KIM, SM
M-1
NTS
245448 o
ACCU AIR COOLED CONDENSING UNIT
ACLD AIR COOLED
ACU AIR CONDITION UNIT (S)
ACV ALARM CHECK VALVE
ADP APPARATUS DEW POINT
AHU AIR HANDLING UNIT
AIR COND AIR CONDITION (-ING,-ED)
AL ALUMINUM
ALT ALTITUDE
AMB AMBIENT
AMP AMPERE(AMP, AMPS)
APPROX APPROXIMATE
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BARO BAROMETER(-TRIC)
BARO PR PRESSURE, BAROMETRIC
BHP BRAKE HORSEPOWER
BP BOILING POINT
CAP CAPACITY
CCW COUNTER CLOCKWISE
CHW CHILLED WATER
CKT CIRCUIT
CLASS CLASSIFICATION
CLG LOAD COOLING LOAD
COEF COEFFICIENT
CONN CONNECTION
CONT CONTINUE
C
CMH CUBIC METER PER HOUR
CU M CUBIC METER
CENTIGRADE/ CELCIUS
CFCI
CONTRACTOR INSTALLED
CONTRACTOR FURNISHED
CIP CAST IRON PIPE
CWP
CU MM CUBIC MILLIMETER
Cv COEFFICIENT, VALVE FLOW
CW CLOCKWISE OR COLD WATER
CIRCULATING WATER PUMP
DB DECIBEL OR DRY BULB
COMPRESSORCPRSR
DBT DRY BULB TEMPERATURE
DCWS DOMESTIC COLD WATER SUPPLY
DEG or ° DEGREE
DFW DIESEL OIL
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER SUPPLY
DHWR
DHWS
DIRECT EXPANSIONDX
DRY PIPE VALVEDPV
DOUBLE POLE DOUBLE THROWDPDT
DEWPOINT TEMPERATUREDPT
DIVISIONDIV
DIFFERENCEDIFF
DIAGRAMDIAG
DIAMETERDIA or
DWG DRAWING
EXPANSION JOINTEXPJT
ENTERING WATER TEMPEWT
EVAPORAT (-E,-ING,-ED,-OR)EVAP
EXTERNAL STATIC PRESSUREESP
EXPLOSION PROOFEP
EQUIPMENTEQPT
ENTERINGENT
EFFICIENCYEFF
EQUIVALENT DIRECT RADIATIONEDR
ECONOMIZERECON
ECCENTRICECC
ENTERING AIR TEMPERATUREEAT
FUEL OILFO
FA FACE AREA OR FRESH AIR
FHC FIRE HOSE CABINET
FHY FIRE HYDRANT
FLA FULL LOAD AMPERES
F FARENHEIT
FLR FLOOR
FEED WATER PUMPFWP
FACE VELOCITYFVEL
FLUSH VALVEFV
FRP
FREQUENCYFREQ
FEMALE PIPE THREADFPT
FIBERGLASS REINFORCED PLASTIC
Ft or ' FEET
FXTR FIXTURE
GALVANIZED STEELGALVS
GAGE OR GAUGEGA
GR GRAMS
GOVERNMENT INSTALLED
GOVERNMENT FURNISHED GFGI
CONTRACTOR INSTALLED
GOVERNMENT FURNISHEDGFCI
GAL GALLONS
GALLONS PER MINUTEGPM
HERTZHZ
HORIZONTALHORIZ
HOT WATER HEATERHWH
HOT WATERHW
HOUR(S)HR
HORSEPOWERHP
MERCURYHG
HEADHD
HB HOSE BIBB
DIAMETER, INSIDEID
ISOMETRICISO
IRON PIPE SIZEIPS
J JOULE
K THERMAL CONDUCTIVITY
K THERMAL CONDUCTIVITY
kG kCAL/HR
KILOGRAM
kG/SQ CM KILOGRAM PER SQ. CENTIMETER kG/SQ CM A
KILOCALORIE PER HOUR
(ABSOLUTE)
KILOGRAM PER SQ. CENTIMETER
kG/SQ CM G
(GAUGE)
KILOGRAM PER SQ. CENTIMETER
kG/SM KILOGRAM PER SQ. METER kG/SM A kG/SM G
(ABSOLUTE)
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (GAGE)
kW KILOWATT kWH KILOWATT HOUR kJ KILOJOULE kPa KILO PASCAL
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LG LENGTH
LH LATENT HEAT
LWT LEAVING WATER TEMPERATURE
LIQUID LINELL
L LITERS
LPD LITERS PER DAY
LPH LITERS PER HOUR
LPS
LM LINEAR METER
LITERS PER SECOND
LAV LAVATORY
LPM LITERS PER MINUTE
LT LAUNDRY TRAY
NUMBERNO
NORMALLY OPENN.O.
NOT IN CONTRACTNIC
NORMALLY CLOSEDN.C.
NOISE CRITERIANC
NCK
MAX
NOT TO SCALENTS
MIN
MPH
M METERS
MAXIMUM
MINIMUM OR MINUTE
METERS PER HOUR
MPS METERS PER SECOND
MM MILLIMETER
NPT NATIONAL TAPER PIPE (THREAD)
NOT APPLICABLEN/A
NECK
MECH MECHANICAL
OS&Y OUTSIDE SCREW & YOKE
OD
OAIL OUTSIDE AIR INTAKE LOUVER
OA OUTSIDE AIR
OUTSIDE DIAMETER
OPNG OPENING
OXY OXYGEN
PERCENT
PRESSURE REDUCING VALVEPRV
PARTS PER MILLIONPPM
POINT OF CONNECTIONPOC
PLUMBINGPLMB
PHASE (ELECTRIC)PH
PRESSURE GAGEPG
PD
POLEP
PRESSURE DROP OR DIFFERENCE
Pa PASCAL
POL PETROLEUM, OIL AND LUBRICANTS
QUANTITYQTY
QUARTQT
REFRIGERATION TONRT
REVOLUTIONS PER MINUTERPM
RADIATORRDTR
RETURN AIRRA
THERMAL RESISTANCER
REFRIGERANT (134A, 22, ETC)R134A,R22
RH RELATIVE HUMIDITY
SUPPLY AIRSA
SYMBOLSYM
SUCTIONSUCT
STORAGESTOR
STEELSTL
STANDARDSTD
STEAMST
SAYBOLT SECONDS UNIVERSALSSU
STAINLESS STEELSST
SAYBOLT SECONDS FUROLSSF
SQUARESQ
SPECIFICATIONSPEC
SINGLE POLE DOUBLE THROWSPDT
SM
LPH, STANDARD CONDITIONSSLPH
LPS, STANDARD CONDITIONSSLPS
SG
SLPD LPD, STANDARD CONDITIONS
SL SENSIBLE LOAD
SH SENSIBLE HEAT
SPECIFIC GRAVITY
SF SAFETY FACTOR
SEC SECOND
SCH SCHEDULE
STATIC PRESSURE
SQUARE METER
SP
SBM
SAN SANITARY
SUBMERSIBLE
TYPICALTYP
THERMOSTATTSTAT
TONS OF REFRIGERATIONTONS
THICKNESSTHK
THERMOMETERTHERM
TEMPERATURETEMP
TEMPERATURE DIFFERENCETD
UNIT HEATERUH
HEAT TRANSFER COEFFICIENTU
WTRPRF
WT
WSHR
WITHW/
WH
WIDTHWD
WCLD
WC
WBT
WB
WATTW
VP
VOL
VISC
VERTICALVERT
VENTILATIONVENT
VELOCITYVEL
VARIABLE AIR VOLUMEVAV
VAC VACUUM
VLV VALVE
V VOLT
WATERPROOF
WEIGHT
WASHER
WATTHOUR OR WATER HEATER
WATER-COOLED
WATER CLOSET
WET BULB TEMPERATURE
WET BULB
PRESSURE, DYNAMIC(VELOCITY)
VOLUME
VISCOSITY
VTR VENT THRU ROOF
UR URINAL
A B B R E V I A T I O N S
MECHANICAL MATERIAL INDICATIONS AND SYMBOLS
FS
VFM
OFM
AVA
PRESSURE RELIEF
TEMPERATURE
EXPANSION LOOP
EXPANSION JOINT
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR VENT, AUTOMATIC
SQUARE HEAD BALANCING COCK
QUICK OPENING
NEEDLE
LOCK SHIELD
FLEXIBLE CONNECTOR
FLOWMETER, ORIFICE
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE GAUGE AND COCK
STRAINER
THERMOMETER
PRESSURE REDUCING
RELIEF OR SAFETY
SLEEVE
BLOW OFF STRAINER
INLINE PUMP
SAFETY
FLOAT
valves, special duty
S
M
GATE, NORMALLY CLOSED
GLOBE
SOLENOID
3 WAY MANUAL
GATE, NORMALLY OPEN
PLUG
MOTOR OPERATED GATE
MOTOR OPERATED GLOBE
3 WAY ELECMOTOR CONTROL
3 WAY AIR MOTOR CONTROLLER
HOSE GATE
HOSE GLOBE
POST INDICATOR
OS Y
ANGLE GLOBE
ANGLE GATE
SWING GATE CHECK
S
M
P
M
M
ALARM CHECK
DRY PIPE
DELUGE
PREACTION
TAMPER DETECTION SWITCH
QUICK OPENING DEVICE
NON-RISING STEM
DIAPHRAGM
SOLENOID
MOTOR ELECTRIC
valve actuators fittings
TEE, SINGLE SWEEP
UNION, SCREWED
UNION, FLANGED
CONNECTION, TOP
ELBOW, 90°
ELBOW, TURNED UP
ELBOW, TURNED DOWN
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
REDUCER, CONCENTRIC
(STRAIGHT, INVERT)
REDUCER, ECCENTRIC
(STRAIGHT, DOWN)
REDUCER, ECCENTRIC
TEE
ELBOW, 45°
LATERAL
SOLVENT CEMENT
BELL AND SPIGOT
SCREWED
FLANGED
WELDED
SOLDERED/BRAZED
M
NS
BUTTERFLY
BALL
DIAPHRAGM
GATE
INDICATING BUTTERFLY
KEY OPERATED
CHECK
SIDEWALL SPRINKLER
UPRIGHT SPRINKLER
DELUGE VALVE
WALL MOUNTED TEST HEADER
FIRE ALARM BELL
HOSE STATION DRY STANDPIPE
MINI HORN
HORN SPEAKER
WALL HYDRANT 2 HOSE OUTLET
SMOKE DETECTOR
PENDENT SPRINKLER DROP NIPPLE
NIPPLED UP UPRIGHT SPRINKLER
OUTSIDE SPRINKLER
CUTTING POINT
CAP
NON-SPRINKLERED SPACE
RISER
(SEE SPRINKLER SCHEDULE)
PENDENT SPRINKLER
CONNECTION (2-WAY SHOWN)
SIAMESE FIRE DEPARTMENT
CONNECTION
SINGLE FIRE DEPARTMENT
valves
POTABLE COLD WATER
POTABLE HOT WATER
POTABLE HOT WATER RETURN
PIPE SLEEVE
BACKFLOW PREVENTER
PITCH OR PIPE, UP(U), DOWN(D)
VENT THRU ROOF
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
PIPE SLEEVE WITH FIRE STOPPING
HOSE BIBB
FLOOR SINK (200mm x 200mm)
HOT WATER (60°C)
HOT WATER (82.22°C)
VENT
SANITARY SEWER
COMPRESSED AIR
FUEL OIL SUPPLY
FUEL OIL RETURN
FLOOR DRAIN WITH CLEANOUT
FLOOR DRAIN WITH DEEP TRAP
FLOOR DRAIN WITH NO TRAP
FLOOR DRAIN WITH TRAP TIME
FD
FCO
SCO
200x200
FIRE PROTECTION WATER SUPPLY
MAIN SUPPLY SPRINKLER
WET STANDPIPE
DRY STANDPIPE
COMBINATION STANDPIPE
plumbing sprinkler
DSP
WSP
CSP
S
F
PLAN ELEV
82.22°C
60°C
S
A
FOS
FOR
RD
RS
RL
D
CWS
CWR
LPC
BBD
PC
VPD
MU
FOD
FOV
FOG
FOS
FOR
HWS
M
HCS
HCR
FILL
MU
HWR
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
VACUUM PUMP DISCHARGE
MAKE UP WATER
FUEL OIL DRAIN
FUEL OIL TANK VENT
FUEL OIL GAUGE
FUEL OIL SUPPLY
FUEL OIL RETURN
CONTROL AIR MAIN
DUAL TEMPERATURE RETURN
FILL LINE
MAKE UP WATER
DUAL TEMPERATURE SUPPLY
WATER SUPPLY
LOW TEMPERATURE HOT
WATER RETURN
LOW TEMPERATURE HOT
SPLITTER DAMPER
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
dampers piping heating air conditioning and refrigeration
DU 13mm
47.2
94.4
DG
300x150
500/300L
R
AD
FC
SG
SR
RG
RR
810mm x 400mm
810mm x 400mm
810mm x 400mm
EG
ER
810mm x 400mm
DIRECTION OF FLOW
FLEXIBLE CONNECTION
TRANSITION
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN
RISE(R), DOWN(D)
CHANGE OF ELEVATION
VERTICAL OR HORIZONTAL
ACCESS DOOR,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
OUTSIDE AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
SUPPLY AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
SECTION, NEGATIVE PRESS.,
RETURN OR EXHAUST AIR DUCT
SUPPLY OR RETURN
FLEXIBLE AIR DUCT,
TRANSITION
SQUARE TO ROUND
REGISTER, CEILING
EXHAUST AIR GRILLE OR
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
RETURN AIR GRILLE OR
OR REGISTER, CEILING
SUPPLY AIR MODULAR DIFFUSER
DOOR GRILLE (300mmx150mmH)
(500mmWx300mmH, 94.4 LPS)
LOUVER, DOOR OR WALL
(13mm, 47.2 LPS)
DOOR UNDERCUT
duct works grilles, registers and diffusers
LEGEND & ABBREVIATION
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CAMP BONIFAS
REPAIR CHAPEL BLDG. NO. T-30
A. REPAIR/MAINTENANCE (K-WORK)
SCOPE OF WORK
NOTE :
KIM, SM
M-2
NTS
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
GENERAL NOTES & SCOPE OF WORK
MECHANICAL GENERAL NOTES
GOVERNMENT.
ACTIVITIES, AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE
16. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION
SHUT-OFF VALVE WITHIN 1M OF THE UNIT.
15. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH
WATER BEING FLUSHED IS CLEAR AS TAP WATER.
14. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL ALL
PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.
RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT.
13. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR USE
CREATE CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.
PIPING RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY
12. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1/4 INCH PER 1 FOOT. INSULATE ALL SEWER
GYPBOARD OR CONCEALED CEILINGS.
THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH
12"x12" ACCESS PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE THAT
DETECTOR, BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION
IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE
11. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS
PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.
10. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC
BALANCING (TAB) REPORT SHALL BE SUBMITTED TO THE COR FOR REVIEW AND APPROVAL.
TECHNICAL SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND
ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL. O & MA STANDARD
9. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT
AND SUBMITTED TO THE CONTRACTING OFFICER FOR APPROAL.
DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS
8. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH
PROJECT. THE DETAILS SHALL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK.
7. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS
CONTRACTING OFFICER.
6. THE CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE
SHALL BE REPAIRED OR REPLACED BY THIS CONTRACTOR AT HIS OWN COST.
EQUIPMENT, DUCT WORK, PIPING ETC. ANY DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT
5. CONNECTION TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE ANY EXISTING
CEILING, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.
AT NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT LIMITED TO ITEMS SUCH AS WALLS, NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS
CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AT HIS OWN COST.
3. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS
CLEARANCE, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
2. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE
TO COMMENCING ANY CONSTRUCTION OR RENOVATION.
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR
A LICENSED OR CERTIFIED INSTALLER.
8. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION BY
7. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
CONDUITS AND ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.
6. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.
5. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT.
LISTED.
DAMPER RATINGS SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL
4. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE
ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES. REFER TO
THE CONTRACTING OFFICER.
2. THE CONTRACTOR SHALL SUBMIT MECHANICAL SYSTEM INSTALLATION SHOP DRAWINGS FOR APPROVAL BY
CLEARANCE, INSTALLATION LOCATIONS AND ADDITIONAL ITEMS.
1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE
CAMP BONIFAS
245448
AS SHOWN ON DRAWINGS.
COOLER, VALVES, WATER HAMMER ARRESTERS, CONTROL, ACCESS DOORS AND ALL ASSOCIATED ACCESSORIES
AND VENT PIPING SYSTEM INCLUDING PLUMBING FIXTURES, INSTANTANEOUS WATER HEATER, ELECTRIC WATER
4. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW DOMESTIC COLD AND HOT WATER PIPING SYSTEM, SEWER
CONSTRUCTION TO VERIFY THAT THE HVAC SYSTEM WORKS PROPERLY.
3. PERFORM DALT (DUCT AIR LEAKAGE TEST) AND T.A.B (TESTING, ADJUSTING, AND BALANCING) AFTER
DOORS, EQUIPMENT SUPPORT AND ALL ASSOCIATED ACCESSORIES FOR HVAC SYSTEM AS SHOWN ON DRAWINGS.
CONTROLS, CO2 SENSOR, CONTROLLER, DIFFUSERS, GRILLES, DAMPERS, DUCTS, INSULATIONS, ACCESS
2. REPAIR THE VENTILATION SYSTEM BY INSTALLING NEW EXHAUST FANS, ENERGY RECOVERY VENTILATOR, ON DRAWINGS. REMOTE CONTROLLER INDICATORS AND LABELS SHALL BE IN ENGLISH.
DOORS, EQUIPMENT SUPPORT (CONC. PAD) AND ALL ASSOCIATED ACCESSORIES FOR HVAC SYSTEM AS SHOWN
& OUTDOOR UNITS, ELECTRIC WALL MOUNTED HEATERS, PIPES, VALVES, INSULATIONS, CONTROLS, ACCESS
1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW VRF DUCT-FREE SPLIT HEAT PUMP INDOOR
QTYITEM D E S C R I P T I O N ITEM QTY D E S C R I P T I O N
1 VARIABLE REFRIGERANT FLOW HEAT PUMP (OUTDOOR UNIT)
HPO
HP
VARIABLE REFRIGERANT FLOW HEAT PUMP3
E Q U I P M E N T S C H E D U L E S
EF
MOTOR
CAPACITY
ELECTRIC WALL HEATER EH
ELECTRIC POWER INPUT
COOLING CAPACITY
: 3.62 Amp, 208 V, 1 PH, 60 Hz
: 2,560 BTU/HR (750 W)
KIM, SM
M-3
NTS
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
1,041 RPM
: 115 V, 1 PH, 60 Hz, : 61.3 LPS (130 CFM) AT 62 Pa SP
ELECTRICAL RATING
COMPRESSOR
HEATING CAPACITY
COOLING CAPACITY
ELECTRICAL RATING
INPUT POWER
COMPRESSOR
HEATING CAPACITY
COOLING CAPACITY
: 208 V, 1 PH, 60 Hz
: 0.144 kW
: 742/671/600 CFM
: 8,000 W (27,300 BTU/HR)
: 7,090 W (24,200 BTU/HR)
MFR. GREENHECK MODEL NO. SP-A90-130-VG OR APPROVED EQUAL.
MFR. BROAN MODEL NO. 192 OR APPROVED EQUAL.
MFR. LG MODEL NO. ARNU243TNA4 OR APPROVED EQUAL.
ERV ENERGY RECOVERY VENTILATOR
VIBRATION ISOLATORS. UL LISTED.
GALVANIZED STEEL HOUSING IWTH ACOUSTICAL INSULATION, MOTOR SHALL BE MOUNTED ON
CEILING MOUNTED, CENTRIFUGAL DIRECT DRIVE TYPE, BACKDRAFT DAMPER, HEAVY-GAUGE
REQUIRMENTS.
ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT
THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY,
NOTE :
EQUIPMENT SCHEDULES
ELECTRICAL RATING
TANK VOLUME
MFR. ARISTON MODEL NO. GL8Ti OR APPROVED EQUAL.
IH
ELECTRICAL RATING
TANK VOLUME
MFR. ARISTON MODEL NO. GL4Ti OR APPROVED EQUAL.
: 12 Amp, 120 V, 1PH, 60Hz
: 3.8 GALLONS
INSTANTANEOUS WATER HEATER (FOR MALE)
INSTANTANEOUS WATER HEATER (FOR FEMALE)
: 12 Amp, 120 V, 1PH, 60Hz
: 7 GALLONS
NECESSARY ACCESSORIES. UL-LISTED.
TAMPERATURE/PRESSURE RELIEF VALVE, DISCHARGE TUNDISH, PIPE FITTINGS AND ALL
COPPER HEATING ELEMENT, GLASS-LINED TANK, EXPANSION VESSEL & NON-RETURN VALVE,
NECESSARY ACCESSORIES. UL-LISTED.
TAMPERATURE/PRESSURE RELIEF VALVE, DISCHARGE TUNDISH, PIPE FITTINGS AND ALL
COPPER HEATING ELEMENT, GLASS-LINED TANK, EXPANSION VESSEL & NON-RETURN VALVE,
IH
EXHAUST FAN (FOR TOILET)
NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.
CONTROLLER, WALL MOUNTED WIRE CO2 SENSOR, HANGING VIBRATION ISOLATORS AND ALL
FILTER WITH A MERV OF 13 WHEN TESTED IAW ASHRAE STANDARD 52.2), WALL MOUNTED WIRE
UNIT. BYPASS MODE WITH DAMPER, FILTERS (PRE FILTER WITH A MERV OF 8 AND FINAL
EXHAUST AIR STREAM. DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR
FAN, EQUIPPED WITH MOTORIZED DAMPER ON OUTDOOR AIR STREAM AND MOTORIZED DAMPER ON
FACTORY ASSEMBLED, INSTALLATION FLEXIBILITY, 3-SPEED SUPPLY FAN & 3-SPEED EXHAUST
ELECTRIC POWER INPUT
LOW
MEDIUM
HIGH
FAN CAPACITY
HEATING CAPACITY
COOLING CAPACITY
: 0.25 Kw, 208 V, 1 PH, 60 Hz
: 259 CFM @ 0.44 WG.ESP.
: 294 CFM @ 0.60 WG.ESP.
: 294 CFM @ 0.72 WG.ESP.
: 6,730 W (22,960 BTU/HR)
: 4,930 W (16,820 BTU/HR)
OR APPROVED EQUAL.
MFR. LG MODEL NO. LZ-H500NX W/ PQRCVSL0 & PES-C0RV0 (CONTROLLER & CO2 SENSOR)
MFR. LG MODEL NO. ARUM096BTE5 OR APPROVED EQUAL.
208 VOLTS, 3 PH, 60 Hz
: 40.1 AMP MCA / 60 AMP MOP
: 1 / INVERTER DC SCROLL
: 31,650 W (108,000 BTU/HR)
: 28,140 W (96,000 BTU/HR)
MANUFACTURE STANDARD ACCESSORIES. UL LISTED.
RCED-AIR HEATER, NICKEL CHROMIUM ELECTRIC HEATING ELEMENT, EQUIPPED WITH
AND WHITE COLOR POLYMERIC GRILLE FINISHED, BUILT-IN ADJUSTABLE THERMOSTAT.
THERMALLY PROTECTED MOTOR AND TRANSVERSE FLOW BLOWER. GALVANIZED STEEL HOUSING
THERMAL FUSE. QUIET FAN AND DOWN FLOW ACTION CIRCULATES AND HEAT RESISTANT.
CUT A HOLE IN A WALL TO FLUSH MOUNTING TYPE. OVER TEMPERATURE PROTECTED BY
3 YEARS WARRTENTY.
OPERATION, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES. ETL LISTED.
LOW AMBIENT CONDITIONS, ALL NECESSARY SENSOR FOR A SAFE AND TROUBLE FREE
VALVES, ADVANCED PROPORTIONAL INTEGRAL DERIVATIVE (PID) CONTROL TO OPERATES AT
CONNECTION PIPING KIT, REFRIGERANT SHUTOFF VALVES, VIBRATION ISOLATORS, SOLENOID
EXPANSION VALVES, OVER CURRENT RELAY, INVERTER OVERLOAD PROTECTION, MULTI
PRESSURE SWITCHES, WEATHER-PROOF, INVERTER COMPRESSOR, COMPLETE WITH ELECTRONIC
SPEED LINEARY TO FOLLOW THE VARIATION IN COOLING & HEATING REQUIREMENTS, HIGH
EVEN DURING DEFROST OPERATIONS, ELECTRONICALLY CONTROLLED AND CAPABLE OF CHANGING
VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT CAPABLE OF CONTINOUS HEATING
3 YEARS WARRTENTY.
MOUNTED WIRE CONTROLLER, AND ALL NECESSARY ACCESSORIES. ETL-LISTED.
CHANGES, CLEANABLE FILTERS, HANGING BRACKETS, WIRELESS REMOTE CONTROLLER, WALL
COOLING OR HEATING MODE TO MAINTAIN THE OPTIMUM ROOM TEMPERATURE DURING SEASON
MOTOR, ADJUSTABLE AIR LOUVERS FOR 4-WAY DISCHARGE, AUTOMATICALLY SWITCHES TO
TURBO FAN, TOTAL VIRUS FILTER, BUILT-IN CONDENSATE PUMP SYSTEM, BLDC INVERTER
AND HEATING. DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT.
VRF HEAT PUMP, ROUND FLOW, CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING
CAMP BONIFAS
REPAIR CHAPEL BLDG. NO. T-30
245448
EWC
ELECTRIC WATER COOLER
WITH AIR COOLED CONDENSER & COMPRESSOR SHALL CONFORM TO ADA/ARI STANDARD 1010.
BUILT-IN PRESSURE REGULATOR W/BOTTLE FILLING STATION. MECHANICALLY AIR COOLED
WALL MOUNTED TYPE, BUBBLER SHAL BE ACTIVATED BY DEPRESSING EITHER PUSH PADS AND
MFR. "ELKAY" MODEL LMABF8WS, OR APPROVED EQUAL.
POWER
CAPACITY
: 4.0 F.L.AMPS, 115 V, 1 PH, 60 HZ
: 30.3 LPH, 32.2°C TO 10°C.
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
KIM, SM
M-4 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
11,000
14,400
1,500 1,900
FEMALE
MALE
CLOSET
COMM/
SCALE = 1:50
NEW H.V.A.C PIPING ENLARGED PLAN
METAL PIPE TRAY
PIPE CHASE
SEE DETAIL 4 OF SHEET M-7 (TYP.)
CONNECTOR VIPER MANUFACTURER
REFRIGERANT PIPE Y-BRANCH
LINES (TYP.)
LIQUID & VAPOR
OUTDOOR UNIT
DUCT-FREE HEAT PUMP
HPO
LINE(TYP.)
DRAIN
LINES (TYP.)
LIQUID & VAPOR
OF SHEET M-7 (TYP.)
FOR DETAIL SEE 2
NEW CONC. PAD
(TYPICAL)
ACCESS DOOR
CEILING ACCESS DOOR DETAIL (TYP.)
AS REQUIRED
STL PLATE FRAME
75 Wx6 THK
& NUT
6 DIA BOLT
@ EACH CORNER
10GA. WIRE HANGER
CAM LATCH
(LIGHT WEIGHT METAL)
FINISH MATCH TO CEILING
14 GA STL ACCESS PANEL
PIANO HINGE
CONTINUOUS
TO CEILING)
(FINISH MATCH
16GA STEEL FRAME
CEILING
GWB
ACST OR
T
HP
(TYP OF 3)
CEILING MOUNTED, 4-WAY
DUCT-FREE HEAT PUMP
HP
PIPE SIZE
VAPOR LIQUID DRAINITEM NO.
HP
HPO
15.88 mm
25 mm12.7 mm 6.35 mm
ERV
25 mm
9.52 mm
15.88 mm 9.52 mm
NOTE :
CONDUITS, AND ALL NECESSARY ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.
5. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING,
SHALL BE PRESSURE TESTED & VACUUM TESTED.
PRESS-CONNECT FITTINGS, GROOVE JOINTS & MECHANICAL JOINTS. THE VRF SYSTEM
TO THE FOLLOWING: PUSH-ON FITTINGS, EXTRUDED FITTINGS, FLARE FITTINGS,
LIST OF FITTINGS AND JOINTS THAT ARE PROHIBITED INCLUDE BUT ARE NOT LIMITED
B31.5 REQUIREMENTS AND THE MANUFACTURER'S INSTALLATION REQUIREMENTS. THE
4. VRF SYSTEMS PIPING/TUBING SHALL HAVE ALL BRAZED CONNECTIONS THAT MEET ASME
SPEC BY A CERTIFIED INSTALLER.
3. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S
RECOMMENDATION.
2. REFRIGERANT PIPE SIZE & INSTALLATION SHALL BE AS PER MANUFACTURER'S
INSTALLATION.
1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PIPEWORK PRIOR TO PIPEWORK
ERV
VENTILATOR UNIT
ENERGY RECOVERY
HP
LINE(TYP.)
DRAIN
& ABOVE CEILING)
WIRING SHALL BE CONCEALED IN THE WALL
WIRING AND RECESSED CONDUIT (ALL CONTROL
RECESSED CONTROLLER WITH JUNCTION BOX,
M4
EH
ELECTRIC WALL HEATER
EH
ELECTRIC WALL HEATER
NEW H.V.A.C PIPING ENLARGED PLAN
CAMP BONIFAS
REPAIR CHAPEL BLDG. NO. T-30
OFFICE
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
KIM, SM
M-5 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
ACCESS DOOR
(TYP OF 2)
RETURN DIFFUSER
ROUND PAN
(TYP OF 3)
SUPPLY DIFFUSER
ROUND PAN
(TYP OF 2)
W/BIRDSCREEN
HOODED WALL CAP
OFF
C
OL
120 VAC
M
EA
SWITCH
"H-O-A"
EXHAUST FAN CONTROL
NOT TO SCALE
EF
EXHAUST FAN
EXHAUST FAN
HAND
AUTO
LADDER DIAGRAM
2. "HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION ENERGIZES THE EXHAUST FAN.
CONTINUOUSLY UNTIL MANUALLY STOPPED.
1. "HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS THE EXHAUST FAN
62 LPS
200 NCD
41 LPS
150 NCD
CAMP BONIFAS
REPAIR CHAPEL BLDG. NO. T-30
245448
SCALE = 1:50M5
OFFICE
CLOSET
COMM/
MALE
FEMALE
11,000
14,400
1,500 1,900
NOTE :
CONDUITS, AND ALL NECESSARY ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.
4. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING,
TYPES.
3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING
SPEC BY A CERTIFIED INSTALLER.
2. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S
INSTALLATION.
1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PIPEWORK PRIOR TO PIPEWORK
NEW H.V.A.C ENLARGED PLAN
41 LPS
150 NCD
41 LPS
150 NCD
62 LPS
200 NCD
ERV
VENTILATOR UNIT
ENERGY RECOVERY
O.A
C CS
200250
E.A
BDD
MD
VD
VD VD
VD VD
CONTROLLER
CO2 SENSOR
EF
EXHAUST FAN
EF
EXHAUST FAN
UL 181 AIR DUCT APPROVED (TYP.)
VAPOR BARRIER EXTERIOR COVER
+ INCOMBUSTIBLE POLYETHYLENE
NE 1000 CORE + POLY INSULATION
PE POLY ACOUSTICAL FLEXIBLE DUCT
BIRD SCREEN (TYP OF 2)
HOODED WALL CAP W/ STS METAL
STAINLESS STEEL SQUARE SHAPE
NEW H.V.A.C ENLARGED PLAN
50mm WATER METER
CLOSET
COMM/
B
C
A
REMARKS
RATING
FU
QTYSYMBOL
P.D.I
1-11
12-32 20
33-60 25
WATER HAMMER ARRESTER SCHEDULE
CONN.
PIPE
INSTRUCTIONS.
PER PDI-WH 201 AND MANUFACTURER'S
2. SIZE AND LOCATE WATER HAMMER ARRESTORS
COMPRESSION CHAMBER W/EXPANSION BELLOWS.
1. COPPER CONSTRUCTION PRESSURIZED
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
KIM, SM
M-6 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CAMP BONIFAS
REPAIR CHAPEL BLDG. NO. T-30
245448
KEY PLAN
SCALE = 1:50M6
ENLARGED PARTIAL PLANS
SEWER & VENT PIPING
NEW DOMESTIC WATER AND
PLUMBING FIXTURES SCHEDULE
PLUMBING FIXTURES QTY
COLD HOT TRAP VENT
REMARKS
1515LAVATORY
-15
50 32
SYMBOL
P-1
P-5 MAX.0.5 GPM @60 PSI
WATER CLOSET (F.T) 100
LOCAL PIPE CONNECTION
3.8 LITERS/FLUSH
505020P-3 1 -
1515 80 40P-8 1SERVICE SINK
URINAL
W/ INTEGRAL BACK
STAINLESS STEEL,
AUTOMATIC SENSOR
NOTE ON INSTALLATION OF PIPE INSULATION :
PIPE INSULATION IS COMPLETED.
FOR QUALITY INSPECTION WHEN THE INSTALLATION OF THE
4. THE CONTRACTOR SHALL INVITE THE MECHANICAL ENGINEER
WHEN TESTED IN ACCORDANCE WITH ASTM E84.
INDEX OF 25 AND A MAX. SMOKE DEVELOPED INDEX OF 50
FIRERESISTANT AND SHALL HAVE A MAXIMUM FLAME SPREAD
3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE AND
IN FM APP GUIDE.
2. INSULATION MATERIALS RECOGNIZED UNDER UL94 AND LISTED
GRADE 1, TYPE I OR II.
SPEC 23 07 00, AND SHALL COMPLY WITH ASTM C534/C534M,
1. INSULATION MATERIALS SHALL CONFORM TO TABLE1 OF OMA
NOTE :
VALVES AND WATER HAMMER ARRESTORS.
3. PROVIDE CEILING / WALL ACCESS PANEL FOR ISOLATION
PIPING) PRIOR TO PLUMBING PIPING INSTALLATION.
PIPING (HOT & COLD WATER PIPING, SEWER AND VENT
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING
1. ALL PIPE LINES SHALL BE COPPER TUBE.
P-8
P-5
P-1
P-1
P-5
P-3
1,500 1,900
CLOSET
COMM/
1,500 1,900
100 FCO
NEW DOMESTIC WATER PIPING ENLARGED PARTIAL PLAN
MALE
FEMALE
MALE
80 VTR
50 FD
50 FD
SCALE = 1:50M6
NEW SEWER & VENT PIPING ENLARGED PARTIAL PLAN
P-8
P-5
P-1
P-1
P-3
P-5 A WATER HAMMER ARRESTER
A WATER HAMMER ARRESTER
SEE CIVIL DRAWING
NEW SEWER MAIN PIPE
CONN. TO UNDERGROUND
100mm SEWER LINE
SEE CIVIL DRAWING
NEW DOMESTIC WATER MAIN PIPE
CONN. TO UNDERGROUND
50mm DOMESTIC WATER LINE
(INSTALLATION UNDER THE SINK)
INSTANTANEOUS WATER HEATERIH
(INSTALLATION UNDER THE SINK)
INSTANTANEOUS WATER HEATERIH
EWC
WATER COOLER
ELECTRIC
FEMALE
EWC
WATER COOLER
ELECTRIC
KIM, SM
M-7
NTS
MECH. DETAILS - 1
FIN. GRADE
150 150
SECTION
PLAN
N F S M
150150ACTUAL EQUIPMENT SIZE
AT EXPOSED EDGES
20mm CHAMFERS#4 @300 O.C.
50 CLR
CONC. PAD
150 150 150150ACTUAL EQUIPMENT SIZE
A C
T U
A L
E Q
U I
P M
E N
T
S I
Z E
EQUIPMENT UNIT
GRAVEL BASE
150mm THK.
1 INDOOR HEAT PUMP UNIT INSTALLATION DETAIL
SECTION
REMOTE CONTROL
FULL BOX
ELECTRICAL CONC. BOX
CEILING
ROOM
(CEILING CASETTE 4-WAY TYPE)
INDOOR HEAT PUMP
ENLARGED SECTION
ROOM
R.L/R.G
DRAIN PIPE
CEILING
PUMP
HEAT
(TYP)
HANGERMIN 300
FOR SERVICE
ACCESS DOOR
600x600 CEILING
CABLE
POWER
CEILING
R.L/R.G
DRAIN PIPE
DRRAIN HOSE
(CEILING CASETTE 4-WAY TYPE)
INDOOR HEAT PUMP
MAX.700
(TYP.)
HANGER
SLOPE
1/50-1/100
SEE
Y JOINT DETAIL
LIQUID PIPE 6.35A/ 9.52A
TAPE
Y-JOINT
INLET
INSULATION REFRIGERANT LIQUID/ GAS PIPE
COVER
OUTLET
SECTION
GAS PIPE 12.7/ 15.88
PIPE INSULATION:19T
EPDM
VCTF-SB1.25x2C
CABLE LINE
CONCRETE PAD DETAIL
WITH MANUFACTURER.
FINAL PAD SIZE SHALL BE CORDINATED
6" (150mm) LARGER THAN UNIT SIZE AND
ALL EQUIPMENT CONC PAD SIZE SHALL BE
NOTE :
FILTER DRIER
LIQUID LINE
CONDENSATE DRAIN
DRAIN PUMP
CONDENSATE
THERMOSTAT
SWITCH
DISCONNECT
FUSED
VAPOR LINE
(OUTDOOR UNIT)
DUCT-FREE HEAT PUMP
(INDOOR UNIT)
DUCT-FREE HEAT PUMP
SWITCH
FUSED DISCONNECT
WEATHERPROOF
ISOLATORS
SPRING
HANGER ROD
HANGER PLATE
VENTILATOR
ENERGY RECOVERY
E.R.V EQUIPMENT INSTALLATION
TYPICAL REFRIGERANT PIPING DIAGRAM3
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CAMP BONIFAS
NOTE :
FROM THE FLOOR (OR PAD)
HEATER SHALL BE DROPPED UP MIN.ƒ" CLEARANCE
•" HOSE BIBB
SERVICE LINE
COLD WATER
AND PRESSURE RELIEF VALVE
COMBINATION TEMPERATURE
MAXIMUM 2" NIPPLE
SUPPLY LINE
HOT WATER
VACUUM BREAKER
ADAPTER (TYP)
WATER HEATER
ELECTRIC
DRAIN
TO NEAREST
RELIEF DRAIN
PIPE
I
N C
L U
D I
N G
I
N S
U L
A T I
O N
P I
P E
D I
A m m
PIPE SLEEVE-THRU FOOTING
EXTERIOR INTERIOR
MASONRY WALL
CONCRETE OR
INSULATION
PIPE WITHOUT
ALL AROUND
MIN. 7 CLEARANCE
METAL JACKET
INSULATION
SEALANT #10
PIPE SLEEVE
BACK UP MATERIAL
INSULATION
PIPE WITH
ANCHOR
RUBBER OR PLASTIC)
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
SEALANT #2
MEMBRANE
WATERPROOFING
CLAMPING FLANGE
WATERPROOFING
PIPE
2 PIPE SLEEVE-THRU INTERIOR WALL
METAL JACKET
SLEEVE
INSULATION
INSULATION
PIPE WITHOUT
SEALANT #2
ALL AROUND
7 MIN CLEARANCE
INSULATION
PIPE WITH
BACK UP MATERIAL
50SEALANT #2
(TYP)
METAL BAND
SLEEVE
CEILING
MASONRY WALL
CONCRETE OR
RUBBER OR PLASTIC)
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
3 PIPE SLEEVE-THRU FLOOR
NOTES
INSTRUCTIONS.
IN ACCORDANCE WITH MANUFACTURER'S LISTED INSTALLATION
2. FIRESTOPPING SHALL BE PROVIDED AND SHALL BE INSTALLED
EQUIPMENT ROOMS.
FLOORS OR CEILINGS, EXCEPT IN BOILER, UTILITY OR
WHERE EXPOSED PIPING, BARE OR INSULATED PASSES THROUGH
1. ESCUTCHEONS SHALL BE PROVIDED AT ALL FINISHED SURFACES
P I
P E
PIPE WITH INSULATIONPIPE WITHOUT INSULATION
METAL JACKET
SLEEVE
PLASTIC)
RUBBER OR
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
7 MIN CLEARANCE
INSULATION
METAL BAND (TYP)
SEALANT #2
MATERIAL
BACK UP
FIN FLOOR
CEMENT
CLIP TYPE
SPRING
ESCUTCHEON
SLEEVE
PIPE SLEEVE-THRU FLOOR WITH WATERPROOFING
P I
P E
PIPE WITHOUT INSULATION PIPE WITH INSULATION
INSULATION
FLOOR
METAL JACKET
METAL BAND
WATERPROOFING
PLASTIC)
RUBBER OR
FLEXIBLE FOAM
(CLOSED CELL
MATERIAL
BACK UP
OR 450 GMS COPPER
20 KG/SQ. METER
FLASHING
SEALANT #2
FLOOR CLEANOUT
NOTES
STAINLESS STEEL FLUSH TYPE ACCESS COVER PLATE.
2. CHROMIUM-PLATED BRONZE, NICKEL BRONZE, NICKEL BRASS OR
1. WATERPROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.
PACKING
TARRED JUTE
WHEN NOT THRU RUN
PLUG Y-BRANCH
3mm BEND
GASKET
NEOPRENESCORIATED COVER, SEE NOTE 2
ADJUSTABLE HOUSING
TWO PIECE THREADED
WATERPROOF MEMBRANE
Y-BRANCH
PIPE
CAST IRON
WATER SERVICE
FFL
REDUCING TEE
UNION
13 FEMALE ADAPTER
WATER METER
PRESSURE GAUGE
MALE ADAPTER
GATE VALVE
MALE ADAPTER
20 HOSE BIBB
SEE DETAIL ON THIS SHEET
PIPE SLEEVE-THRU FOOTING
ON THIS SHEET
FLOOR SEE DETAIL
PIPE SLEEVE-THRU
G.L
CIVIL DRAWING
ELEVATION SEE
FOR INVERT
MASTIC
WATERPROOF
REDUCING TEE
INSTALLATION
VERTICAL
SUITABLE FOR
STRAINER
8 WATER HAMMER ARRESTOR
PLAN FRONT ELEVATION
6 PIPE SUPPORT INSTALLATION
BOLT (TYP)
19mm EXPANSION
CLAMP (TYP)
PIPE
WATER METER
MONITORED TYPE
DDC
PIPE
CONCRETE WALLCONCRETE WALL
CLAMP
PIPE
TYPE
D
C
B
A
HEIGHT DIAMETER
DIMENSION SHALL BE
VARIED DEPEND UPON
MFR
CAPACITY(FU)
61-113
33-60
12-32
1-11
FIXTURE UNIT
H E I
G H
T
COPPER SHELL
THREADED PLUG
DIAMETER
COPPER ADAPTOR
BELLOWS
FOR LOCATION AND SIZE
20mm OR 25mm SEE DWGS
DISPLACEMENT CUSHION
PRESSURE PNEMATIC
DISPLACEMENT FLUID
HYDRAULIC
ORIFICE
FLOW CONTROL
CONN.SIZE
BRANCH SUPPLY
FROM
LAST FIXTURE
TO
KIM, SM
M-8
NTS
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
MECH. DETAILS - 2
ELECTRIC WATER HEATER
CAMP BONIFAS