IRS ENTERPRISE COMPUTER CENTER COOLING TOWER
250 Murall Drive
Kearneysville, West Virginia
GSA # GS-P-03-15-DX-5027
SECTION 104416 - FIRE EXTINGUISHERS (Applies to Base Bid)
GENERALPART 1 -
RELATED DOCUMENTS1.1
Drawings and general provisions of the Contract, including General and SupplementaryA.
Conditions and Division 01 Specification Sections, apply to this Section.
SUMMARY1.2
Section includes portable, hand-carried fire extinguishers and mounting brackets for fireA.
extinguishers.
SUBMITTALS1.3
Product Data: For each type of product indicated. Include rating and classification,A.
material descriptions, dimensions of individual components and profiles, and finishes for fire extinguisher and mounting brackets.
Operation and Maintenance Data: For fire extinguishers to include in maintenanceB.
manuals.
Warranty: Sample of special warranty.C.
QUALITY ASSURANCE1.4
NFPA Compliance: Fabricate and label fire extinguishers to comply with NFPA 10,A.
"Portable Fire Extinguishers."
Fire Extinguishers: Listed and labeled for type, rating, and classification by anB.
independent testing agency acceptable to authorities having jurisdiction.
Provide fire extinguishers approved, listed, and labeled by FMG.1.
FIRE EXTINGUISHERS
PROPERTY OF THE U.S. GOVERNMENT - FOR OFFICIAL USE ONLY
Do not remove this notice - Properly destroy documents when no longer needed
104416 - 1 Bid Documents
11 MARCH 2016
Kearneysville, West Virginia
GSA # GS-P-03-15-DX-5027
WARRANTY1.5
Special Warranty: Manufacturer's standard form in which manufacturer agrees to repairA.
or replace fire extinguishers that fail in materials or workmanship within specified warranty period.
Failures include, but are not limited to, the following:1.
Failure of hydrostatic test according to NFPA 10.a.
Faulty operation of valves or release levers.b.
Warranty Period: Six years from date of Substantial Completion.2.
PRODUCTSPART 2 -
PORTABLE, HAND-CARRIED FIRE EXTINGUISHERS2.1
Fire Extinguishers: Type, size, and capacity for each mounting bracket indicated.A.
Valves: Chrome Plated Brass.1.
Handles and Levers: Stainless Steel.2.
Instruction Labels: Include pictorial marking system complying with NFPA 10,3.
Appendix B and bar coding for documenting fire extinguisher location, inspections, maintenance, and recharging.
Bi-lingual Labels: Spanish and English.4.
Multipurpose Dry-Chemical Type in Steel Container: UL-rated 4-A:80-B:C, 10-lb nominalB.
capacity, with monoammonium phosphate-based dry chemical in steel container. Finish shall be red durable High Gloss Polyester Powder Paint.
MOUNTING BRACKETS2.2
Mounting Brackets: Manufacturer's standard steel, designed to secure fire extinguisherA.
to wall or structure, of sizes required for types and capacities of fire extinguishers indicated, with plated or red baked-enamel finish.
Identification: Lettering complying with authorities having jurisdiction for letter style, size,B.
spacing, and location. Locate as indicated on drawings.
FIRE EXTINGUISHERS
PROPERTY OF THE U.S. GOVERNMENT - FOR OFFICIAL USE ONLY
Do not remove this notice - Properly destroy documents when no longer needed
104416 - 2
Kearneysville, West Virginia
GSA # GS-P-03-15-DX-5027
Identify bracket-mounted fire extinguishers with the words "FIRE EXTINGUISHER"1.
in red letter decals applied to mounting surface.
Orientation: Vertical.a.
EXECUTIONPART 3 -
EXAMINATION3.1
Examine fire extinguishers for proper charging and tagging.A.
Remove and replace damaged, defective, or undercharged fire extinguishers.1.
Proceed with installation only after unsatisfactory conditions have been corrected.B.
INSTALLATION3.2
General: Install fire extinguishers and mounting bracket in locations indicated and inA.
compliance with requirements of authorities having jurisdiction.
Mounting Brackets: 54 inches above finished floor to top of fire extinguisher.1.
Mounting Brackets: Fasten mounting brackets to surfaces, square and plumb, atB.
locations indicated.
The location intent is to maximize line of sight to the extinguisher. The contractor is atC.
liberty to propose an alternate location subject to construction management team approval.
END OF SECTION 104416
FIRE EXTINGUISHERS
PROPERTY OF THE U.S. GOVERNMENT - FOR OFFICIAL USE ONLY
Do not remove this notice - Properly destroy documents when no longer needed
104416 - 3
Kearneysville, West Virginia
GSA # GS-P-03-15-DX-5027
THIS PAGE INTENTIONALLY LEFT BLANK
FIRE EXTINGUISHERS
PROPERTY OF THE U.S. GOVERNMENT - FOR OFFICIAL USE ONLY
Do not remove this notice - Properly destroy documents when no longer needed
104416 - 4
| RELATED DOCUMENTS |
| SUMMARY |
| SUBMITTALS |
| Operation and Maintenance Data: For fire extinguishers to include in maintenance manuals. |
| Warranty: Sample of special warranty. |
| QUALITY ASSURANCE |
| Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent test |
| WARRANTY |
| Faulty operation of valves or release levers. |