Questions and Answers:
Q: Would a generator with the following specification exceptions be acceptable?
Requested Prime Power 26kva/21kw Amp 3 phase 72A @ 208v, 31A @ 480v Fuel Tank Capacity 100 Gals Full Load Runtime 42.9 Hours
Proposed Prime Power 25kva/20kw Amp 3 phase 70A @ 208v, 30A @ 480v Fuel Tank Capacity 73 Gals Full Load Runtime 41 Hours
A: Yes those specs will work
Q: Specifications state the generator is mobile/portable, what is the means of moving it?
A: The generator will be moved by forklift, so it should be skid mounted