Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment your desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION
NO.
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO.
IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
NSN 7540-01-152-8070
Previous edition unusable
7PQD
Shawna Villarreal, Contracting Officer
Amendment 0002 is issued to provide Exhibits E - F and to respond to questions. The proposal due date has been extended from 7/12/2017 to 7/17/2017 at 2:00 PM CDT.
7PQD
ACQUISITION MANAGEMENT DIVISION
ACQUISITION ENERGY & ACQUISITION SUPPORT
BRANCH
819 TAYLOR ST RM 12B01
FORT WORTH TX 6102
ACQUISITION MANAGEMENT DIVISION
ACQUISITION ENERGY & ACQUISITION SUPPORT
BRANCH
819 TAYLOR ST RM 12B01
FORT WORTH TX 6102
EQ7PMD-17-0033
GS-07-P-17-HT-C-0008
1 12
7/10/2017
5/31/2017
Amendment No. 2 – Solicitation No. GS-07-P-17-HT-C-0008 for Chiller Removal & Installation at the Roswell Federal Building in Roswell, NM
This amendment is issued to provide Exhibits E - F and to respond to questions. The proposal due date has been extended from 7/12/2017 to 7/17/2017 at 2:00 PM CDT.
1. Does the chiller have to be a 4 pass heat exchanger? No, but the pressure drop must be equal to or less than what is listed in the solicitation or your proposal will not be accepted.
2. Confirming that chiller is a single compressor design. The original bid description states it needs to be two compressors. These two (2) magnetic bearing chillers are a single compressor design.
3. Please provide information on existing lighting to be replaced such as controls, output, B/U capabilities, and quantity. Contractor shall remove and replace existing fixtures to match all associated existing conditions. The existing thirty (30) fixture(s) does not have controls and/or B/U capabilities. Contractor shall provide fixture factory specification cut-sheet for review and acceptance prior to purchasing materials. No linear L.E.D.’s (TLED’s) will accepted as an option for this project.
4. Please confirm existing pumps are 208v. Existing pumps are connected to a 460 volt source. The existing pumps are dual voltage 208/460 volts.
5. I do not see Exhibits e. & f. with the revised SOW. Please let me know if these were left out or can be found elsewhere. The exhibits are attached.
Submittal Ref. #: 619673.1 rev1
Split coupled vertical in line pump
Model: Series 4300-1.5x1.5x8-1.5 hp Pump (Motor supplier: Armstrong choice)
Project name: GSA Roswell
Location: Roswell, NM Representative: Texas Air Systems LLC DFW
Date submitted: 6/26/2017 8:18:38 AM Phone number:
Engineer: e-mail: patrick.mooney@texasairsystems.com
Contractor: Submitted by: Patrick Mooney12
Application design data Tag number: HWP-1,2 Pipe orientation: Single
Suction pressure: 0 ftService: HW
Location: CUP Fluid: Water:
Quantity: 2 Operating temperature: 60 F Viscosity: 31 SSUDuty flow per pump: 52 USgpm
Specific gravity: 1.0000Duty head: 55 ft
Total dissolved solids: 0 ppm
Materials of construction Construction: BF Impeller: Bronze (B584-844) Rating: ANSI-125 Pump shaft: SS ASTM A276 Type 416 Connections: Inlet: 1.5 in, Outlet: 1.5 in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron (A48-30) Casing gasket: Confined Non-Asbestos Fiber
Mechanical seal data Seal type Outside Balanced Rotating face: Resin Bonded Carbon Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel
Motor electrical data Factory ChoiceSupplier: Insulation class: Class F Insulation
Size: 1.5 hp Inverter motor type: Inverter Duty Frame number: 145TC Efficiency: NEMA Prem (12.12) Enclosure: ODP Speed: 1760 rpm Motor Electrics: 460/3/60
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 200 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 1 of 7
Performance curve
--- Admin Data --- Tag Num: HWP-1,2 Service: HW Location: CUP
--- Motor Data --- Motor Size: 1.5 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 52 usgpm Head: 55 ft Impeller: 8.05 in
--- Performance Data ---
• NPSHR: 5.2654 ft
• Eff. @ Design: 51.72 %
• BHP @ Design: 1.40 hp
• Mtr Capability @ Rated Spd: 1.5 hp
• %Mtr Safety: 7.42% ->Contract Efficiency NCP req.
• BEP @ Design Imp.:
51.84 % @ 48.9 usgpm
• Impeller Max BHP @ Flow:
1.81 hp @ 73.4 usgpm
• %max imp. range: 93.71 %
• Outlet Velocity: 8.19 ft/s
• VFD Setting: 60.0 Hz
Series 4300 1.5x1.5x8 @ 1760 rpm
0 20 40 60 80 100
Flow (usgpm)
Head (ft)
8.19 in
6.00 in
System
8.05 in
1 hp
1.5 hp
2 hp
35%
Water:, spgr= 1.0000
PT14-1-0 (3.29.0.21)
ANSI/HI 14.6.3.4.1
--- Admin Data --- Tag Num: HWP-1,2 Service: HW Location: CUP
--- Motor Data --- Motor Size: 1.5 hp Motor Speed: 1800 rpm
--- Design Duty Point --- Flow: 52 usgpm Head: 55 ft Impeller: 8.05 in
--- System Intersect Data ---
1. System @ 60.0 Hz:
• 52 @ 55, 1.4 hp
2. System @ 51.5 Hz:
• 44.6 @ 40.5, 0.88 hp
3. System @ 43.3 Hz:
• 37.5 @ 28.6, 0.52 hp
4. System @ 34.8 Hz:
• 30.1 @ 18.5, 0.27 hp
5. System @ 26.6 Hz:
• 23 @ 10.8, 0.12 hp
6. System @ 18.0 Hz:
• 15.6 @ 4.9469, 0.04 hp
Series 4300 1.5x1.5x8 @ 8.05 in
0 20 40 60 80 100
Flow (usgpm)
Head (ft)
1848 rpm
1760 rpm
528 rpm
System
1760 rpm
1 hp
1.5 hp
2 hp
3 hp
1510 rpm
1270 rpm
1020 rpm
780 rpm
Water:, spgr= 1.0000
PT14-1-0 (3.29.0.21)
ANSI/HI 14.6.3.4.1
www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 2 of 7
Dimensional data (not for construction) Top viewSide view
Weight: 213 lb
• Not to scale
• R = minimum lifting clearance required above motor
• Units of measure : inches [millimeters]
• Coupling guard and flush line (not shown) are supplied
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 1.5 5ANSI-125 4 0.53.88
Outlet 1.5 5ANSI-125 4 0.53.88
*Equally spaced straddling centreline
Special instructions
Armstrong Motor Specification AES 05007 The program has defaulted to a NEMA Premium Efficiency motor supplied with NEMA MG-1 Part 31.4.4.2 insulation standards for inverter-fed polyphase motors.
%Motor Safety is less than standard test tolerance, motor may overload on site.
Additional equipment Flotrex: FTV-2TS (570200-218) Suction Guide: SG-1515TF (516860-052) www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 3 of 7
Flo-trex valve Model:
Project name: GSA Roswell
Location: Roswell, NM Representative: Texas Air Systems LLC DFW
Date submitted: 6/26/2017 8:18:38 AM Phone number:
Engineer: e-mail: patrick.mooney@texasairsystems.com
Contractor: Submitted by: Patrick Mooney12
Application design data
Design flowrateTag Qty Model Size Config Flange rating Pressure
Drop* Associated pump
HWP-1,2 2 FTV-2TS 2 in Straight Threaded
None 52.0 USgpm 1.5 psi HWP-1,2 4300-1.5x1.5x8-1.5 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction FTV-2TS-Flo-Trex Valve-Straight Threaded FTV1.25-2
Body: SS 304 A351 Spring: SS ASTM A-313 TYPE 302-(18-8)
Disc: Brass C46500 EPDMO rings:
2 metering ports: Brass Body with EPDM Check and
Gasketed Cap Stem: Brass C46500
2 drain tappings: ¼" NPT with SS 304 Plug
Operating limits (temperature - pressure)
FTV-2TS-Flo-Trex Valve-Straight Threaded
Maximum pressure: 175 psi
Maximum temperature: 230 F www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 4 of 7
Model: FTV-2TS-Flo-Trex Valve-Straight Threaded Weight: 6 lb
Side view Front view
Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 5 of 7
Suction guide Model: SG-TF
Project name: GSA Roswell
Location: Roswell, NM Representative: Texas Air Systems LLC DFW
Date submitted: 6/26/2017 8:18:38 AM Phone number:
Engineer: e-mail: patrick.mooney@texasairsystems.com
Contractor: Submitted by: Patrick Mooney12
Application design data
Design flowrateTag Qty Model System Pump Pressure
Drop* Associated pump
HWP-1,2 2 SG-1515TF 1.5 in 1.5 in 52.0 USgpm 0.1 psi HWP-1,2 4300-1.5x1.5x8-1.5 hp Pump (Factory Choice Motor)
*at design flow
Materials of construction
SG-1515TF
Body: Ductile Iron Cover gasket: Synthetic fiber
Guide vanes: Ductile Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Ductile Iron Start-up strainer*: Fine Mesh Galvanized Steel
*Remove start up strainer after 24 hours
Operating limits (temperature - pressure)
SG-1515TF-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 230 F
Units are hydrostatically tested to 150% of maximum working pressure www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 6 of 7
SG-1515TF Weight: 22 lb
Side view Top view
Not to scale Units of measure: inches [millimeters] Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative www.armstrongfluidtechnology.com 6/26/2017, Ref. # 619673.1 rev1 Page 7 of 7