Text version

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment your desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE

2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 10-83)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICITATION

NO.

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. DATED (SEE ITEM 13)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended.

12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO.

IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

NSN 7540-01-152-8070

Previous edition unusable

7PQD

Shawna Villarreal, Contracting Officer

This amendment is issued to provide a revised Exhibit F that replaces the exhibit included in Amendment 0002.

7PQD

ACQUISITION MANAGEMENT DIVISION

ACQUISITION ENERGY & ACQUISITION SUPPORT

BRANCH

819 TAYLOR ST RM 12B01

FORT WORTH TX 6102

ACQUISITION MANAGEMENT DIVISION

ACQUISITION ENERGY & ACQUISITION SUPPORT

BRANCH

819 TAYLOR ST RM 12B01

FORT WORTH TX 6102

EQ7PMD-17-0033

GS-07-P-17-HT-C-0008

1 10

7/13/2017

5/31/2017

Amendment No. 4 – Solicitation No. GS-07-P-17-HT-C-0008 for Chiller Removal & Installation at the Roswell Federal Building in Roswell, NM

This amendment is issued to respond to questions.

1. There are 5 pumps to be replaced; 2 CHW, 2 CW, and 1 CHW “perimeter” pump. The pump specs released with Amendment 002 have the new perimeter pump designated as HWP-1,2 as in two heating water pumps. I can only assume this is a typing error but can you please confirm or clarify. Please see the attached revised document.

2. Is the Distech controller referenced below existing and to be replaced by the BAS upgrade already underway? YES, the Siemens plant controller will be replaced with a Distech ECB-610 IO-34 and ECB-410 IO-34 BACnet MS/TP unitary plant controllers networked to a True Vykon Niagara 4 JACE 8000.

3. Or is it going to be replaced by the BAS upgrade underway to an Open Protocol Controller? The Distech ECB-610 IO-34 and ECB-410 IO-34 BACnet MS/TP unitary plant controllers and True Vykon Niagara 4 JACE 8000 are considered open due to open licences, open BACnet protocol, Open licenses engineering tools installed on the Roswell BAS engineering laptop, and DDC open warehouse distribution parts channels.

The only real consideration to be made is that the GSA requires 20% spare I/O and Solid State on board flash RAM capacity at the end of the project warranty for all DDC projects at the unitary and supervisory integration layers. It is incumbent on the controls contractor to ensure that the existing plant I/O and the new plant I/O counts are the within similar capacity so to ensure that the 20% requirement is not violated by the plant project. If the new plant requires more I/O that what is currently there or on the attached control drawing, then an additional BACnet MS/TP Distech controller will need to be added.

Submittal Ref. #: 619673.1 rev1

Split coupled vertical in line pump

Model: Series 4300-1.5x1.5x8-1.5 hp Pump (Motor supplier: Armstrong choice)

Project name: GSA Roswell

Location: Roswell, NM

Date submitted: 6/26/2017 8:18:38 AM

Engineer:

Contractor:

Application design data Tag number: HWP-1,2 Pipe orientation: Single

Suction pressure: 0 ftService: HW

Location: CUP Fluid: Water:

Quantity: 2 Operating temperature: 60 F Viscosity: 31 SSUDuty flow per pump: 52 USgpm

Specific gravity: 1.0000Duty head: 55 ft

Total dissolved solids: 0 ppm

Materials of construction Construction: BF Impeller: Bronze (B584-844) Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416 Connections: Inlet: 1.5 in, Outlet: 1.5 in Flush line: Braided Stainless Steel

Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data Seal type Outside Balanced Rotating face: Resin Bonded Carbon Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide

Springs: Stainless Steel Secondary seal: Viton

Rotating hardware: Stainless Steel

Motor electrical data Factory ChoiceSupplier: Insulation class: Class F Insulation

Size: 1.5 hp Inverter motor type: Inverter Duty Frame number: 145TC Efficiency: NEMA Prem (12.12) Enclosure: ODP Speed: 1760 rpm Motor Electrics: 460/3/60

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 1 of 7

Performance curve

--- Admin Data --- Tag Num:

HWP-1,2 Service:

HW Location: CUP

--- Motor Data --- Motor Size: 1.5 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 52 usgpm Head: 55 ft Impeller: 8.05 in

--- Performance Data ---

• NPSHR: 5.2654 ft

• Eff. @ Design: 51.72 %

• BHP @ Design: 1.40 hp

• Mtr Capability @ Rated Spd: 1.5 hp

• %Mtr Safety: 7.42% ->Contract Efficiency NCP req.

• BEP @ Design Imp.:

51.84 % @ 48.9 usgpm

• Impeller Max BHP @ Flow:

1.81 hp @ 73.4 usgpm

• %max imp. range: 93.71 %

• Outlet Velocity: 8.19 ft/s

• VFD Setting: 60.0 Hz

Series 4300 1.5x1.5x8 @ 1760 rpm

0 20 40 60 80 100

Flow (usgpm)

Head (ft)

8.19 in

6.00 in

System

8.05 in

1 hp

1.5 hp

2 hp

35%

Water:, spgr= 1.0000

PT14-1-0 (3.29.0.21)

ANSI/HI 14.6.3.4.1

--- Admin Data --- Tag Num:

HWP-1,2 Service:

HW Location: CUP

--- Motor Data --- Motor Size: 1.5 hp Motor Speed: 1800 rpm

--- Design Duty Point --- Flow: 52 usgpm Head: 55 ft Impeller: 8.05 in

--- System Intersect Data ---

1. System @ 60.0 Hz:

• 52 @ 55, 1.4 hp

2. System @ 51.5 Hz:

• 44.6 @ 40.5, 0.88 hp

3. System @ 43.3 Hz:

• 37.5 @ 28.6, 0.52 hp

4. System @ 34.8 Hz:

• 30.1 @ 18.5, 0.27 hp

5. System @ 26.6 Hz:

• 23 @ 10.8, 0.12 hp

6. System @ 18.0 Hz:

• 15.6 @ 4.9469, 0.04 hp

Series 4300 1.5x1.5x8 @ 8.05 in

0 20 40 60 80 100

Flow (usgpm)

Head (ft)

1848 rpm

1760 rpm

528 rpm

System

1760 rpm

1 hp

1.5 hp

2 hp

3 hp

1510 rpm

1270 rpm

1020 rpm

780 rpm

Water:, spgr= 1.0000

PT14-1-0 (3.29.0.21)

ANSI/HI 14.6.3.4.1

www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 2 of 7

Dimensional data (not for construction) Top viewSide view

Weight: 213 lb

• Not to scale

• R = minimum lifting clearance required above motor

• Units of measure : inches [millimeters]

• Coupling guard and flush line (not shown) are supplied

• Tolerance of ± 0.125 inch (± 3 mm) should be used

• For certified dimensions, please contact your Armstrong representative

• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 1.5 5ANSI-125 4 0.53.88

Outlet 1.5 5ANSI-125 4 0.53.88

*Equally spaced straddling centreline

Special instructions

Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.

%Motor Safety is less than standard test tolerance, motor may overload on site.

Additional equipment Flotrex: FTV-2TS (570200-218) Suction Guide: SG-1515TF (516860-052) www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 3 of 7

Flo-trex valve Model:

Project name: GSA Roswell

Location: Roswell, NM Representative:

Date submitted: 6/26/2017 8:18:38 AM Phone number:

Engineer: e-mail:

Contractor: Submitted by:

Application design data

Design flowrateTag Qty Model Size Config Flange rating Pressure

Drop* Associated pump

HWP-1,2 2 FTV-2TS 2 in Straight Threaded

None 52.0 USgpm 1.5 psi HWP-1,2 4300-1.5x1.5x8-1.5 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction FTV-2TS-Flo-Trex Valve-Straight Threaded FTV1.25-2

Body: SS 304 A351 Spring: SS ASTM A-313 TYPE 302-(18-8)

Disc: Brass C46500 EPDMO rings:

2 metering ports: Brass Body with EPDM Check and

Gasketed Cap Stem: Brass C46500

2 drain tappings: ¼" NPT with SS 304 Plug

Operating limits (temperature - pressure)

FTV-2TS-Flo-Trex Valve-Straight Threaded

Maximum pressure: 175 psi

Maximum temperature: 230 F www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 4 of 7

Model: FTV-2TS-Flo-Trex Valve-Straight Threaded Weight: 6 lb

Side view Front view

Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 5 of 7

Suction guide Model: SG-TF

Project name: GSA Roswell

Location: Roswell, NM Representative:

Date submitted: 6/26/2017 8:18:38 AM Phone number:

Engineer: e-mail:

Contractor: Submitted by:

Application design data

Design flowrateTag Qty Model System Pump Pressure

Drop* Associated pump

HWP-1,2 2 SG-1515TF 1.5 in 1.5 in 52.0 USgpm 0.1 psi HWP-1,2 4300-1.5x1.5x8-1.5 hp Pump (Factory Choice Motor)

*at design flow

Materials of construction

SG-1515TF

Body: Ductile Iron Cover gasket: Synthetic fiber

Guide vanes: Ductile Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Ductile Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)

SG-1515TF-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 6 of 7

SG-1515TF Weight: 22 lb

Side view Top view

Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 7 of 7