This is a set of 100% Construction Documents prepared by NBP Engineers, Inc. for Gordon State College's Lambdin Hall Chiller Replacement project located in Barnesville, Georgia. The project involves the replacement of an air-cooled chiller system and includes demolition and new work across the mechanical yard on the first floor and the mechanical room on the third floor. The scope encompasses HVAC work including chiller replacement, piping modifications, pump installations with variable frequency drive (VFD) controls, expansion tank installation, and associated controls and instrumentation. Electrical work includes new disconnects, circuit breakers, conduit routing, and connections to support the new chiller and VFD equipment. The construction documents are dated October 29, 2026, and represent the final design phase for bidding and construction purposes.

The documents include detailed mechanical and electrical drawings showing demolition plans, new work layouts, piping schematics, equipment schedules, and electrical single-line diagrams. Key equipment specifications include two redundant end-suction pumps (P-1 and P-2) rated at 70 GPM with VFD controls, a Carrier 30RC air-cooled chiller with nominal capacity of 120 tons, Armstrong pumps with BACnet/MSTP communication capability, and new electrical service upgrades including an 800-amp fused disconnect and 800-amp/3-phase breaker. The project consultant is NBP Engineers, Inc., located in Macon, Georgia, with a Certificate of Authorization expiring June 30, 2028. The drawings note that existing conditions were documented to the best of the engineer's knowledge, but discrepancies between design documents and actual site conditions should be reported to the design professional and owner prior to performing work.

View the file

Other files

File Type Posted
Gordon State Lambdin Hall Chiller_Project Man.pdf PDF
Invitation to Bid.pdf PDF
Gordon State Map.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDEX OF

DRAWINGS

PROJECT CONSULTANTS

NBP ENGINEERS, INC.

MACON, GEORGIA316 CORPORATE PARKWAY

NBP

ENGINEERS

CONSULTANTS

478-745-1691 www.nbpengineers.com

PROJECT No. 26056

BARNESVILLE, GEORGIA

TITLESHEET NO.

M10

ABBREVIATIONS, LEGENDS, & SCHEDULES - HVAC

M30

M00

PARTIAL FIRST FLOOR /MECH. YARD - DEMOLITION & NEW WORK - HVAC

M20 PARTIAL THIRD FLOOR MECH. RM. - DEMOLITION & NEW WORK - HVAC

CHILLED WATER PIPING SCHEMATIC - DEMOLTION & NEW WORK - HVAC

E00

E10 PARTIAL FIRST FLOOR /MECH. YARD - DEMOLITION & NEW WORK - ELEC

E20 PARTIAL THIRD FLOOR MECH. RM. - DEMOLITION & NEW WORK - ELEC

LEGEND, & RISER - ELECTRICAL

LAMBDIN HALL - CHILLER REPLACEMENT

GORDON STATE COLLEGE

10.29.2026 100% CONSTRUCTION DOCUMENTS

P:\26056\26056m00.dgn

DATE PLOTTED

DGN FILE

28-OCT-2026

SEAL

SCALE:

FILE PATH:

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26056\26056m00.dgn

AS SHOWN

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

N B P P ro je c t

N o

G O

R D

O N S

T A

T E C

O L L E

G E

L A

M B

D

IN

H

A L L C

H

IL

L E

R R

E P

L A

C E

M E

N T

B a rn e s v il le

G e o rg ia

LTF

DRH

10.29.2026

26056

DRH

C O

N S T

R U

C T

IO

N

D

C U

M E

N T S

M00

SCHEDULES - HVAC

LEGENDS, &

ABBREVIATIONS,

A COMPRESSED AIR

AAV AUTOMATIC AIR VENT

AF AIR FOIL

-AFF ABOVE FINISHED FLOOR

AV ACID VENT

AVD AUTOMATIC VOLUME DAMPER

AW ACID WASTE

-AC ABOVE CEILING

AH- AIR HANDLING UNIT

BBD BOILER BLOW DOWN

BE BOTTOM ELEVATION

BOL BOTTOM OF LINE (UNINSULATED)

BOD BOTTOM OF DUCT

BP- BOOSTER PUMP

BTUH BRITISH THERMAL UNIT PER HOUR

-BF BELOW FLOOR

BFP BACK FLOW PREVENTOR

C CONDUIT

CC COOLING COIL

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CR CONDENSER WATER RETURN

CS CONDENSER WATER SUPPLY

CW DOMESTIC COLD WATER

CAB CABINET FAN

CF CENTRIFICAL FAN

CFM CUBIC FEET PER MINUTE

CFP CHEMICAL FEED PUMP

CFT CHEMICAL FEED TANK

CH CABINET HEATER

CHR CHILLER

CL CENTER LINE

CO CLEANOUT

CP CHILLER PUMP

CPHB CHROME PLATED HOSE BIBB

CT COOLING TOWER

CU COPPER

CV- CONVECTOR

Cv VALVE COEFFICIENT

D DRAIN

DDC DIRECT DIGITAL CONTROL

DHW DOMESTIC HOT WATER

DN DOWN

DP DIFFERENTIAL PRESSURE

DS DOWN SPOUT

DSO DOWN SPOUT OVER FLOW

DX DIRECT EXCHANGE

EAD EXHAUST AIR DAMPER

EAT ENTERING AIR TEMPERATURE

EDB ENTERING DRY BULB

EWB ENTERING WET BULB

ESP END SUCTION PUMP

ESP EXTERNAL STATIC PRESSURE

ELL ELBOW

ET EXPANSION TANK

EQT EQUIPMENT TRAP SET

EWT ENTERING WATER TEMPERATURE

EX EXPANSION TANK LINE

EXT EXTERNAL

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

F&BP FACE & BYPASS

FC FAN COIL UNIT

BPD BYPASS DAMPER

EAL EXHAUST AIR LOUVER

ECH ELECTRIC CABINET HEATER

ABBREVIATIONS

FD FLOOR DRAIN

FF FOULING FACTOR

FF- FLY FAN

FF FINISHED FLOOR

FF FINAL FILTER

FFM FIRE FLOW METER

FLEX FLEXIBLE

FM FIRE MAIN

FMS FLOW METER STATION

FOF FUEL OIL FLOW

FOR FUEL OIL RETURN

FOV FUEL OIL VENT

FOP FUEL OIL PUMP

FP FIRE PUMP

FP- FAN POWERED

FPM FEET PER MINUTE

FPS FEET PER SECOND

FRT FLOW RATE TRANSMITTER

FT FEET

G LOW PRESSURE GAS

GA GAUGE

GPM GALLONS PER MINUTE

GT GREASE TRAP

GTH GRAND TOTAL HEAT

H HEIGHT

HC HEATING COIL

HB HOSE BIBB

HBT HORIZONTAL BLOW THROUGH

HD HUB DRAIN

HDT HORIZONTAL DRAW THROUGH

HP HORSEPOWER/HIGH PRESSURE

HPA HIGH PRESSURE AIR

HPG HIGH PRESSURE GAS

HPS HIGH PRESSURE STEAM

HPWS HEAT PUMP WATER SUPPLY

HPWR HEAT PUMP WATER RETURN

HSC HORIZONTAL SPLIT CASE

HWG HOT WATER GENERATOR

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

ILC IN-LINE CENTRIFICAL

IT INTERVAL TIMER

IN INCHES

INV INVERT

JB JUNCTION BOX

L LENGTH

LR LONG RADIUS

LAT LEAVING AIR TEMPERATURE

LCP LOCAL CONTROL PANEL

LDB LEAVING DRY BULB

LN LIQUID NITROGEN

LWB LEAVING WET BULB

LWT LEAVING WATER TEMPERATURE

LPS LOW PRESSURE STEAM

MAV MANUAL AIR VENT

MVD MANUAL VOLUME DAMPER

MAX MAXIMUM

MBH ONE THOUSAND BTUH PER HOUR

MCC MOTOR CONTROL CENTER

MIN MINIMUM

MH MAN HOLE

MP SUMP (MUD) PUMP

MPS MEDIUM PRESSURE STEAM

MPR MEDIUM PRESSURE RETURN

MTS MEDIUM TEMPERATURE SUPPLY

MTR MEDIUM TEMPERATURE RETURN

MUA MAKE-UP AIR

MUW MAKE-UP WATER

MZ MULTIZONE

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OAD OUTSIDE AIR DAMPER

ODT OUTDOOR TEMPERATURE

PC PUMP CONDENSATE

PD PRESSURE DROP

PRV PRESSURE REDUCING VALVE

PWF PROPELLER WALL FAN

R REFRIGERANT

RA RETURN AIR

RAD RETURN AIR DAMPER

RAS RELIEF AIR SUPPLY

RP RECIRCULATING PUMP

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

RD ROOF DRAIN

RV RELIEF VALVE

SR SHORT RADIUS

OAL OUTSIDE AIR LOUVER

SAN SANITARY SEWER

SC SILL COCK

SCD SMOKE DAMPER

SD STORM DRAIN

SD SMOKE DETECTOR

SF SQUARE FEET

SDO STORM DRAIN OVERFLOW

SHC SENSIBLE HEAT CAPACITY

SP STAND PIPE

SP SUMP PUMP

SPS STATIC PRESSURE SENSOR

STA STATION

TR TEMPERED WATER RETURN

UG UNDERGROUND

VAC VACUUM PIPING

VDT VERTICAL DRAW THROUGH

VTR VENT THROUGH ROOF

WB WET BULB

O2 OXYGEN

F DEGREES FAHRE C DEGREES CENTI

WM WATER METER

WL WATER LINE

WH WATER HEATER

WG WATER GAUGE

W WIDTH

W WASTE

VT VERTICAL TURBINE

VFD VARIABLE FREQUENCY DRIVE

VB VACUUM BREAKER

VAV VARIABLE AIR VOLUME

V VENT

UC UNDERCUT (DOOR - 3/4")

V- VALVE

TOS TOP OF STRUCTURE

TB THRUST BLOCK

T TEMPERED WATER

STR STRAINER

SP STATIC PRESSURE

SP SPRINKLER PIPE

SG SPECIALTY GAS

EUH ELECTRIC UNIT HEATER

RECIRCULATING

DHR DOMESTIC HOT WATER

TRANSMITTER

DPT DIFFERENTIAL PRESSURE

PER MINUTE

SCIM STANDARD CUBIC INCHES

TEMPERATURE

SST SATURATED SUCTION

(UNINSULATED)

TE TOP ELEVATION

(TOWER) PUMP

TP CONDENSER WATER

FSD FIRE/SMOKE DAMPER

EA EXHAUST AIR

MA MIXED AIR

AE ADJUSTABLE AIR EXTRACTOR

RAO RETURN AIR OPENING

AD AREA DRAIN/ACCESS DOOR

SPS

SD

COMBINATION STARTER

STARTER

PIPE SLEEVE

CONCENTRIC REDUCER

PIPE ANCHOR

HVAC LEGEND

BALL VALVE WITH

3/4" HOSE END

BALANCE VALVE

THREADED & FLANGED

GLOBE VALVE

CHECK VALVE

3-WAY MIXING VALVE

BALL VALVE

BUTTERFLY VALVE

SOLENOID VALVE

CONTROL VALVE

PLAN VIEW

2-WAY MOTORIZED VALVE

RELIEF VALVE

FLANGED UNION

BRANCH OUT TOP

STRAINER

BRANCH OUT BOTTOM

ELBOW DOWN

ELBOW UP

TEE OUT TOP

BLIND FLANGE

PIPE CAP

AUTOMATIC AIR VENTAAV

FLEX. PIPE CONN.

BACKFLOW PREVENTER

THERMOMETER

TEE OUT BOTTOM

MANUAL AIR VENT

PIPE TEST PLUG

HEATING WATER FLOW

COLD WATER DOMESTIC

NATURAL GAS

CONDENSER WATER FLOW

DRAIN

HEATING WATER RETURN

HOT WATER DOMESTIC

G

D

DUCT SIZE FIRST DIMENSION

IS SIDE SHOWN

24\12

DOOR GRILLE

REFERS TO DETAIL OR

PLAN ON SHEET M-1.THERMOSTAT

INTERVAL TIMER

T

I.T.

1\M-4

DUCT/PLENUM w/LINER

FIRE DAMPER

ELBOW WITH

TURNING VANES

FLEX. DUCT CONN.

TURNING VANES

ELBOW WITHOUT

ADJUSTABLE AIR

EXTRACTOR

INSULATED FLEX. DUCT

INSULATED FLEX. DUCT

c

ECCENTRIC REDUCER

HWS

HWR

SCHS

SCHR

CONDENSER WATER RETURN

CS

CR

STATIC PRESSURE SENSOR

SMOKE DETECTOR

POINT OF CONNECTION

DUCT SPLIT

THREADED & FLANGED

THREADED & FLANGED

UNION

GAUGE TAPPING

GAUGE WITH TAPPING

THREADED & FLANGED

THREADED & FLANGED

PIPE SOCKET WELL

FLOW INDICATOR BALANCER

M

T G THERMOSTAT w/GROUND

ANNULAR ELEMENT FLOW STATION

M

DAMPER - BLADE VIEW DAMPER - END VIEW

xx{K OR xx/xx}K ROUND OR FLAT OVAL DUCT (K)

DOUBLE WALL INSULATED

ROUND OR FLAT OVAL DUCTxx{ OR xx/xx}

CHILLED WATER FLOW

CHILLED WATER RETURN

CHS

CHR

WATER SUPPLY

SECONDARY CHILLED

WATER RETURN

SECONDARY CHILLED

CV

CVA

CONSTANT VOLUME

ADJUSTABLE

CONSTANT VOLUME

CFM

PRESSURE SENSOR

NOTIFY DESIGN PROFESSIONAL AND OWNER OF ANY DISCREPANCIES PRIOR TO PERFORMING ANY WORK.

IS ANTICIPATED THERE ARE DISCREPANCIES VERSUS THE AS-BUILT CONDITIONS. CONTRACT TO IDENTIFY AND

SURVEYS. THESE DOCUMENTS REFLECT EXISTING CONDITIONS TO THE BEST OF OUR KNOWLEDGE. HOWEVER, IT

THESE DRAWINGS HAVE BEEN PRODUCED UTILIZING A COMBINATION OF ORIGINAL DESIGN DOCUMENTS AND FIELD

MINIMUM

CAPACITY-MBH

RATING

EWT LWT

WATER

FLOW-GPM

EVAPORATOR DATA

MAXIMUM PRESSURE

DROP-FT-H O

FOULING

FACTOR

MAX. TOTAL

INPUT

ELECTRICAL DATA

KW

MARK VOLTAGE/PHASE/HERTZ

EACH

REMARKS

AIR COOLED CHILLER SCHEDULE

MIN.

IPLV

CHR-1

MANUFACTURERS

YORK TRANE

NOTES:

MINIMUM

TONS

NOM. CAPACITY

MARK SERVICE

TYPE

PUMP

GPM APPROX.

FT.H O

MAX. MIN.

EFF.%

REMARKS

2 B&G(EA.) HP

MANUFACTURERS

PUMP SCHEDULE

PATTERSON

RPM

56 42 120 0.0001 79.2 208/3/60 15.9 YLAA CGAM 1 2

NOTES:

1 PUMPS ARE N+1 REDUNDANT.

P-1

P-2

CHILLED WATER

CHILLED WATER

ES

ES

5.0

5.0

E1510-2BD

E1510-2BD

VFD

VFD

UNIT MUST HAVE A BACNET/MSTP COMMUNICATION CARD.

UNIT COMPRESSORS MUST HAVE HIGH HOT GAS BYPASS AND VARIABLE SPEED CONDENSER FAN(S) ON LEAD CIRCUIT.

HVES-1.5BA

HVES-1.5BA

70 839 15.3

CARRIER

30RC

ARMSTRONG

4030-3X1.5X8

4030-3X1.5X8

P:\26056\26056m10.dgn

DGN FILE

28-OCT-2026

SEAL

SCALE:

FILE PATH:

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26056\26056m10.dgn

AS SHOWN

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

N B P P ro je c t

N o

G O

R D

O N S

T A

T E C

O L L E

G E

L A

M B

D

IN

H

A L L C

H

IL

L E

R R

E P

L A

C E

M E

N T

B a rn e s v il le

G e o rg ia

LTF

DRH

10.29.2026

26056

DRH

N S T

R U

C T

C U

M E

N T S

1 12

STAIR 2

1 1 1

MECH. YARD

1 13

MECH. SHAFT

1 12

STAIR 2

1 1 1

MECH. YARD

1 13

MECH. SHAFT

GENERATOR

EXISTING

FF

CHR

CHS

4"

4" UP

PIPE SLEEVE

(TYPICAL)

PIPE SUPPORT

CONCRETE

EXISTING CONCRETE PAD

"C

H S

"C

H R

M10

SCALE:

= 1'-0

4 0 2 4 8

N

GENERATOR

EXISTING

FF

PARTIAL FIRST FLOOR/MECHANICAL YARD - DEMOLITION - HVAC

CHR

CHS

4"

4" UP

PIPE SLEEVE

(TYPICAL)

PIPE SUPPORT

CONCRETE

S Y

S T

E M

G R

A P

H

IC

IS

P L

A Y

S T

A R

T

S T

O P

E N

A B

L E

D

IS

A B

L E

O P

E N

C L

O S

E

S T

A R

T

S T

P

A

K E

U P

S E

T P

O

IN

T

A

J

U S

T

D

N T

R O

L

D

IF

F E

R E

N T

IA

L

P

R E S

S U

R E

P R

E S

S U

R E

S

W

IT

C H

A U

X

IL

IA

Y

N T

A C

T

A L

A

N T

A C

T

T E

M P

E R

A T

U R

E

R E

L A

T

IV

U

M

ID

IT

Y

P R

E S

S U

R E

H

IG

H

L

W

L

IM

IT

R

T A

L

IZ

A T

IO

N

P R

O P

O R

T

IO

N A

L

P R

O P

IN

T E

G R

A L

T

IM

E

S

C H

E D

U L

E

S

S

O P

T

IM

A R

T

S T

O P

D A

Y

N

IG

T B

A C

K

D E

M A

IT

C Y

C L

E

R E S

T

IM

IZ

A T

IO

N

E C

O N

O M

IZ

E R

F A

IL

U

D E (S

T E S

A

N D

N O

T E S

OUTPUTS INPUTS SOFTWARE

DDC PANELS

INPUT/OUTPUT

SUMMARIES

DIGITAL ANALOG ANALOG ALARM DDC ENERGY MGMT.DIGITAL

C U

R R

E

L A

Y

D R

IV

E

S

T A

T U

S

S P

E E

D

IN

D

IC

A T

IO

N

S P

E

N T

R O

L

E

W

IT

C H

C O

C A

L C

U L

A T

IN

T

P O

S

IT

IO

N

IN

D

IC

A T

IO

N

O P

E N

C L

O S

S

IT

IO

N

ACP

S T

A T

U S

T R

E

G

LOGS

F

E N

F U

O S

E

CHILLED WATER SYSTEM

TAG POINT DESCRIPTION

CHR-1 CHILLER

CCHILLER PUMPS - VFD CONTROL

1. FAILURE MODES:

2. WHERE FAILURE MODE IS INDICATED, THE INDICATED POSITION SHALL OCCUR ON INTERRUPTION OF

ELECTRIC POWER TO THE DDC PANEL.

L - LAST COMMAND

O - OPEN OR ON

C - CLOSE OR OFF

W A

T

F

O W

INPUT/OUTPUT NOTES:

CP-1

HT HEAT TRACE

DI

HT

SCALE:

= 1'-0

4 0 2 4 8

N

NEW WORK - HVAC

DEMOLITION &

FLOOR/MECH YARD -

PARTIAL FIRST

LINE LEGEND

POINT OF CONNECTION

NEW WORK

EXISTING TO REMAIN

DEMOLITION

NOTES:(THIS SHEET ONLY)

PARTIAL FIRST FLOOR/MECHANICAL YARD - NEW WORK - HVAC

NEW BUTTERFLY VALVE (TYP)

TRACE TO ALL EXPOSED CH PIPING

APPLY NEW HYDRONIC HEAT

EXISTING CONCRETE PAD

TO BE REPLACED IN NEW WORK

REMOVE EXISTING HEAT TRACE;

"C

H S

"C

H R

CHR-1

NEW CHILLER

& REPLACED IN NEW WORK

TO CHILLER TO BE REMOVED

EXISTING VALVES & PIPING

NEW 4" RUNOUT WITH BUTTERFLY VALVE AND BLIND FLANGE FOR

FUTURE CONNECTION OF TEMPORARY CHILLER.

PROVIDE NEW PIPE SUPPORTS WITH CONCRETE BASE AS REQUIRED.

CHILLER

AIR COOLED

EXISTING

REMOVE

CONCRETE PAD

ON EXISTING

AI AODI DO

CHR-1

CHR-1

CHILLED WATER FLOW DIAGRAM - HVAC

NOT TO SCALE

C H S

C H

R

4"

CHR-

PIPING AT CHILLER YARD

HEAT TRACE ALL EXPOSED

P:\26056\26056m20.dgn

DGN FILE

28-OCT-2026

SEAL

SCALE:

FILE PATH:

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26056\26056m20.dgn

AS SHOWN

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

N B P P ro je c t

N o

G O

R D

O N S

T A

T E C

O L L E

G E

L A

M B

D

IN

H

A L L C

H

IL

L E

R R

E P

L A

C E

M E

N T

B a rn e s v il le

G e o rg ia

LTF

DRH

10.29.2026

26056

DRH

N S T

R U

C T

C U

M E

N T S

T T

SD

T

P

S

24"{

AP

AP

72/30

C ƒ"

4"

3"

VFD-1 VFD-2

4"CHR

4"CHS

FDFD

AHU-1

2"CHR

2"CHS

1‚"HWS

1‚"HWR

2"

1‚"

4"

CHR

DDCICS

C H S

M U

W

ABOVE SA DUCT

48"X60" w/FD

4" DN

80/80

L-1

(TYPICAL)

PIPE SLEEVE

TANK

EXPANSION

SUPPORT (TYP)

6"x4" CONCRETE

COOLING COIL

ACCESS

MIXING BOX

FILTER

PREHEAT COIL

FAN

DAMPER CONTROLLER

VENTURI

M20

SCALE:

= 1'-0

4 0 2 4 8

N

T T

SD

T

P

S

24"{

AP

AP

72/30

C

1"CF ƒ"

4"

3"

P-1

P-2

VFD-1 VFD-2

4"CHR

4"CHS

FDFD

AHU-1

2"CHR

2"CHS

1‚"HWS

1‚"HWR

2"

1‚"

4"

CHR

DDCICS

C H S

M U

W

ABOVE SA DUCT

48"X60" w/FD

4" DN

PARTIAL THIRD FLOOR MECHANICAL ROOM - DEMOLITION - HVAC

80/80

L-1

(TYPICAL)

PIPE SLEEVE

TANK

EXPANSION

CHEMICAL FEED

SCALE:

= 1'-0

4 0 2 4 8

N

PARTIAL THIRD FLOOR MECHANICAL ROOM - NEW WORK - HVAC

NEW WORK - HVAC

DEMOLITION &

FLOOR MECH. RM. -

PARTIAL THIRD

LINE LEGEND

POINT OF CONNECTION

NEW WORK

EXISTING TO REMAIN

DEMOLITION

AIR SEPARATOR

SUPPORT (TYP)

6"x4" CONCRETE

COOLING COIL

ACCESS

MIXING BOX

FILTER

PREHEAT COIL

FAN

DAMPER CONTROLLER

VENTURI

NOTES:(THIS SHEET ONLY)

REMOVE EXISTING PUMP, ISOLATION VALVE, TRIPLE DUTY VALVE,

FLEX CONNECTORS, STRAINER, CONTROLS, GAUGES, AND

ASSOCIATED STARTER FOR REPLACEMENT IN NEW WORK.

REMOVE EXISTING CHEMICAL FEEDER FOR REPLACEMENT

IN NEW WORK.

NEW VFD ON WALL.

NEW P-2 ON EXISTING CONCRETE PAD, REFER TO DETAIL.

P-1

P-2

NEW P-1 ON EXISTING CONCRETE PAD, REFER TO DETAIL.

CHEMICAL FEED

NEW

VFD P-2

P-1

VFD

P:\26056\26056m30.dgn

DGN FILE

28-OCT-2026

SEAL

SCALE:

FILE PATH:

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26056\26056m30.dgn

AS SHOWN

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

N B P P ro je c t

N o

G O

R D

O N S

T A

T E C

O L L E

G E

L A

M B

D

IN

H

A L L C

H

IL

L E

R R

E P

L A

C E

M E

N T

B a rn e s v il le

G e o rg ia

LTF

DRH

10.29.2026

26056

DRH

N S T

R U

C T

C U

M E

N T S

T

C H S

C H

R

AHU-1

E X

P

AAV

4" 4"

C H

R

C H

R

4" 4"

C H

RC

H

R

4"

4"

4"4"

CHR

ƒ" ƒ"

D

PRV

CW

1 ‚"

4"

4"

4"

4"

4"4"

AAV

AAV

CHR

T4"

CHR

CHS

2"4"

CHR

2"

4"

4" 1 •"

3"

C H

R C H S

3"

M U

PAN (TYPICAL)

SS DRAIN

PAD (TYPICAL)

CONCRETE

SENSOR (TYPICAL)

TEMPERATURE

VENTURI

INSIDE MECH. SHAFT

CHR/S PIPING DROP

M30

NOT TO SCALE

CHILLED WATER PIPING SCHEMATIC - DEMOLITION - HVAC

NEW WORK - HVAC

DEMOLITION &

PIPING SHEMATIC -

CHILLED WATER

T

C H S

C H

R

AHU-1

E

X P

AAV

P-1

2•"3"

2"

4" 4"

C H

R

C H

R

P-2

2•"

3"

2"

4" 4"

C H

RC

H

R

CF

CF

1"

4"

4"

4"4"

CHR

ƒ" ƒ"

D

PRV

CW

1 ‚"

4"

4"

4"

4"

4"4"

AAV

AAV

CHR

T4"

CHR

CHS

2"4"

CHR

2"

4"

4" 1 •"

3"

C H

R C H S

3"

M U

PAN (TYPICAL)

SS DRAIN

PAD (TYPICAL)

CONCRETE

CHEMICAL FEED

ONE SHOT

SENSOR (TYPICAL)

TEMPERATURE

VENTURI

INSIDE MECH. SHAFT

CHR/S PIPING DROP

NOT TO SCALE

CHILLED WATER PIPING SCHEMATIC - NEW WORK - HVAC

LINE LEGEND

POINT OF CONNECTION

NEW WORK

EXISTING TO REMAIN

DEMOLITION

EXTEND PAD AS REQUIRED FOR NEW WORK. REFER TO DETAIL.

NEW END SUCTION PUMP ON EXISTING CONCRETE PAD,

REPLACEMENT IN NEW WORK.

REMOVE EXISTING CHEMICAL FEEDER FOR

GAUGES, AND ASSOCIATED STARTER FOR REPLACEMENT IN NEW WORK.

TRIPLE DUTY VALVE, FLEX CONNECTORS, STRAINER, CONTROLS,

REMOVE EXISTING PUMP, ISOLATION VALVES,

NOTES:(THIS SHEET ONLY)

AIR COOLED CHILLER ISOMETRIC

DRAIN VALVE WITH HOSE

CONNECTION AT LOW POINT

M.A.V. AT

HIGH POINTS

(FOR ESTIMATING PURPOSES ONLY. PROVIDE PIPING ARRANGEMENT FOR UNIT FURNISHED.)

C H S

C H

R

CABLE ON PIPING

OUTDOORS ABOVE

GRADE

FLANGE ON GROUND

CONDUCTOR TO EVAPORATOR

ELECTRIC HEATING

WALL

AS SYSTEM PIPE.

MANUAL AIR VENT

TERMINATE DRAIN WITH HOSE END

CONNECTION 18" ABOVE FLOOR.

WHERE AIR VENTS OCCUR ABOVE ACCESSIBLE

CEILING. LOCATE VALVE AND TERMINATE DRAIN

HERE, UNLESS NOTED OTHERWISE AND POSITION

VALVE FOR VERTICAL DOWN DISCHARGE.

•" PIPE SAME MATERIAL

2•"

VERTICAL

PIPE

SUPPORT

WELDED PIPETHREADED / BRAISED

PIPING

BALL VALVE (EXPOSED) OR

GATE VALVE (CONCEALED)

ARRANGEMENT FOR LOCATIONS

WITH LIMITED CLEARANCE

6"MAX.

NOT TO SCALE

NOT TO SCALE

BRANCH CIRCUIT FROM

PANELBOARD,SWITCHGEAR,OR MCC

(2600)

SYSTEM SHOWN IN NORMAL (VFD NOT BYPASSED)

NUMBERS IN PARENTHESES INDICATE DIVISION

UNDER WHICH WORK OR EQUIPMENT IS SPECIFIED.

NOT TO SCALE

MODE, MOTOR RUNNING.

OVERLOAD

CIRCUIT

BREAKER

VFD SINGLE LINE DIAGRAM

VFD PACKAGE

RECTIFIER AND

INVERTER

NOTES:(THIS DETAIL ONLY)

TYPICAL END SUCTION PUMP

ELEVATION

FLEXIBLE CONNECTION

FLEXIBLE COUPLING AND

COUPLING GUARD

PIPE INSULATION

PRESSURE GAUGE

TEST PLUG

‚" BALL VALVE, TYPICAL

ADJUSTABLE FOOT

FULL SIZE BLOWDOWN ‚" DRAIN

TO FLOOR DRAIN

PAN (CHILLED WATER

PUMP(S) ONLY

18 GA. S.S. DRIP

2"

1"

SUCTION DIFFUSER

WITH STRAINER

BALL OR BUTTERFLY

•" DRAIN TAPPING

PIPE TO FLOOR DRAIN

CIRCUIT SETTER

NOT TO SCALE

(2600)

(2300)

MOTOR (2300)

EXISTING CONCRETE BASE

CHEMICAL FEED

NEW ONE SHOT

P-1 P-2

1"

CF

CF

3 3

A

BC

E

TO SYSTEM

B - ƒ" TO DISCHARGE OF PUMP.

C - ƒ" TO SUCTION OF PUMP.

F - RISER CLAMP. WELD TO 2X3/4 " FLAT

OFFSET BRACKET TO WALL.

A - CHEMICAL FEEDER TANK.

D - ƒ" TO FLOOR DRAIN.

D

4"MIN.

WELD

F

BALL VALVES

BY-PASS CHEMICAL FEEDER

NEW NEW

E - ‚" BALL VALVE FOR VENT.

NOT TO SCALE

P:\26056\26056e00.dgn

DGN FILE

28-OCT-2026

SEAL

SCALE:

FILE PATH:

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26056\26056e00.dgn

AS SHOWN

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

N B P P ro je c t

N o

G O

R D

O N S

T A

T E C

O L L E

G E

L A

M B

D

IN

H

A L L C

H

IL

L E

R R

E P

L A

C E

M E

N T

B a rn e s v il le

G e o rg ia

BCO

KMS

10.29.2026

26056

MJS

N S T

R U

C T

C U

M E

N T S

E00

ELECTRICAL

LEGEND, & RISER -

NOT TO SCALE

CONNECTION TO EQUIPMENT

CAP

CONDUIT DOWN

CONDUIT UP

RECEPTACLES

CIRCUITS

ELECTRICAL LEGEND

DUPLEX RECEPTACLE - NORMAL

QUAD - NORMAL

GFCI DUPLEX RECEPTACLE - NORMAL

GFCI QUAD - NORMAL

SPECIAL - TYPE NOTED OR SHOWN

WEATHER PROOF RECEPTACLE (GFCI)

ELECTRIC WATER COOLER RECEPTACLE(GFCI)

CONDUIT CONCEALED IN CEILING OR WALL

CONDUIT IN GROUND, SLAB, OR UNDER FLOOR

FLEXIBLE RACEWAY

RACEWAY EXPOSED

WP

AC

ABOVE COUNTER DUPLEX RECEPTACLE (COORDINATE

HEIGHT WITH ARCHITECT)DUPLEX RECEPTACLE - TAMPER PROOFT

HOMERUN - ONE ARROW PER CIRCUIT

WP

PANELBOARD-250 VAC OR LESS

SURFACE MOUNTED

PANELBOARD-250 VAC OR LESS

RECESSED

PANELBOARD-OVER 250 VAC

SURFACE MOUNTED

PANELBOARD-OVER 250 VAC

RECESSED

BACKBOARD

J

M

GENERAL EQUIPMENT

T

JJ

TRANSFORMER

FRAME AMPS/POLES/NEMA TYPE

FUSE PER MANUFACTURERS RECOMMENDATIONS

ENCLOSED BREAKER-RECESSED IN WALL

ENCLOSED CIRCUIT BREAKER

EMERGENCY PUSHBUTTON

COMBINATION STARTER AND DISCONNECT

EXHAUST FAN

MANUAL STARTER AND MOTOR RATED SWITCH

MOTOR

JUNCTION BOX - WALL/CEILING/FLOOR

SURGE SUPPRESSOR

DISCONNECT SWITCH: "F" IF FUSED

F

SLAB OR BELOW GRADE

GROUNDING CONDUCTOR- UNDER

G

C GROUND ROD - C IF CHEMICAL

GROUND CONNECTION (SCHEMATIC)

GROUNDING

PARTIAL POWER RISER

LB

EXISTING

CB

EXISTING

LGA

EXISTING

LC

EXISTING

CC

EXISTING

LAP

EXISTING

TCS

EXISTING

TCS

EXISTING

SIEMENS SWBD

EXISTING

CHILLER

NEW

FF

SAME LOCATION

BREAKER WITH NEW IN THE

REPLACE THE EXISTING 800A/3P

PUMPS

PANEL TO BE REUSED FOR THE NEW

THE EXISTING 40/3 BREAKERS IN THIS

F-CH-CNTRL

DISCONNECT

FUSED

NEW 30/3/3R

F-CH

DISCONNECT

FUSED

NEW 800/3/3R

LIQUIDTITE WITHIN 24".

1#4/0G IN 4" IMC. TRANSITION TO

ROUTE 3#600 KCMIL CU CONDUCTORS,

WITH PIPE SUPPORT ON 36" INTERVALS.

CHILLER MAY BE ROUTED ON GRADE

NEW CONDUIT FROM DISCONNECT TO

P:\26056\26056e10.dgn

DGN FILE

28-OCT-2026

SEAL

SCALE:

FILE PATH:

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26056\26056e10.dgn

AS SHOWN

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

N B P P ro je c t

N o

G O

R D

O N S

T A

T E C

O L L E

G E

L A

M B

D

IN

H

A L L C

H

IL

L E

R R

E P

L A

C E

M E

N T

B a rn e s v il le

G e o rg ia

BCO

KMS

10.29.2026

26056

MJS

N S T

R U

C T

C U

M E

N T S

1 12

STAIR 2

1 14

BREAK RM

MECH. 121

MECH.

MECH.

1 1 1

MECH. YARD

1 13

MECH. SHAFT

1 12

STAIR 2

1 14

BREAK RM

MECH. 121

MECH.

MECH.

1 1 1

MECH. YARD

1 13

MECH. SHAFT

GENERATOR

EXISTING

(TYPICAL)

PIPE SUPPORT

CONCRETE

EXISTING CONCRETE PAD

LGA

SWBD

EXISTING PULLBOX

CHR-1

NEW CHILLER

E10

SCALE:

= 1'-0

4 0 2 4 8

N

GENERATOR

EXISTING

FF

PARTIAL FIRST FLOOR/MECHANICAL YARD - DEMOLITION - ELEC

(TYPICAL)

PIPE SUPPORT

CONCRETE

SCALE:

= 1'-0

4 0 2 4 8

N

NEW WORK - ELEC

DEMOLITION &

FLOOR/MECH YARD -

PARTIAL FIRST

PARTIAL FIRST FLOOR/MECHANICAL YARD - NEW WORK - ELEC

EXISTING CONCRETE PAD

CHILLER

AIR COOLED

EXISTING

REMOVE

GENERAL NOTES:(THIS SHEET ONLY)

A

DOCUMENTS AND ACTUAL CONDITIONS AT THE SITE MAY VARY.

OWNER NOR THE ARCHITECT WARRANT THESE TO BE "AS-BUILT"

BEEN PREPARED USING "AS-DESIGN" DOCUMENTS. NEITHER THE

DRAWINGS FOR ARCHITECTURAL AND ENGINEERING WORK HAVE

B

TO COMPLETE THE DEMOLITION/NEW WORK.

CONTRACTOR FROM PROVIDING ANY AND ALL WORK REQUIRED

SCOPE OF DEMOLITION/NEW WORK AND IN NO WAY RELIEVES THE

THE WORK INDICATED IS INTENDED TO SHOW THE GENERAL

C COORDINATE DEMOLITION WORK WITH NEW WORK.

D

AREA REQUIRING WORK.

COMPONENTS, BUILDING SYSTEMS, ETC. ADJACENT TO OR NEAR

PROTECT FROM DAMAGE/MAINTAIN EXISTING ITEMS,

E

TEXTURE, QUALITY, ETC.)

MATERIAL, SIZE, ALIGNMENT, JOINT WORK, FINISHES, COLOR,

SURFACES SHALL BE REPAIRED TO MATCH EXISTING (IN

MECHANICAL, ELECTRICAL, AND PLUMBING WORK), SUCH

WHERE SURFACES ARE DAMAGED BY DEMOLITION (INCLUDING

F

EXISTING SURROUNDINGS.

ABANDONED CUT FLUSH TO FLOOR AND FINISH TO MATCH

COVER FOR ANY ABANDONED BOXES. WHERE CONDUIT IN SLAB IS

SHALL BE NO UNTERMINATED CONDUCTORS. PROVIDE BLANK

LONGER BE IN USE TO THE POINT OF LAST TERMINATION. THERE

REMOVE ALL CONDUCTORS FROM CIRCUITS THAT WILL NO

NOTES:(THIS SHEET ONLY)

LGA

SWBD 2

2 REMOVE EXISTING 800A CHILLER BREAKER AND REPLACE WITH NEW.

EXISTING PULLBOX

BE REUSED.

EXISTING CONDUCTORS FROM THE PULLBOX TO THE SWITCHBOARD TO

LOCATION.

THE LOAD SIDE OF THE OLD DISCONNECT TO THE DEMOLISHED CHILLER

REMOVE EXISTING CONDUCTORS (OR ABANDON IF UNDERGROUND) FROM

5 REMOVE EXISTING DISCONNECTS AND REPLACE WITH NEW.

FF

THE OLD. FUSE DOWN TO NEW CHILLER MOCP (400A ASSUMED)

PROVIDE A NEW 800A FUSED DISCONNECT IN THE SAME LOCATION AS

CONTROLLER.

EXTEND A NEW PORTION OF THE CIRCUITOVER TO THE HEAT TRACE

LOCATION. MAKE ALL CONNECTIONS BACK TO EXISTING 120V CIRCUITS.

PROVIDE NEW FUSED DISCONNECT TO REPLACE THE OLD IN THE SAME

THE DEMOLISHED CHILLER.

WAS LOCATED. TRACE EXISTING CIRCUIT TO CONFIRM IT SERVES ONLY

ADD NEW 800A/3P BREAKER IN THE SAME SPACE AS THE EXISTING

CONTROLLER. MAKE ALL FINAL CONNECTIONS.

3#10 IN •" IMC ROUTED NEATLY ALONG WALL TO NEW HEAT TAPE

P:\26056\26056e20.dgn

DGN FILE

28-OCT-2026

SEAL

SCALE:

FILE PATH:

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26056\26056e20.dgn

AS SHOWN

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

N B P P ro je c t

N o

G O

R D

O N S

T A

T E C

O L L E

G E

L A

M B

D

IN

H

A L L C

H

IL

L E

R R

E P

L A

C E

M E

N T

B a rn e s v il le

G e o rg ia

BCO

KMS

10.29.2026

26056

MJS

N S T

R U

C T

C U

M E

N T S

T

P

S

C

VFD-1 VFD-2

AHU-1

DDCICS

L-1

TANK

EXPANSION

COOLING COIL

ACCESS

MIXING BOX

FILTER

PREHEAT COIL

FAN

DAMPER CONTROLLER

P-1

P-2

VFD P-2

P-1

VFD

E20

SCALE:

= 1'-0

4 0 2 4 8

N

T

P

S

C

P-1

P-2

VFD-1 VFD-2

AHU-1

DDCICS

PARTIAL THIRD FLOOR MECHANICAL ROOM - DEMOLITION - ELEC

L-1

TANK

EXPANSION

CHEMICAL FEED

SCALE:

= 1'-0

4 0 2 4 8

N

PARTIAL THIRD FLOOR MECHANICAL ROOM - NEW WORK - ELEC

NEW WORK - ELEC

DEMOLITION &

FLOOR MECH. RM. -

PARTIAL THIRD

COOLING COIL

ACCESS

MIXING BOX

FILTER

PREHEAT COIL

FAN

DAMPER CONTROLLER

GENERAL NOTES:(THIS SHEET ONLY)

A

DOCUMENTS AND ACTUAL CONDITIONS AT THE SITE MAY VARY.

OWNER NOR THE ARCHITECT WARRANT THESE TO BE "AS-BUILT"

BEEN PREPARED USING "AS-DESIGN" DOCUMENTS. NEITHER THE

DRAWINGS FOR ARCHITECTURAL AND ENGINEERING WORK HAVE

B

TO COMPLETE THE DEMOLITION/NEW WORK.

CONTRACTOR FROM PROVIDING ANY AND ALL WORK REQUIRED

SCOPE OF DEMOLITION/NEW WORK AND IN NO WAY RELIEVES THE

THE WORK INDICATED IS INTENDED TO SHOW THE GENERAL

C COORDINATE DEMOLITION WORK WITH NEW WORK.

D

AREA REQUIRING WORK.

COMPONENTS, BUILDING SYSTEMS, ETC. ADJACENT TO OR NEAR

PROTECT FROM DAMAGE/MAINTAIN EXISTING ITEMS,

E

TEXTURE, QUALITY, ETC.)

MATERIAL, SIZE, ALIGNMENT, JOINT WORK, FINISHES, COLOR,

SURFACES SHALL BE REPAIRED TO MATCH EXISTING (IN

MECHANICAL, ELECTRICAL, AND PLUMBING WORK), SUCH

WHERE SURFACES ARE DAMAGED BY DEMOLITION (INCLUDING

F

EXISTING SURROUNDINGS.

ABANDONED CUT FLUSH TO FLOOR AND FINISH TO MATCH

COVER FOR ANY ABANDONED BOXES. WHERE CONDUIT IN SLAB IS

SHALL BE NO UNTERMINATED CONDUCTORS. PROVIDE BLANK

LONGER BE IN USE TO THE POINT OF LAST TERMINATION. THERE

REMOVE ALL CONDUCTORS FROM CIRCUITS THAT WILL NO

NOTES:(THIS SHEET ONLY)

VFD 2

G

THE BREAKERS AND CONDUCTORS TO POWER THE NEW VFDs.

THE TWO 40/3P BREAKERS CURRENTLY SERVING THE PUMPS. REUSE

PANEL LC IS LOCATED OFF THE SHEET IN THIS LOCATION, AND HAS

THE BREAKERS AND CONDUCTORS TO POWER THE NEW VFDs.

THE TWO 40/3P BREAKERS CURRENTLY SERVING THE PUMPS. REUSE

PANEL LC IS LOCATED OFF THE SHEET IN THIS LOCATION, AND HAS

(LIQUIDTITE WITHIN 24").

VFD LOCATIONS. MAKE ALL FINAL CONNECTIONS WITH 3#8, 1#10G IN ƒ" C

NEW VFDs BY DIV 23. EXTEND THE EXISTING CIRCUITS TO THE NEW

PREP EXISTING CIRCUITS FOR CONNECTION TO THE NEW VFDs.