H1 Drawing files _ 245448 _ Mech.pdf

PDF 2 MB Posted

Attached to
REPAIR CHAPEL, B #30
Solicitation number
W91QVN22R0087
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KIM, SM

M-1

NTS

245448 o

ACCU AIR COOLED CONDENSING UNIT

ACLD AIR COOLED

ACU AIR CONDITION UNIT (S)

ACV ALARM CHECK VALVE

ADP APPARATUS DEW POINT

AHU AIR HANDLING UNIT

AIR COND AIR CONDITION (-ING,-ED)

AL ALUMINUM

ALT ALTITUDE

AMB AMBIENT

AMP AMPERE(AMP, AMPS)

APPROX APPROXIMATE

AVG AVERAGE

AWG AMERICAN WIRE GAUGE

BARO BAROMETER(-TRIC)

BARO PR PRESSURE, BAROMETRIC

BHP BRAKE HORSEPOWER

BP BOILING POINT

CAP CAPACITY

CCW COUNTER CLOCKWISE

CHW CHILLED WATER

CKT CIRCUIT

CLASS CLASSIFICATION

CLG LOAD COOLING LOAD

COEF COEFFICIENT

CONN CONNECTION

CONT CONTINUE

C

CMH CUBIC METER PER HOUR

CU M CUBIC METER

CENTIGRADE/ CELCIUS

CFCI

CONTRACTOR INSTALLED

CONTRACTOR FURNISHED

CIP CAST IRON PIPE

CWP

CU MM CUBIC MILLIMETER

Cv COEFFICIENT, VALVE FLOW

CW CLOCKWISE OR COLD WATER

CIRCULATING WATER PUMP

DB DECIBEL OR DRY BULB

COMPRESSORCPRSR

DBT DRY BULB TEMPERATURE

DCWS DOMESTIC COLD WATER SUPPLY

DEG or ° DEGREE

DFW DIESEL OIL

DOMESTIC HOT WATER RETURN

DOMESTIC HOT WATER SUPPLY

DHWR

DHWS

DIRECT EXPANSIONDX

DRY PIPE VALVEDPV

DOUBLE POLE DOUBLE THROWDPDT

DEWPOINT TEMPERATUREDPT

DIVISIONDIV

DIFFERENCEDIFF

DIAGRAMDIAG

DIAMETERDIA or

DWG DRAWING

EXPANSION JOINTEXPJT

ENTERING WATER TEMPEWT

EVAPORAT (-E,-ING,-ED,-OR)EVAP

EXTERNAL STATIC PRESSUREESP

EXPLOSION PROOFEP

EQUIPMENTEQPT

ENTERINGENT

EFFICIENCYEFF

EQUIVALENT DIRECT RADIATIONEDR

ECONOMIZERECON

ECCENTRICECC

ENTERING AIR TEMPERATUREEAT

FUEL OILFO

FA FACE AREA OR FRESH AIR

FHC FIRE HOSE CABINET

FHY FIRE HYDRANT

FLA FULL LOAD AMPERES

F FARENHEIT

FLR FLOOR

FEED WATER PUMPFWP

FACE VELOCITYFVEL

FLUSH VALVEFV

FRP

FREQUENCYFREQ

FEMALE PIPE THREADFPT

FIBERGLASS REINFORCED PLASTIC

Ft or ' FEET

FXTR FIXTURE

GALVANIZED STEELGALVS

GAGE OR GAUGEGA

GR GRAMS

GOVERNMENT INSTALLED

GOVERNMENT FURNISHED GFGI

CONTRACTOR INSTALLED

GOVERNMENT FURNISHEDGFCI

GAL GALLONS

GALLONS PER MINUTEGPM

HERTZHZ

HORIZONTALHORIZ

HOT WATER HEATERHWH

HOT WATERHW

HOUR(S)HR

HORSEPOWERHP

MERCURYHG

HEADHD

HB HOSE BIBB

DIAMETER, INSIDEID

ISOMETRICISO

IRON PIPE SIZEIPS

J JOULE

K THERMAL CONDUCTIVITY

K THERMAL CONDUCTIVITY

kG kCAL/HR

KILOGRAM

kG/SQ CM KILOGRAM PER SQ. CENTIMETER kG/SQ CM A

KILOCALORIE PER HOUR

(ABSOLUTE)

KILOGRAM PER SQ. CENTIMETER

kG/SQ CM G

(GAUGE)

KILOGRAM PER SQ. CENTIMETER

kG/SM KILOGRAM PER SQ. METER kG/SM A kG/SM G

(ABSOLUTE)

KILOGRAM PER SQ. METER

KILOGRAM PER SQ. METER (GAGE)

kW KILOWATT kWH KILOWATT HOUR kJ KILOJOULE kPa KILO PASCAL

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LG LENGTH

LH LATENT HEAT

LWT LEAVING WATER TEMPERATURE

LIQUID LINELL

L LITERS

LPD LITERS PER DAY

LPH LITERS PER HOUR

LPS

LM LINEAR METER

LITERS PER SECOND

LAV LAVATORY

LPM LITERS PER MINUTE

LT LAUNDRY TRAY

NUMBERNO

NORMALLY OPENN.O.

NOT IN CONTRACTNIC

NORMALLY CLOSEDN.C.

NOISE CRITERIANC

NCK

MAX

NOT TO SCALENTS

MIN

MPH

M METERS

MAXIMUM

MINIMUM OR MINUTE

METERS PER HOUR

MPS METERS PER SECOND

MM MILLIMETER

NPT NATIONAL TAPER PIPE (THREAD)

NOT APPLICABLEN/A

NECK

MECH MECHANICAL

OS&Y OUTSIDE SCREW & YOKE

OD

OAIL OUTSIDE AIR INTAKE LOUVER

OA OUTSIDE AIR

OUTSIDE DIAMETER

OPNG OPENING

OXY OXYGEN

PERCENT

PRESSURE REDUCING VALVEPRV

PARTS PER MILLIONPPM

POINT OF CONNECTIONPOC

PLUMBINGPLMB

PHASE (ELECTRIC)PH

PRESSURE GAGEPG

PD

POLEP

PRESSURE DROP OR DIFFERENCE

Pa PASCAL

POL PETROLEUM, OIL AND LUBRICANTS

QUANTITYQTY

QUARTQT

REFRIGERATION TONRT

REVOLUTIONS PER MINUTERPM

RADIATORRDTR

RETURN AIRRA

THERMAL RESISTANCER

REFRIGERANT (134A, 22, ETC)R134A,R22

RH RELATIVE HUMIDITY

SUPPLY AIRSA

SYMBOLSYM

SUCTIONSUCT

STORAGESTOR

STEELSTL

STANDARDSTD

STEAMST

SAYBOLT SECONDS UNIVERSALSSU

STAINLESS STEELSST

SAYBOLT SECONDS FUROLSSF

SQUARESQ

SPECIFICATIONSPEC

SINGLE POLE DOUBLE THROWSPDT

SM

LPH, STANDARD CONDITIONSSLPH

LPS, STANDARD CONDITIONSSLPS

SG

SLPD LPD, STANDARD CONDITIONS

SL SENSIBLE LOAD

SH SENSIBLE HEAT

SPECIFIC GRAVITY

SF SAFETY FACTOR

SEC SECOND

SCH SCHEDULE

STATIC PRESSURE

SQUARE METER

SP

SBM

SAN SANITARY

SUBMERSIBLE

TYPICALTYP

THERMOSTATTSTAT

TONS OF REFRIGERATIONTONS

THICKNESSTHK

THERMOMETERTHERM

TEMPERATURETEMP

TEMPERATURE DIFFERENCETD

UNIT HEATERUH

HEAT TRANSFER COEFFICIENTU

WTRPRF

WT

WSHR

WITHW/

WH

WIDTHWD

WCLD

WC

WBT

WB

WATTW

VP

VOL

VISC

VERTICALVERT

VENTILATIONVENT

VELOCITYVEL

VARIABLE AIR VOLUMEVAV

VAC VACUUM

VLV VALVE

V VOLT

WATERPROOF

WEIGHT

WASHER

WATTHOUR OR WATER HEATER

WATER-COOLED

WATER CLOSET

WET BULB TEMPERATURE

WET BULB

PRESSURE, DYNAMIC(VELOCITY)

VOLUME

VISCOSITY

VTR VENT THRU ROOF

UR URINAL

A B B R E V I A T I O N S

MECHANICAL MATERIAL INDICATIONS AND SYMBOLS

FS

VFM

OFM

AVA

PRESSURE RELIEF

TEMPERATURE

EXPANSION LOOP

EXPANSION JOINT

ANCHOR, INTERMEDIATE

ALIGNMENT GUIDE

AIR VENT, AUTOMATIC

SQUARE HEAD BALANCING COCK

QUICK OPENING

NEEDLE

LOCK SHIELD

FLEXIBLE CONNECTOR

FLOWMETER, ORIFICE

FLOWMETER, VENTURI

FLOW SWITCH

PRESSURE GAUGE AND COCK

STRAINER

THERMOMETER

PRESSURE REDUCING

RELIEF OR SAFETY

SLEEVE

BLOW OFF STRAINER

INLINE PUMP

SAFETY

FLOAT

valves, special duty

S

M

GATE, NORMALLY CLOSED

GLOBE

SOLENOID

3 WAY MANUAL

GATE, NORMALLY OPEN

PLUG

MOTOR OPERATED GATE

MOTOR OPERATED GLOBE

3 WAY ELECMOTOR CONTROL

3 WAY AIR MOTOR CONTROLLER

HOSE GATE

HOSE GLOBE

POST INDICATOR

OS Y

ANGLE GLOBE

ANGLE GATE

SWING GATE CHECK

S

M

P

M

M

ALARM CHECK

DRY PIPE

DELUGE

PREACTION

TAMPER DETECTION SWITCH

QUICK OPENING DEVICE

NON-RISING STEM

DIAPHRAGM

SOLENOID

MOTOR ELECTRIC

valve actuators fittings

TEE, SINGLE SWEEP

UNION, SCREWED

UNION, FLANGED

CONNECTION, TOP

ELBOW, 90°

ELBOW, TURNED UP

ELBOW, TURNED DOWN

TEE, OUTLET UP

TEE, OUTLET DOWN

CONNECTION, BOTTOM

REDUCER, CONCENTRIC

(STRAIGHT, INVERT)

REDUCER, ECCENTRIC

(STRAIGHT, DOWN)

REDUCER, ECCENTRIC

TEE

ELBOW, 45°

LATERAL

SOLVENT CEMENT

BELL AND SPIGOT

SCREWED

FLANGED

WELDED

SOLDERED/BRAZED

M

NS

BUTTERFLY

BALL

DIAPHRAGM

GATE

INDICATING BUTTERFLY

KEY OPERATED

CHECK

SIDEWALL SPRINKLER

UPRIGHT SPRINKLER

DELUGE VALVE

WALL MOUNTED TEST HEADER

FIRE ALARM BELL

HOSE STATION DRY STANDPIPE

MINI HORN

HORN SPEAKER

WALL HYDRANT 2 HOSE OUTLET

SMOKE DETECTOR

PENDENT SPRINKLER DROP NIPPLE

NIPPLED UP UPRIGHT SPRINKLER

OUTSIDE SPRINKLER

CUTTING POINT

CAP

NON-SPRINKLERED SPACE

RISER

(SEE SPRINKLER SCHEDULE)

PENDENT SPRINKLER

CONNECTION (2-WAY SHOWN)

SIAMESE FIRE DEPARTMENT

CONNECTION

SINGLE FIRE DEPARTMENT

valves

POTABLE COLD WATER

POTABLE HOT WATER

POTABLE HOT WATER RETURN

PIPE SLEEVE

BACKFLOW PREVENTER

PITCH OR PIPE, UP(U), DOWN(D)

VENT THRU ROOF

SURFACE CLEANOUT

FLOOR CLEANOUT

FLOOR DRAIN

PIPE SLEEVE WITH FIRE STOPPING

HOSE BIBB

FLOOR SINK (200mm x 200mm)

HOT WATER (60°C)

HOT WATER (82.22°C)

VENT

SANITARY SEWER

COMPRESSED AIR

FUEL OIL SUPPLY

FUEL OIL RETURN

FLOOR DRAIN WITH CLEANOUT

FLOOR DRAIN WITH DEEP TRAP

FLOOR DRAIN WITH NO TRAP

FLOOR DRAIN WITH TRAP TIME

FD

FCO

SCO

200x200

FIRE PROTECTION WATER SUPPLY

MAIN SUPPLY SPRINKLER

WET STANDPIPE

DRY STANDPIPE

COMBINATION STANDPIPE

plumbing sprinkler

DSP

WSP

CSP

S

F

PLAN ELEV

82.22°C

60°C

S

A

FOS

FOR

RD

RS

RL

D

CWS

CWR

LPC

BBD

PC

VPD

MU

FOD

FOV

FOG

FOS

FOR

HWS

M

HCS

HCR

FILL

MU

HWR

LOW PRESSURE CONDENSATE

BOILER BLOW DOWN

PUMPED CONDENSATE

VACUUM PUMP DISCHARGE

MAKE UP WATER

FUEL OIL DRAIN

FUEL OIL TANK VENT

FUEL OIL GAUGE

FUEL OIL SUPPLY

FUEL OIL RETURN

CONTROL AIR MAIN

DUAL TEMPERATURE RETURN

FILL LINE

MAKE UP WATER

DUAL TEMPERATURE SUPPLY

WATER SUPPLY

LOW TEMPERATURE HOT

WATER RETURN

LOW TEMPERATURE HOT

SPLITTER DAMPER

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION

REFRIGERANT LIQUID

DRAIN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

dampers piping heating air conditioning and refrigeration

DU 13mm

47.2

94.4

DG

300x150

500/300L

R

AD

FC

SG

SR

RG

RR

810mm x 400mm

810mm x 400mm

810mm x 400mm

EG

ER

810mm x 400mm

DIRECTION OF FLOW

FLEXIBLE CONNECTION

TRANSITION

(810mm WIDTH x 400mm DEPTH)

DUCT SIZES SHOWN

RISE(R), DOWN(D)

CHANGE OF ELEVATION

VERTICAL OR HORIZONTAL

ACCESS DOOR,

FIRST FIGURE IS ON TOP

POSITIVE PRESS.,

OUTSIDE AIR DUCT SECTION,

FIRST FIGURE IS ON TOP

POSITIVE PRESS.,

SUPPLY AIR DUCT SECTION,

FIRST FIGURE IS ON TOP

SECTION, NEGATIVE PRESS.,

RETURN OR EXHAUST AIR DUCT

SUPPLY OR RETURN

FLEXIBLE AIR DUCT,

TRANSITION

SQUARE TO ROUND

REGISTER, CEILING

EXHAUST AIR GRILLE OR

REGISTER, SIDEWALL

SUPPLY AIR GRILLE OR

REGISTER, CEILING

RETURN AIR GRILLE OR

OR REGISTER, CEILING

SUPPLY AIR MODULAR DIFFUSER

DOOR GRILLE (300mmx150mmH)

(500mmWx300mmH, 94.4 LPS)

LOUVER, DOOR OR WALL

(13mm, 47.2 LPS)

DOOR UNDERCUT

duct works grilles, registers and diffusers

LEGEND & ABBREVIATION

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CAMP BONIFAS

REPAIR CHAPEL BLDG. NO. T-30

A. REPAIR/MAINTENANCE (K-WORK)

SCOPE OF WORK

NOTE :

KIM, SM

M-2

NTS

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

GENERAL NOTES & SCOPE OF WORK

MECHANICAL GENERAL NOTES

GOVERNMENT.

ACTIVITIES, AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE

16. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION

SHUT-OFF VALVE WITHIN 1M OF THE UNIT.

15. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH

WATER BEING FLUSHED IS CLEAR AS TAP WATER.

14. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL ALL

PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.

RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT.

13. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR USE

CREATE CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.

PIPING RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY

12. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1/4 INCH PER 1 FOOT. INSULATE ALL SEWER

GYPBOARD OR CONCEALED CEILINGS.

THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH

12"x12" ACCESS PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE THAT

DETECTOR, BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION

IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE

11. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS

PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.

10. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC

BALANCING (TAB) REPORT SHALL BE SUBMITTED TO THE COR FOR REVIEW AND APPROVAL.

TECHNICAL SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND

ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL. O & MA STANDARD

9. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT

AND SUBMITTED TO THE CONTRACTING OFFICER FOR APPROAL.

DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS

8. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH

PROJECT. THE DETAILS SHALL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK.

7. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS

CONTRACTING OFFICER.

6. THE CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE

SHALL BE REPAIRED OR REPLACED BY THIS CONTRACTOR AT HIS OWN COST.

EQUIPMENT, DUCT WORK, PIPING ETC. ANY DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT

5. CONNECTION TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE ANY EXISTING

CEILING, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.

AT NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT LIMITED TO ITEMS SUCH AS WALLS, NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS

CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AT HIS OWN COST.

3. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS

CLEARANCE, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.

2. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE

TO COMMENCING ANY CONSTRUCTION OR RENOVATION.

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR

A LICENSED OR CERTIFIED INSTALLER.

8. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION BY

7. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.

CONDUITS AND ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.

6. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.

5. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT.

LISTED.

DAMPER RATINGS SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL

4. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE

ARCHITECTURAL DRAWINGS FOR CEILING TYPES.

3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES. REFER TO

THE CONTRACTING OFFICER.

2. THE CONTRACTOR SHALL SUBMIT MECHANICAL SYSTEM INSTALLATION SHOP DRAWINGS FOR APPROVAL BY

CLEARANCE, INSTALLATION LOCATIONS AND ADDITIONAL ITEMS.

1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE

CAMP BONIFAS

245448

AS SHOWN ON DRAWINGS.

COOLER, VALVES, WATER HAMMER ARRESTERS, CONTROL, ACCESS DOORS AND ALL ASSOCIATED ACCESSORIES

AND VENT PIPING SYSTEM INCLUDING PLUMBING FIXTURES, INSTANTANEOUS WATER HEATER, ELECTRIC WATER

4. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW DOMESTIC COLD AND HOT WATER PIPING SYSTEM, SEWER

CONSTRUCTION TO VERIFY THAT THE HVAC SYSTEM WORKS PROPERLY.

3. PERFORM DALT (DUCT AIR LEAKAGE TEST) AND T.A.B (TESTING, ADJUSTING, AND BALANCING) AFTER

DOORS, EQUIPMENT SUPPORT AND ALL ASSOCIATED ACCESSORIES FOR HVAC SYSTEM AS SHOWN ON DRAWINGS.

CONTROLS, CO2 SENSOR, CONTROLLER, DIFFUSERS, GRILLES, DAMPERS, DUCTS, INSULATIONS, ACCESS

2. REPAIR THE VENTILATION SYSTEM BY INSTALLING NEW EXHAUST FANS, ENERGY RECOVERY VENTILATOR, ON DRAWINGS. REMOTE CONTROLLER INDICATORS AND LABELS SHALL BE IN ENGLISH.

DOORS, EQUIPMENT SUPPORT (CONC. PAD) AND ALL ASSOCIATED ACCESSORIES FOR HVAC SYSTEM AS SHOWN

& OUTDOOR UNITS, ELECTRIC WALL MOUNTED HEATERS, PIPES, VALVES, INSULATIONS, CONTROLS, ACCESS

1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW VRF DUCT-FREE SPLIT HEAT PUMP INDOOR

QTYITEM D E S C R I P T I O N ITEM QTY D E S C R I P T I O N

1 VARIABLE REFRIGERANT FLOW HEAT PUMP (OUTDOOR UNIT)

HPO

HP

VARIABLE REFRIGERANT FLOW HEAT PUMP3

E Q U I P M E N T S C H E D U L E S

EF

MOTOR

CAPACITY

ELECTRIC WALL HEATER EH

ELECTRIC POWER INPUT

COOLING CAPACITY

: 3.62 Amp, 208 V, 1 PH, 60 Hz

: 2,560 BTU/HR (750 W)

KIM, SM

M-3

NTS

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

1,041 RPM

: 115 V, 1 PH, 60 Hz, : 61.3 LPS (130 CFM) AT 62 Pa SP

ELECTRICAL RATING

COMPRESSOR

HEATING CAPACITY

COOLING CAPACITY

ELECTRICAL RATING

INPUT POWER

COMPRESSOR

HEATING CAPACITY

COOLING CAPACITY

: 208 V, 1 PH, 60 Hz

: 0.144 kW

: 742/671/600 CFM

: 8,000 W (27,300 BTU/HR)

: 7,090 W (24,200 BTU/HR)

MFR. GREENHECK MODEL NO. SP-A90-130-VG OR APPROVED EQUAL.

MFR. BROAN MODEL NO. 192 OR APPROVED EQUAL.

MFR. LG MODEL NO. ARNU243TNA4 OR APPROVED EQUAL.

ERV ENERGY RECOVERY VENTILATOR

VIBRATION ISOLATORS. UL LISTED.

GALVANIZED STEEL HOUSING IWTH ACOUSTICAL INSULATION, MOTOR SHALL BE MOUNTED ON

CEILING MOUNTED, CENTRIFUGAL DIRECT DRIVE TYPE, BACKDRAFT DAMPER, HEAVY-GAUGE

REQUIRMENTS.

ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT

THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY,

NOTE :

EQUIPMENT SCHEDULES

ELECTRICAL RATING

TANK VOLUME

MFR. ARISTON MODEL NO. GL8Ti OR APPROVED EQUAL.

IH

ELECTRICAL RATING

TANK VOLUME

MFR. ARISTON MODEL NO. GL4Ti OR APPROVED EQUAL.

: 12 Amp, 120 V, 1PH, 60Hz

: 3.8 GALLONS

INSTANTANEOUS WATER HEATER (FOR MALE)

INSTANTANEOUS WATER HEATER (FOR FEMALE)

: 12 Amp, 120 V, 1PH, 60Hz

: 7 GALLONS

NECESSARY ACCESSORIES. UL-LISTED.

TAMPERATURE/PRESSURE RELIEF VALVE, DISCHARGE TUNDISH, PIPE FITTINGS AND ALL

COPPER HEATING ELEMENT, GLASS-LINED TANK, EXPANSION VESSEL & NON-RETURN VALVE,

NECESSARY ACCESSORIES. UL-LISTED.

TAMPERATURE/PRESSURE RELIEF VALVE, DISCHARGE TUNDISH, PIPE FITTINGS AND ALL

COPPER HEATING ELEMENT, GLASS-LINED TANK, EXPANSION VESSEL & NON-RETURN VALVE,

IH

EXHAUST FAN (FOR TOILET)

NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.

CONTROLLER, WALL MOUNTED WIRE CO2 SENSOR, HANGING VIBRATION ISOLATORS AND ALL

FILTER WITH A MERV OF 13 WHEN TESTED IAW ASHRAE STANDARD 52.2), WALL MOUNTED WIRE

UNIT. BYPASS MODE WITH DAMPER, FILTERS (PRE FILTER WITH A MERV OF 8 AND FINAL

EXHAUST AIR STREAM. DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR

FAN, EQUIPPED WITH MOTORIZED DAMPER ON OUTDOOR AIR STREAM AND MOTORIZED DAMPER ON

FACTORY ASSEMBLED, INSTALLATION FLEXIBILITY, 3-SPEED SUPPLY FAN & 3-SPEED EXHAUST

ELECTRIC POWER INPUT

LOW

MEDIUM

HIGH

FAN CAPACITY

HEATING CAPACITY

COOLING CAPACITY

: 0.25 Kw, 208 V, 1 PH, 60 Hz

: 259 CFM @ 0.44 WG.ESP.

: 294 CFM @ 0.60 WG.ESP.

: 294 CFM @ 0.72 WG.ESP.

: 6,730 W (22,960 BTU/HR)

: 4,930 W (16,820 BTU/HR)

OR APPROVED EQUAL.

MFR. LG MODEL NO. LZ-H500NX W/ PQRCVSL0 & PES-C0RV0 (CONTROLLER & CO2 SENSOR)

MFR. LG MODEL NO. ARUM096BTE5 OR APPROVED EQUAL.

208 VOLTS, 3 PH, 60 Hz

: 40.1 AMP MCA / 60 AMP MOP

: 1 / INVERTER DC SCROLL

: 31,650 W (108,000 BTU/HR)

: 28,140 W (96,000 BTU/HR)

MANUFACTURE STANDARD ACCESSORIES. UL LISTED.

RCED-AIR HEATER, NICKEL CHROMIUM ELECTRIC HEATING ELEMENT, EQUIPPED WITH

AND WHITE COLOR POLYMERIC GRILLE FINISHED, BUILT-IN ADJUSTABLE THERMOSTAT.

THERMALLY PROTECTED MOTOR AND TRANSVERSE FLOW BLOWER. GALVANIZED STEEL HOUSING

THERMAL FUSE. QUIET FAN AND DOWN FLOW ACTION CIRCULATES AND HEAT RESISTANT.

CUT A HOLE IN A WALL TO FLUSH MOUNTING TYPE. OVER TEMPERATURE PROTECTED BY

3 YEARS WARRTENTY.

OPERATION, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES. ETL LISTED.

LOW AMBIENT CONDITIONS, ALL NECESSARY SENSOR FOR A SAFE AND TROUBLE FREE

VALVES, ADVANCED PROPORTIONAL INTEGRAL DERIVATIVE (PID) CONTROL TO OPERATES AT

CONNECTION PIPING KIT, REFRIGERANT SHUTOFF VALVES, VIBRATION ISOLATORS, SOLENOID

EXPANSION VALVES, OVER CURRENT RELAY, INVERTER OVERLOAD PROTECTION, MULTI

PRESSURE SWITCHES, WEATHER-PROOF, INVERTER COMPRESSOR, COMPLETE WITH ELECTRONIC

SPEED LINEARY TO FOLLOW THE VARIATION IN COOLING & HEATING REQUIREMENTS, HIGH

EVEN DURING DEFROST OPERATIONS, ELECTRONICALLY CONTROLLED AND CAPABLE OF CHANGING

VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT CAPABLE OF CONTINOUS HEATING

3 YEARS WARRTENTY.

MOUNTED WIRE CONTROLLER, AND ALL NECESSARY ACCESSORIES. ETL-LISTED.

CHANGES, CLEANABLE FILTERS, HANGING BRACKETS, WIRELESS REMOTE CONTROLLER, WALL

COOLING OR HEATING MODE TO MAINTAIN THE OPTIMUM ROOM TEMPERATURE DURING SEASON

MOTOR, ADJUSTABLE AIR LOUVERS FOR 4-WAY DISCHARGE, AUTOMATICALLY SWITCHES TO

TURBO FAN, TOTAL VIRUS FILTER, BUILT-IN CONDENSATE PUMP SYSTEM, BLDC INVERTER

AND HEATING. DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT.

VRF HEAT PUMP, ROUND FLOW, CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING

CAMP BONIFAS

REPAIR CHAPEL BLDG. NO. T-30

245448

EWC

ELECTRIC WATER COOLER

WITH AIR COOLED CONDENSER & COMPRESSOR SHALL CONFORM TO ADA/ARI STANDARD 1010.

BUILT-IN PRESSURE REGULATOR W/BOTTLE FILLING STATION. MECHANICALLY AIR COOLED

WALL MOUNTED TYPE, BUBBLER SHAL BE ACTIVATED BY DEPRESSING EITHER PUSH PADS AND

MFR. "ELKAY" MODEL LMABF8WS, OR APPROVED EQUAL.

POWER

CAPACITY

: 4.0 F.L.AMPS, 115 V, 1 PH, 60 HZ

: 30.3 LPH, 32.2°C TO 10°C.

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

KIM, SM

M-4 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

11,000

14,400

1,500 1,900

FEMALE

MALE

CLOSET

COMM/

SCALE = 1:50

NEW H.V.A.C PIPING ENLARGED PLAN

METAL PIPE TRAY

PIPE CHASE

SEE DETAIL 4 OF SHEET M-7 (TYP.)

CONNECTOR VIPER MANUFACTURER

REFRIGERANT PIPE Y-BRANCH

LINES (TYP.)

LIQUID & VAPOR

OUTDOOR UNIT

DUCT-FREE HEAT PUMP

HPO

LINE(TYP.)

DRAIN

LINES (TYP.)

LIQUID & VAPOR

OF SHEET M-7 (TYP.)

FOR DETAIL SEE 2

NEW CONC. PAD

(TYPICAL)

ACCESS DOOR

CEILING ACCESS DOOR DETAIL (TYP.)

AS REQUIRED

STL PLATE FRAME

75 Wx6 THK

& NUT

6 DIA BOLT

@ EACH CORNER

10GA. WIRE HANGER

CAM LATCH

(LIGHT WEIGHT METAL)

FINISH MATCH TO CEILING

14 GA STL ACCESS PANEL

PIANO HINGE

CONTINUOUS

TO CEILING)

(FINISH MATCH

16GA STEEL FRAME

CEILING

GWB

ACST OR

T

HP

(TYP OF 3)

CEILING MOUNTED, 4-WAY

DUCT-FREE HEAT PUMP

HP

PIPE SIZE

VAPOR LIQUID DRAINITEM NO.

HP

HPO

15.88 mm

25 mm12.7 mm 6.35 mm

ERV

25 mm

9.52 mm

15.88 mm 9.52 mm

NOTE :

CONDUITS, AND ALL NECESSARY ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.

5. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING,

SHALL BE PRESSURE TESTED & VACUUM TESTED.

PRESS-CONNECT FITTINGS, GROOVE JOINTS & MECHANICAL JOINTS. THE VRF SYSTEM

TO THE FOLLOWING: PUSH-ON FITTINGS, EXTRUDED FITTINGS, FLARE FITTINGS,

LIST OF FITTINGS AND JOINTS THAT ARE PROHIBITED INCLUDE BUT ARE NOT LIMITED

B31.5 REQUIREMENTS AND THE MANUFACTURER'S INSTALLATION REQUIREMENTS. THE

4. VRF SYSTEMS PIPING/TUBING SHALL HAVE ALL BRAZED CONNECTIONS THAT MEET ASME

SPEC BY A CERTIFIED INSTALLER.

3. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S

RECOMMENDATION.

2. REFRIGERANT PIPE SIZE & INSTALLATION SHALL BE AS PER MANUFACTURER'S

INSTALLATION.

1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PIPEWORK PRIOR TO PIPEWORK

ERV

VENTILATOR UNIT

ENERGY RECOVERY

HP

LINE(TYP.)

DRAIN

& ABOVE CEILING)

WIRING SHALL BE CONCEALED IN THE WALL

WIRING AND RECESSED CONDUIT (ALL CONTROL

RECESSED CONTROLLER WITH JUNCTION BOX,

M4

EH

ELECTRIC WALL HEATER

EH

ELECTRIC WALL HEATER

NEW H.V.A.C PIPING ENLARGED PLAN

CAMP BONIFAS

REPAIR CHAPEL BLDG. NO. T-30

OFFICE

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

KIM, SM

M-5 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

ACCESS DOOR

(TYP OF 2)

RETURN DIFFUSER

ROUND PAN

(TYP OF 3)

SUPPLY DIFFUSER

ROUND PAN

(TYP OF 2)

W/BIRDSCREEN

HOODED WALL CAP

OFF

C

OL

120 VAC

M

EA

SWITCH

"H-O-A"

EXHAUST FAN CONTROL

NOT TO SCALE

EF

EXHAUST FAN

EXHAUST FAN

HAND

AUTO

LADDER DIAGRAM

2. "HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION ENERGIZES THE EXHAUST FAN.

CONTINUOUSLY UNTIL MANUALLY STOPPED.

1. "HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS THE EXHAUST FAN

62 LPS

200 NCD

41 LPS

150 NCD

CAMP BONIFAS

REPAIR CHAPEL BLDG. NO. T-30

245448

SCALE = 1:50M5

OFFICE

CLOSET

COMM/

MALE

FEMALE

11,000

14,400

1,500 1,900

NOTE :

CONDUITS, AND ALL NECESSARY ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.

4. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING,

TYPES.

3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING

SPEC BY A CERTIFIED INSTALLER.

2. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S

INSTALLATION.

1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PIPEWORK PRIOR TO PIPEWORK

NEW H.V.A.C ENLARGED PLAN

41 LPS

150 NCD

41 LPS

150 NCD

62 LPS

200 NCD

ERV

VENTILATOR UNIT

ENERGY RECOVERY

O.A

C CS

200250

E.A

BDD

MD

VD

VD VD

VD VD

CONTROLLER

CO2 SENSOR

EF

EXHAUST FAN

EF

EXHAUST FAN

UL 181 AIR DUCT APPROVED (TYP.)

VAPOR BARRIER EXTERIOR COVER

+ INCOMBUSTIBLE POLYETHYLENE

NE 1000 CORE + POLY INSULATION

PE POLY ACOUSTICAL FLEXIBLE DUCT

BIRD SCREEN (TYP OF 2)

HOODED WALL CAP W/ STS METAL

STAINLESS STEEL SQUARE SHAPE

NEW H.V.A.C ENLARGED PLAN

50mm WATER METER

CLOSET

COMM/

B

C

A

REMARKS

RATING

FU

QTYSYMBOL

P.D.I

1-11

12-32 20

33-60 25

WATER HAMMER ARRESTER SCHEDULE

CONN.

PIPE

INSTRUCTIONS.

PER PDI-WH 201 AND MANUFACTURER'S

2. SIZE AND LOCATE WATER HAMMER ARRESTORS

COMPRESSION CHAMBER W/EXPANSION BELLOWS.

1. COPPER CONSTRUCTION PRESSURIZED

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

KIM, SM

M-6 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CAMP BONIFAS

REPAIR CHAPEL BLDG. NO. T-30

245448

KEY PLAN

SCALE = 1:50M6

ENLARGED PARTIAL PLANS

SEWER & VENT PIPING

NEW DOMESTIC WATER AND

PLUMBING FIXTURES SCHEDULE

PLUMBING FIXTURES QTY

COLD HOT TRAP VENT

REMARKS

1515LAVATORY

-15

50 32

SYMBOL

P-1

P-5 MAX.0.5 GPM @60 PSI

WATER CLOSET (F.T) 100

LOCAL PIPE CONNECTION

3.8 LITERS/FLUSH

505020P-3 1 -

1515 80 40P-8 1SERVICE SINK

URINAL

W/ INTEGRAL BACK

STAINLESS STEEL,

AUTOMATIC SENSOR

NOTE ON INSTALLATION OF PIPE INSULATION :

PIPE INSULATION IS COMPLETED.

FOR QUALITY INSPECTION WHEN THE INSTALLATION OF THE

4. THE CONTRACTOR SHALL INVITE THE MECHANICAL ENGINEER

WHEN TESTED IN ACCORDANCE WITH ASTM E84.

INDEX OF 25 AND A MAX. SMOKE DEVELOPED INDEX OF 50

FIRERESISTANT AND SHALL HAVE A MAXIMUM FLAME SPREAD

3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE AND

IN FM APP GUIDE.

2. INSULATION MATERIALS RECOGNIZED UNDER UL94 AND LISTED

GRADE 1, TYPE I OR II.

SPEC 23 07 00, AND SHALL COMPLY WITH ASTM C534/C534M,

1. INSULATION MATERIALS SHALL CONFORM TO TABLE1 OF OMA

NOTE :

VALVES AND WATER HAMMER ARRESTORS.

3. PROVIDE CEILING / WALL ACCESS PANEL FOR ISOLATION

PIPING) PRIOR TO PLUMBING PIPING INSTALLATION.

PIPING (HOT & COLD WATER PIPING, SEWER AND VENT

2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING

1. ALL PIPE LINES SHALL BE COPPER TUBE.

P-8

P-5

P-1

P-1

P-5

P-3

1,500 1,900

CLOSET

COMM/

1,500 1,900

100 FCO

NEW DOMESTIC WATER PIPING ENLARGED PARTIAL PLAN

MALE

FEMALE

MALE

80 VTR

50 FD

50 FD

SCALE = 1:50M6

NEW SEWER & VENT PIPING ENLARGED PARTIAL PLAN

P-8

P-5

P-1

P-1

P-3

P-5 A WATER HAMMER ARRESTER

A WATER HAMMER ARRESTER

SEE CIVIL DRAWING

NEW SEWER MAIN PIPE

CONN. TO UNDERGROUND

100mm SEWER LINE

SEE CIVIL DRAWING

NEW DOMESTIC WATER MAIN PIPE

CONN. TO UNDERGROUND

50mm DOMESTIC WATER LINE

(INSTALLATION UNDER THE SINK)

INSTANTANEOUS WATER HEATERIH

(INSTALLATION UNDER THE SINK)

INSTANTANEOUS WATER HEATERIH

EWC

WATER COOLER

ELECTRIC

FEMALE

EWC

WATER COOLER

ELECTRIC

KIM, SM

M-7

NTS

MECH. DETAILS - 1

FIN. GRADE

150 150

SECTION

PLAN

N F S M

150150ACTUAL EQUIPMENT SIZE

AT EXPOSED EDGES

20mm CHAMFERS#4 @300 O.C.

50 CLR

CONC. PAD

150 150 150150ACTUAL EQUIPMENT SIZE

A C

T U

A L

E Q

U I

P M

E N

T

S I

Z E

EQUIPMENT UNIT

GRAVEL BASE

150mm THK.

1 INDOOR HEAT PUMP UNIT INSTALLATION DETAIL

SECTION

REMOTE CONTROL

FULL BOX

ELECTRICAL CONC. BOX

CEILING

ROOM

(CEILING CASETTE 4-WAY TYPE)

INDOOR HEAT PUMP

ENLARGED SECTION

ROOM

R.L/R.G

DRAIN PIPE

CEILING

PUMP

HEAT

(TYP)

HANGERMIN 300

FOR SERVICE

ACCESS DOOR

600x600 CEILING

CABLE

POWER

CEILING

R.L/R.G

DRAIN PIPE

DRRAIN HOSE

(CEILING CASETTE 4-WAY TYPE)

INDOOR HEAT PUMP

MAX.700

(TYP.)

HANGER

SLOPE

1/50-1/100

SEE

Y JOINT DETAIL

LIQUID PIPE 6.35A/ 9.52A

TAPE

Y-JOINT

INLET

INSULATION REFRIGERANT LIQUID/ GAS PIPE

COVER

OUTLET

SECTION

GAS PIPE 12.7/ 15.88

PIPE INSULATION:19T

EPDM

VCTF-SB1.25x2C

CABLE LINE

CONCRETE PAD DETAIL

WITH MANUFACTURER.

FINAL PAD SIZE SHALL BE CORDINATED

6" (150mm) LARGER THAN UNIT SIZE AND

ALL EQUIPMENT CONC PAD SIZE SHALL BE

NOTE :

FILTER DRIER

LIQUID LINE

CONDENSATE DRAIN

DRAIN PUMP

CONDENSATE

THERMOSTAT

SWITCH

DISCONNECT

FUSED

VAPOR LINE

(OUTDOOR UNIT)

DUCT-FREE HEAT PUMP

(INDOOR UNIT)

DUCT-FREE HEAT PUMP

SWITCH

FUSED DISCONNECT

WEATHERPROOF

ISOLATORS

SPRING

HANGER ROD

HANGER PLATE

VENTILATOR

ENERGY RECOVERY

E.R.V EQUIPMENT INSTALLATION

TYPICAL REFRIGERANT PIPING DIAGRAM3

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CAMP BONIFAS

NOTE :

FROM THE FLOOR (OR PAD)

HEATER SHALL BE DROPPED UP MIN.ƒ" CLEARANCE

•" HOSE BIBB

SERVICE LINE

COLD WATER

AND PRESSURE RELIEF VALVE

COMBINATION TEMPERATURE

MAXIMUM 2" NIPPLE

SUPPLY LINE

HOT WATER

VACUUM BREAKER

ADAPTER (TYP)

WATER HEATER

ELECTRIC

DRAIN

TO NEAREST

RELIEF DRAIN

PIPE

I

N C

L U

D I

N G

I

N S

U L

A T I

O N

P I

P E

D I

A m m

PIPE SLEEVE-THRU FOOTING

EXTERIOR INTERIOR

MASONRY WALL

CONCRETE OR

INSULATION

PIPE WITHOUT

ALL AROUND

MIN. 7 CLEARANCE

METAL JACKET

INSULATION

SEALANT #10

PIPE SLEEVE

BACK UP MATERIAL

INSULATION

PIPE WITH

ANCHOR

RUBBER OR PLASTIC)

FLEXIBLE FOAM

(CLOSED CELL

BACK UP MATERIAL

SEALANT #2

MEMBRANE

WATERPROOFING

CLAMPING FLANGE

WATERPROOFING

PIPE

2 PIPE SLEEVE-THRU INTERIOR WALL

METAL JACKET

SLEEVE

INSULATION

INSULATION

PIPE WITHOUT

SEALANT #2

ALL AROUND

7 MIN CLEARANCE

INSULATION

PIPE WITH

BACK UP MATERIAL

50SEALANT #2

(TYP)

METAL BAND

SLEEVE

CEILING

MASONRY WALL

CONCRETE OR

RUBBER OR PLASTIC)

FLEXIBLE FOAM

(CLOSED CELL

BACK UP MATERIAL

3 PIPE SLEEVE-THRU FLOOR

NOTES

INSTRUCTIONS.

IN ACCORDANCE WITH MANUFACTURER'S LISTED INSTALLATION

2. FIRESTOPPING SHALL BE PROVIDED AND SHALL BE INSTALLED

EQUIPMENT ROOMS.

FLOORS OR CEILINGS, EXCEPT IN BOILER, UTILITY OR

WHERE EXPOSED PIPING, BARE OR INSULATED PASSES THROUGH

1. ESCUTCHEONS SHALL BE PROVIDED AT ALL FINISHED SURFACES

P I

P E

PIPE WITH INSULATIONPIPE WITHOUT INSULATION

METAL JACKET

SLEEVE

PLASTIC)

RUBBER OR

FLEXIBLE FOAM

(CLOSED CELL

BACK UP MATERIAL

7 MIN CLEARANCE

INSULATION

METAL BAND (TYP)

SEALANT #2

MATERIAL

BACK UP

FIN FLOOR

CEMENT

CLIP TYPE

SPRING

ESCUTCHEON

SLEEVE

PIPE SLEEVE-THRU FLOOR WITH WATERPROOFING

P I

P E

PIPE WITHOUT INSULATION PIPE WITH INSULATION

INSULATION

FLOOR

METAL JACKET

METAL BAND

WATERPROOFING

PLASTIC)

RUBBER OR

FLEXIBLE FOAM

(CLOSED CELL

MATERIAL

BACK UP

OR 450 GMS COPPER

20 KG/SQ. METER

FLASHING

SEALANT #2

FLOOR CLEANOUT

NOTES

STAINLESS STEEL FLUSH TYPE ACCESS COVER PLATE.

2. CHROMIUM-PLATED BRONZE, NICKEL BRONZE, NICKEL BRASS OR

1. WATERPROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.

PACKING

TARRED JUTE

WHEN NOT THRU RUN

PLUG Y-BRANCH

3mm BEND

GASKET

NEOPRENESCORIATED COVER, SEE NOTE 2

ADJUSTABLE HOUSING

TWO PIECE THREADED

WATERPROOF MEMBRANE

Y-BRANCH

PIPE

CAST IRON

WATER SERVICE

FFL

REDUCING TEE

UNION

13 FEMALE ADAPTER

WATER METER

PRESSURE GAUGE

MALE ADAPTER

GATE VALVE

MALE ADAPTER

20 HOSE BIBB

SEE DETAIL ON THIS SHEET

PIPE SLEEVE-THRU FOOTING

ON THIS SHEET

FLOOR SEE DETAIL

PIPE SLEEVE-THRU

G.L

CIVIL DRAWING

ELEVATION SEE

FOR INVERT

MASTIC

WATERPROOF

REDUCING TEE

INSTALLATION

VERTICAL

SUITABLE FOR

STRAINER

8 WATER HAMMER ARRESTOR

PLAN FRONT ELEVATION

6 PIPE SUPPORT INSTALLATION

BOLT (TYP)

19mm EXPANSION

CLAMP (TYP)

PIPE

WATER METER

MONITORED TYPE

DDC

PIPE

CONCRETE WALLCONCRETE WALL

CLAMP

PIPE

TYPE

D

C

B

A

HEIGHT DIAMETER

DIMENSION SHALL BE

VARIED DEPEND UPON

MFR

CAPACITY(FU)

61-113

33-60

12-32

1-11

FIXTURE UNIT

H E I

G H

T

COPPER SHELL

THREADED PLUG

DIAMETER

COPPER ADAPTOR

BELLOWS

FOR LOCATION AND SIZE

20mm OR 25mm SEE DWGS

DISPLACEMENT CUSHION

PRESSURE PNEMATIC

DISPLACEMENT FLUID

HYDRAULIC

ORIFICE

FLOW CONTROL

CONN.SIZE

BRANCH SUPPLY

FROM

LAST FIXTURE

TO

KIM, SM

M-8

NTS

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

MECH. DETAILS - 2

ELECTRIC WATER HEATER

CAMP BONIFAS

File details come from the government source that posted it. Updated .