existing Building Exterior Photo Reference:
Main Building - Roof Flashings
Main Building - Cement Board Deterioration
Existing Building Exterior Photo Reference:
North Annex - Down Spout
Missing splash block or not connected to drainage system
South-West Corner of the South Annex (WIC)
Broken / missing siding and exposed concrete block foundation
4-31
Mechanical:
Rating Description
Good
Minor improvements needed. Only shows superficial damage or defects with no functional impact. Issues are addressed via routine maintenance.
Equipment age may be between 5-10 years old.
Fair
Repairs are needed and components show signs of corrosion and damage.
Equipment is cosmetically worn but functioning as intended under the routine maintenance schedule.
Equipment age may be between 11-14 years old.
Poor
Components or sub-components need replacement or repair. More substantial part replacement and/or repair is frequent. There currently does not appear to be a safety issue.
Equipment is between 15-20+ years old.
Main Building:
The building is conditioned by four multizone rooftop units (ACU-1, ACU-2, ACU- 3, ACU-4). These units were installed in 2007.
o The rooftop units are provided with integral air-cooled condensing unit sections, gas fired heat exchangers, direct expansion cooling coils, single inlet air foil supply fans, 2� filter racks, and single inlet air foil return fans.
o The compressors are equipped with hot gas bypass to assist during low load conditions.
o ACU-1 has four zones, ACU-2 has five zones, and both ACU-3 and ACU-4 have seven zones. The areas served are indicated in the attached zoning plans.
o The supply and return fans have 2� spring isolation.
o The condensers utilize R22 refrigerant.
o The units are approximately 15 years old. While they have reached their median life expectancy, the units appear to be in good condition.
o Many filters were wet and partially deformed or deteriorating. This could be due to improperly balanced supply and return fans which lead to negative pressurization within the unit. (See photos below)
4-32 o The base rail of the units have a large amount of corrosion.
o Multizone units provide a limited amount of control for different thermal zones. Each zone conditions a large area of the building, allowing some areas to be satisfied while other are not.
o Multizone systems have a constant volume airflow, using a large amount of fan energy and is considered to be inefficient.
The rooftop units supply conditioned air to the spaces through a low-pressure duct system. The supply air is distributed to each space through ceiling mounted supply diffusers. Many of the grilles appeared to be covered in dirt and dust. (See photos below) Each of the multizone rooftop units are provided with shut off dampers that individually close during unoccupied mode or when the unit is not operating.
No perimeter heat has been provided for the building.
Return air for each of the units is through the ceiling plenum above the spaces.
Return grilles located in the ceiling throughout the building provide a transfer path for the return air to get into the ceiling plenum and be return to the rooftop units. Many of the grilles appeared to be covered in dirt and dust. (See photos below) Suite 312 is a tuberculosis center located on the Main Entrance Level.
The suite is designed with walls to deck in order to contain the highly contagious disease.
In addition to the special architectural design, the space is designed to maintain a negative pressure relative to the surrounding spaces.
The negative pressure is accomplished by a dedicated exhaust fan.
The age of the exhaust fan serving the Suite 312 is unknown. We noticed the exterior of the fan and the associated ductwork are heavily corroded and rusted which will reduce the equipment�s life expectancy. (See photos below) One issue that was noticed was the location of the suite. The suite is located to the back of the building, requiring the patients to travel from the entry through the main lobby to this suite.
The Maintenance Office is provided with an electric unit heater to temper the space during the heating season.
The main building is provided with a direct digital control building management system (BMS). The BMS is approximately 3 years old. The main temperature control panel is located in the Phone Room adjacent to the Maintenance Office.
The controllers in this panel are linked to the web-based program called WebCTRL. The main computer located within the Maintenance Office allows the staff to view space conditions as well as adjust them. (See photos below) The BMS system is in good condition.
The BMS is only provided in the Main building, the north and south annex buildings are not connected to this system.
The building is conditioned by three high efficient, condensing, gas fired furnaces (F-1, F-2, F-3). The furnaces were installed in 2002.
4-33
F-1 and F-2 are horizontal units, suspended from roof structure. The units serve the conference area.
o The combustion air and flue ducts are made of PVC.
o The combustion air and flue ducts are combined and routed up through the roof where they terminate to the atmosphere.
o Each furnace is equipped with a 1� disposable filter rack.
o A cooling coil is attached to the outlet of each furnace. The cooling coils are direct expansion coils with an associated air-cooled condensing unit located on the east side of the building.
o The condensing units are provided with a concrete housekeeping pad mounted on grade. (See photos below) o The PVC condensate piping from both furnaces are combined and routed through the exterior wall on the south side of the building. The piping discharges directly above the sidewalk. (See photos below) o The ventilation air for the furnaces are brought in through a single exterior wall mounted louver. The louver is located on the south side of building. The ventilation ductwork is extended and connected to each furnace�s return ductwork upstream of the furnace inlet.
o The refrigerant suction lines are insulated with flexible elastomeric insulation while the refrigerant liquid lines are not insulated.
o Pipe insulation installed on the refrigerant piping located outdoors appears to be weathered and wearing. (See photos below) o The supply ductwork is routed above the ceiling to the areas served.
o The supply air main is not insulated, but the diffuser branch ductwork is insulated with fiberglass blanket insulation.
o Supply air is distributed to the spaces through square, ceiling mounted diffusers.
o The air is returned from the space through a fully ducted system that is located above the ceiling and connected to ceiling mounted return grilles.
o The return ductwork is not insulated.
o F-2�s heat exchanger was replaced 6 years ago according to the maintenance staff. This indicates that the other two furnaces installed in the same timeframe may soon require further repair or replacement.
F-3 is floor mounted, vertical style furnace located in Custodial Closet in the center to building. F-3 serves the west portion of building consisting of multiple offices, restrooms, storage room, and a corridor. (See photos below) o The combustion air and flue ducts are made of PVC.
o The combustion air and flue ducts are combined and routed up through the roof where they terminate to the atmosphere.
o The furnace is equipped with a 1� disposable filter rack.
o A cooling coil is attached to the outlet of the furnace. This cooling coil is a direct expansion coil with an associated air-cooled condensing unit located on the east side of the building.
o The condensing unit is provided with a concrete housekeeping pad mounted on grade. (See photos below)
4-34 o The condensate piping, which is PVC, is routed from the cooling coil to the nearest floor drain.
o The ventilation air for the furnace is brought in through an exterior wall mounted louver. The louver is located on the north side of building. The ventilation ductwork is extended and connected to the return ductwork upstream of the furnace inlet.
o The refrigerant suction lines are insulated with flexible elastomeric insulation while the refrigerant liquid lines are not insulated.
o The supply ductwork is insulated with fiberglass blanket and routed above the ceiling to the areas served.
o Supply air is distributed to the spaces through square, ceiling mounted diffusers.
o The air is returned from the space through a fully ducted system that is located above the ceiling and connected to ceiling mounted return grilles.
o The return ductwork is not insulated.
F-1, F-2, and F-3 and the associated air-cooled condensing units are 20 years old. These units have exceeded their life expectancy but appear to be in fair condition.
The restrooms are provided with individual ceiling mounted exhaust fans.
The restroom exhaust fans are 20 years old. This units have exceeded their life expectancy but are in fair condition.
The discharge ductwork for each fan is connected and routed through the roof as one penetration.
The conference room prep counter is equipped with an exhaust fan controlled by a local power switch on the wall.
The prep counter exhaust fan discharged into the ceiling plenum.
The exhaust fan is 20 years old. This unit has exceeded its life expectancy but is in fair condition.
The building�s temperature controls system is standalone without a main building management system. Each furnace is provided with a 7-day programmable thermostat. (See photos below)
The South Annex is conditioned by three 4-ton packaged roof top units that were installed in 2015. The roof top units are 7 years old. These units are in good condition. (See photos below) The roof top units are constant volume.
The unit components are as follows:
o A single speed, scroll type compressor o A 2-stage gas heat exchanger o A standard 2� MERV 4 rated filter o A 1.5 HP, forward curved, single speed, belt driven supply fan
The roof top units are mounted on standard roof curbs, however during our field investigation the units were not accessed due to inclement weather. There is
4-35 not a permanent access ladder to the roof which makes it dangerous to maintain the equipment on the roof during the winter.
Supply air is distributed to the spaces through square, ceiling mounted diffusers. The supply ductwork above the ceiling was not witnessed during our field investigation.
The air is returned from the spaces through wall mounted transfer grilles between the rooms and the corridor. The transfer grilles are mounted below the ceiling. The corridor is used as a return path back to large return grilles mounted below each roof top unit. This is a Michigan Mechanical Code violation as indicated in section 601.2. (See photos below) The buildings temperature controls system in the building is stand alone.
A 7-day programmable thermostat is provided for each roof top unit. (See photos below) Each rooftop unit serves several temperature control zones with a single thermostat.
The perimeter spaces are provided with hot water radiators that are controlled by a local thermostat.
The two entrances are provided with hot water radiators controlled by their respective thermostats.
The hot water radiators appear to be original to the building. No leaks were witnessed or indicated by the maintenance staff. These units have exceeded their life expectancy but appears to be in fair condition. (See photos below) Heating hot water for the building is supplied by a single gas-fired cast iron boiler.
The boiler has an input of 210,000 btu/hr with a net output of 152,000 btu/hr resulting in a 72% efficiency.
The boiler is 29 years old.
The boiler has light signs of rust and damage to the casing but appears to be in fair condition. (See photos below) The boiler is not provided with a backup in the event of failure.
The leaving water temperature during the site observation was 145-degree Fahrenheit.
The boiler appears to have been installed in 1993.
The boiler flue is routed up through the ceiling tiles and terminates above the roof to the atmosphere.
During our site observation, the ceiling tiles were observed to have water damper around the flue duct. (See photos below) Water damage could either be from an active roof leak or a previous leak.
The combustion air intake for the boiler is drawn from an exterior wall louver adjacent to the system. The louver is mounted approximately 7�-0� above grade.
The combustion air intake for the boiler is located above the exterior gas meter and regulator. (See photos below) The closed loop heating system is piped in a primary configuration with two ¾ hp inline pumps circulating the hot water heating water to each of the heating
4-36 devices through the building. One pump was valved off and appears to be a standby pump.
The circulating pumps were not provided with variable frequency drives which indicated the system is a constant volume system.
The inline pumps are 27 years old. These units have exceeded their life expectancy but appears to be in fair condition. (See photos below) The hot water heating piping is routed through an underground pipe tunnel that connects to all perimeter hot water radiators throughout the building.
The hot water heating piping is insulated with fiberglass insulation and appears to approximately 1 ½� thick.
The hot water heating piping appears to be 1 ½� copper with soldered connections. Where piping was visible, green residue was present, indicating oxidation and corrosion is occurring. (See photos below) The heating hot water piping system is provided with ball valves for isolation.
The heating system is not provided with an air separator or chemical feeder typically found in hot water heating systems. Air separators and chemical feeders are installed in closed loop systems to remove air, treat the water, and reduce corrosion of the piping. This is a layer of protection for the piping system and the associated equipment.
The existing heating system is equipped with a cold water make up and pressure reducing valve, a low water cut off switch, and outside air reset. The cold water make up is connected the hot water heating supply downstream of the circulator pumps and prior to entering the pipe tunnel.
Two horizontal, compression tanks are connected to the hot water heating return piping prior to entering the boiler.
A roof mounted exhaust fan handles the restrooms.
The restrooms exhaust fan appears appear to be original to the building. This unit has exceeded its end of life and is in fair condition.
The roof mounted exhaust fan is a down blast style fan.
4-37
Plumbing:
Rating Description
Good
Minor improvements needed. Only shows superficial damage or defects with no functional impact. Issues are addressed via routine maintenance.
Equipment age may be between 5-10 years old.
Fair
Repairs are needed and components show signs of corrosion and damage.
Equipment is cosmetically worn but functioning as intended under the routine maintenance schedule.
Equipment age may be between 11-14 years old.
Poor
Components or sub-components need replacement or repair. More substantial part replacement and/or repair is frequent. There currently does not appear to be a safety issue.
Equipment is between 15-20+ years old.
Main Building:
The domestic cold-water service comes from the street as a 2� pipe that passes through the slab in north-east corner of the Maintenance Office. The water service is not provided with a means of backflow prevention.
The 2� domestic water main is routed through a 2� meter. A 2� bypass has been provided around the meter without a lockable isolation valve. (See photos below) The piping increases from 2� to 2-1/2� after leaving the meter.
The incoming services are provided with a gate valve for isolation. All other valves downstream of the incoming service location appear to be ball valves. A few newer valves were indicated to be low lead. The original valves are assumed to contain solder with lead.
The piping was not observed throughout the building only in locations where insulation was removed or missing in the mechanical room. It is assumed the piping transitions to copper with soldered joints prior to leaving the mechanical room.
Most of the pipe insulation appeared contain asbestos but must be tested to confirm. Some existing insulation appeared to have been replaced with
4-38 fiberglass insulation and some insulation appeared to have been repaired with duct tape. (See photos below) According to the existing pressure gauges, the incoming water pressure is 49 PSI and the temperature is 40-degree Fahrenheit.
The 2 ½� domestic cold-water piping is extended and connected to the plumbing fixtures on all levels of the main building.
A 1 ½� cold water pipe is connected to the domestic hot water heater located within the Maintenance Office.
The domestic hot water heater a single commercial, storage type, atmospheric vent, gas fired water heater.
The water heater has an 80-gallon nominal storage capacity with an input of 199,999 Btuh/hr and a recovery rate of approximately 194 gallons per hour at 100-degree temperature rise. The water heater was replaced in 2021. The water heater set point was 120 degrees Fahrenheit.
The water heater relief valve is routed to the floor and discharges freely.
The 1 1/2� domestic hot water piping is extended to plumbing fixtures on all levels of the main building.
The domestic hot water system was observed to be copper piping with soldered joints and is insulated.
A hot water recirculation is provided with the domestic hot water system.
The hot water recirculation is made up of copper piping with soldered joints.
The domestic hot water inline return pump is located in the Maintenance Office above the water heater. The pump is activated by an aqua stat located in the hot water return piping. Isolation valves and a check valve were provided with the pump.
The sanitary system in the building flows by gravity to a 6� sanitary sewer that exits the building along the west exposure.
The existing sanitary piping was not visible during our field investigation, it is assumed to be cast iron hub and spigot piping based on the existing drawings.
The sanitary system is provided with vents at the plumbing fixtures and vents through the roof.
Based on the vent piping material extended through the roof, it is our assumption the vent piping under the roof is cast iron hub and spigot. The piping was not visible during our field investigation since the piping is concealed in walls.
There were no issues reported with the existing sanitary and vent systems.
The building is provided with primary roof drains that are connected to internal roof conductors routed down through the building and connected to two 6� underground storm sewer.
The roof sumps were clear of debris and no issues where noted. The primary roof conductor piping appeared to be PVC piping where exposed. Most of the piping could not be observed in the building since it was concealed in the ceilings and walls.
The storm sewers flow by gravity to a 10� utility connection that exits the building along the west exposure.
4-39
The existing below grade storm piping was not visible during our field investigation. The pipe material is unknown.
The existing drawings indicate a perimeter drain tile along the exterior of the building and two interior drain tiles along the lower-level walls of the north and south wings of the main building. The drain tile system is connected to the underground storm drainage system. The drain tile flows by gravity and is not equipped with a sump pump. The system is not visible and could not be verified to be installed.
Two elevators were added to the building in 1980 (42 years old). The elevator pits were not observed. Based on site observations, it appears each elevator pit is drained into a sump pump located within the elevator machine rooms adjacent to the elevator pits. These sump pumps are duplex style with water sensors linked back to the building management system. (See photos below) There are check valves on the outlet of each of the sump pumps.
The discharge piping is galvanized with threaded fittings.
The discharge piping was routed through a wall and final termination could not be observed. According to the existing drawings, the outlet is directly connected to the storm piping adjacent to the elevator shafts.
Hydraulic elevator pit drainage is required by code to discharge into an oil separator prior to connecting to the sewer or storm piping. Oil must be disposed of properly.
The maintenance staff did not report any issues with the storm system in the building.
The natural gas service is provided on the east side of the building adjacent to the existing Maintenance Office.
The high-pressure natural gas service is routed through a meter and a pressure regulator on the exterior of the building. The 2� main branches to three locations. A 1 ½� pipe is routed underground to the North Annex. The 2� pipe is routed aboveground and serves the Main Building. A 1� branch at the end of the exterior piping connects to the main generator adjacent to the gas meter.
This generator serves the vaccine refrigerator, phone server and computer server.
The 2� branch to the Main Building enters the Maintenance Office where it increases in size to 3�. The piping is connected to the hot water heater in the Maintenance Office and continues through the building to the four roof top units. The gas piping is routed through the ceiling plenum and penetrates the roof adjacent to each roof top unit.
The branch connection to the water heater also branches to a second exterior generator located south of the Maintenance Office. This generator serves the North Annex and the sump pumps.
The gas service was originally sized for one water heater, the four roof top units and an incinerator. The incinerator has been removed from the building.
The existing natural gas piping on the exterior of the building appears to be black steel threaded and has extensive corrosion. (See photos below) The interior gas piping is black steel threaded.
4-40
The gas piping serving the two generators is not provided with a dirt leg. (See photos below) The gas piping dirt leg associated with the water heater appears to be supporting the weight of the piping. (See photos below) No dirt leg is visible on the roof for each roof top unit.
The water closets found in the restrooms were wall mounted with a combination of automatic and manual flush valves. The water closets appeared to be pulling from the wall in some locations.
The lavatories found in the restrooms were wall hung with manual faucets. The strainers were missing at several lavatories.
A few lavatories were cracked and pulling from the wall.
The lavatories were not provided with temperature limiting mixing valves.
The urinals found in the restrooms were wall hung with automatic flush valves.
The strainer appeared to be missing from the drain.
Many of the plumbing fixtures in the building were in poor condition. (See photos below) In suites and exam rooms, counter mounted sinks with manual gooseneck faucets were provided. Temperature limiting mixing valves were not provided at all sinks. (See photos below) The electric water coolers appeared to be original to the building and possibly manufactured in 1966.
The paint and finish appear to be wearing and appear to be in poor condition.
Two water coolers are located side by side at the same mounting height and have a solid front surface that does not provide knee clearance. This installation does not appear to meet ADA requirements. (See photos below) The condensate from the roof top units is a flexible piping routed to the nearest roof drain. There are no pipe supports and the piping is flush to the roof.
The domestic cold-water service comes from the street as a 1� pipe and passes through the slab in Custodial Closet. The system is not provided with a backflow preventor.
Ball valves are provided at the inlet and outlet of the meter and there is no bypass around the meter.
The domestic water piping was not observed throughout the entire building but was exposed in the Custodial Closet. The piping was not insulated and appeared to be copper piping with soldered connections.
A ¾� cold water is connected to an electric, hot water heater within the Custodial Closet.
The electric water heater is a short, residential style, with 12-gallons of capacity, a 1500-watt heating element, and a 7 GPH recovery at 90 deg rise. The unit was manufactured and installed in 2013.
The water heater is 9 years old. Based on our experience, the water heater is nearing the end of life for this type of equipment, but it appears to be in good condition. (See photos below)
4-41
The water heater is supported from a wood shelf above the janitor�s sink. The inlet and outlet piping connected to the water heater is not provided with isolation valves.
The relief valve discharges to the drain pan below the water heater. The drain outlet is piped to the janitor�s sink below and discharges freely into the sink.
A ¾� domestic hot water pipe is extended to the plumbing fixtures in the restrooms and to the sink located in the conference room counter.
No hot water recirculation has been provided for this system.
The existing underground sanitary piping is unknown as it was not visible during our field investigation, Most of the aboveground sanitary piping was not visible during our field investigation since the piping is concealed in walls and floors. The exposed sanitary piping below the sink and lavatories were a mix of stainless steel and
PVC.
The sanitary system is provided with vents that terminated through the roof.
The vent piping was not visible during our field investigation since the piping is concealed in walls. The exposed piping terminating the roof appeared to be
PVC.
There were no issues reported with the existing sanitary and vent systems.
The building was constructed with a gutter and downspout system. The roof is pitched, and the rainwater flows by gravity into the gutter system.
The natural gas to the building is supplied from the gas meter and regulator that serves the main building.
A 1-½� natural gas main pipe is routed underground from the exit of the main building�s meter to the southeast corner of the North Annex building. The piping enters the North Annex near grade where it is routed up into the wall and then into the ceiling plenum. Once in the ceiling plenum, it is connected to the three furnaces outlined above.
The existing natural gas piping on the exterior of the building appears to be galvanized threaded. A portion of the pipe has been painted and is weathered in several locations.
The interior gas piping is black steel threaded.
The water closets found in the restrooms were floor mounted, tank type.
The urinal in the men�s restroom is a floor mounted, bottom outlet with an automatic flush valve.
The lavatories found in the restrooms were drop in style mounted in a laminate countertop with manual faucets. The sanitary piping appeared to be offset for ADA accessibility but manufactured plastic wraps covering the hot- and cold-water supplies and sanitary trap and drain piping were not fully provided for both fixtures. This does not comply with Americans with Disabilities Act (ADA) requirements. A water-temperature limiting device was not installed for on supplies for one of the two lavatories.
4-42
The sink at the prep counter is drop-in, stainless-steel sink with a manual, gooseneck faucet. A water-temperature limiting device was not installed on supplies to this sink.
The plumbing fixtures in the building appeared to be in good condition.
The janitors closet sink is a square corner, floor mounted, cast-polymer fixture with a wall mounted manual faucet.
The electric water cooler is a wall mounted, single, non-filtered refrigerated unit that was manufactured in 2014.
The electric water cooler is 8 years old and appears to be in good condition.
(See photos below)
South Annex (WIC Suite):
A 1� domestic water service is located in the southwest corner of the boiler room. The maintenance staff indicated there is an underground water meter near the south side of the building. Due to snow cover, this was not verified.
There is not a means of backflow prevention on the incoming service.
The domestic water service is connected to the boiler make up, domestic hot water heater, and to the plumbing fixtures within the building.
The incoming services is provided with a gate valve for isolation. All other valves downstream of the incoming service location appear to be ball valves. A few newer valves were indicated to be low lead. The original valves are assumed to contain solder with lead.
The piping was not observed throughout the building only in locations where insulation was removed or missing, however where exposed, the piping was copper with soldered joints.
The piping was insulated with fiberglass insulation.
The domestic hot water heater is single, storage type, gas fired water heater.
The water heater has a 40-gallon nominal storage capacity. The water heater has an input of 34,000 Btuh/hr. The water heater was installed in 1993 (29 years old).
The domestic hot water heater is 29 years old. Based on our experience, the water heater is nearing the end of life for this type of equipment, and it appears to be in poor condition. (See photos below) The 3/4� domestic hot water piping is extended to plumbing fixtures within the building.
The domestic hot water system is copper piping with soldered joints and is insulated.
The hot water heater supplies fixtures greater than 50 feet from the water heater, which required a recirculation system by the Michigan Plumbing Code.
A hot water recirculation is not provided with the domestic hot water system.
The water closets found in the restrooms were floor mounted, tank type.
The lavatories found in the restrooms were wall hung with manual faucets. The strainers were missing at various lavatories.
Temperature limiting mixing valves were not provided at all lavatories.
A single electric water cooler was installed in 2010.
4-43
The electric water cooler is 12 years old and appears to be in fair condition.
(See photos below) The sanitary system in the building appears to flow by gravity to the site utilities at the east side of the building.
The existing sanitary piping was not visible during our field investigation and the pipe material could not be confirmed.
The sanitary system is provided with vents at the plumbing fixtures and vents through the roof.
The vent piping material is unknown. The piping was not visible during our field investigation since the piping is concealed in walls.
There were no issues reported with the existing sanitary and vent systems.
The building is provided with primary roof drains that are connected to internal roof conductors routed through the ceiling plenum out the exterior wall above the ceiling, and down the face of the wall. The piping discharges to grade.
The roof conductor piping is PVC piping.
The natural gas service is provided on the west side of the building adjacent to the boiler room. (See photos below) The high-pressure natural gas service is routed through a meter and a pressure regulator on the exterior of the building. The 1� main enters boiler room where it branches to the roof, the boiler, and the domestic water heater.
The gas piping routed to the roof is connected to the rooftop units.
The gas pipe supports located on the roof were observed from the adjacent roof and appeared to be 4x4 wooden blocks.
The ceiling tiles below the roof has water damage indicating a current or previous leak.
The existing natural gas piping on the exterior of the building appears to be black steel threaded and has extensive corrosion.
The interior gas piping is black steel threaded. The interior piping is painted red.
The gas piping serving the water heater is provided with a dirt leg.
The gas piping serving the roof top units appeared to have dirt legs.
Fire Protection:
There is no existing fire protection in any of the three buildings, however the buildings are equipped with fire extinguishers throughout.
Electrical:
Main Building 208/120V power is provided from an overhead utility pole to a General Electric 1200A main distribution panel located within the northeast maintenance office.
The existing MDP is assumed to be the same age as facility leading the MDP to approximately 50+ years old. (See photos below) Main electrical room shares space with mechanical equipment as well as general storage, and an office space for maintenance personnel.
4-44
225A Panels located throughout the facility appear to be same age as the MDP;
some newer 100A panels have been installed in more recent work. Newer panels include space for future circuits. (See photos below) Two Natural Gas generators are located outside of the northeast maintenance office.
o Natural Gas generator 1 includes phones, computer server, vaccine fridge (See photos below) o Natural Gas generator 2 includes North Annex and sump pumps.
General receptacles located within corridors, offices, and in conference areas.
No complaints noted of receptacles not performing.
Lighting throughout interior of building are T8 Fluorescent fixtures. A variety of color temperatures appear to be used at different areas. Few fixtures have had tubes removed to avoid glare on computer screens but are in otherwise working order. (See photos below) Emergency lighting is covered using emergency battery units throughout.
Site lighting is all LED fixtures and appear to be in good condition. (See photos below) Lighting controls are a combination of switching and occupancy sensors. A majority of the spaces are controlled with on/off switching.
Smoke detectors located throughout the facility
North Annex The North Annex, added in 2001, utilizes a 225A panel which is fed from the MDP located within the main building feeds loads throughout. (See photos below) North Annex generator provides back up within this portion of the facility along with additional sump pumps.
General receptacles located within corridors, offices, and in conference areas.
No complaints noted of receptacles not preforming.
Lighting throughout interior of building are T8 Fluorescent fixtures.
Emergency lighting is covered using emergency battery units throughout.
Lighting controls are a combination of switching and occupancy sensors. A majority of the spaces are controlled with on/off switching.
South Annex (WIC Suite):
A 225A panel fed from the MDP located within the main building feeds loads throughout the WIC Annex. An additional 225A panel feeds various AC units and is assumed to also be fed from the MDP in the main building. (See photos below) General receptacles located within corridors, offices, and in conference areas.
No complaints noted of receptacles not preforming.
Lighting throughout interior of building are T8 Fluorescent fixtures.
Emergency lighting is covered using emergency battery units throughout.
Lighting controls are a combination of switching and occupancy sensors. A majority of the spaces are controlled with on/off switching.
4-45
Data/Telecommunications:
Main Building Main data/telecommunications cabling rack and phone cabling system located in Phone Room off of maintenance office to northeast. Room doubling as storage for general equipment. (See photos below) An existing phone system is still in place but not in use throughout. A new VOIP system is being utilized.
Typical telecom connections within conference rooms and offices.
There is a working speaker system still installed throughout entire facility.
North Annex Main data/telecommunications cabling rack and phone cabling system located in Phone Room off of maintenance office to northeast. Room doubling as storage for replacement parts, general equipment, and misc. storage.
An existing phone system is still in place but not…