Dyess AFB Power Outage Log
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY 2010
3-Jan-10 0800 to 0830 B-4300 Ryder & Thomas EXTERIOR/S
Kill power to Tower for contractor 4hrs./C
3-Jan-10 1500 to 1530 B-6117 Ryder & Thomas INTERIOR/US
Customer overloaded circuit/reset breaker 30min./C
3-Jan-10 1900 to 1930 B-8008 Ryder EXTERIOR/S
Hotline clamp & stirrup arching 30min./S
4-Jan-10 1200 to 0030 B-6030B Ryder Security Alarms/US
Security Alarm will not reset 30min/S
16-17-Jan-10 0800 (16) 1500(17) Bldgs.5100,5111.5140 Rosario & Baker EXTERIOR/S
Took power down for contractor work 2hrs./C
18-Jan-10 0800 to 1030 B2-circuit Rosario & Baker EXTERIOR/S
Took power down for contractor work 2hrs./C
18-Feb-10 1930 to shop B1 ramp lights Catalan/Etter AIRFIELD/US
B1 ramp lights out/reset 2ea.turned
2ea.on hand op 1hr.
2-Mar-10 730 to 1030 B-8032
Collier,Rosario,Rodriq uez,Baker EXTERIOR/S replaced cutouts & LA
2 1/2 hrs./C
4-Mar-10 1500 to 1600 B-7004 Collier & baker EXTERIOR/S install static caps 1hr/C
9-Mar-10 0730 to 1030 B-9121
Collier,Rosario &
Ryder EXTERIOR/S Changed out switch 3 hrs./C
3-Mar-10 1920 to 1955 B-4101Airfield Bland & Thomas AIRFIELD/US
Taxiway alpha breaker tripped,reset 45min/C
7-Mar-10 1410 to 1530 By B-4216 Rosario & Etter EXTERIOR/US
Conductor fell off pole/belongs to contractor 1.3hrs./C
16-Mar-10 0700 to 0800 B-7320 Collier & Ryder EXTERIOR/S installed static caps 1 hr./C
16-Mar-10 1730 to 1830 B-7339 Batz & Bland INTERIOR/US
Charlie's stove had fire/set off smoke det./by-passed,shopped 1 hr.
17-Mar-10 0700 to 0800 B-7106 Collier & Ryder EXTERIOR/S install static caps 1 hr./C
19-Mar-10 1700 to 1745 B-8130 Bland INTERIOR/US
Fire suppression leak,checked out eletrical/nothing found wrong elect. 45min/C
20-Mar-10 1930 to 2330 B-4201 Batz,Cat & Bland EXTERIOR/US
Replaced saddle & clamp on pole# B1-38 4hrs./C
23-Mar-10 0700 to 1130
B-
9110,9121,9112,9123,91
Collier,Jones,Ryder, Long,Hooter &
Thomas EXTERIOR/S
Replaced buckarms & crossarms
4 1/2 hrs./C
25-Mar-10 1745 to 1830 B-6240 rm 601 Catalan & Thomas INTERIOR/US
Light switch ballast bad
45min/sh opped
27-Mar-10 2100 to 2130 B6138 Rm 117 Ryder & Thomas INTERIOR/US
Tripped breaker,cause unknown 30 min/C
29-Mar-10 2300 to 2400 Ramp lights Ryder & Thomas EXTERIOR/US
Tower needed to reset panel/poles were on hand/reset to auto
30-Mar-10 0700 to 0900
B-
9203,9199,9243,9265,Tr affic Light Shop EXTERIOR/S
Change out cross arms & braces 2hrs./
10-Apr-10 1200 to 1230 B-9212/pinic grds. Dewitt INTERIOR/US Check voltage to area 30 min./C
14-Apr-10 0700 to 0800 B-5130 &5113 Collier & Watson EXTERIOR/S
Fuse blew open on pole 1hr./C
16-Apr-10 1900 to2000 B-8031 Jones & Delacot Alarms/US
Couldn't arm door
Paul will fix Mon. 1hr./C
19-Apr-10 0930 to 1030 B7004
Collier,Jones,Hooter
& Catalan EXTERIOR/US
Fuse blew open because contractor shorted out cable inside trans. 1hr./C
3-May-10 0830 to1700 pole C4-13 Shop EXTERIOR/US
Dirt boys hit primary overhead pole/busted at base of pole 7hrs./C
6-May-10 1800 to 2200 C1 circuit Cuevas,Dewitt,Eilers EXTERIOR/US
C1-circuit tripping on/off…refused blown fuse link/cause unknown 4hrs./C
10-May-10 0530 to 600 A2-circuit Jones & Rosario EXTERIOR/US
A2-circuit tripped off…Switch to A2 circuit 30min./C
10-May-10 2030 to 2245 Papi light 16 end out Rosario & Thomas AIRFIELD/US
Papi out due to contractor running over cable/Turned over to shop for repair
2hrs.15mi n.
15-May-10 0830 to 1000 B-8042 Catalan & Etter INTERIOR/US doors out of power but can be opened maually/Turned over to shop 2 1/2 hrs.
15-May-10 1130 to 1300 B-9220 Catalan & Etter EXTERIOR/US
Fuse blew feeding dip pole/re-fused & it blew again/Turned over to shop 1 1/2 hrs.
21-May-10 0000 to 0100 Ramp A9-A15 Catalan & Etter AIRFIELD/US
Turned Ramp lights to hand/Tower had no control/Turned over to Shop 1hr.
23-May-10 1030 to 1200 B-7000 Jones & Dewitt INTERIOR/US
Watre break caused main to trip because of FACP alarm/Reset
1 1/2 hrs./C
24-May-10 0000 to 0200 B-4225
Jones & Fetchic
(havc) INTERIOR/US
Lt.Col Fargus wanted apron lights repaired/repaired 3 of the 4/need ballast/Turned over to
Shop 2hrs.
24-May-10 2300 to 0000 ramp lights
25,20,19,18,17
Jones & Fetchic
(havc) AIRFIELD/US put all lights in hand operation/# 23 has bad contactor 1hr.
25-May-10 0000 to 0100 B-4217
Jones & Fetchic
(havc) INTERIOR/US lights going off & on/relamped 8ea.150w hps/requestor needs to buy 15ea.more lamps 1hr.
28-May-10 1500 to 1545 B-7312 Bland & Thomas Fire Alarms/US
Heat detector in trouble status/took out of the loop & turned over to shop 45min.
30-May-10 2155 to 2230 Flag pole Bland & Thomas INTERIOR/US
Breaker in control box tripped 35min/C
3-Jun-10 1630 to 1900 B-6136 Bland & thomas Fire Alarms/US
Resisdent started a fire on stove setting off suppression & smoke detector 2.5hrs
9-Jun-10
1630-1640 to 1730-
1830 B-8202
Dewitt,Thomas &
Alexander Fire Alarms/US
Alarm went off twice/to hot in attic/attic detector/shopped 45min.
9-Jun-10 1430 to 1530 B3 circuit
Dewitt,Thomas &
Collier & Rosario EXTERIOR/US
Downed power line/hospital backfeed from AEP's side 1hr./C
15-Jun-10 7:30 to 14:30 B8211
Watson,Rosario,Tho mas,Etter,dewitt,Cat alan,Jones & Eilers EXTERIOR/US
Replaced bad 300KVA pad mount transformer 9hrs./C
17-Jun-10 2200 to 2230 Ramp lights Rosario EXTERIOR/US
Ramp lights inop because contractor is changing out poles 30min./C
22-Jun-10 2245 to 2300 B-6112 Bland & Catalan Fire Alarms/US
1st.floor janitor closet smoke detector full of water/shopped, could not find source of water 15min
24-Jun-10 2320 to 0040 B-5224 Bland & Catalan INTERIOR/US
Main breaker tripped/reset breaker
& it held
1hr.20mi n
6-Jul-10 210-320 B-7000 Catalan & Eilers INTERIOR/US
Main panel# 2 tripped/did proper sequence & tripped breaker back on
1hr
30min/C
21-Jul-10 1730 to 1800 B-7233/rm 203 Jones INTERIOR/US
Lt freeman removed an air freashner from an outlet & shorted it out up against the metal plate 30min/C
24-Jul-10 0200-0600 B-5225 Dewitt & Etter EXTERIOR/US
Light hanging down from pole/tried to find lift,contractor had it/turned over to contractor 26-July-10 4hrs./C
26-Jul-10 1600 to 1630 B7233 Dewitt & Etter INTERIOR/US
Reset tripped breaker in room 203 30min./C
26-Jul-10 2200 to 2230 Ramp lights Dewitt & Etter INTERIOR/US
Ramp lights going off
& on/Contractor still working 30min/C
28-Jul-10 1630 to 1700 B-6138 Dewitt & Etter INTERIOR/US Reset main breaker 30min/C
28-Jul-10 1700 to 1730 B-5020 Dewitt & Etter INTERIOR/US just had to check & make sure water stayed out of panel 30min/C
28-Jul-10 1730 to 1800 B-8016 Dewitt & Etter INTERIOR/US Reset main panel 30min/C
28-Jul-10 1800 to 2000 B5005 Dewitt & Etter INTERIOR/US checked power for ups system,found it was an hvac problem 2hrs./C
30-Jul-10 1800 to 1830
Bldgs.5013,5017,5014,5
016,5102,5101 & 5105 Jones & Thomas EXTERIOR/US
Bird landed on primary line{ave D2 &
2nd.St} blew fuse open 30min/C
10-Aug-10 1730 to 1800 A2-circuit/FY 95 also
Jones.Dewitt &
Catalan EXTERIOR/US
Fuse blew on Pole#
A2-3/will go back & put solid blades up
30min/sh opped
17-Aug-10 0800 to 0900 MSA Collier & Etter EXTERIOR/US refused riser feeder feeding MSA 1hr./C
18-Aug-10 2045 to 2115 B-4225 Bland & Etter FIRE ALARM/US Alarm going off 30min/C
20-Aug-10 1700 to 1745 B-8150 Bland & Alvarez INTERIOR/US
Hvac plugged in
4ea.humitifiers tripped circuit 45min./C
30-Aug-10 2130 to 22:15 B-5105 Long INTERIOR/US
Breaker tripped/overloaded circuit/Reset 45min/C
30-Aug-10 22:50 to 23:15 Ramp lights 1-4 Long & Thomas EXTERIOR/US
Contractor turned off ramp lights 1-4 25 min/C
7-Sep-10 0900 to 1000 B-9120
Dewitt,Jones &
Alvarez EXTERIOR/US
Repair primary jumper on pole feeding MSA 1hr./C
7-Sep-10 22:30 to Shopped B4101 Bland & Long AIRFIELD/US
No power from the transfer panel to regulator
1hrs./Sho pped
12-Sep-10 1200 to 1400 B-7339 Ward & Eilers FIRE ALARM/US
Reset
FACP/suppression problem
2hrs./sho pped
18-Sep-10 1500 to 1830 B3500
Rosario,rodriguez &
Etter EXTERIOR/US
Marion drop zone out of power/AEP's side fuse blown/
2hrs.30mi n./C
20-Sep-10 2100 to 2130 Taxiway bravo Rodriguez AIRFIELD/US
Tower could'nt control Bravo taxiway/placed regulator in local
30min/sh opped
23-Sep-10 1700 to 2030 pole#B2-1
Rod,rosario,etter,jon es & cuevas EXTERIOR/US jumper,cutout,la burn't up
3hrs30mi n/shoppe d
23-Sep-10 2030/shopped B-5111
Rod,rosario,etter,jon es & cuevas INTERIOR/US
Dry pack trans.burn't up
1hr./shop ped
25-Sep-10 1200 to 800 Housing Ward & Dewitt INTERIOR/US
Suddenlink battery pack service burn,t up/Replaced service 8hrs./C
1-Oct-10 2100 to 2200 B-5110 Dewitt & Thomas INTERIOR/US
Middle sections lights going off/on turned off & reset 1hr./C
16-Oct-10 1200 to 1300 B-11981(golf pump) Dewitt & Thomas EXTERIOR/US two fuse doors opened on laterial feeding 3 phase line 1hr./C
19-Oct-10 5:30 to 0800 B-5204 Dewitt & Thomas EXTERIOR/US
Cable rubbed up on insulation,causing short to grd. 2.5hrs./C
19-Oct-10 1730 to 1735
Wind sock charlie taxiway Dewitt & Thomas AIRFIELD/US lights on top of wind sock inop 5min/S
25-Oct-10 1800/S Football Field Jones & Alvarez EXTERIOR/US
Step down trans.feeding contacts bad 1hr/S
31-Oct-10 2330 to 2400 Sub Alpha Jones EXTERIOR/US
Both A1 & A2 tripped/Chaged out cross arm,phases slapped together 30 mi/S
28-Nov-10 0930 to 1700 B2-circuit
Cuevas,Thomas &
Eilers EXTERIOR/US
PTS B2-L3-4 burned up/Jumpered it Fuses on pole C2-L1-7 blown fuses 7 hrs./S
29-Nov-10 0700 to 0800 B-11981
Collier,Miller,Rosario
& Eilers EXTERIOR/US
Blown fuses on 3 phase line feeding B-
11981 1hr./C
11-Dec-10 1230 to 1330 B-6112 Bland & Dewitt FIRE ALARM/US
NAOC went offf/comm needs to look at problem/CFP Group bldg. 1hr./C
13-Dec-10 720 to 0800 B5110 Bland & Dewitt INTERIOR/US
Breaker tripped in office 40min./C
FY 2011
3-Jan-11 AIRFIELD B-4101Airfield Hooter & Dewitt AIRFIELD/US
Sequence flashers would not shut off
1hr.30mi n./S
7-Jan-11 1800 to 1830 B-7220 Catalan & Alvarez INTERIOR/US
Breaker tripped overloaded circuit 30min./C
9-Jan-11 2130 to 2230 16 sequence flashers Catalan & Alvarez AIRFIELD/US
Went out this morning & they were operational 1hr./S
10-Jan-11 1900 to 2130 B-4314 Catalan & Alvarez INTERIOR/US
Foun switch was not fully closed to HVAC equip 2 .5 hrs./C
Cuevas
10-Jan-11 2000 to 2100 34 sequence fashers Rosario & Dewitt AIRFIELD/US
Placed on manual operation 1hr./S
14-Jan-11 1830 to 1900 B-7219 Dewitt & Thomas INTERIOR/US
Breaker was tripped/cause unknown/reset 30min./C
17-Jan-11 0900 to 0930 B-8031 Dewitt & Thomas INTERIOR/US
Breaker was tripped/cause unknown/reset breaker in hallway 30min./S
19-Jan-11 930 to 1200 B2-circuit
Collier,Cuevas,Thom as,Miller,Jones,Etter, Dewitt, & Bland EXTERIOR/US
2 primary phases slapped together betweem 4th & 5th St.
off Ave D/isolated area & fixed problem 3hrs/C
19-Jan-11 1930 to 2030 Airfield/strobes 16 Dewitt & Thomas AIRFIELD/US
16 strobe lights wouldn't turn on for tower/went to control cabinet & turned on. 1hr/S
22-Jan-11 0700 to 1100 B-7316
Collier,Miller,Jones
& Rosario EXTERIOR/S
Changed out transformer (pad mount) 4hrs/C
1-Feb-11 1300 to 1430 B-7316
Collier,Miller,Jones
& Etter EXTERIOR/S
Changed out elbow in transformer (pad mount) 1.5hrs./C
2-Feb-11 730 to shopped B-9270 Jones INTERIOR/US heat coils burned up in heater 45min/S
2-Feb-11 0900 to 1230 Bravo sub Jones & Etter EXTERIOR/US
Peterson wanted
Generators run up
B/C of power demands 3.5hrs.
3-Feb-11 0530 to 0630 Bravo sub Jones & Etter EXTERIOR/US
Generators shut off &
BT opened up feeding commercial/all of
Bravo Sub went down 1hr/c
3-Feb-11 1800 to 1900 Bravo sub Jones & Etter EXTERIOR/US
Closed in BT breaker/opened UT breaker/Opened ABS between AEP & Bravo sub 1hr./c
5-Feb-11 1200 to 1300 B-9326 Jones FIRE ALARM/US alarm panel wet/took fuses out & disconnected battery 1hr/S
7-Feb-11 1200 to 1350 B-5005 Collier & Miller EXTERIOR/S
Tightened load brake elbow pin & primary bushings 1.50/C
7-Feb-11 1730 to 1745 Base Traffic Light Catalan Traffic light/US
2ea.red led lights burned out/Put in flash until the morning 45min/S
7-Feb-11 510 to 545 B-5225 Long FIRE ALARM/US
Suppression busted/needed to reset facp 35min/S
10-Feb-11 2330 to 030 34 Approach Catalan AIRFIELD/US
Tower could not turn off sequence flashers 1hr/S
13-Feb-11 0700 to 1130 B-7409
Miller,Collier,,Jones, Cuevas,Bland EXTERIOR/S
Pulled cable/terminated elbows & replaced transformer (PD) 4.5 hrs./C
15-Feb-11 9:20 to 1200 Papi's Rodriguez/Dewitt AIRFIELD/US
Was told all Papi's
/But there was only one 2.5 hrs./C
17-Feb-11 1730 to 1830 Pennsylvania St. Rodriguez/Dewitt EXTERIOR/S
Streetlight hit by car/isolated & picked up light 1hr./S
17-Feb-11 11:40 to 1240 B-4300 Rodriguez INTERIOR/US
Isolated elevator from disconnect/motor is bad they need to call a contractor to repair 1hr./C
19-Feb-11 0945 to 1200 Power outage
Miller,Jones,Etter,Co llier,Cuevas,Dewitt<
Thomas EXTERIOR/US
Isolated circuit to take slack out of overhead lines slapping together 19.5hrs/C
25-Feb-11 0700 to 1100 B1-l1-1 & B1-13
Miller,Jones,Etter,Co llier,Rosario EXTERIOR/S
Replaced cross arms on poles 4hrs/C
25-Feb-11 1700 to 1730 B-9121 Eilers INTERIOR/US
Checked voltage to air compressor/Compres sor bad. 30min/C
25-Feb-11 1735 to 1750 B-11751 Eilers INTERIOR/US Changed out lamps 15min/C
25-Feb-11 2300 to 2345 B-7316 Bland/Eilers Security Alarms/US Reset Security Alarm 45min/S
7-Mar-11 2000 to 2030 Airfield/strobes N Jones & Alvarez AIRFIELD/US
(N) Strobes couldn't turn off/Reset power in vault…caused receiver to reset & turn off strobes 30min/S
7-Mar-11 2030 to 2100 B-4216 Jones EXTERIOR/S
Timer bad that controls lights/Will go back tommorrow & put new one in 30min/S
8-Mar-11 10:45 to 11:15 B-9153 Jones/Alvarez INTERIOR/US
Ballast bad
/Disconnected power to ballast/shopped 30min/S
13-Mar-11 2200 to 2300 B-6126 Dewitt/Eilers INTERIOR/US
Outlet sparking/removed wires off outlet/shopped 1hr/S
16-Mar-11 2200 to 2300 Airfield/N strobes Dewitt/Eilers AIRFIELD/US
North strobes would not turn off/Shopped 1Hr/S
17-Mar-11 1600 to 1700 B-9265 Dewitt & Eilers INTERIOR/US
AC was inop,breaker kept tripping/replaced double pole breaker 1hr./C
25-Mar-11 1420-1450 B-9265 Catalan & Watson INTERIOR/US
Breaker trips on
HVAC side 30min/C
27-Mar-11 1200 to 1300 B-4217 Catalan & Alvarez Security Alarms/US
Needed to reset sec alarm/door not able to be armed 1 hr./S
3-Apr-11 1930 to 2030 B-6112 Dewitt Security Alarms/US
Klaxton would not shut off/Tested on plane 1hr./S
8-Apr-11 145 to 230 Airfield/Ramp Lights Rodriguez EXTERIOR/US
Ramp lights A5-A8 were inop/Did manual reset/Operator error 45min/S
10-Apr-11 1300 to 1615 B-5110 Rodriguez & Cedeno INTERIOR/US main tripped/door # 6 which has a 332 on it tripped breaker 3hrs/C
12-Apr-11 330 to 430 B-5110 Jones & Rodriguez INTERIOR/US main tripped/grd.fault/2500 amp main 1hr./S
17-Apr-11 Bland & EXTERIOR/S
Squirrel got on dip pole feeding b-8202 and blew 100amp fuse 1hr./C
1-May-11 0930 to 1100 B-9001 Dewitt & Baker EXTERIOR/US
Pole feeding B-9001 blew fuse 1.5/C
17-May-11 1300 to 1500 B8202 EXTERIOR/US
Squirrel got on dip pole feeding b-8202 and blew 100amp fuse 2hrs.
26-May-11 1645 to 1745 B-4201 Cedeno Security Alarms/US
Had to leave in alarm over week-in 1hr/S
30-May-11 0100/0130 B-5005 Cedeno INTERIOR/US
Open mech.rm.for customer to reset aircraft equip. 30min/C
31-May-11 2250/next day B-9109 Cedeno & Thomas EXTERIOR/US
Customer said we could wait until next day to fix problem 1hr.S
2-Jun-11 2200 to 2300 Ramp lights Dewitt & McMullen EXTERIOR/US
Operator in control tower error 1hr./C
4-Jun-11 0930 to 1030 B-4216 Dewitt & McMullen INTERIOR/US
Customer overloaded circuit/reset breaker himself 1hr./C
11-Jun-11 1800-1900 B-7402 Ryder & Thomas EXTERIOR/US Exterior lights inop 1 hr/S
11-Jun-11 1900-2000 B-7401 Ryder & Thomas Keys/US
They lost teir keys & thought our would work/no! 1hr/C
13-Jun-11 2400-100 B-3500 Ryder & Thomas AIRFIELD/US
Taxiway lights on
Taxi H & J/Not open because of contract work 1hr./S
16-Jun-11 1600-1700 B-4201 Ryder & Alvarez Fire Alarms/US
Attic detector in trouble 1hr./S
18-Jun-11 1600-1630 B-8030 Eilers Fire Alarms/US
Attic detector in trouble 30Min/S
18-Jun-11 1630-1745 Alpha Sub Eilers,Jones & AL EXTERIOR/US
Lightning arrestor middle phase blew 1hr.15min
21-Jun-11 030-430 Sub Bravo
Jones,Eilers,Baker &
Ward EXTERIOR/US Lost power AEP side 4hrs../C
21-Jun-11 0700-0930 B-5208
Jones,Dewitt,Thoma s EXTERIOR/US
Explosion proof breaker tripped 2.5hrs./C
21-Jun-11 0930-1130 B-4216 ,4218 & 4217
Miller,Watson,Etter,J ones,Dewitt,Bland EXTERIOR/US
Jumper wire blew off lateral line 2hrs./C
21-Jun-11 1130-1330 B-7002,7007 & 7010
Miller,Watson,Etter,D ewitt,Eilers EXTERIOR/US
Jumper wire blew off dip pole 2hrs./C
21-Jun-11 1330-1530
B-4112,4111,4225,4202
& 4201
Miller,Watson,Etter,D ewitt,Eilers EXTERIOR/US
Jumper wire blew off lateral line 2hrs./C
22-Jun-11 0730-1000 B-9001,4101 & 9024
Miller,Bland,Ryder,Ei lers EXTERIOR/S
Changed out cross arm 2.5hrs./C
23-Jun-11 0800-1030 B-8080
Miller,Bland,Alvarez
& Baker EXTERIOR/US
Changed out transformer(150kva) 3.5hrs./C
24-Jun-11 0730-1130 Muti-bldgs.
Miller,Jones,Etter,De witt,Baker,Thomas EXTERIOR/S
Changed out Pole
Top switch 5hrs./C
25-Jun-11 1000-1200 B-8202
Jones,Cedeno,Ryder
,Dewitt,Thomas EXTERIOR/US
Changed out Pole fuse & transformer fuse 2hrs./C
28-Jun-11 0730-1030 B-7008
Collier,Baker,Dewitt, Jones & Miller EXTERIOR/S
Changed out transformer (750kva) 3hrs./C
28-Jun-11 0900-1130 B11751
Collier,Baker,Dewitt, Jones & Miller EXTERIOR/US
Changed out transformer (500kva) 2.5hrs./C
28-Jun-11 1100-1500 B8015
Collier,Baker,Dewitt, Jones & Miller EXTERIOR/US
Changed out transformer (300kva) 4hrs./C
15-Jul-11 1600-1630 B-6030C Eilers INTERIOR/US Reset breaker 30min/C
8-Aug-11 2200 to 2210 B7339 Ryder Security Alarms/US Roof alarm activated 10min/S
9-Aug-11 1500 to 1530 B7420 Ryder & Delacot Security Alarms/US
Maid pulled pull station alarm by accident 30min/C
12-Aug-11 1630 to 1730 B-5225 Cedeno INTERIOR/US
Reset breaker in server vault 1hr/C
15-Aug-11 1730 to 2000
POLE# B3-26A/SCADA
SWITCH
Cedeno,Ryder &
Thomas EXTERIOR/US
Isolated switch from circuit/contacted
Denslow with info 2.5hrs/S
22-Aug-11 0710 to 0745 B-5138 Collier & Miller EXTERIOR/US
Refused 10 amp fuse door blown at 3 pot bank 35min/C
H1992
H1970
H1982
H1983
H1994
H2014
H3193
H1849
H3187
G6921
H3438
H3486
G8282
H3731
G8282
H3785
H3789
H0643
H3879
H3893
H0625 &
H0646
H4205
H4272
H4376
H4385
H4685
H4766
H4899
H4899
H5036
H5033
H5168
H5189
H5190
H5202
H5203
H5288
H5293
H5419
H5617
H5605
H5744
H5969
H6038
H6214
H6715
H6776
H6808
H6810
H6847
H6848
H6850
H6851
H6972
H7236
H7354
H7391
H7442
H7571
H7572
H7669
H7750
H7804
H7964
H7982
H8069
H8078
H8139
H8220
J0229
J0286
J0313
J0417
J0519
J1074
J1094
J1451
J1425
J1751
J1894
J1913
J1869
J1913
J2128
J2131
J2189
J2230
J1932
H6075
J2550
J2562
J2562
J2562
J2903
H6076
J2695
J2705
J2932
H6545
J3159
J3123
J3125
J2189
H6459/60
J3235
J3236
J3254
J3468/J34
J3585
J3682
J3738
J4029
J4088
J4267
J4262
J4848
J4393
J4799
J5598
J5566
J5626
J5699
J5702
J5902-01
J5903
J5919
J6002
J6069
S/J6072
J6151
J6117
J6135
J6141
J6144
H6463
J6251
H7294
J6360
J5466
J6405
J6210
J6786
J7250
J7305
J7406
J7431
J7564
File details come from the government source that posted it. Updated .