The file's text, extracted by GovTribe without its formatting.
Air Force Utilities Privatization - REQUEST for proposal Attachment J1
Air Force Utilities Privatization - REQUEST for proposal (RFP) Attachment JA1
Attachment JA1
Mountain Home AFB Electric Distribution System Table of Contents
1Mountain Home AFB Electric Distribution System
JA1-
1Table of Contents
JA1-
1LIST OF TABLES
JA1-
2JA1 Mountain Home AFB Electric Distribution System
JA1-
3JA1.2 Electric Distribution System Description
JA1-
3JA1.2.1 Electric Distribution System Fixed Equipment Inventory
JA1-
17JA1.2.2 Electric Distribution System Non-Fixed Equipment and Specialized Tools
JA1-
18JA1.2.3 Electric Distribution System Manuals, Drawings, and Records
JA1-
18JA1.3 Specific Service Requirements
JA1-
19JA1.4 Current Service Arrangement
JA1-
19JA1.5 Metering
JA1-
19JA1.5.1 Existing Meters
JA1-
21JA1.5.2 Required New Meters
JA1-
21JA1.6 Monthly Submittals
JA1-
21JA1.7 Energy-Savings Projects
JA1-
22JA1.8 Service Area
JA1-
22JA1.9 Off-Installation Sites
JA1-
22JA1.10 Specific Transition Requirements
JA1-
22JA1.11 Initial System Deficiency Corrections (ISDC)
JA1-
22JA1.12 Right of Access to the Utility System
JA1-
22JA1.12.1 Map of the Utility System
JA1-
23JA1.12.2 Lateral Extent of the Right-of-Access, and Points of Demarcation
JA1-
27JA1.12.3 Environmental Baseline Survey
JA1-
LIST OF TABLES
table 1 - 4Fixed Inventory
JA1-
table 2 - Spare Parts
JA1-17
table 3 - Specialized Vehicles and Tools
JA1-18
table 4 - Manuals, Drawings, and Records
JA1-18
table 5 - Existing Meters
JA1-19
table 6 - Required New Meters
JA1-21
table 7 - Energy-Savings Projects
JA1-21
table 8 - Service Connections and Disconnections
JA1-22
table 9 - Initial System Deficiency Corrections
JA1-22
table 10 - Standard Points of Demarcation
JA1-23
table 11 - Unique Points of Demarcation
JA1-27
JA1 Mountain Home AFB Electric Distribution System JA1.1 Mountain Home AFB Overview
Mountain Home AFB (MHAFB) is an active military installation located in Elmore County, Idaho. The base is approximately 10 miles west of the city of Mountain Home, seven miles northeast of I-84 Exit 95, on Idaho Highway 20.
MHAFB is the home of the 366th Wing. The mission of the 366th Fighter Wing (FW) is to prepare Airmen and their families, professionally and personally, for expeditionary operations and foster an environment that promotes integration of all facets of wing operations. The mission is to execute directed missions designed to identify and destroy enemy forces, supplies, equipment, communication systems, and installations within the design limits of the weapons systems capabilities. The 366th FW serves as the host wing overseeing day to day operations of the base such as personnel, finance, civil engineering and supply. Other base tenants include:
· Air Combat Command Contract Performance Squadron (ACCCPS)
· Air Force Audit Agency Area Office (AFAA)
· Air Force Office of Special Investigations (AFOSI)
· American Red Cross (ARC)
· Area Defense Council (ADC)
· Army and Air Force Exchange Services (AAFES)
· Defense Commissary Agency (DeCA)
· Defense Investigative Service (DIS)
· Defense Printing Service (DPS)
· Defense Reutilization and Marketing Office (DRMO)
· Idaho Army National Guard
· US Army Corps of Engineers (USACE)
· 372d Training Detachment MHAFB and its geographically separated units (GSUs) occupy 119,431 acres consisting of Air Force owned lands, private property easements, public lands withdrawn from use, public domain permits, and rights-of-way. The base area encompasses 6,729 acres. Utilities at the GSUs are not being considered for privatization.
The Base General Plan states that the total installation population is 10,392. This includes active duty military, family members on and off base, DOD civilians and private business personnel. MHAFB contributes significantly to the local economy through civilian employment, contracting, and purchases from local businesses.
JA1.2 Electric Distribution System Description
JA1.2.1 Electric Distribution System Fixed Equipment Inventory
The Mountain Home AFB electric distribution system consists of all appurtenances physically connected to the distribution system from the point of demarcation defined by the Right of Access. The distribution system consists of the items listed in Table 1 “Fixed Inventory Electric Distribution System” in Section JA1.2.1.2 Inventory. The actual inventory of items sold will be in the bill of sale at the time the system is transferred. The following description and inventory is included to provide the Offeror with a general understanding of the size and configuration of the distribution system. The Government makes no representation that the inventory is accurate. The Offeror shall base its proposal on the Table 1 inventory below. However, the Offeror should use the following reference points for developing other aspects of its proposal: site inspections, information in the technical library, and other pertinent information.
Specifically excluded from the electric distribution system privatization are:
· airfield lighting
· parking lot lights serviced by secondary feed from a building
· emergency generators that exist for the purpose of emergency back-up for AF facilities
· Electric distribution facilities at GSUs including: Saylor Creek Gunnery Range, the Small Arms Range Annex, the C.J. Strike Dam Marina, Rattlesnake Radar Station, Middle Marker, Grasmere Electronic Combat Site, and Seneca Ground Wave Emergency Network Station.
JA1.2.1.1 Description
The base electrical distribution system is powered by two services from Idaho Power. One service enters the site at 138 kV and the second enters at 69 kV. The 138 kV line enters the base from the northwest on Liberator road and the 69 kV line enters the site from the northeast on Perimeter Road, east of the main gate. The two services are terminated at the main base electrical substation located on Liberator road. The substation consists of two separate areas, the utility-owned substation and the base-owned substation. Both areas are fenced separately and located adjacent to each other. The connection between the two substations is by overhead wiring. The utility owns the overhead lines to the point where it terminates on the base owned bus bars inside the base-owned area. The base takes ownership of the system at the termination point on the busbar.
There are eight feeders leaving the main substation that powers the base.
Each feeder leaving the substation has primary CT metering, an automatic recloser and bypass switch. Each circuit has a meter to measure the power consumed on each circuit. Seven meters were rebuilt in 2007 and a new meter was provided with the pad-mounted equipment in 2008.
Idaho Power owns a distribution line that runs from the main substation down Phantom Road and Eagle Drive to a dead end point at the end of Eagle Drive. There is no equipment powered from this line, but it is energized. This line is going to be removed in the future but has not yet been funded.
There are two housing areas that will be demolished in the future. They are the Elk Heights (formerly “Desert Vista”) and Falcon Estates (formerly “Old Gunfighter”) subdivisions. Both of these areas have overhead primary and secondary distribution. The inventory for those subdivisions will remain and is included in the Table 1 inventory.
The Dunes subdivision is currently under demolition. The existing street lighting and power distribution system will remain and is included in the Table 1 inventory.
The base roadway lighting system is powered from the primary distribution system through step-down transformers and distribution panels located around the base. The transformers step the voltage down to 120/240v, single phase power and the power is distributed on the site from outdoor panel boards.
JA1.2.1.2 Inventory
Table 1 provides a general list of the major electric distribution system fixed assets for the Mountain Home AFB electric distribution system included in the sale. The design life column indicated in Table 1 is used by the Government in the development of the Government Should Cost Estimate. The design life is not mandated in the Offeror’s proposal. However, the proposal must clearly explain the use of any system component design life that significantly differs from the published Government design life.
Table 1
Fixed Inventory
Electric Distribution System
| Item |
| Size |
| Quantity |
| Unit |
| Approximate Year of Construction |
| Design Life |
(Years)
| UG Cable, Copper, 15 kV |
| #2 AWG |
| 6,200 |
| SCLF |
| 2008 |
| 45 |
| UG Cable, Copper, 15 kV |
| #2 AWG |
| 65,600 |
| SCLF |
| 2004 |
| 45 |
| UG Cable, Copper, 15 kV |
| #2 AWG |
| 24,026 |
| SCLF |
| 2002 |
| 45 |
| UG Cable, Copper, 15 kV |
| #2 AWG |
| 9,440 |
| SCLF |
| 2001 |
| 45 |
| UG Cable, Copper, 15 kV |
| #2 AWG |
| 1,940 |
| SCLF |
| 1997 |
| 45 |
| UG Cable, Copper, 15 kV |
| #4/0 AWG |
| 27,652 |
| SCLF |
| 2002 |
| 45 |
| UG Cable, Copper, 15 kV |
| 500 MCM |
| 32,600 |
| SCLF |
| 2008 |
| 45 |
| UG Cable, Copper, 15 kV |
| 500 MCM |
| 10,300 |
| SCLF |
| 2006 |
| 45 |
| UG Cable, Copper, 15 kV |
| 500 MCM |
| 17,600 |
| SCLF |
| 2005 |
| 45 |
| UG Cable, Copper, 15 kV |
| 500 MCM |
| 16,000 |
| SCLF |
| 2004 |
| 45 |
Elk Heights (Former Desert Vista)
| OH Residential Cable |
| 3/0 |
| 9,950 |
| SCLF |
| 1977 |
| 50 |
Falcon Estates (Former Old Gunfighter)
| OH Residential Cable |
| 3/0 |
| 5,350 |
| SCLF |
| 1960 |
| 50 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 2,640 |
| SCLF |
| 2008 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 1,920 |
| SCLF |
| 2006 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 1,360 |
| SCLF |
| 2005 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 8,080 |
| SCLF |
| 2004 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 5,280 |
| SCLF |
| 2002 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 3,200 |
| SCLF |
| 2001 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 1,200 |
| SCLF |
| 2000 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 2,960 |
| SCLF |
| 1997 |
| 35 |
| Ground Wire, Bare Copper, 600 V |
| #4/0 AWG |
| 1,440 |
| SCLF |
| 1960 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 132 |
| Ea |
| 2008 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 96 |
| Ea |
| 2006 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 68 |
| Ea |
| 2005 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 404 |
| Ea |
| 2004 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 264 |
| Ea |
| 2002 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 160 |
| Ea |
| 2001 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 60 |
| Ea |
| 2000 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 120 |
| Ea |
| 1997 |
| 35 |
| Ground Rod |
| ¾”x10’ |
| 100 |
| Ea |
| 1960 |
| 35 |
| Hand hole, Concrete |
| 4’-6" x 3’-2" x 2’-0" |
| 10 |
| Ea |
| 2006 |
| 60 |
| Hand hole, Concrete |
| 4’-6" x 3’-2" x 2’-0" |
| 20 |
| Ea |
| 2005 |
| 60 |
| Hand hole, Concrete |
| 4’-6" x 3’-2" x 2’-0" |
| 8 |
| Ea |
| 2004 |
| 60 |
| Hand hole, Concrete |
| 4’-6" x 3’-2" x 2’-0" |
| 59 |
| Ea |
| 2002 |
| 60 |
| Hand hole, Concrete |
| 4’-6" x 3’-2" x 2’-0" |
| 19 |
| Ea |
| 2000 |
| 60 |
| Manhole, Concrete |
| 6’ x 6’ x 10’ |
| 6 |
| Ea |
| 2005 |
| 60 |
| Manhole, Concrete |
| 6’ x 6’ x 10’ |
| 11 |
| Ea |
| 2004 |
| 60 |
| Manhole, Concrete |
| 6’ x 6’ x 10’ |
| 1 |
| Ea |
| 1960 |
| 60 |
| 2” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 3,500 |
| LF |
| 2007 |
| 100 |
| 2” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 1,000 |
| LF |
| 2006 |
| 100 |
| 2” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 2,150 |
| LF |
| 2005 |
| 100 |
| 2” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 2,650 |
| LF |
| 2004 |
| 100 |
| 2” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 2,414 |
| LF |
| 2002 |
| 100 |
| 2” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 3,000 |
| LF |
| 2001 |
| 100 |
| 2” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 3,500 |
| LF |
| 1997 |
| 100 |
| 4” Duct Bank, PVC, Concrete encased |
| 2 x 4 |
| 5,304 |
| LF |
| 2002 |
| 100 |
| 5” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 3,100 |
| LF |
| 2008 |
| 100 |
| 5” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 2,560 |
| LF |
| 2006 |
| 100 |
| 5” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 11,375 |
| LF |
| 2004 |
| 100 |
| 5” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 5,002 |
| LF |
| 2002 |
| 100 |
| 6” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 6,600 |
| LF |
| 2008 |
| 100 |
| 6” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 4,400 |
| LF |
| 2005 |
| 100 |
| 6” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 9,000 |
| LF |
| 2004 |
| 100 |
| 6” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 1,175 |
| LF |
| 2002 |
| 100 |
| 6” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 2,360 |
| LF |
| 2001 |
| 100 |
| 6” Duct Bank, PVC, Concrete encased |
| 1 x 2 |
| 485 |
| LF |
| 1997 |
| 100 |
| 4” Conduit, RGS, Direct bury |
| 1 x 1 |
| 427 |
| LF |
| 2002 |
| 50 |
| 5” Conduit, RGS, Direct bury |
| 1 x 1 |
| 742 |
| LF |
| 2002 |
| 50 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 3 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 1 |
| Ea |
| 2006 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 1 |
| Ea |
| 2004 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 6 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 2 |
| Ea |
| 2000 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 7 |
| Ea |
| 1960 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 1 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 3 |
| Ea |
| 2006 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 59 |
| Ea |
| 2004 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 2 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 17 |
| Ea |
| 2001 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 2 |
| Ea |
| 2000 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 4 |
| Ea |
| 1960 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 1 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 1 |
| Ea |
| 2006 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 1 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, Single Ph, 15 kV |
| 100 kVA |
| 2 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 45 kVA |
| 1 |
| Ea |
| 2004 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 45 kVA |
| 3 |
| Ea |
| 2000 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 75 kVA |
| 7 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 150 kVA |
| 2 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 150 kVA |
| 1 |
| Ea |
| 2005 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 150 kVA |
| 6 |
| Ea |
| 2004 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 150 kVA |
| 4 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 150 kVA |
| 7 |
| Ea |
| 1960 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 225 kVA |
| 1 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 225 kVA |
| 2 |
| Ea |
| 2006 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 225 kVA |
| 3 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 225 kVA |
| 4 |
| Ea |
| 1960 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 300 kVA |
| 3 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 300 kVA |
| 1 |
| Ea |
| 2006 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 300 kVA |
| 1 |
| Ea |
| 2005 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 300 kVA |
| 4 |
| Ea |
| 2004 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 300 kVA |
| 5 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 500 kVA |
| 7 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 500 kVA |
| 4 |
| Ea |
| 1960 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 750 kVA |
| 1 |
| Ea |
| 2006 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 750 kVA |
| 1 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 750 kVA |
| 2 |
| Ea |
| 1960 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 1000 kVA |
| 1 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 1000 kVA |
| 1 |
| Ea |
| 2005 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 1000 kVA |
| 1 |
| Ea |
| 2004 |
| 35 |
| Pad-mount Transformer, 3 Ph, 15 kV |
| 1000 kVA |
| 1 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Sectionalizing Switch, 4-way |
| 15 kV |
| 7 |
| Ea |
| 2008 |
| 35 |
| Pad-mount Sectionalizing Switch, 4-way |
| 15 kV |
| 2 |
| Ea |
| 2006 |
| 35 |
| Pad-mount Sectionalizing Switch, 4-way |
| 15 kV |
| 3 |
| Ea |
| 2005 |
| 35 |
| Pad-mount Sectionalizing Switch, 4-way |
| 15 kV |
| 25 |
| Ea |
| 2004 |
| 35 |
| Pad-mount Sectionalizing Switch, 4-way |
| 15 kV |
| 4 |
| Ea |
| 2002 |
| 35 |
| Pad-mount Sectionalizing Switch, 4-way |
| 15 kV |
| 2 |
| Ea |
| 2001 |
| 35 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 33 |
| Ea |
| 2008 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 24 |
| Ea |
| 2006 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 17 |
| Ea |
| 2005 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 109 |
| Ea |
| 2004 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 66 |
| Ea |
| 2002 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 40 |
| Ea |
| 2001 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 15 |
| Ea |
| 2000 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 30 |
| Ea |
| 1997 |
| 60 |
| Concrete pad, 4’ x 4’ x 6” |
| 16 SF |
| 31 |
| Ea |
| 1960 |
| 60 |
| OH Wire, Copper, 15 kV |
| #8 AWG |
| 2,900 |
| SCLF |
| 1960 |
| 50 |
| OH Wire, Copper, 15 kV |
| #2 AWG |
| 25,000 |
| SCLF |
| 1960 |
| 50 |
| OH Wire, Aluminum, 15 kV |
| #4 ACSR |
| 30,325 |
| SCLF |
| 2004 |
| 50 |
| OH Wire, Aluminum, 15 kV |
| #4 ACSR |
| 53,000 |
| SCLF |
| 1960 |
| 50 |
| OH Wire, Aluminum, 15 kV |
| #2 ACSR |
| 34,000 |
| SCLF |
| 2000 |
| 50 |
| OH Wire, Aluminum, 15 kV |
| #1/0 ACSR |
| 16,800 |
| SCLF |
| 1960 |
| 50 |
| Power Pole, Wood, with 6’ arm |
| 40’ |
| 189 |
| Ea |
| 2004 |
| 50 |
| Power Pole, Wood, with 6’ arm |
| 40’ |
| 100 |
| Ea |
| 2000 |
| 50 |
| Power Pole, Wood, with 6’ arm |
| 40’ |
| 8 |
| Ea |
| 1980 |
| 50 |
| Power Pole, Wood, with 6’ arm |
| 40’ |
| 551 |
| Ea |
| 1960 |
| 50 |
| Power Pole, Wood, with 6’ arm |
| 60’ |
| 8 |
| Ea |
| 1980 |
| 50 |
| Power Pole, Wood, with 6’ arm |
| 80’ |
| 8 |
| Ea |
| 1980 |
| 50 |
| Power Pole, Wood, with 6’ arm |
| 40’ |
| 50 |
| Ea |
| 1977 |
| 50 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 3 kVA |
| 1 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 3 kVA |
| 1 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 5 kVA |
| 8 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 5 kVA |
| 4 |
| Ea |
| 2000 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 5 kVA |
| 118 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 10 kVA |
| 2 |
| Ea |
| 2006 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 10 kVA |
| 25 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 10 kVA |
| 36 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 15 kVA |
| 3 |
| Ea |
| 2006 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 15 kVA |
| 12 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 15 kVA |
| 6 |
| Ea |
| 1980 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 15 kVA |
| 43 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 6 |
| Ea |
| 2006 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 63 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 4 |
| Ea |
| 2000 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 4 |
| Ea |
| 1980 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 25 kVA |
| 32 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 37.5 kVA |
| 5 |
| Ea |
| 2006 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 37.5 kVA |
| 10 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 37.5 kVA |
| 4 |
| Ea |
| 2000 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 37.5 kVA |
| 17 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 3 |
| Ea |
| 2006 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 21 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 50 kVA |
| 9 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 2 |
| Ea |
| 2006 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 5 |
| Ea |
| 2004 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 3 |
| Ea |
| 2000 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 2 |
| Ea |
| 1980 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 75 kVA |
| 15 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 100 kVA |
| 6 |
| Ea |
| 2000 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 100 kVA |
| 3 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 167 kVA |
| 12 |
| Ea |
| 1960 |
| 35 |
| Pole-mount Transformer, Single Ph, 15 kV |
| 5 kVA |
| 50 |
| Ea |
| 1977 |
| 35 |
| Fused Cutout |
| 15 kV |
| 92 |
| Ea |
| 2004 |
| 30 |
| Fused Cutout |
| 15 kV |
| 21 |
| Ea |
| 2000 |
| 30 |
| Fused Cutout |
| 15 kV |
| 12 |
| Ea |
| 1980 |
| 30 |
| Fused Cutout |
| 15 kV |
| 181 |
| Ea |
| 1960 |
| 30 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 21,000 |
| SCLF |
| 2007 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 6,000 |
| SCLF |
| 2006 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 13,000 |
| SCLF |
| 2005 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 16,000 |
| SCLF |
| 2004 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 13,644 |
| SCLF |
| 2002 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 18,000 |
| SCLF |
| 2001 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 18,000 |
| SCLF |
| 2000 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 18,000 |
| SCLF |
| 1997 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 44,750 |
| SCLF |
| 1990 |
| 50 |
| Street Lighting Wire, Copper, 600 V |
| #6 AWG |
| 15,000 |
| SCLF |
| 1960 |
| 50 |
| Flood Light, Metal Halide on power pole |
| 1000 W |
| 101 |
| Ea |
| 1980 |
| 20 |
| Flood Light, HPS on power pole |
| 250 W |
| 157 |
| Ea |
| 1960 |
| 20 |
| Street Light, Metal Halide |
| 100 W |
| 90 |
| Ea |
| 2007 |
| 20 |
| Street Light, Metal Halide |
| 100 W |
| 26 |
| Ea |
| 2006 |
| 20 |
| Street Light, Metal Halide |
| 100 W |
| 59 |
| Ea |
| 2005 |
| 20 |
| Street Light, Metal Halide |
| 100 W |
| 70 |
| Ea |
| 2004 |
| 20 |
| Street Light, Metal Halide |
| 100 W |
| 79 |
| Ea |
| 2001 |
| 20 |
| Street Light, Metal Halide |
| 175 W |
| 81 |
| Ea |
| 1997 |
| 20 |
| Street Light, Metal Halide |
| 100 W |
| 42 |
| Ea |
| 1960 |
| 20 |
| Street Light, Metal Halide |
| 100 W |
| 17 |
| Ea |
| 1977 |
| 20 |
| Street Light, HPS |
| 150 W |
| 24 |
| Ea |
| 2000 |
| 20 |
| Street Light, HPS |
| 250 W |
| 36 |
| Ea |
| 2002 |
| 20 |
| Street Light, HPS |
| 250 W |
| 24 |
| Ea |
| 2000 |
| 20 |
| Street Light, HPS |
| 400 W |
| 24 |
| Ea |
| 2000 |
| 20 |
| Street Light, HPS on power pole |
| 150 W |
| 60 |
| Ea |
| 1990 |
| 20 |
| Street Light, HPS on power pole |
| 250 W |
| 60 |
| Ea |
| 1990 |
| 20 |
| Street Light, HPS on power pole |
| 400 W |
| 59 |
| Ea |
| 1990 |
| 20 |
| Light Pole, Steel |
| 15' |
| 90 |
| Ea |
| 2007 |
| 35 |
| Light Pole, Steel |
| 15' |
| 26 |
| Ea |
| 2006 |
| 35 |
| Light Pole, Steel |
| 15' |
| 59 |
| Ea |
| 2005 |
| 35 |
| Light Pole, Steel |
| 15' |
| 70 |
| Ea |
| 2004 |
| 35 |
| Light Pole, Steel |
| 15' |
| 79 |
| Ea |
| 2001 |
| 35 |
| Light Pole, Steel |
| 15' |
| 81 |
| Ea |
| 1997 |
| 35 |
| Light Pole, Steel |
| 15' |
| 28 |
| Ea |
| 1960 |
| 35 |
| Light Pole, Steel |
| 25’ |
| 36 |
| Ea |
| 2002 |
| 35 |
| Light Pole, Steel |
| 25’ |
| 72 |
| Ea |
| 2000 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 17 |
| Ea |
| 1977 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 36 |
| Ea |
| 2002 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 24 |
| Ea |
| 2000 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 24 |
| Ea |
| 2000 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 24 |
| Ea |
| 2000 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 60 |
| Ea |
| 1990 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 60 |
| Ea |
| 1990 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 59 |
| Ea |
| 1990 |
| 35 |
| Pole Arm, Steel |
| 6' |
| 14 |
| Ea |
| 1960 |
| 35 |
| Pole Base, Concrete |
| 18” x 3’ |
| 90 |
| Ea |
| 2007 |
| 60 |
| Pole Base, Concrete |
| 18” x 3’ |
| 26 |
| Ea |
| 2006 |
| 60 |
| Pole Base, Concrete |
| 18” x 3’ |
| 59 |
| Ea |
| 2005 |
| 60 |
| Pole Base, Concrete |
| 18” x 3’ |
| 70 |
| Ea |
| 2004 |
| 60 |
| Pole Base, Concrete |
| 18” x 3’ |
| 36 |
| Ea |
| 2002 |
| 60 |
| Pole Base, Concrete |
| 18” x 3’ |
| 79 |
| Ea |
| 2001 |
| 60 |
| Pole Base, Concrete |
| 18” x 3’ |
| 81 |
| Ea |
| 1997 |
| 60 |
| Main Substation Bypass Switch |
| 15 kV |
| 1 |
| Ea |
| 2008 |
| 35 |
| Main Substation Bypass Switch |
| 15 kV |
| 7 |
| Ea |
| 1972 |
| 35 |
| Main Substation CT Metering, 15 kV |
| 400 A |
| 1 |
| Ea |
| 2008 |
| 20 |
| Main Substation CT Metering, 15 kV |
| 400 A |
| 7 |
| Ea |
| 2007 |
| 20 |
| Main Substation Recloser |
| 15 kV |
| 1 |
| Ea |
| 2008 |
| 35 |
| Main Substation Recloser |
| 15 kV |
| 7 |
| Ea |
| 1972 |
| 35 |
| Substation Bus bar Structure, Steel |
| Medium |
| 1 |
| Ea |
| 1972 |
| 50 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 14 |
| Ea |
| 2008 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 13 |
| Ea |
| 2006 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 11 |
| Ea |
| 2005 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 33 |
| Ea |
| 2004 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 25 |
| Ea |
| 2002 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 21 |
| Ea |
| 2001 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 8 |
| Ea |
| 2000 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 9 |
| Ea |
| 1997 |
| 35 |
| Sector/Terminal Boxes, 4-way |
| 15 kV |
| 3 |
| Ea |
| 1960 |
| 35 |
| Fac. 1100 Vehicle Maintenance Shop Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 1224 EMS Building/Terminal Bldg Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 1225 Shop Weapon and Release Systems Meter, Digital |
| 400 A |
| 2 |
| Ea |
| 1995 |
| 20 |
| Fac. 1320& 1322 LRS Meter, Analog |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 1330 Aircraft Corrosion Control Meter, Digital |
| 400 A |
| 2 |
| Ea |
| 1995 |
| 20 |
| Fac. 1330 Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 1333 Maintenance Dock Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 1339 Jet Engine Maintenance Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 1807 Horse Stables Meter, Analog |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 1807 Horse Stables Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 195 Gunfighter Club Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 196 MXG Headquarters Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 198 Maintenance Hanger Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 200 Maintenance Dock Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 206Fire Crash/Rescue Station Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 21 Maintenance Dock Meter, Digital |
| 400 A |
| 3 |
| Ea |
| 1995 |
| 20 |
| Fac. 2201 Vet Clinic Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2215 Group Headquarters Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2312 Dorm Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2314 Dorm Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2318 Dorm Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2320 Dorm Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2371/2370 Gymnasium Meter, Digital |
| 400 A |
| 4 |
| Ea |
| 1995 |
| 20 |
| Fac. 2412 Dorm Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2416 Dorm Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2422 Dorm Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2610 Base Supply Admin. Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2620 Wells Fargo Bank Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2621 Credit Union Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2700 Sales Store, Exchange Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2706 Commissary Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 2706 Store, Commissary Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 4401 Quest Meter, Analog |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 510 Comm. Squadron Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 512 MPF Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 512 Wing Headquarters Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 6000 Hospital A Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 6000 Hospital B Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| Fac. 920 Avionics Shop Meter -Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| MFH Capehart Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| MFH Dunes Meter, Analog |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| MFH Eagle View Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
| MFH Phase 3 Meter, Digital |
| 400 A |
| 1 |
| Ea |
| 1995 |
| 20 |
Notes:
A = amps
ACSR = Aluminum conductor steel reinforced
AWG = American Wire Gauge
EA = each
HPS = high pressure sodium kV = kilovolts kVA = kilovolt-amperes lf = linear feet
MCM = kcmil = thousand circular mils
MFH = military family housing MH = metal halide
Nom kVA = nominal kilovolt-amperes
OH = overhead
PH = phase
PVC = polyvinyl chloride
RGS = rigid galvanized steel
SCLF = single conductor linear feet
SF = square feet
V = volts
W = wire
JA1.2.2 Electric Distribution System Non-Fixed Equipment and Specialized Tools
Table 2 lists other ancillary equipment (spare parts) and Table 3 lists specialized vehicles and tools included in the purchase. Offeror shall field verify all equipment, vehicles, and tools prior to submitting a bid. Offeror shall make its own determination of the adequacy of all equipment, vehicles, and tools.
Table 2
Spare Parts
Electric Distribution System
| Item |
| Make/Model |
| Description |
| Quantity |
| Remarks |
None
Table 3
Specialized Vehicles and Tools
Electric Distribution System
| Item |
| Make/Model |
| Description |
| Quantity |
| Remarks |
None
JA1.2.3 Electric Distribution System Manuals, Drawings, and Records
Table 4 lists the manuals, drawings, and records that will be transferred with the system.
Table 4
Manuals, Drawings, and Records
Electric Distribution System
| Item |
| Description |
| Quantity |
| Remarks |
| Site Plans |
| TIF image utility drawings |
| 120 |
| Updated 1995 (estimated) |
JA1.3 Specific Service Requirements
Service requirements for this electric distribution system are as defined in the RFP Section C, Description/Specifications/Work Statement. The following requirements are specific to the base electric distribution system and are in addition to those found in Section C.
1. The Government will provide the electricity, natural gas, and water commodities and the wastewater collection required to operate and maintain the systems being privatized at no cost to the System Owner (SO). The Government will also provide any infrastructure necessary to connect the facilities required to operate and maintain the systems being privatized to electricity, natural gas, water, and wastewater collection services at no cost to the SO. If fuel oil or propane is required to operate emergency generators, purchase and supply of that fuel oil or propane will be the responsibility of the SO.
2. The Government reserves the right to underground some or all of the existing overhead lines at a future time. For price proposal purposes, the Offeror shall assume that when existing overhead lines require replacement, they will be replaced with overhead lines. If the Government exercises its right to underground these overhead lines that require replacement, an equitable adjustment will be accomplished to cover the difference in installation and maintenance costs between overhead and underground lines. To ensure the Government is afforded the opportunity to exercise this right, the System Owner shall consult and coordinate with the Government prior to replacement of any overhead electrical lines.
JA1.4 Current Service Arrangement
The base is supplied power from Idaho Electric Power Company with two separate overhead power lines. One enters the base from the Northwest and is rated at 138 kV; the other enters the base from the East and is rated at 69 kV. The approximate connected load on the 138 kV line is 26,880 kW and 10,400 kW on the 69 kV line. The power usage for the year 2008 was 45,736, 949 kWh. The main substation on the base consists of two separate substations that are adjacent to each other. One is owned by the utility company and the other is owned by the base. The utility substation provides power overhead to the base owned substation. The utility owns the overhead lines to the point where they connect to the substation busbars which are located inside the base owned substation. Both substations are fenced separately.
JA1.5 Metering
JA1.5.1 Existing Meters
Table 5 provides a list of the existing (at the time of contract award) meters that will be transferred to the SO. The SO shall provide meter readings for all meters listed below.
Table 5
Existing Meters
Electric Distribution System
| Meter Location |
| Meter Size |
| Remarks |
| Fac. 1100 Vehicle Maintenance Shop |
| 400A, |
| Digital |
| Fac. 1224 EMS Building/Terminal Bldg |
| 400A |
| Digital |
| Fac. 1225 Shop Weapon and Release Systems (2) |
| 400A |
| Digital |
| Fac. 1320& 1322 LRS |
| 400A |
| Analog |
| Fac. 1330 Aircraft Corrosion Control (2) |
| 400A |
| Digital |
| Fac. 1330 Meter |
| 400A |
| Digital |
| Fac. 1333 Maintenance Dock |
| 400A |
| Digital |
| Fac. 1339 Jet Engine Maintenance |
| 400A |
| Digital |
| Fac. 1807 Horse Stables |
| 400A |
| Digital |
| Fac. 1807 Horse Stables |
| 400A |
| Analog |
| Fac. 195 Gunfighter Club |
| 400A |
| Digital |
| Fac. 196 MXG Headquarters |
| 400A |
| Digital |
| Fac. 198 Maintenance Hanger |
| 400A |
| Digital |
| Fac. 200 Maintenance Dock |
| 400A |
| Digital |
| Fac. 206Fire Crash/Rescue Station |
| 400A |
| Digital |
| Fac. 21 Maintenance Dock (3) |
| 400A |
| Digital |
| Fac. 2201 Vet Clinic |
| 400A |
| Digital |
| Fac. 2215 Group Headquarter |
| 400A |
| Digital |
| Fac. 2312 Dorm |
| 400A |
| Digital |
| Fac. 2314 Dorm |
| 400A |
| Digital |
| Fac. 2318 Dorm |
| 400A |
| Digital |
| Fac. 2320 Dorm |
| 400A |
| Digital |
| Fac. 2371/2370 Gymnasium (4) |
| 400A |
| Digital |
| Fac. 2412 Dorm |
| 400A |
| Digital |
| Fac. 2416 Dorm |
| 400A |
| Digital |
| Fac. 2422 Dorm |
| 400A |
| Digital |
| Fac. 2610 Base Supply Admin. |
| 400A |
| Digital |
| Fac. 2620 Wells Fargo Bank |
| 400A |
| Digital |
| Fac. 2621 Credit Union |
| 400A |
| Digital |
| Fac. 2700 Sales Store, Exchange |
| 400A |
| Digital |
| Fac. 2706 Commissary |
| 400A |
| Digital |
| Fac. 2706 Store, Commissary |
| 400A |
| Digital |
| Fac. 4401 Quest |
| 400A |
| Analog |
| Fac. 510 Comm. Squadron |
| 400A |
| Digital |
| Fac. 512 MPF |
| 400A |
| Digital |
| Fac. 512 Wing Headquarters |
| 400A |
| Digital |
| Fac. 6000 Hospital A |
| 400A |
| Digital |
| Fac. 6000 Hospital B |
| 400A |
| Digital |
| Fac. 920 Avionics Shop |
| 400A |
| Digital |
| MFH Capehart |
| 400A |
| Digital |
| MFH Eagle View |
| 400A |
| Digital |
JA1.5.2 Required New Meters
The SO shall install and calibrate new meters as listed in Table 6.
Table 6
Required New Meters
Electric Distribution System
| Meter Location |
| Meter Size |
| Remarks |
None
JA1.6 Monthly Submittals
The SO shall provide the Government with monthly submittals for the following:
1. Outage Report. The SO’s monthly outage report will be prepared in the format proposed by the SO and accepted by the Contracting Officer. Outage reports shall be submitted by the 25th of each month for the previous month. Outage reports shall be submitted to:
Organization/Office Symbol:
366CES/CEOE
Address:
Mountain Home AFB, ID 89191-7260 Phone number:
(208) 828-3830
2. Meter Reading Report. The monthly meter reading report shall show the current and previous month readings for all meters. The SO’s monthly meter reading report will be prepared in the format proposed by the SO and accepted by the Contracting Officer. Meter reading reports shall be submitted by the 15th of each month for the previous month. Meter reading reports shall be submitted to:
Organization/Office Symbol:
366CES/CEOE
Address:
Mountain Home AFB, ID 89191-7260 Phone number:
(208) 828-3830 JA1.7 Energy-Savings Projects
The following projects listed in Table 7 have been implemented on the distribution system by the Government for energy conservation purposes.
Table 7
Energy-Savings Projects Electric Distribution System
| Project Location |
| Project Description |
None
JA1.8 Service Area
The current service area is defined as all areas within the Mountain Home AFB boundaries.
JA1.9 Off-Installation Sites
No off-installation sites are included in the sale of the Mountain AFB electric distribution system. Specifically excluded are the electric distribution facilities at GSU sites: Saylor Creek Gunnery Range, the Small Arms Range Annex, the C.J. Strike Dam Marina, Rattlesnake Radar Station, Middle Marker, Grasmere Electronic Combat Site, and Seneca Ground Wave Emergency Network Station.
JA1.10 Specific Transition Requirements
Table 8 provides a list of service connections and disconnections required upon transfer.
Table 8
Service Connections and Disconnections
Electric Distribution System
None
JA1.11 Initial System Deficiency Corrections (ISDC)
Table 9 provides a list of ISDC projects the Government has planned for this system. The Government recognizes these projects represent current deficiencies associated with the system. If the system is sold, the Government will not accomplish these projects. The SO shall determine the actual need and timing of any and all such projects.
Table 9
Initial System Deficiency Corrections
Electric Distribution System
| Project Location |
| Project Description |
None
JA1.12 Right of Access to the Utility System
No leased property was identified with the Electrical Distribution System.
JA1.12.1 Map of the Utility System
Maps from the Base Comprehensive Plan or other drawings show the known locations of the utility system and are available in the technical library at the base civil engineer organization. Portions of the utility system may not be fully shown on the map or maps. Any such failure to show the complete utility system on the map or maps shall not be interpreted as that part of the utility system being outside the Installation. The Installation is co-extensive with the entire linear extent of the utility system sold to Grantee (SO), whether or not precisely shown on the map or maps.
JA1.12.2 Lateral Extent of the Right-of-Access, and Points of Demarcation
JA1.12.2.1 Lateral Extent of Utility System Right-of-Access
Where the utility system is installed aboveground and/or underground, the Right-of-Access is defined as 26 feet wide, extending 13 feet on each side of the utility system, as installed.
JA1.12.2.2 Utility System Points of Demarcation
The point of demarcation (POD) is defined as the point on the utility system where ownership changes from the utility SO to the facility owner. Table 10 identifies the type and general location of the point of demarcation with respect to the facility for each scenario.
Table 10
Standard Points of Demarcation
Electric Distribution System
| Point of Demarcation |
| Applicable Scenario |
| Sketch |
| POD is the secondary terminal of the transformer. |
| Pad-mounted transformer is located outside the structure with underground service to the structure. No meter exists. |
| POD is the load side of the meter. |
| Pad-mounted transformer is located outside the structure with underground service to the structure. Meter exists on the structure or between the structure and the pad-mounted transformer. |
| POD is the secondary terminal of the transformer. |
| Pad-mounted transformer is located outside the structure with underground service to the structure. Three-phase CT metered service exists. |
Note: The meter, can, CTs, and associated wires are owned and maintained by the electric utility owner.
| POD is the secondary terminal of the transformer (located inside the structure). |
| Transformer is located inside the structure. An isolation device is in place with or without a meter. |
Note: Electric utility owner must be granted 24-hour access to transformer room.
SHAPE \* MERGEFORMAT
| POD is the secondary terminal of the transformer (located inside the structure). |
| Transformer is located inside the structure. No isolation device exists. |
Note: Electric utility owner must be granted 24-hour access to transformer room.
SHAPE \* MERGEFORMAT
| POD is the load side of the meter. |
| Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. Electric meter is connected to the exterior of the structure. |
Note: The meter, meter can, and weather head, are owned and maintained by the electric utility owner.
SHAPE \* MERGEFORMAT
| POD is where the overhead conductor is connected to the weather head. |
| Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. No meter exists. |
| SHAPE \* MERGEFORMAT |
| POD is where the overhead conductor is connected to the weather head. |
| Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. A disconnect switch or junction box is mounted to the exterior of the structure and no meter exists. |
SHAPE \* MERGEFORMAT
POD is where the overhead conductor is connected to the service entrance mast.
Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The water utility owner owns the service entrance mast and all wiring on the load side of the POD.
Electric power is provided to a water facility via an overhead service drop. This configuration could be found at facilities dedicated to the water utility such as a water well, pump station, or storage facility.
None
POD is at the secondary terminal of the transformer.
Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The water utility owner owns all wiring on the load side of the transformer.
Electric power is provided to a water facility via an underground service connection. This configuration could be found at facilities dedicated to the water utility such as a water well, pump station, or storage facility.
None
POD is where the overhead conductor is connected to the service entrance mast.
Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The wastewater utility owner owns the service entrance mast and all wiring on the load side of the POD.
Electric power is provided to a wastewater facility via an overhead service drop. This configuration could be found at facilities dedicated to the wastewater utility such as a lift station or wastewater treatment plant.
None
POD is the secondary terminal of the transformer.
Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The wastewater utility owner owns all wiring on the load side of the transformer.
Electric power is provided to a wastewater facility via an underground service connection. This configuration could be found at facilities dedicated to the wastewater utility such as a lift station or wastewater treatment plant.
None
| PODs are where the secondary conductor is attached to the electric utility owner's pole and where the light fixture is attached to the electric utility owner's pole. |
| Government-owned secondary circuit and light fixture are attached to the electric utility owner's pole. |
| SHAPE \* MERGEFORMAT |
WITHIN HOUSING AREAS
POD is the line side of the meter.
Residential structure.
Pad-mounted transformer is located outside the structure with underground service to the structure. Existing meter.
WITHIN HOUSING AREAS
POD is the line side of the service panel.
Residential structure.
Pad-mounted transformer is located outside the structure with underground service to the structure. No existing meter.
Note: If a meter is installed on the load side of the service panel in the future, then the POD becomes the line side of the meter.
WITHIN HOUSING AREAS
POD is the line side of the meter.
Residential structure.
Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. Electric meter is connected to the exterior of the structure. The owner of the residential structure owns the service mast.
SHAPE \* MERGEFORMAT
WITHIN HOUSING AREAS
POD is the line side of the disconnect switch or junction box.
Residential structure.
Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. A disconnect switch or junction box is mounted to the exterior of the structure and no meter exists. The owner of the residential structure owns the service mast.
SHAPE \* MERGEFORMAT
WITHIN HOUSING AREAS
POD is where the overhead conductor is connected to the weather head.
Residential structure.
Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. A disconnect switch or junction box is not mounted to the exterior of the structure, and no meter exists. The owner of the residential structure owns the service mast
Note: If a meter, disconnect switch, or junction box is installed in the future, then the POD becomes the line side of the meter, disconnect switch, or junction box.
SHAPE \* MERGEFORMAT
Table 11 lists anomalous “unique” points of demarcation that do not fit any of the above scenarios. These unique points of demarcation shall take precedence over the standard points of demarcation shown in Table 10.
TABLE 11
Unique Points of Demarcation
Electric Distribution System
| Military Family housing with installed meter base without meter |
| MFH where meter base is installed but no meter has been installed. The POD is the line side of the meter base. |
| Main Substation |
| The connection of the utility-owned overhead line at the load side of the busbars in the base-owned substation |
| Airfield Lighting |
| The load side of the pad-mounted switch feeding the airfield lighting vault, Building 258 |
| Facilities w/o meters |
| The supply or secondary side of the transformer feeding the facility |
| EMCS Equipment |
| The POD is the supply side of a connection to any EMCS device or meter that is part of the collective EMCS system. |
JA1.12.3 Environmental Baseline Survey
The Air Force has determined that it is not required to conduct an EBS in regard to the sale of this utility system.
Structure
Service
Line
Point of Demarcation
Distribution Line
S P
Isolation
Device
Point of
Demarcation
Utility
Pole
Pole Mounted
Transformer
Meter
Disconnect or
Junction Box
Government-Owned
Secondary Circuit
Utility-Owned Pole
Government-Owned
Light Fixture
Points of Demarcation
Disconnect or
Junction Box
Point of
Demarcation
Isolation
Device
(Attachment J1 Template - 10 May 2009) Edited DD MMM Yy – Version xx J1-i (Attachment JA1 Electric Distribution System Template – SEPTEMBER 2009_REV_MAY 2010) User Edited: ver:08 05Oct10
JA1-1
_1313237576.doc
Pad Mounted
_1313319183.doc
Service Line
_1300868474.doc
Pad Mounted Transformer
Service Panel
_1300868878.doc
Pad Mounted Transformer
Service Panel