Air Force Utilities Privatization - REQUEST for proposal Attachment J1

Air Force Utilities Privatization - REQUEST for proposal (RFP) Attachment JA1

Attachment JA1

Mountain Home AFB Electric Distribution System Table of Contents

1Mountain Home AFB Electric Distribution System

JA1-

1Table of Contents

JA1-

1LIST OF TABLES

JA1-

2JA1 Mountain Home AFB Electric Distribution System

JA1-

3JA1.2 Electric Distribution System Description

JA1-

3JA1.2.1 Electric Distribution System Fixed Equipment Inventory

JA1-

17JA1.2.2 Electric Distribution System Non-Fixed Equipment and Specialized Tools

JA1-

18JA1.2.3 Electric Distribution System Manuals, Drawings, and Records

JA1-

18JA1.3 Specific Service Requirements

JA1-

19JA1.4 Current Service Arrangement

JA1-

19JA1.5 Metering

JA1-

19JA1.5.1 Existing Meters

JA1-

21JA1.5.2 Required New Meters

JA1-

21JA1.6 Monthly Submittals

JA1-

21JA1.7 Energy-Savings Projects

JA1-

22JA1.8 Service Area

JA1-

22JA1.9 Off-Installation Sites

JA1-

22JA1.10 Specific Transition Requirements

JA1-

22JA1.11 Initial System Deficiency Corrections (ISDC)

JA1-

22JA1.12 Right of Access to the Utility System

JA1-

22JA1.12.1 Map of the Utility System

JA1-

23JA1.12.2 Lateral Extent of the Right-of-Access, and Points of Demarcation

JA1-

27JA1.12.3 Environmental Baseline Survey

JA1-

LIST OF TABLES

table 1 - 4Fixed Inventory

JA1-

table 2 - Spare Parts

JA1-17

table 3 - Specialized Vehicles and Tools

JA1-18

table 4 - Manuals, Drawings, and Records

JA1-18

table 5 - Existing Meters

JA1-19

table 6 - Required New Meters

JA1-21

table 7 - Energy-Savings Projects

JA1-21

table 8 - Service Connections and Disconnections

JA1-22

table 9 - Initial System Deficiency Corrections

JA1-22

table 10 - Standard Points of Demarcation

JA1-23

table 11 - Unique Points of Demarcation

JA1-27

JA1 Mountain Home AFB Electric Distribution System JA1.1 Mountain Home AFB Overview

Mountain Home AFB (MHAFB) is an active military installation located in Elmore County, Idaho. The base is approximately 10 miles west of the city of Mountain Home, seven miles northeast of I-84 Exit 95, on Idaho Highway 20.

MHAFB is the home of the 366th Wing. The mission of the 366th Fighter Wing (FW) is to prepare Airmen and their families, professionally and personally, for expeditionary operations and foster an environment that promotes integration of all facets of wing operations. The mission is to execute directed missions designed to identify and destroy enemy forces, supplies, equipment, communication systems, and installations within the design limits of the weapons systems capabilities. The 366th FW serves as the host wing overseeing day to day operations of the base such as personnel, finance, civil engineering and supply. Other base tenants include:

· Air Combat Command Contract Performance Squadron (ACCCPS)

· Air Force Audit Agency Area Office (AFAA)

· Air Force Office of Special Investigations (AFOSI)

· American Red Cross (ARC)

· Area Defense Council (ADC)

· Army and Air Force Exchange Services (AAFES)

· Defense Commissary Agency (DeCA)

· Defense Investigative Service (DIS)

· Defense Printing Service (DPS)

· Defense Reutilization and Marketing Office (DRMO)

· Idaho Army National Guard

· US Army Corps of Engineers (USACE)

· 372d Training Detachment MHAFB and its geographically separated units (GSUs) occupy 119,431 acres consisting of Air Force owned lands, private property easements, public lands withdrawn from use, public domain permits, and rights-of-way. The base area encompasses 6,729 acres. Utilities at the GSUs are not being considered for privatization.

The Base General Plan states that the total installation population is 10,392. This includes active duty military, family members on and off base, DOD civilians and private business personnel. MHAFB contributes significantly to the local economy through civilian employment, contracting, and purchases from local businesses.

JA1.2 Electric Distribution System Description

JA1.2.1 Electric Distribution System Fixed Equipment Inventory

The Mountain Home AFB electric distribution system consists of all appurtenances physically connected to the distribution system from the point of demarcation defined by the Right of Access. The distribution system consists of the items listed in Table 1 “Fixed Inventory Electric Distribution System” in Section JA1.2.1.2 Inventory. The actual inventory of items sold will be in the bill of sale at the time the system is transferred. The following description and inventory is included to provide the Offeror with a general understanding of the size and configuration of the distribution system. The Government makes no representation that the inventory is accurate. The Offeror shall base its proposal on the Table 1 inventory below. However, the Offeror should use the following reference points for developing other aspects of its proposal: site inspections, information in the technical library, and other pertinent information.

Specifically excluded from the electric distribution system privatization are:

· airfield lighting

· parking lot lights serviced by secondary feed from a building

· emergency generators that exist for the purpose of emergency back-up for AF facilities

· Electric distribution facilities at GSUs including: Saylor Creek Gunnery Range, the Small Arms Range Annex, the C.J. Strike Dam Marina, Rattlesnake Radar Station, Middle Marker, Grasmere Electronic Combat Site, and Seneca Ground Wave Emergency Network Station.

JA1.2.1.1 Description

The base electrical distribution system is powered by two services from Idaho Power. One service enters the site at 138 kV and the second enters at 69 kV. The 138 kV line enters the base from the northwest on Liberator road and the 69 kV line enters the site from the northeast on Perimeter Road, east of the main gate. The two services are terminated at the main base electrical substation located on Liberator road. The substation consists of two separate areas, the utility-owned substation and the base-owned substation. Both areas are fenced separately and located adjacent to each other. The connection between the two substations is by overhead wiring. The utility owns the overhead lines to the point where it terminates on the base owned bus bars inside the base-owned area. The base takes ownership of the system at the termination point on the busbar.

There are eight feeders leaving the main substation that powers the base.

Each feeder leaving the substation has primary CT metering, an automatic recloser and bypass switch. Each circuit has a meter to measure the power consumed on each circuit. Seven meters were rebuilt in 2007 and a new meter was provided with the pad-mounted equipment in 2008.

Idaho Power owns a distribution line that runs from the main substation down Phantom Road and Eagle Drive to a dead end point at the end of Eagle Drive. There is no equipment powered from this line, but it is energized. This line is going to be removed in the future but has not yet been funded.

There are two housing areas that will be demolished in the future. They are the Elk Heights (formerly “Desert Vista”) and Falcon Estates (formerly “Old Gunfighter”) subdivisions. Both of these areas have overhead primary and secondary distribution. The inventory for those subdivisions will remain and is included in the Table 1 inventory.

The Dunes subdivision is currently under demolition. The existing street lighting and power distribution system will remain and is included in the Table 1 inventory.

The base roadway lighting system is powered from the primary distribution system through step-down transformers and distribution panels located around the base. The transformers step the voltage down to 120/240v, single phase power and the power is distributed on the site from outdoor panel boards.

JA1.2.1.2 Inventory

Table 1 provides a general list of the major electric distribution system fixed assets for the Mountain Home AFB electric distribution system included in the sale. The design life column indicated in Table 1 is used by the Government in the development of the Government Should Cost Estimate. The design life is not mandated in the Offeror’s proposal. However, the proposal must clearly explain the use of any system component design life that significantly differs from the published Government design life.

Table 1

Fixed Inventory

Electric Distribution System

Item
Size
Quantity
Unit
Approximate Year of Construction
Design Life

(Years)

UG Cable, Copper, 15 kV
#2 AWG
6,200
SCLF
2008
45
UG Cable, Copper, 15 kV
#2 AWG
65,600
SCLF
2004
45
UG Cable, Copper, 15 kV
#2 AWG
24,026
SCLF
2002
45
UG Cable, Copper, 15 kV
#2 AWG
9,440
SCLF
2001
45
UG Cable, Copper, 15 kV
#2 AWG
1,940
SCLF
1997
45
UG Cable, Copper, 15 kV
#4/0 AWG
27,652
SCLF
2002
45
UG Cable, Copper, 15 kV
500 MCM
32,600
SCLF
2008
45
UG Cable, Copper, 15 kV
500 MCM
10,300
SCLF
2006
45
UG Cable, Copper, 15 kV
500 MCM
17,600
SCLF
2005
45
UG Cable, Copper, 15 kV
500 MCM
16,000
SCLF
2004
45

Elk Heights (Former Desert Vista)

OH Residential Cable
3/0
9,950
SCLF
1977
50

Falcon Estates (Former Old Gunfighter)

OH Residential Cable
3/0
5,350
SCLF
1960
50
Ground Wire, Bare Copper, 600 V
#4/0 AWG
2,640
SCLF
2008
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
1,920
SCLF
2006
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
1,360
SCLF
2005
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
8,080
SCLF
2004
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
5,280
SCLF
2002
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
3,200
SCLF
2001
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
1,200
SCLF
2000
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
2,960
SCLF
1997
35
Ground Wire, Bare Copper, 600 V
#4/0 AWG
1,440
SCLF
1960
35
Ground Rod
¾”x10’
132
Ea
2008
35
Ground Rod
¾”x10’
96
Ea
2006
35
Ground Rod
¾”x10’
68
Ea
2005
35
Ground Rod
¾”x10’
404
Ea
2004
35
Ground Rod
¾”x10’
264
Ea
2002
35
Ground Rod
¾”x10’
160
Ea
2001
35
Ground Rod
¾”x10’
60
Ea
2000
35
Ground Rod
¾”x10’
120
Ea
1997
35
Ground Rod
¾”x10’
100
Ea
1960
35
Hand hole, Concrete
4’-6" x 3’-2" x 2’-0"
10
Ea
2006
60
Hand hole, Concrete
4’-6" x 3’-2" x 2’-0"
20
Ea
2005
60
Hand hole, Concrete
4’-6" x 3’-2" x 2’-0"
8
Ea
2004
60
Hand hole, Concrete
4’-6" x 3’-2" x 2’-0"
59
Ea
2002
60
Hand hole, Concrete
4’-6" x 3’-2" x 2’-0"
19
Ea
2000
60
Manhole, Concrete
6’ x 6’ x 10’
6
Ea
2005
60
Manhole, Concrete
6’ x 6’ x 10’
11
Ea
2004
60
Manhole, Concrete
6’ x 6’ x 10’
1
Ea
1960
60
2” Duct Bank, PVC, Concrete encased
1 x 2
3,500
LF
2007
100
2” Duct Bank, PVC, Concrete encased
1 x 2
1,000
LF
2006
100
2” Duct Bank, PVC, Concrete encased
1 x 2
2,150
LF
2005
100
2” Duct Bank, PVC, Concrete encased
1 x 2
2,650
LF
2004
100
2” Duct Bank, PVC, Concrete encased
1 x 2
2,414
LF
2002
100
2” Duct Bank, PVC, Concrete encased
1 x 2
3,000
LF
2001
100
2” Duct Bank, PVC, Concrete encased
1 x 2
3,500
LF
1997
100
4” Duct Bank, PVC, Concrete encased
2 x 4
5,304
LF
2002
100
5” Duct Bank, PVC, Concrete encased
1 x 2
3,100
LF
2008
100
5” Duct Bank, PVC, Concrete encased
1 x 2
2,560
LF
2006
100
5” Duct Bank, PVC, Concrete encased
1 x 2
11,375
LF
2004
100
5” Duct Bank, PVC, Concrete encased
1 x 2
5,002
LF
2002
100
6” Duct Bank, PVC, Concrete encased
1 x 2
6,600
LF
2008
100
6” Duct Bank, PVC, Concrete encased
1 x 2
4,400
LF
2005
100
6” Duct Bank, PVC, Concrete encased
1 x 2
9,000
LF
2004
100
6” Duct Bank, PVC, Concrete encased
1 x 2
1,175
LF
2002
100
6” Duct Bank, PVC, Concrete encased
1 x 2
2,360
LF
2001
100
6” Duct Bank, PVC, Concrete encased
1 x 2
485
LF
1997
100
4” Conduit, RGS, Direct bury
1 x 1
427
LF
2002
50
5” Conduit, RGS, Direct bury
1 x 1
742
LF
2002
50
Pad-mount Transformer, Single Ph, 15 kV
25 kVA
3
Ea
2008
35
Pad-mount Transformer, Single Ph, 15 kV
25 kVA
1
Ea
2006
35
Pad-mount Transformer, Single Ph, 15 kV
25 kVA
1
Ea
2004
35
Pad-mount Transformer, Single Ph, 15 kV
25 kVA
6
Ea
2002
35
Pad-mount Transformer, Single Ph, 15 kV
25 kVA
2
Ea
2000
35
Pad-mount Transformer, Single Ph, 15 kV
25 kVA
7
Ea
1960
35
Pad-mount Transformer, Single Ph, 15 kV
50 kVA
1
Ea
2008
35
Pad-mount Transformer, Single Ph, 15 kV
50 kVA
3
Ea
2006
35
Pad-mount Transformer, Single Ph, 15 kV
50 kVA
59
Ea
2004
35
Pad-mount Transformer, Single Ph, 15 kV
50 kVA
2
Ea
2002
35
Pad-mount Transformer, Single Ph, 15 kV
50 kVA
17
Ea
2001
35
Pad-mount Transformer, Single Ph, 15 kV
50 kVA
2
Ea
2000
35
Pad-mount Transformer, Single Ph, 15 kV
50 kVA
4
Ea
1960
35
Pad-mount Transformer, Single Ph, 15 kV
75 kVA
1
Ea
2008
35
Pad-mount Transformer, Single Ph, 15 kV
75 kVA
1
Ea
2006
35
Pad-mount Transformer, Single Ph, 15 kV
75 kVA
1
Ea
2002
35
Pad-mount Transformer, Single Ph, 15 kV
100 kVA
2
Ea
2002
35
Pad-mount Transformer, 3 Ph, 15 kV
45 kVA
1
Ea
2004
35
Pad-mount Transformer, 3 Ph, 15 kV
45 kVA
3
Ea
2000
35
Pad-mount Transformer, 3 Ph, 15 kV
75 kVA
7
Ea
2002
35
Pad-mount Transformer, 3 Ph, 15 kV
150 kVA
2
Ea
2008
35
Pad-mount Transformer, 3 Ph, 15 kV
150 kVA
1
Ea
2005
35
Pad-mount Transformer, 3 Ph, 15 kV
150 kVA
6
Ea
2004
35
Pad-mount Transformer, 3 Ph, 15 kV
150 kVA
4
Ea
2002
35
Pad-mount Transformer, 3 Ph, 15 kV
150 kVA
7
Ea
1960
35
Pad-mount Transformer, 3 Ph, 15 kV
225 kVA
1
Ea
2008
35
Pad-mount Transformer, 3 Ph, 15 kV
225 kVA
2
Ea
2006
35
Pad-mount Transformer, 3 Ph, 15 kV
225 kVA
3
Ea
2002
35
Pad-mount Transformer, 3 Ph, 15 kV
225 kVA
4
Ea
1960
35
Pad-mount Transformer, 3 Ph, 15 kV
300 kVA
3
Ea
2008
35
Pad-mount Transformer, 3 Ph, 15 kV
300 kVA
1
Ea
2006
35
Pad-mount Transformer, 3 Ph, 15 kV
300 kVA
1
Ea
2005
35
Pad-mount Transformer, 3 Ph, 15 kV
300 kVA
4
Ea
2004
35
Pad-mount Transformer, 3 Ph, 15 kV
300 kVA
5
Ea
2002
35
Pad-mount Transformer, 3 Ph, 15 kV
500 kVA
7
Ea
2002
35
Pad-mount Transformer, 3 Ph, 15 kV
500 kVA
4
Ea
1960
35
Pad-mount Transformer, 3 Ph, 15 kV
750 kVA
1
Ea
2006
35
Pad-mount Transformer, 3 Ph, 15 kV
750 kVA
1
Ea
2002
35
Pad-mount Transformer, 3 Ph, 15 kV
750 kVA
2
Ea
1960
35
Pad-mount Transformer, 3 Ph, 15 kV
1000 kVA
1
Ea
2008
35
Pad-mount Transformer, 3 Ph, 15 kV
1000 kVA
1
Ea
2005
35
Pad-mount Transformer, 3 Ph, 15 kV
1000 kVA
1
Ea
2004
35
Pad-mount Transformer, 3 Ph, 15 kV
1000 kVA
1
Ea
2002
35
Pad-mount Sectionalizing Switch, 4-way
15 kV
7
Ea
2008
35
Pad-mount Sectionalizing Switch, 4-way
15 kV
2
Ea
2006
35
Pad-mount Sectionalizing Switch, 4-way
15 kV
3
Ea
2005
35
Pad-mount Sectionalizing Switch, 4-way
15 kV
25
Ea
2004
35
Pad-mount Sectionalizing Switch, 4-way
15 kV
4
Ea
2002
35
Pad-mount Sectionalizing Switch, 4-way
15 kV
2
Ea
2001
35
Concrete pad, 4’ x 4’ x 6”
16 SF
33
Ea
2008
60
Concrete pad, 4’ x 4’ x 6”
16 SF
24
Ea
2006
60
Concrete pad, 4’ x 4’ x 6”
16 SF
17
Ea
2005
60
Concrete pad, 4’ x 4’ x 6”
16 SF
109
Ea
2004
60
Concrete pad, 4’ x 4’ x 6”
16 SF
66
Ea
2002
60
Concrete pad, 4’ x 4’ x 6”
16 SF
40
Ea
2001
60
Concrete pad, 4’ x 4’ x 6”
16 SF
15
Ea
2000
60
Concrete pad, 4’ x 4’ x 6”
16 SF
30
Ea
1997
60
Concrete pad, 4’ x 4’ x 6”
16 SF
31
Ea
1960
60
OH Wire, Copper, 15 kV
#8 AWG
2,900
SCLF
1960
50
OH Wire, Copper, 15 kV
#2 AWG
25,000
SCLF
1960
50
OH Wire, Aluminum, 15 kV
#4 ACSR
30,325
SCLF
2004
50
OH Wire, Aluminum, 15 kV
#4 ACSR
53,000
SCLF
1960
50
OH Wire, Aluminum, 15 kV
#2 ACSR
34,000
SCLF
2000
50
OH Wire, Aluminum, 15 kV
#1/0 ACSR
16,800
SCLF
1960
50
Power Pole, Wood, with 6’ arm
40’
189
Ea
2004
50
Power Pole, Wood, with 6’ arm
40’
100
Ea
2000
50
Power Pole, Wood, with 6’ arm
40’
8
Ea
1980
50
Power Pole, Wood, with 6’ arm
40’
551
Ea
1960
50
Power Pole, Wood, with 6’ arm
60’
8
Ea
1980
50
Power Pole, Wood, with 6’ arm
80’
8
Ea
1980
50
Power Pole, Wood, with 6’ arm
40’
50
Ea
1977
50
Pole-mount Transformer, Single Ph, 15 kV
3 kVA
1
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
3 kVA
1
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
5 kVA
8
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
5 kVA
4
Ea
2000
35
Pole-mount Transformer, Single Ph, 15 kV
5 kVA
118
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
10 kVA
2
Ea
2006
35
Pole-mount Transformer, Single Ph, 15 kV
10 kVA
25
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
10 kVA
36
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
15 kVA
3
Ea
2006
35
Pole-mount Transformer, Single Ph, 15 kV
15 kVA
12
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
15 kVA
6
Ea
1980
35
Pole-mount Transformer, Single Ph, 15 kV
15 kVA
43
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
25 kVA
6
Ea
2006
35
Pole-mount Transformer, Single Ph, 15 kV
25 kVA
63
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
25 kVA
4
Ea
2000
35
Pole-mount Transformer, Single Ph, 15 kV
25 kVA
4
Ea
1980
35
Pole-mount Transformer, Single Ph, 15 kV
25 kVA
32
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
37.5 kVA
5
Ea
2006
35
Pole-mount Transformer, Single Ph, 15 kV
37.5 kVA
10
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
37.5 kVA
4
Ea
2000
35
Pole-mount Transformer, Single Ph, 15 kV
37.5 kVA
17
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
50 kVA
3
Ea
2006
35
Pole-mount Transformer, Single Ph, 15 kV
50 kVA
21
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
50 kVA
9
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
75 kVA
2
Ea
2006
35
Pole-mount Transformer, Single Ph, 15 kV
75 kVA
5
Ea
2004
35
Pole-mount Transformer, Single Ph, 15 kV
75 kVA
3
Ea
2000
35
Pole-mount Transformer, Single Ph, 15 kV
75 kVA
2
Ea
1980
35
Pole-mount Transformer, Single Ph, 15 kV
75 kVA
15
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
100 kVA
6
Ea
2000
35
Pole-mount Transformer, Single Ph, 15 kV
100 kVA
3
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
167 kVA
12
Ea
1960
35
Pole-mount Transformer, Single Ph, 15 kV
5 kVA
50
Ea
1977
35
Fused Cutout
15 kV
92
Ea
2004
30
Fused Cutout
15 kV
21
Ea
2000
30
Fused Cutout
15 kV
12
Ea
1980
30
Fused Cutout
15 kV
181
Ea
1960
30
Street Lighting Wire, Copper, 600 V
#6 AWG
21,000
SCLF
2007
50
Street Lighting Wire, Copper, 600 V
#6 AWG
6,000
SCLF
2006
50
Street Lighting Wire, Copper, 600 V
#6 AWG
13,000
SCLF
2005
50
Street Lighting Wire, Copper, 600 V
#6 AWG
16,000
SCLF
2004
50
Street Lighting Wire, Copper, 600 V
#6 AWG
13,644
SCLF
2002
50
Street Lighting Wire, Copper, 600 V
#6 AWG
18,000
SCLF
2001
50
Street Lighting Wire, Copper, 600 V
#6 AWG
18,000
SCLF
2000
50
Street Lighting Wire, Copper, 600 V
#6 AWG
18,000
SCLF
1997
50
Street Lighting Wire, Copper, 600 V
#6 AWG
44,750
SCLF
1990
50
Street Lighting Wire, Copper, 600 V
#6 AWG
15,000
SCLF
1960
50
Flood Light, Metal Halide on power pole
1000 W
101
Ea
1980
20
Flood Light, HPS on power pole
250 W
157
Ea
1960
20
Street Light, Metal Halide
100 W
90
Ea
2007
20
Street Light, Metal Halide
100 W
26
Ea
2006
20
Street Light, Metal Halide
100 W
59
Ea
2005
20
Street Light, Metal Halide
100 W
70
Ea
2004
20
Street Light, Metal Halide
100 W
79
Ea
2001
20
Street Light, Metal Halide
175 W
81
Ea
1997
20
Street Light, Metal Halide
100 W
42
Ea
1960
20
Street Light, Metal Halide
100 W
17
Ea
1977
20
Street Light, HPS
150 W
24
Ea
2000
20
Street Light, HPS
250 W
36
Ea
2002
20
Street Light, HPS
250 W
24
Ea
2000
20
Street Light, HPS
400 W
24
Ea
2000
20
Street Light, HPS on power pole
150 W
60
Ea
1990
20
Street Light, HPS on power pole
250 W
60
Ea
1990
20
Street Light, HPS on power pole
400 W
59
Ea
1990
20
Light Pole, Steel
15'
90
Ea
2007
35
Light Pole, Steel
15'
26
Ea
2006
35
Light Pole, Steel
15'
59
Ea
2005
35
Light Pole, Steel
15'
70
Ea
2004
35
Light Pole, Steel
15'
79
Ea
2001
35
Light Pole, Steel
15'
81
Ea
1997
35
Light Pole, Steel
15'
28
Ea
1960
35
Light Pole, Steel
25’
36
Ea
2002
35
Light Pole, Steel
25’
72
Ea
2000
35
Pole Arm, Steel
6'
17
Ea
1977
35
Pole Arm, Steel
6'
36
Ea
2002
35
Pole Arm, Steel
6'
24
Ea
2000
35
Pole Arm, Steel
6'
24
Ea
2000
35
Pole Arm, Steel
6'
24
Ea
2000
35
Pole Arm, Steel
6'
60
Ea
1990
35
Pole Arm, Steel
6'
60
Ea
1990
35
Pole Arm, Steel
6'
59
Ea
1990
35
Pole Arm, Steel
6'
14
Ea
1960
35
Pole Base, Concrete
18” x 3’
90
Ea
2007
60
Pole Base, Concrete
18” x 3’
26
Ea
2006
60
Pole Base, Concrete
18” x 3’
59
Ea
2005
60
Pole Base, Concrete
18” x 3’
70
Ea
2004
60
Pole Base, Concrete
18” x 3’
36
Ea
2002
60
Pole Base, Concrete
18” x 3’
79
Ea
2001
60
Pole Base, Concrete
18” x 3’
81
Ea
1997
60
Main Substation Bypass Switch
15 kV
1
Ea
2008
35
Main Substation Bypass Switch
15 kV
7
Ea
1972
35
Main Substation CT Metering, 15 kV
400 A
1
Ea
2008
20
Main Substation CT Metering, 15 kV
400 A
7
Ea
2007
20
Main Substation Recloser
15 kV
1
Ea
2008
35
Main Substation Recloser
15 kV
7
Ea
1972
35
Substation Bus bar Structure, Steel
Medium
1
Ea
1972
50
Sector/Terminal Boxes, 4-way
15 kV
14
Ea
2008
35
Sector/Terminal Boxes, 4-way
15 kV
13
Ea
2006
35
Sector/Terminal Boxes, 4-way
15 kV
11
Ea
2005
35
Sector/Terminal Boxes, 4-way
15 kV
33
Ea
2004
35
Sector/Terminal Boxes, 4-way
15 kV
25
Ea
2002
35
Sector/Terminal Boxes, 4-way
15 kV
21
Ea
2001
35
Sector/Terminal Boxes, 4-way
15 kV
8
Ea
2000
35
Sector/Terminal Boxes, 4-way
15 kV
9
Ea
1997
35
Sector/Terminal Boxes, 4-way
15 kV
3
Ea
1960
35
Fac. 1100 Vehicle Maintenance Shop Meter, Digital
400 A
1
Ea
1995
20
Fac. 1224 EMS Building/Terminal Bldg Meter, Digital
400 A
1
Ea
1995
20
Fac. 1225 Shop Weapon and Release Systems Meter, Digital
400 A
2
Ea
1995
20
Fac. 1320& 1322 LRS Meter, Analog
400 A
1
Ea
1995
20
Fac. 1330 Aircraft Corrosion Control Meter, Digital
400 A
2
Ea
1995
20
Fac. 1330 Meter, Digital
400 A
1
Ea
1995
20
Fac. 1333 Maintenance Dock Meter, Digital
400 A
1
Ea
1995
20
Fac. 1339 Jet Engine Maintenance Meter, Digital
400 A
1
Ea
1995
20
Fac. 1807 Horse Stables Meter, Analog
400 A
1
Ea
1995
20
Fac. 1807 Horse Stables Meter, Digital
400 A
1
Ea
1995
20
Fac. 195 Gunfighter Club Meter, Digital
400 A
1
Ea
1995
20
Fac. 196 MXG Headquarters Meter, Digital
400 A
1
Ea
1995
20
Fac. 198 Maintenance Hanger Meter, Digital
400 A
1
Ea
1995
20
Fac. 200 Maintenance Dock Meter, Digital
400 A
1
Ea
1995
20
Fac. 206Fire Crash/Rescue Station Meter, Digital
400 A
1
Ea
1995
20
Fac. 21 Maintenance Dock Meter, Digital
400 A
3
Ea
1995
20
Fac. 2201 Vet Clinic Meter, Digital
400 A
1
Ea
1995
20
Fac. 2215 Group Headquarters Meter, Digital
400 A
1
Ea
1995
20
Fac. 2312 Dorm Meter, Digital
400 A
1
Ea
1995
20
Fac. 2314 Dorm Meter, Digital
400 A
1
Ea
1995
20
Fac. 2318 Dorm Meter, Digital
400 A
1
Ea
1995
20
Fac. 2320 Dorm Meter, Digital
400 A
1
Ea
1995
20
Fac. 2371/2370 Gymnasium Meter, Digital
400 A
4
Ea
1995
20
Fac. 2412 Dorm Meter, Digital
400 A
1
Ea
1995
20
Fac. 2416 Dorm Meter, Digital
400 A
1
Ea
1995
20
Fac. 2422 Dorm Meter, Digital
400 A
1
Ea
1995
20
Fac. 2610 Base Supply Admin. Meter, Digital
400 A
1
Ea
1995
20
Fac. 2620 Wells Fargo Bank Meter, Digital
400 A
1
Ea
1995
20
Fac. 2621 Credit Union Meter, Digital
400 A
1
Ea
1995
20
Fac. 2700 Sales Store, Exchange Meter, Digital
400 A
1
Ea
1995
20
Fac. 2706 Commissary Meter, Digital
400 A
1
Ea
1995
20
Fac. 2706 Store, Commissary Meter, Digital
400 A
1
Ea
1995
20
Fac. 4401 Quest Meter, Analog
400 A
1
Ea
1995
20
Fac. 510 Comm. Squadron Meter, Digital
400 A
1
Ea
1995
20
Fac. 512 MPF Meter, Digital
400 A
1
Ea
1995
20
Fac. 512 Wing Headquarters Meter, Digital
400 A
1
Ea
1995
20
Fac. 6000 Hospital A Meter, Digital
400 A
1
Ea
1995
20
Fac. 6000 Hospital B Meter, Digital
400 A
1
Ea
1995
20
Fac. 920 Avionics Shop Meter -Digital
400 A
1
Ea
1995
20
MFH Capehart Meter, Digital
400 A
1
Ea
1995
20
MFH Dunes Meter, Analog
400 A
1
Ea
1995
20
MFH Eagle View Meter, Digital
400 A
1
Ea
1995
20
MFH Phase 3 Meter, Digital
400 A
1
Ea
1995
20

Notes:

A = amps

ACSR = Aluminum conductor steel reinforced

AWG = American Wire Gauge

EA = each

HPS = high pressure sodium kV = kilovolts kVA = kilovolt-amperes lf = linear feet

MCM = kcmil = thousand circular mils

MFH = military family housing MH = metal halide

Nom kVA = nominal kilovolt-amperes

OH = overhead

PH = phase

PVC = polyvinyl chloride

RGS = rigid galvanized steel

SCLF = single conductor linear feet

SF = square feet

V = volts

W = wire

JA1.2.2 Electric Distribution System Non-Fixed Equipment and Specialized Tools

Table 2 lists other ancillary equipment (spare parts) and Table 3 lists specialized vehicles and tools included in the purchase. Offeror shall field verify all equipment, vehicles, and tools prior to submitting a bid. Offeror shall make its own determination of the adequacy of all equipment, vehicles, and tools.

Table 2

Spare Parts

Electric Distribution System

Item
Make/Model
Description
Quantity
Remarks

None

Table 3

Specialized Vehicles and Tools

Electric Distribution System

Item
Make/Model
Description
Quantity
Remarks

None

JA1.2.3 Electric Distribution System Manuals, Drawings, and Records

Table 4 lists the manuals, drawings, and records that will be transferred with the system.

Table 4

Manuals, Drawings, and Records

Electric Distribution System

Item
Description
Quantity
Remarks
Site Plans
TIF image utility drawings
120
Updated 1995 (estimated)

JA1.3 Specific Service Requirements

Service requirements for this electric distribution system are as defined in the RFP Section C, Description/Specifications/Work Statement. The following requirements are specific to the base electric distribution system and are in addition to those found in Section C.

1. The Government will provide the electricity, natural gas, and water commodities and the wastewater collection required to operate and maintain the systems being privatized at no cost to the System Owner (SO). The Government will also provide any infrastructure necessary to connect the facilities required to operate and maintain the systems being privatized to electricity, natural gas, water, and wastewater collection services at no cost to the SO. If fuel oil or propane is required to operate emergency generators, purchase and supply of that fuel oil or propane will be the responsibility of the SO.

2. The Government reserves the right to underground some or all of the existing overhead lines at a future time. For price proposal purposes, the Offeror shall assume that when existing overhead lines require replacement, they will be replaced with overhead lines. If the Government exercises its right to underground these overhead lines that require replacement, an equitable adjustment will be accomplished to cover the difference in installation and maintenance costs between overhead and underground lines. To ensure the Government is afforded the opportunity to exercise this right, the System Owner shall consult and coordinate with the Government prior to replacement of any overhead electrical lines.

JA1.4 Current Service Arrangement

The base is supplied power from Idaho Electric Power Company with two separate overhead power lines. One enters the base from the Northwest and is rated at 138 kV; the other enters the base from the East and is rated at 69 kV. The approximate connected load on the 138 kV line is 26,880 kW and 10,400 kW on the 69 kV line. The power usage for the year 2008 was 45,736, 949 kWh. The main substation on the base consists of two separate substations that are adjacent to each other. One is owned by the utility company and the other is owned by the base. The utility substation provides power overhead to the base owned substation. The utility owns the overhead lines to the point where they connect to the substation busbars which are located inside the base owned substation. Both substations are fenced separately.

JA1.5 Metering

JA1.5.1 Existing Meters

Table 5 provides a list of the existing (at the time of contract award) meters that will be transferred to the SO. The SO shall provide meter readings for all meters listed below.

Table 5

Existing Meters

Electric Distribution System

Meter Location
Meter Size
Remarks
Fac. 1100 Vehicle Maintenance Shop
400A,
Digital
Fac. 1224 EMS Building/Terminal Bldg
400A
Digital
Fac. 1225 Shop Weapon and Release Systems (2)
400A
Digital
Fac. 1320& 1322 LRS
400A
Analog
Fac. 1330 Aircraft Corrosion Control (2)
400A
Digital
Fac. 1330 Meter
400A
Digital
Fac. 1333 Maintenance Dock
400A
Digital
Fac. 1339 Jet Engine Maintenance
400A
Digital
Fac. 1807 Horse Stables
400A
Digital
Fac. 1807 Horse Stables
400A
Analog
Fac. 195 Gunfighter Club
400A
Digital
Fac. 196 MXG Headquarters
400A
Digital
Fac. 198 Maintenance Hanger
400A
Digital
Fac. 200 Maintenance Dock
400A
Digital
Fac. 206Fire Crash/Rescue Station
400A
Digital
Fac. 21 Maintenance Dock (3)
400A
Digital
Fac. 2201 Vet Clinic
400A
Digital
Fac. 2215 Group Headquarter
400A
Digital
Fac. 2312 Dorm
400A
Digital
Fac. 2314 Dorm
400A
Digital
Fac. 2318 Dorm
400A
Digital
Fac. 2320 Dorm
400A
Digital
Fac. 2371/2370 Gymnasium (4)
400A
Digital
Fac. 2412 Dorm
400A
Digital
Fac. 2416 Dorm
400A
Digital
Fac. 2422 Dorm
400A
Digital
Fac. 2610 Base Supply Admin.
400A
Digital
Fac. 2620 Wells Fargo Bank
400A
Digital
Fac. 2621 Credit Union
400A
Digital
Fac. 2700 Sales Store, Exchange
400A
Digital
Fac. 2706 Commissary
400A
Digital
Fac. 2706 Store, Commissary
400A
Digital
Fac. 4401 Quest
400A
Analog
Fac. 510 Comm. Squadron
400A
Digital
Fac. 512 MPF
400A
Digital
Fac. 512 Wing Headquarters
400A
Digital
Fac. 6000 Hospital A
400A
Digital
Fac. 6000 Hospital B
400A
Digital
Fac. 920 Avionics Shop
400A
Digital
MFH Capehart
400A
Digital
MFH Dunes
400A
Analog
MFH Eagle View
400A
Digital
MFH Phase 3
400A
Digital

JA1.5.2 Required New Meters

The SO shall install and calibrate new meters as listed in Table 6.

Table 6

Required New Meters

Electric Distribution System

Meter Location
Meter Size
Remarks

None

JA1.6 Monthly Submittals

The SO shall provide the Government with monthly submittals for the following:

1. Outage Report. The SO’s monthly outage report will be prepared in the format proposed by the SO and accepted by the Contracting Officer. Outage reports shall be submitted by the 25th of each month for the previous month. Outage reports shall be submitted to:

Organization/Office Symbol:

366CES/CEOE

Address:

Mountain Home AFB, ID 89191-7260 Phone number:

(208) 828-3830

2. Meter Reading Report. The monthly meter reading report shall show the current and previous month readings for all meters. The SO’s monthly meter reading report will be prepared in the format proposed by the SO and accepted by the Contracting Officer. Meter reading reports shall be submitted by the 15th of each month for the previous month. Meter reading reports shall be submitted to:

Organization/Office Symbol:

366CES/CEOE

Address:

Mountain Home AFB, ID 89191-7260 Phone number:

(208) 828-3830 JA1.7 Energy-Savings Projects

The following projects listed in Table 7 have been implemented on the distribution system by the Government for energy conservation purposes.

Table 7

Energy-Savings Projects Electric Distribution System

Project Location
Project Description

None

JA1.8 Service Area

The current service area is defined as all areas within the Mountain Home AFB boundaries.

JA1.9 Off-Installation Sites

No off-installation sites are included in the sale of the Mountain AFB electric distribution system. Specifically excluded are the electric distribution facilities at GSU sites: Saylor Creek Gunnery Range, the Small Arms Range Annex, the C.J. Strike Dam Marina, Rattlesnake Radar Station, Middle Marker, Grasmere Electronic Combat Site, and Seneca Ground Wave Emergency Network Station.

JA1.10 Specific Transition Requirements

Table 8 provides a list of service connections and disconnections required upon transfer.

Table 8

Service Connections and Disconnections

Electric Distribution System

Location
Description

None

JA1.11 Initial System Deficiency Corrections (ISDC)

Table 9 provides a list of ISDC projects the Government has planned for this system. The Government recognizes these projects represent current deficiencies associated with the system. If the system is sold, the Government will not accomplish these projects. The SO shall determine the actual need and timing of any and all such projects.

Table 9

Initial System Deficiency Corrections

Electric Distribution System

Project Location
Project Description

None

JA1.12 Right of Access to the Utility System

No leased property was identified with the Electrical Distribution System.

JA1.12.1 Map of the Utility System

Maps from the Base Comprehensive Plan or other drawings show the known locations of the utility system and are available in the technical library at the base civil engineer organization. Portions of the utility system may not be fully shown on the map or maps. Any such failure to show the complete utility system on the map or maps shall not be interpreted as that part of the utility system being outside the Installation. The Installation is co-extensive with the entire linear extent of the utility system sold to Grantee (SO), whether or not precisely shown on the map or maps.

JA1.12.2 Lateral Extent of the Right-of-Access, and Points of Demarcation

JA1.12.2.1 Lateral Extent of Utility System Right-of-Access

Where the utility system is installed aboveground and/or underground, the Right-of-Access is defined as 26 feet wide, extending 13 feet on each side of the utility system, as installed.

JA1.12.2.2 Utility System Points of Demarcation

The point of demarcation (POD) is defined as the point on the utility system where ownership changes from the utility SO to the facility owner. Table 10 identifies the type and general location of the point of demarcation with respect to the facility for each scenario.

Table 10

Standard Points of Demarcation

Electric Distribution System

Point of Demarcation
Applicable Scenario
Sketch
POD is the secondary terminal of the transformer.
Pad-mounted transformer is located outside the structure with underground service to the structure. No meter exists.
POD is the load side of the meter.
Pad-mounted transformer is located outside the structure with underground service to the structure. Meter exists on the structure or between the structure and the pad-mounted transformer.
POD is the secondary terminal of the transformer.
Pad-mounted transformer is located outside the structure with underground service to the structure. Three-phase CT metered service exists.

Note: The meter, can, CTs, and associated wires are owned and maintained by the electric utility owner.

POD is the secondary terminal of the transformer (located inside the structure).
Transformer is located inside the structure. An isolation device is in place with or without a meter.

Note: Electric utility owner must be granted 24-hour access to transformer room.

SHAPE \* MERGEFORMAT

POD is the secondary terminal of the transformer (located inside the structure).
Transformer is located inside the structure. No isolation device exists.

Note: Electric utility owner must be granted 24-hour access to transformer room.

SHAPE \* MERGEFORMAT

POD is the load side of the meter.
Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. Electric meter is connected to the exterior of the structure.

Note: The meter, meter can, and weather head, are owned and maintained by the electric utility owner.

SHAPE \* MERGEFORMAT

POD is where the overhead conductor is connected to the weather head.
Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. No meter exists.
SHAPE \* MERGEFORMAT
POD is where the overhead conductor is connected to the weather head.
Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. A disconnect switch or junction box is mounted to the exterior of the structure and no meter exists.

SHAPE \* MERGEFORMAT

POD is where the overhead conductor is connected to the service entrance mast.

Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The water utility owner owns the service entrance mast and all wiring on the load side of the POD.

Electric power is provided to a water facility via an overhead service drop. This configuration could be found at facilities dedicated to the water utility such as a water well, pump station, or storage facility.

None

POD is at the secondary terminal of the transformer.

Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The water utility owner owns all wiring on the load side of the transformer.

Electric power is provided to a water facility via an underground service connection. This configuration could be found at facilities dedicated to the water utility such as a water well, pump station, or storage facility.

None

POD is where the overhead conductor is connected to the service entrance mast.

Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The wastewater utility owner owns the service entrance mast and all wiring on the load side of the POD.

Electric power is provided to a wastewater facility via an overhead service drop. This configuration could be found at facilities dedicated to the wastewater utility such as a lift station or wastewater treatment plant.

None

POD is the secondary terminal of the transformer.

Note: If an electric meter is present, or is to be installed, the owner of the electric distribution system on the installation is the owner and maintainer of the electric meter and the can, regardless of their location. The wastewater utility owner owns all wiring on the load side of the transformer.

Electric power is provided to a wastewater facility via an underground service connection. This configuration could be found at facilities dedicated to the wastewater utility such as a lift station or wastewater treatment plant.

None

PODs are where the secondary conductor is attached to the electric utility owner's pole and where the light fixture is attached to the electric utility owner's pole.
Government-owned secondary circuit and light fixture are attached to the electric utility owner's pole.
SHAPE \* MERGEFORMAT

WITHIN HOUSING AREAS

POD is the line side of the meter.

Residential structure.

Pad-mounted transformer is located outside the structure with underground service to the structure. Existing meter.

WITHIN HOUSING AREAS

POD is the line side of the service panel.

Residential structure.

Pad-mounted transformer is located outside the structure with underground service to the structure. No existing meter.

Note: If a meter is installed on the load side of the service panel in the future, then the POD becomes the line side of the meter.

WITHIN HOUSING AREAS

POD is the line side of the meter.

Residential structure.

Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. Electric meter is connected to the exterior of the structure. The owner of the residential structure owns the service mast.

SHAPE \* MERGEFORMAT

WITHIN HOUSING AREAS

POD is the line side of the disconnect switch or junction box.

Residential structure.

Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. A disconnect switch or junction box is mounted to the exterior of the structure and no meter exists. The owner of the residential structure owns the service mast.

SHAPE \* MERGEFORMAT

WITHIN HOUSING AREAS

POD is where the overhead conductor is connected to the weather head.

Residential structure.

Pole-mounted transformer is located outside the structure with overhead conductor attached to the structure. A disconnect switch or junction box is not mounted to the exterior of the structure, and no meter exists. The owner of the residential structure owns the service mast

Note: If a meter, disconnect switch, or junction box is installed in the future, then the POD becomes the line side of the meter, disconnect switch, or junction box.

SHAPE \* MERGEFORMAT

Table 11 lists anomalous “unique” points of demarcation that do not fit any of the above scenarios. These unique points of demarcation shall take precedence over the standard points of demarcation shown in Table 10.

TABLE 11

Unique Points of Demarcation

Electric Distribution System

Location
POD Description
Military Family housing with installed meter base without meter
MFH where meter base is installed but no meter has been installed. The POD is the line side of the meter base.
Main Substation
The connection of the utility-owned overhead line at the load side of the busbars in the base-owned substation
Airfield Lighting
The load side of the pad-mounted switch feeding the airfield lighting vault, Building 258
Facilities w/o meters
The supply or secondary side of the transformer feeding the facility
EMCS Equipment
The POD is the supply side of a connection to any EMCS device or meter that is part of the collective EMCS system.

JA1.12.3 Environmental Baseline Survey

The Air Force has determined that it is not required to conduct an EBS in regard to the sale of this utility system.

Structure

Service

Line

Point of Demarcation

Distribution Line

S P

Isolation

Device

Point of

Demarcation

Utility

Pole

Pole Mounted

Transformer

Meter

Disconnect or

Junction Box

Government-Owned

Secondary Circuit

Utility-Owned Pole

Government-Owned

Light Fixture

Points of Demarcation

Disconnect or

Junction Box

Point of

Demarcation

Isolation

Device

(Attachment J1 Template - 10 May 2009) Edited DD MMM Yy – Version xx J1-i (Attachment JA1 Electric Distribution System Template – SEPTEMBER 2009_REV_MAY 2010) User Edited: ver:08 05Oct10