Grit Room Force Main Replacement - Addendum 2.pdf

PDF 6 MB Posted

Attached to
Grit Room Force Main Replacement
Solicitation number
#ITB-WW-25-01
Issued by
Livingston County, Michigan

About this file

This document is Addendum No. 2 for the Grit Room Force Main Replacement project (ITB-WW-25-01) issued by the City of Brighton Wastewater Division on March 14, 2025. The addendum provides clarifications and additional information for the project, which involves replacing approximately 20 feet of force main pipes in the grit room. The document confirms the specifications of three existing flow meters (two 8-inch and one 6-inch) and notes that these meters will be purchased by the City of Brighton and provided to the contractor for installation. The addendum also specifies that new ductile iron pipe and pipe fittings will be coated with an epoxy coating system, though the newly installed flow meters will not require this coating.

The addendum serves to supplement the original project specifications, drawings, general conditions, and instructions to bidders. It answers questions raised during a pre-event meeting and includes an attachment providing information about the meters to assist bidders in determining the appropriate pipe fittings for installation. The document emphasizes that the information in the addendum should be considered as part of the contractors' proposals, ensuring that all bidders have the most up-to-date and comprehensive information about the project requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

420 S. Third St., Brighton, MI 48116 l 810-225-8001

City of Brighton

WASTEWATER DIVISION

March 14, 2025

Grit Room Force Main Replacement

#ITB-WW-25-01

ADDENDUM NO. 2

It is understood and accepted that the work of this Addendum shall supplement and form a part of the original Specifications, Drawings, General Conditions, Special Conditions, Instructions to Bidders, and all stipulations thereof.

This Addendum is issued prior to the receipt of bids and the intent thereof is to record and insert certain changes, additions, and clarifications of the contract documents. All items shall be considered in connection with the various Contractors’ Proposals.

This addendum answers ques ons raised at the pre-event mee ng. It also includes an a achment that provides informa on about the meters to assist bidders with determining the what pipe fi ngs are needed when installing them.

In order to perform the work on the force mains on the outside of the building approximately

20’ of pipe will need to be replaced with new duc le iron pipe.

There are currently 2 – 8” flow meters and 1 – 6” flow meter installed on the force main pipes in the grit room. A er discussion about meter size at the pre-bid mee ng we have confirmed the sizes of the current meters are correct. These flow meters will be purchased by the City of

Brighton and provided to the contractor for installa on.

New duc le iron pipe and pipe fi ngs will be coated with an epoxy coa ng system. The newly installed flow meters do not need to be coated with this epoxy coa ng system.

Product Data Sheet 00813-0300-4750, Rev CD

July 2024

Rosemount™ 8750W Magnetic Flowmeter System

■ Best in class value with performance, reliability, and diagnostics suited for monitoring applications

■ Optimized for general purpose, utility, water, and wastewater applications

■ Reliable all welded coil housing and lightweight sensor design rated to IP68

■ Available in 4–20 mA with HART®, FOUNDATION™ Fieldbus, Modbus® RS-485, Process Diagnostics, and SMART™ Meter

Verification to improve reliability and performance

■ Available with drinking water certifications

Product Selection Guide The Rosemount 8750W Magnetic Flowmetersensor is available in a flanged style and transmitter is available in remote and integral transmitter configurations to ensure compatibility with general purpose, utility, water, and wastewater applications.

Transmitter selection Transmitter General characteristics Field mount ■ Integral and remote configurations available

■ HART/Analog and Pulse outputs available

■ FOUNDATION™ Fieldbus and pulse output available

■ Modbus RS-485 and Pulse output available

■ Advanced Diagnostics available

■ LCD display, optional (with optional optical switch local operator interface)(1)

■ Three independent totalizers (A/B/C)

■ Two discrete channels (optional)

Wall mount ■ Wall mount configuration

■ HART/Analog and Pulse outputs available

■ Modbus RS-485 and Pulse output available

■ FOUNDATION™ Fieldbus and pulse output available

■ Advanced Diagnostics available

■ Local LCD display, optional (with optional 15 button tactile key pad(1))

■ Three independent totalizers (A/B/C)

■ Two discrete channels, optional

(1) HART or Modbus protocol only.

Contents Product Selection Guide Magmeter Diagnostics Magnetic flow meter sizing Ordering information Product specifications Product certifications Dimensional drawings

July 2024

2 Emerson.com/Rosemount

Sensor selection Table 1: Sensor Selection Sensor General characteristics Flanged ■ Flanged process connections Welded coil housing

■ ½-in. (15 mm) to 48-in. (1200 mm)

■ Standard, reference, and bullet-nose electrodes available

Selecting materials For guidance on selecting materials, refer to the Rosemount™ Magnetic Flowmeter Material Selection Guide (00816-0100-3033), available at www.emerson.com/rosemount.

Access information when you need it with asset tags Newly shipped devices include a unique QR code asset tag that enables you to access serialized information directly from the device. With this capability, you can:

■ Access device drawings, diagrams, technical documentation, and troubleshooting information in your MyEmerson account

■ Improve mean time to repair and maintain efficiency

■ Ensure confidence that you have located the correct device

■ Eliminate the time-consuming process of locating and transcribing nameplates to view asset information

Magmeter Diagnostics Rosemount diagnostics reduce cost & improve output by enabling new practices Rosemount Magnetic Flowmeters provide device diagnostics that detect and warn of abnormal situations throughout the life of the meter - from installation to maintenance and meter verification. With Rosemount Magnetic Flowmeter diagnostics enabled, plant availability and throughput can be improved, and costs through simplified installation, maintenance and troubleshooting can be reduced.

Table 2: Magnetic flowmeter diagnostics Diagnostic name Diagnostic category Product capability Basic diagnostics Grounding and Wiring Fault Installation Standard Tunable Empty Pipe Process Standard Electronics Temperature Meter Health Standard Coil Fault Meter Health Standard Transmitter Fault Meter Health Standard

July 2024

Rosemount 8750W Magnetic Flowmeter System 3 http://www.emerson.com/rosemount

Table 2: Magnetic flowmeter diagnostics (continued) Diagnostic name Diagnostic category Product capability Reverse Flow Process Standard Coil current Maintenance Standard Electrode saturation Process/Maintenance Standard Advanced diagnostics High Process Noise Process Suite 1 (DA1) Coated Electrode Detection Process Suite 1 (DA1) Commanded Smart Meter Verification Meter Health Suite 2 (DA2) Continuous Smart Meter Verification Meter Health Suite 2 (DA2) 4-20 mA Loop Verification(1) Installation Suite 2 (DA2)

(1) Available with HART output only.

Options for accessing diagnostics Rosemount Magmeter Diagnostics can be accessed through the Local Operator Interface (LOI), ProLink® III v3.1, a HART Field Communicator(1), and AMS® Suite: Intelligent Device Manager(1). Contact your local Rosemount representative to activate diagnostics or for diagnostic availability on existing transmitters.

Access diagnostics through the LOI for quicker installation, maintenance, and meter verification Rosemount Magnetic Flowmeter Diagnostics are available through the LOI to simplify maintenance.

Access diagnostics through ProLink III v. 3.0 (HART)/ProLink III v. 3.1 (HART, Modbus) Simplify maintenance and troubleshooting practices by utilizing ProLink III v3.0/v3.1 to access diagnostics and troubleshooting information, log variable data, run SMART Meter Verification, and print verification reports.

Access diagnostics through AMS Intelligent Device Manager(1) for the ultimate value The value of the diagnostics increases significantly when AMS Intelligent Device Manager is used. AMS Intelligent Device Manager provides a simplified screen flow and procedures for how to respond to the diagnostic messages.

Magnetic flow meter sizing Selecting the appropriate sensor size is an important step when considering a magnetic flow meter. The physical properties of the process fluid, as well as the fluid velocity should be considered. It may be necessary to select a flow sensor that is larger or smaller than the adjacent piping to ensure the fluid velocity is in the recommended flow range for the application.

Table 3: Sizing guidelines Application Velocity range (ft/s) Velocity range (m/s) Full Range 0 to 39 0 to 12 Preferred Service 2 to 20 0.6 to 6.1 Abrasive Slurries 3 to 10 0.9 to 3.1 Non-Abrasive Slurries 5 to 15 1.5 to 4.6

(1) Available with HART output only.

4 Emerson.com/Rosemount

Note Operation outside these guidelines may also give acceptable performance.

To convert flow rate to velocity, use the appropriate factor listed in Table 4 and the following equation:

Velocity = Flow Rate

Factor

Example: English units Example: SI units Magmeter Size: 4 in. (factor from Table 4 = 39.679) Normal Flow Rate: 300 GPM

Velocity = 300 (gpm)

39.679

Velocity = 7.56 ft/s

Magmeter Size: 100 mm (factor from Table 4 = 492.78) Normal Flow Rate: 800 L/min

Velocity = 800 (L/min)

492.78

Velocity = 1.62 m/s

Table 4: Line size vs. conversion factor Nominal line size—Inches (mm) Gallons per minute factor Liters per minute factor ½ (15) 0.947 11.762 1 (25) 2.694 33.455 1½ (40) 6.345 78.806 2 (50) 10.459 129.89 2 ½ (65) 14.923 185.33 3 (80) 23.042 286.17 4 (100) 39.679 492.78 5 (125) 62.356 774.42 6 (150) 90.048 1,118.3 8 (200) 155.93 1,936.5 10 (250) 245.78 3,052.4 12 (300) 352.51 4,378.0 14 (350) 421.70 5,237.3 16 (400) 550.80 6,840.6 18 (450) 697.19 8,658.6 20 (500) 866.51 10,761 24 (600) 1,253.2 15,564 30 (750) 2006.0 24,913 36 (900) 2,935.0 36,451 40 (1000) 3,652.1 45,357 42 (1050) 4,115.1 51,107 48 (1200) 5,407.6 67,159

Rosemount 8750W Magnetic Flowmeter System 5

Table 5: Line size vs. velocity/rate Nominal line size in inches (mm)

Minimum/maximum flow rate Gallons per minute Liters per minute at 0.04 ft/s (low-flow cutoff) at 1 ft/s (min range setting) at 3 ft/s at 39.37 ft/s (max range setting) at 0.012 m/s (low-flow cutoff) at 0.3 m/s (min range setting) at 1 m/s at 12 m/s (max range setting)

½ (15) 0.038 0.947 2.841 37.287 0.141 3.529 11.76 141.15 1 (25) 0.108 2.694 8.081 106.05 0.401 10.04 33.45 401.46 1½ (40) 0.254 6.345 19.04 249.82 0.946 23.64 78.81 945.67 2 (50) 0.418 10.459 31.38 411.77 1.559 38.97 129.89 1,558.7 2½ (65) 0.597 14.923 44.77 587.51 2.224 55.60 185.33 2,224.0 3 (80) 0.922 23.042 69.13 907.17 3.434 85.85 286.17 3,434.0 4 (100) 1.587 39.679 119.04 1,562.2 5.913 147.84 492.78 5,913.4 5 (125) 2.494 62.356 187.07 2,454.9 9.293 232.33 774.42 9,293.0 6 (150) 3.602 90.048 270.14 3,545.2 13.42 335.50 1,118.3 13,420 8 (200) 6.237 155.93 467.79 6,138.9 23.24 580.96 1,936.5 23,238 10 (250) 9.831 245.78 737.34 9,676.3 36.63 915.73 3,052.4 36,629 12 (300) 14.10 352.51 1,057.5 13,878 52.54 1,313.4 4,378.0 52,535 14 (350) 16.87 421.71 1,265.1 16,603 62.85 1,571.2 5,237.3 62,848 16 (400) 22.03 550.80 1,652.4 21,685 82.09 2,052.2 6,840.6 82,087 18 (450) 27.89 697.19 2,091.6 27,448 103.90 2,597.6 8,658.6 103,903 20 (500) 34.66 866.51 2,599.5 34,114 129.14 3,228.4 10,761 129,137 24 (600) 50.13 1,253.2 3,759.6 49,339 186.77 4,669.2 15,564 186,769 30 (750) 80.24 2,006.0 6,018.0 78,976 298.96 7,474.0 24,913 298,959 36 (900) 117.40 2,935.0 8,805.1 115,553 437.42 10,935 36,451 437,416 40 (1000) 146.09 3,652.1 10,956 143,785 544.29 13,607 45,357 544,286 42 (1050) 164.60 4,115.1 12,345 162,011 613.28 15,332 51,107 613,278 48 (1200) 216.30 5,407.6 16,223 212.898 805.91 20,148 67,159 805,908

Upstream and downstream piping To ensure specified accuracy over widely varying process conditions, it is recommended to install the sensor with a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane.

6 Emerson.com/Rosemount

Figure 1: Upstream and downstream straight pipe diameters

A. Five pipe diameters (upstream) B. Two pipe diameters (downstream) C. Flow direction

Installations with reduced upstream and downstream straight runs are possible. In reduced straight run installations, the meter may not meet accuracy specifications. Reported flow rates will still be highly repeatable.

Sensor process reference grounding In addition to grounding required by applicable safety/electrical standards or codes, a reliable ground path is required between the sensor and the process fluid. Optional grounding rings or process reference electrodes are available with the sensor to ensure proper grounding. See Table 5 and Table 6.

Ordering information Rosemount 8750W Magnetic Flowmeter Platform

The Rosemount 8750W Magnetic Flowmeter is available in a flanged sensor design. The sensors are fabricated from stainless and carbon steel and welded to provide a sealed coil housing that protects against moisture or other contaminants. Sizes range from ½ inch (15 mm) to 48 inch (1200 mm). The field mount transmitter has a die cast aluminum housing for excellent reliability. The wall mount transmitter features an easy to use operator interface. Both transmitter styles are available with advanced diagnostics to provide the best insight into the process and the meter's health.

Rosemount 8750W Magnetic Flowmeter System 7

Model code structure Figure 2: Guide to model code structure

A

8750W

L

B

D

C

M

D

T

E

M

C

N

A1

F

A

G

J

S

K

A

H

F

I

P

O

Z5 DA2 AX M4 BD G5 B6 R15 V1 Q4 HR7 WG YF

A Base model—Magnetic Flowmeter System (utility, water, and wastewater) B Sensor design revision I Lining material C Transmitter class J Electrode material D Transmitter mount K Electrode type E Transmitter power L Line size F Transmitter outputs M Flange type and material G Conduit entries N Flange rating H Sensor style O Options

Example model code with one selection out of each required category:

8750W D M T 1 A 1 F P S A 010 CA1 Z5 DA2 AX M4 BD G5 B6 R15 V1 Q4 HR7 WG YF

The starred (★) offerings represent the best delivery options.

Requirements Table 6: Requirements - select one from each available choice Code Description Transmitter class M Revision 4 electronics ★

0 Spare sensor, no transmitter Transmitter mount T Integral field mount ★

R Remote field mount ★

W Remote wall mount ★

Transmitter power 1 AC Power Supply (90–250 VAC, 50/60 Hz) ★

2 DC Power Supply (12–42 VDC) ★

0 Spare sensor, no transmitter Transmitter outputs A 4–20 mA output with digital HART protocol & scalable pulse output ★

F FOUNDATION™ Fieldbus & scalable pulse output ★

M Modbus RS-485 electronics, scalable pulse ★

0 Spare sensor, no transmitter

8 Emerson.com/Rosemount

Table 6: Requirements - select one from each available choice (continued) Code Description Conduit entries Code Type Integral mount quantity Remote mount quantity

1 ½–14 NPT 2 4 ★

2 M20–1.5 adapters 2 4 ★

4(1) ½–14 NPT, additional entry 3 5 5(1) M20–1.5, additional entry 3 5 0 Spare sensor, integral mount only, no transmitter N/A N/A Sensor style F Flanged ★

0 Spare transmitter, no sensor Lining material

T(2) PTFE ★

P(3) Polyurethane ★

N(4) Neoprene ★

0 Spare transmitter, no sensor Electrode material S 316L stainless steel ★

H Nickel alloy 276 (UNS N 10276) ★

0 Spare transmitter, no sensor Electrode type A 2 Measurement electrodes – standard ★

B(5) 2 Measurement electrodes – bulletnose ★

E 2 Measurement electrodes plus 1 reference electrode – standard ★

F(5) 2 Measurement electrodes plus 1 reference electrode – bulletnose ★

0 Spare transmitter, no sensor

Rosemount 8750W Magnetic Flowmeter System 9

Line size Liner availability(6)

PTFE code T Poly code P Neoprene code N 005 ½-in. (15 mm) ★

010 1-in. (25 mm) ★ ★ ★

015 1½-in. (40 mm) ★ ★ ★

020 2-in. (50 mm) ★ ★ ★

025 2 ½-in. (65 mm) ★ ★

030 3-in. (80 mm) ★ ★ ★

040 4-in. (100 mm) ★ ★ ★

050 5-in. (125 mm) ★ ★

060 6-in. (150 mm) ★ ★ ★

080 8-in. (200 mm) ★ ★ ★

100 10-in. (250 mm) ★ ★ ★

120 12-in. (300 mm) ★ ★ ★

140 14-in. (350 mm) ★ ★ ★

160 16-in. (400 mm) ★ ★ ★

180 18-in. (450 mm) ★ ★ ★

200 20-in. (500 mm) ★ ★ ★

240 24-in. (600 mm) ★ ★ ★

300 30-in. (750 mm) ★ ★ ★

360 36-in. (900 mm) ★ ★ ★

400 40-in. (1000 mm) ★

420 42-in. (1050 mm) ★ ★

480 48-in. (1200 mm) ★ ★

000 Spare transmitter, no sensor Flange type - see Table 8 for line size vs. flange type and rating C Slip-on, raised-face, carbon steel ★

S Slip-on, raised-face, 304/304L SST ★

F Slip-on, flat-face, carbon steel G Slip-on, flat-face, 304/304L SST 0 Spare transmitter, no sensor

10 Emerson.com/Rosemount

Flange rating - see Table 8 for line size vs. flange type and rating A1 ASME B16.5, Class 150 A3 ASME B16.5, Class 300 AD AWWA C207Class D; line size 30-in. and above; flat face flange only AE AWWA C207Class E; line size 30-in. and above; flat face flange only

DD EN1092-1, PN10

DE EN1092-1, PN16

DF EN 1092-1, PN25

DH EN 1092-1, PN40

GD GB/T9119, PN10

GE GB/T9119, PN16

GH GB/T9119, PN40

JP JISB2220, 10K

JR JISB2220, 20K

KU AS4087, PN16

KW AS4087, PN21

KY AS4087, PN35

TK AS2129, Table D TL AS2129, Table E 00 Spare transmitter, no sensor

(1) Not available with the wall mount transmitter.

(2) Available in ½ - to 36-in. (15 mm to 900 mm) line sizes.

(3) Available in line sizes 1- to 36-in., 42-in., and 48-in. (25 mm to 900 mm, 1050 mm, and 1200 mm) line sizes.

(4) Available in line sizes 1- to 48-in. (25 mm to 1200 mm) line sizes.

(5) Not available in ½-in. (15mm).

(6) In the Line size section, the starred (★) offerings represent available liner based on line size. Consult factory for additional Flange

Type/Rating sensor availability.

Options Note These are not required, but they must be included in the model number if desired.

Rosemount 8750W Magnetic Flowmeter System 11

Table 7: Rosemount 8750W options

Hazardous area certifications -(1) Ordinary Locations - (no code required) ★

Z5 US Approvals, Class I Div 2, Non-Incendive and Dust for Non-Flammable Fluids ★

Z6 Canadian Approvals, Class I Div 2, Non-Incendive and Dust for Non-Flammable Fluids ★

ND ATEX Dust ★

Z1(2) ATEX Non-Sparking and Dust for Non-Flammable Fluids ★

NF IECEx Dust ★

Z7(2) IECEx Non-Sparking and Dust for Non-Flammable Fluids ★

Z2(2) INMETRO Non-Sparking and Dust for Non-Flammable Fluids ★

Z3(2) NEPSI Non-Sparking and Dust for Non-Flammable Fluids ★

Advanced diagnostics DA1 Process Diagnostics, High Process Noise Detection, and Electrode Coating ★

DA2 Smart Meter Verification ★

Discrete input/discrete output AX(3)(4) Two Discrete Channels (DI/DO 1, DO 2) ★

Display M4(4) LCD with Local Operator Interface ★

M5 LCD display only Certifications PD European Pressure Equipment Directive Certification (PED) ★

CR Canadian Registration Number (CRN) Certification BD ASME B31.3 Process Piping Standard DW(5) NSF Drinking Water Certification Grounding rings G1 316L stainless steel (Qty 2) ★

G2 Nickel alloy C-276; UNS N 10276 (Qty 2) G5 316L stainless steel (Qty 1) ★

G6 Nickel alloy C-276; UNS N 10276 (Qty 1) Miscellaneous C1 Custom Configuration (completed CDS form required with order) D1 High Accuracy Calibration (base ref accuracy 0.2% of rate) B6 316 SST Mounting Bracket with U-bolt Kit for 2-in. Pipe Mount P05(6) 5 Velocity Calibration Verification Report (1 point each at 2, 4, 6, 8, 10 ft/s)

12 Emerson.com/Rosemount

Table 7: Rosemount 8750W options (continued)

Increased submergence protection R05 Potted junction box with 50 feet of combo cable/cable gland for use in conduit R10 Potted junction box with 100 feet of combo cable/cable gland for use in conduit R15 Potted junction box with 150 feet of combo cable/cable gland for use in conduit R20 Potted junction box with 200 feet of combo cable/cable gland for use in conduit R25 Potted junction box with 250 feet of combo cable/cable gland for use in conduit R30 Potted junction box with 300 feet of combo cable/cable gland for use in conduit S05 Potted junction box with 50 feet of submersible combo cable/cable gland S10 Potted junction box with 100 feet of submersible combo cable/cable gland S15 Potted junction box with 150 feet of submersible combo cable/cable gland S20 Potted junction box with 200 feet of submersible combo cable/cable gland S25 Potted junction box with 250 feet of submersible combo cable/cable gland S30 Potted junction box with 300 feet of submersible combo cable/cable gland Special paint V1 Coal tar paint (submersible/direct burial) Quality certificates Q4 Calibration certificate per ISO 10474 3.1/EN 10204 3.1 Q8 Material traceability per ISO 10474 3.1/EN 10204 3.1 Revision configuration HR7 HART Revision 7 Witness inspection WG Witness Inspection Quick Start Guide language YF French ★

YG German ★

YI Italian ★

YM Chinese (Mandarin) ★

YP Portuguese (Brazil) ★

YR Russian ★

YS Spanish ★

(1) CSA (C/US) marked, CE marked, EAC marked and C-tick marked.

(2) DC power only.

(3) Requires Conduit Entry code 4 or 5 when ordered with field mount transmitter.

(4) Not available with FOUNDATION Fieldbus (output code F).

(5) NSF drinking water certification is available with the PTFE liner in line sizes 0.5- to 36-in (15 mm to 900 mm) and the polyurethane liner in line sizes 4 to 36-in., 42-in., and 48-in. (80 mm to 900 mm, 1050 mm, and 1200 mm).

(6) Available for ½ - to 24-in (15 mm to 600 mm) at velocities 2, 4, 6, 8, 10 ft/s; 30-in. (700 mm) at velocities 1, 2, 3, 4, 6, 8 ft/s; 36-in.

(900 mm) at velocities 1, 2, 3, 4, 5, 6 ft/s; 40- to 48-in. (1000 mm to 1200 mm) not available.

Rosemount 8750W Magnetic Flowmeter System 13

Table 8: Slip on flange options by line size Flange code and rating

A1 A3 AD AE DD DE DF DH GD GE GH JP JR KU KW KY TK TL

Size code

A

SM

E Cl as s 1

A

SM

E Cl as s 3

AW

W

A C la ss

D

AW

W

A C la ss

E

EN

P

N

EN

P

N

EN

P

N

EN

P

N

G B/

T

PN

G B/

T

PN

G B/

T

PN

JI

S

K

JI

S

K

A S4

PN

A S4

PN

A S4

PN

A S2

Ta bl e D

A S2

Ta bl e E

005 ★ ★ ★ ★ ★ ★ ★ ★

010 ★ ★ ★ ★ ★ ★ ★ ★

015 ★ ★ ★ ★ ★ ★ ★ ★

020 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

025 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

030 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

040 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

050 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

060 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

080 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

100 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

120 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

140 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

160 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

180 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

200 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

240 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

300 ★ ★ ★ ★ ★ ★ ★

360 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

400 ★ ★ ★ ★ ★ ★ ★ ★ ★ ★

420 ★ ★

480 ★ ★ ★ ★ ★

14 Emerson.com/Rosemount

Ordering flowmeter equipment Ordering procedure To order, select the desired sensor and/or transmitter by specifying model codes from the ordering table.

For remote transmitter applications, note the cable specification requirements.

Standard configuration Unless the Configuration Data Sheet is completed, the transmitter will be shipped as follows:

Engineering units: ft/sec 4mA: 0 20mA: 30 Sensor size: 3-in.

Empty pipe: On Sensor calibration number: 1000005010000000

Integrally mounted transmitters are factory configured with the paired sensor size and appropriate calibration number.

Custom configuration (option code C1) If Option Code C1 is ordered, the Configuration Data Sheet (CDS) must be submitted at the time of order.

Standard tagging Instrument tags for the transmitter and sensors are as follows:

■ 316SST laser etched label, permanently attached

■ Main label:

Model string 8712EM: character height 0.060 in. (1.5 mm) 8732EM: character height 0.085 in. (2.1 mm) 8705, 8711, 8721: character height 0.065 in. (1.6 mm)

Tag name 1 line 21 characters, height 0.065 in. (1.6 mm)

■ Additional 316SST 'wire-on' tag available: 5 lines, 17 characters per line (3.2 mm height) Interconnecting cable Interconnecting cables are required to connect a remote mount transmitter to the sensor. When ordering cable, review the hazardous area approval requirements and the installation location requirements for proper cable selection.

■ Cables can be ordered as individual component cables or a combination coil drive/electrode cable.

■ Cables can be ordered as part of the transmitter model number or as a spare parts kit. Integrally mounted transmitters are factory wired and do not require additional interconnecting cables.

■ Individual component cables require equal lengths of coil drive cable and electrode cable and should be limited to less than 500 feet (152 m). Consult an Emerson Flow representative for lengths between 500-1000 feet (152-300 m).

■ Combination coil drive/electrode cable is only available for Ordinary Locations and should be limited to less than

330 feet (100 m).

Rosemount 8750W Magnetic Flowmeter System 15

Component cable kits Standard temperature – -4 °F to 167 °F (-20 °C to 75 °C) Cable kit # Description Component Alpha direct p/n Alpha equivalent 08732-0065-0001 (feet)

Kit, Component Cables, Std Temp, (includes Coil and Electrode)

Coil 518243 2442C Electrode 518245 2413C

08732-0065-0002 (meters)

Kit, Component Cables, Std Temp (includes Coil and Electrode)

Coil Not available Not available Electrode Not available Not available

08732-0065-0003 (feet)

Kit, Component Cables, Std Temp (includes Coil and I. S. Electrode)

Coil 518243 Not available I. S. Electrode 518244 Not available

08732-0065-0004 (meters)

Kit, Component Cables, Std Temp (includes Coil and I. S. Electrode)

Coil Not available Not available I.S. Electrode Not available Not available

Extended temperature – -58 °F to 257 °F (-50 °C to 125 °C) Cable kit # Description Component Alpha direct p/n Alpha equivalent 08732-0065-1001 (feet)

Kit, Component Cables, Ext Temp (includes Coil and Electrode)

Coil 840310 Not available Electrode 518189 Not available

08732-0065-1002 (meters)

Kit, Component Cables, Ext Temp (includes Coil and Electrode)

Coil Not available Not available Electrode Not available Not available

08732-0065-1003 (feet)

Kit, Component Cables, Ext Temp (includes Coil and I. S. Electrode)

Coil 840310 Not available I. S. Electrode 840309 Not available

08732-0065-1004 (meters)

Kit, Component Cables, Ext Temp (includes Coil and I. S. Electrode)

Coil Not available Not available I.S. Electrode Not available Not available

Combo cable kits Coil/electrode cable – -4 °F to 176 °F (-20 °C to 80 °C) Cable Kit #(1)

08732-0065-2001 (feet)

Kit, Combo Cable, Standard

08732-0065-2002 (meters) 08732-0065-3001 (feet)

Kit, Combo Cable, Submersible(2)

08732-0065-3002 (meters)

(1) Only available for Ordinary Locations.

(2) 80 °C dry/60 °C wet/33 ft continuous submergence.

16 Emerson.com/Rosemount

Product specifications Basic specifications The tables below outline some of the basic performance, physical, and functional specifications.

Table 9: Wall mount transmitter Specifications

Style Wall mount Base accuracy(1) 0.5% Standard 0.2% High Accuracy Option Mounting Remote Power supply Global AC or DC User interface LCD display with 15 button tactile keypad (optional)

LCD display only (optional) No display (standard)

Communication protocol HART with 4–20 mA FOUNDATION™ fieldbus Modbus RS-485

Diagnostics Basic, DA1, DA2 Sensor compatibility All Rosemount plus other manufacturers Detailed specifications Transmitter specifications Ordering information Ordering information

(1) For complete accuracy specifications, please refer to Transmitter functional specifications.

Table 10: Field mount transmitter specifications Style Field mount Base accuracy(1) 0.5% Standard 0.2% High Accuracy Option Mounting Integral or Remote Power supply Global AC or DC User interface LCD display with 4 Optical Switch LOI (optional)

LCD display only (optional) No display (standard)

Communication protocol HART FOUNDATION™ fieldbus Modbus RS-485

Diagnostics Basic, DA1, DA2 Sensor compatibility All Rosemount plus other manufacturers Detailed specifications Transmitter specifications Ordering information Ordering information

(1) For complete accuracy specifications, please refer to Transmitter functional specifications.

Rosemount 8750W Magnetic Flowmeter System 17

Table 11: Sensor specifications Style Flanged Base accuracy(1) 0.5% Standard 0.25% High Accuracy Option Line sizes ½-in. to 48-in. (15 mm to 1200 mm) Design features Standard Process Design Detailed specifications Sensor specifications Ordering information Ordering information

(1) For complete accuracy specifications, refer to the sensor detailed specifications.

Table 12: Lining Material Selection Liner material General characteristics PTFE Process temperature: 0 to +248 °F (-18 to +120 °C)

Polyurethane Process temperature: 0 to +140 °F (-18 to +60 °C) Typically applied in clean water

Neoprene Typically applied in water with chemicals, and sea water Process temperature: 0 to 176 °F (-18 to 80 °C)

Table 13: Electrode Material Electrode material General characteristics 316L Stainless Steel Good corrosion resistance

Good abrasion resistance Nickel Alloy 276

(UNS N10276)

Better corrosion resistance High strength

Table 14: Electrode Type Electrode type General characteristics Standard Measurement

Lowest cost Good for most applications

Measurement + Reference Electrode

Low cost grounding option especially for large line sizes If using a reference electrode, process fluid must have a minimum conductivity of 100 microSiemens/cm.

18 Emerson.com/Rosemount

Table 14: Electrode Type (continued) Electrode type General characteristics (Also see Table 15 and Table 16 for grounding options and installation)

Not recommended for electrolytic or galvanic corrosion applications

Bulletnose Extended head protrudes into the flow stream for self-cleaning Best option for coating processes

Table 15: Process Reference Options Grounding options General characteristics No Grounding Options (grounding straps)

Acceptable for conductive unlined pipe Grounding straps provided at no cost

Reference Electrode Same material as measurement electrodes Sufficient grounding option when process fluid conductivity is greater than 100 microSiemens/cm.

Not recommended in electrolysis applications, galvanic corrosion applications, applications where the electrodes may coat, or non-conductive pipe.

Grounding Rings Low conductivity process fluids Cathodic or electrolysis applications that may have stray currents in or around the process Variety of materials for process fluid compatibility

Table 16: Process Reference Installation Type of pipe Grounding straps Grounding rings Reference electrode Lining protectors Conductive unlined pipe Acceptable Not required Not required Not required Conductive lined pipe Not acceptable Acceptable Acceptable Acceptable Non-conductive pipe Not acceptable Acceptable Not recommended Acceptable

Transmitter specifications

Transmitter functional specifications Transmitter coil drive current 500 mA Flow rate range Capable of processing signals from fluids with velocities between 0.04 and 39 ft/s (0.01 to 12 m/s) for both forward and reverse flow in all sensor sizes. Full scale continuously adjustable between –39 and 39 ft/s (–12 to 12 m/s).

Conductivity limits Process liquid must have a conductivity of 100 microSiemens/cm (100 micromhos/cm) or greater.

Power supply

■ 90 - 250 VAC @ 50/60 Hz

■ 12 - 42 VDC

Rosemount 8750W Magnetic Flowmeter System 19

Line power fuses

■ 90 - 250 VAC systems:

— 2 amp quick acting

— Bussman AGC2 or equivalent

■ 12 - 42 VDC systems

— 3 amp quick acting

— Bussman AGC3 or equivalent

Power consumption

■ 90 - 250 VAC: 40 VA maximum

■ 12 - 42 VDC: 15 W maximum Switch-on current

■ At 250 VAC: Maximum 35.7 A (< 5 ms)

■ At 42 VDC: Maximum 42 A (< 5 ms) AC power supply requirements Units powered by 90 - 250 VAC have the following power requirements. Peak inrush is 35.7 A at 250 VAC supply, lasting approximately 1 ms. Inrush for other supply voltages can be estimated with: Inrush (Amps) = Supply (Volts) / 7.0 Figure 3: AC current requirements

0.12

0.14

0.16

0.18

0.20

0.22

0.24

110 130 150 170 B

190 210 230 250

A

A. Supply current (amps) B. Power supply (VAC)

20 Emerson.com/Rosemount

Figure 4: Apparent power

110 130 150 170 B

190 210 230 250

A

A. Apparent power (VA) B. Power supply (VAC)

DC power supply requirements Units powered by 12 VDC power supply may draw up to 1.2 A of current steady state. Peak inrush is 42 A at 42 VDC supply, lasting approximately 1 ms. Inrush for other supply voltages can be estimated with: Inrush (Amps) = Supply (Volts) / 1.0 Figure 5: DC current requirements

0.2 0.3 0.4 0.5 0.6 0.7

0.9 1.0 1.1 1.2

0.8

17 22 27 B

32 37 42

A

A. Supply current (amps) B. Power supply (VDC)

Ambient temperature limits

■ Operating:

— –58 to 140 °F (–50 to 60 °C) without LOI/Display

— –4 to 140 °F (–20 to 60 °C) with LOI/Display

— The LOI/Display will not be visible at temperatures below –4 °F (–20 °C).

■ Storage:

— –58 to 185 °F (–50 to 85 °C) without LOI/Display

— –22 to 176 °F (–30 to 80 °C) with LOI/Display

Humidity limits 0–95% RH to 140 °F (60 °C)

Rosemount 8750W Magnetic Flowmeter System 21

Altitude limits AC Input Voltage: Maximum 250 VAC – Up to 2000 meters ( 6,500 feet) AC Input Voltage: Maximum 150 VAC – Up to 4000 meters (13,000 feet) DC Input Voltage: No altitude limit Transient protection rating Built in transient protection that conforms to:

■ IEC 61000-4-4 for burst currents

■ IEC 61000-4-5 for surge currents

■ IEC 611185-2.2000, Class 3 up to 2 kV and up to 2 kA protection Turn-on time

■ 5 minutes to rated accuracy from power up

■ 5 seconds from power interruption Start-up time 50ms from zero flow Low flow cut-off Adjustable between 0.01 and 38.37 ft/s (0.003 and 11.7 m/s). Below selected value, output is driven to the zero flow rate signal level.

Overrange capability Signal output will remain linear until 110% of upper range value or 44 ft/s (13 m/s). The signal output will remain constant above these values. Out of range message displayed on LOI/Display and the Field Communicator.

Damping Adjustable between 0 and 256 seconds

Advanced diagnostics capabilities Basic

■ Ground/wiring fault

■ Self test

■ Transmitter faults

■ Pulse output test

■ Tunable empty pipe

■ Reverse flow

■ Coil circuit fault

■ Electronics temperature Process diagnostics (DA1)

■ High process noise

■ Electrode coating diagnostic Smart Meter Verification (DA2)

■ Smart Meter Verification (continuous or commanded)

■ 4-20 mA loop verification(1)

22 Emerson.com/Rosemount

Output signals Analog output adjustment (2)

4–20 mA, switch-selectable as internally or externally powered.

Analog loop load limitations

■ Internally powered 24 VDC max, 500 ohms max loop resistance

■ Externally powered 10.8 - 30 VDC max.

■ Loop resistance is determined by the voltage level of the external power supply at the transmitter terminals:

Figure 6: Analog loop load limitations

10. 8 30

C

B

A

A. Load (ohms) B. Power supply (volts) C. Operating region

■ Rmax = 31.25 (Vps–10.8)

■ Vps = power supply voltage (volts)

■ Rmax = maximum loop resistance (ohms)

The analog output is automatically scaled to provide 4 mA at lower range value and 20 mA at upper range value. Full scale continuously adjustable between -39 and 39 ft/s (-12 to 12 m/sec), 1 ft/s (0.3 m/s) minimum span.

HART Communications is a digital flow signal. The digital signal is superimposed on the 4–20 mA signal and is available for the control system interface. A minimum of 250 ohms loop resistance is required for HART communications.

Analog alarm mode High or low alarm signal is user-selectable via the Alarm switch on the front of the electronics. NAMUR-compliant alarm limits are software configurable and can be preset via CDS (C1). Individual diagnostic alarms are also software configurable. Alarms will drive the analog signal to the following mA values.

Low 3.75 mA Requires CDS (C1) High 22.60 mA Factory default NAMUR Low 3.5 mA Requires CDS (C1) NAMUR High 22.6 mA Requires CDS (C1)

(2) For transmitters with intrinsically safe outputs (option code B), power must be supplied externally.

Rosemount 8750W Magnetic Flowmeter System 23

FOUNDATION™ Fieldbus output Output signal Manchester-encoded digital signal that conforms to IEC 1158-2 and ISA

50.02 Scheduled Entries Seven (7) Links Twenty (20) Virtual Communications Relationships (VCRs)

One (1) predefined (F6, F7) Nineteen (19) configurable

FISCO compliant Reference appropriate 8732EM Approvals QSG for details

FOUNDATION™ fieldbus function blocks Table 17: Function block execution times Block Execution time (milliseconds) Resource (RB) — Transducer (TB) — Analog Input (AI) 15 Proportional/Integral/Derivative (PID) 20 Integrator (INT) 25 Arithemetic (AR) 25 Discrete Output (DO) 15

Transducer Block The transducer block calculates flow from the measured induced voltage. The calculation includes information related to the calibration number, line size, and diagnostics.

Resource Block The resource block contains physical transmitter information, including available memory, manufacturer identification, device type, software tag, and unique identification.

Backup Link Active Scheduler

(LAS)

The transmitter is classified as a device link master. A device link master can function as a Link Active Scheduler (LAS) if the current link master device fails or is removed from the segment. The host or other configuration tool is used to download the schedule for the application to the link master device. In the absence of a primary link master, the transmitter will claim the LAS and provide permanent control for the H1 segment.

Diagnostics The transmitter automatically performs continuous self-diagnostics. The user can perform on-line testing of the transmitter digital signal. Advanced simulation diagnostics are available. This enables remote verification of the electronics via a flow signal generator built into the electronics.

The sensor strength value can be used to view the process flow signal and provide information regarding filter settings.

Analog Input The AI function block processes the measurement and makes it available to other function blocks.

The AI function block also allows filtering, alarming, and engineering unit changes.

Arithmetic Block Provides pre-defined application-based equations including flow with partial density compensation, electronic remote seals, hydrostatic tank gauging, ratio control and others.

Proportional/ Integral/ Derivative

The PID function block provides a sophisticated implementation of the universal PID algorithm.

The PID function block features input for feed forward control, alarms on the process variable, and control deviation. The PID type (series or Instrument Society of America [ISA]) is user-selectable on the derivative filter.

Integrator The standard integrator block is available for totalization of flow.

Reverse Flow Detects and reports reverse flow Software Lockout A write-lock switch and software lockout are provided in the resource function block.

24 Emerson.com/Rosemount

Totalizer Non-volatile totalizer for net, gross, forward and reverse totals.

Discrete Output The DO function block processes a discrete setpoint and saves it to a specified channel to produce an output signal. The block supports mode control, output tracking, and simulation.

Modbus RS-485 output Transmitters with a Modbus output provide an RS-485 signal to a Modbus host system; data rates can be configured from 1200 baud to 115.2 kilobaud.

Scalable pulse frequency adjustment

■ 0-10,000 Hz, switch-selectable as internally or externally powered (3)

■ Pulse value can be set to equal desired volume in selected engineering units

■ Pulse width adjustable from 0.1 to 650 ms

■ Internally powered: Outputs up to 12 VDC(4)

■ Externally powered: Input 5 - 28 VDC Output testing Analog output test (4) Transmitter may be commanded to supply a specified current between 3.5 and 23 mA.

Pulse output test Transmitter may be commanded to supply a specified frequency between 1 and 10,000 Hz.(3)

Optional discrete output function (AX option) Externally powered at 5 - 28 VDC, 240 mA max, solid state switch closure to indicate either:

Reverse flow Activates switch closure output when reverse flow is detected.

Zero flow Activates switch closure output when flow goes to 0 ft/s or below low flow cutoff.

Empty pipe Activates switch closure output when an empty pipe condition is detected.

Transmitter faults Activates switch closure output when a transmitter fault is detected.

Flow limit 1, flow limit 2 Activates switch closure output when the transmitter measures a flow rate that meets the conditions established for this alert. There are two independent flow limit alerts that can be configured as discrete outputs.

Totalizer limit Activates switch closure output when the transmitter measures a total flow that meets the conditions established for this alert.

Diagnostic status Activates switch closure output when the transmitter detects a condition that meets the configured criteria of this output.

Optional discrete input function (AX option) Externally powered at 5 - 28 VDC, 1.4 - 20 mA to activate switch closure to indicate either:

Reset Totalizer A (or B or C) Resets Totalizer A (or B or C) value to zero.

Reset All Totals Resets all totalizer values to zero.

Positive Zero Return (PZR) Forces outputs of the transmitter to zero flow.

Security lockout Security lockout switch on the electronics board can be set to deactivate all LOI and HART-based communicator functions to protect configuration variables from unwanted or accidental change.

(3) For transmitters with intrinsically safe outputs (option code B), frequency range is limited to 0-5000 Hz and must be powered externally.

(4) For transmitters with intrinsically safe outputs (option code B), power must be supplied externally.

Rosemount 8750W Magnetic Flowmeter System 25

LOI lockout The display can be manually locked to prevent unintentional configuration changes. The display lock can be activated through a HART communication device, or by holding the UP arrow for 3 seconds and then following the on-screen instructions. When the display lock is activated, a lock symbol will appear in the lower right hand corner of the display.

To deactivate the display lock, hold the UP arrow for 3 seconds and follow the on-screen instructions.

Display auto lock can be configured from the LOI with the following settings: OFF, 1 Minute, or 10 Minutes.

Sensor compensation Rosemount sensors are calibrated in a flow lab at the factory and are assigned a calibration number. The calibration number must be entered into the transmitter, enabling interchangeability of sensors without calculations or a compromise in standard accuracy.

Transmitters and other manufacturers’ sensors can be calibrated at known process conditions or at the Rosemount NIST-Traceable Flow Facility. Transmitters calibrated on site require a two-step procedure to match a known flow rate.

This procedure can be found in the operations manual.

Performance specifications System specifications are given using the frequency output and with the unit at reference conditions.

Accuracy Includes the combined effects of linearity, hysteresis, and repeatability.

■ Standard system accuracy:

— ±0.5% of rate from 1 to 39 ft/s (0.3 to 12 m/s)

— ±0.005 ft/s (0.0015 m/s) from the low flow cutoff to 1 ft/s (0.3 m/s)

■ Optional high accuracy:(5)

— ±0.2% of rate ±1.0 mm/sec from 2.5 to 39 ft/s (0.8 to 12 m/s)

B

A

0.5

1.0

1.5

2.0.

2.5

0 3 (1)

(2)

(4)

(6)

(8)

(10)

0.5% 0.2%

A. Percentage of rate B. Velocity in ft/s (m/s)

Analog output effects Analog output has the same accuracy as frequency output plus an additional ±4 μA at room temperature.

Repeatability ±0.1% of reading Response time (analog output) 20 ms max response time to step change in input Stability ±0.1% of rate over six months

(5) For sensor sizes greater than 12 in. (300 mm), the high accuracy is ±0.50% of rate from 2.5 to 39 ft/sec (0.8 to 12 m/sec).

26 Emerson.com/Rosemount

Ambient temperature effect ±0.25% change over operating temperature range

Wall mount transmitter physical specifications Materials of construction Housing Low copper aluminum

Type 4X and IEC 60529 IP66, IP69 Paint Polyurethane coat (1.8 to 2.2 mils thick) Cover gaskets Silicone

Electrical connections Conduit entries ½–14 NPT or M20–1.5(1)

Terminal block screws 6-32 (No. 6) suitable for up to 14 AWG wire Safety grounding screws External stainless assembly, M5; internal 8-32 (No. 8)

(1) M20–1.5 connections provided with an adapter.

Vibration rating 2G per IEC 61298 Dimensions See Dimensional drawings.

Weight Wall mount transmitter Approximately 11 lbs. (5 kg)

Add 1 pound (0.5 kg) for LOI/Display.

Field mount transmitter physical specifications Materials of construction Standard housing Low copper aluminum

Type 4X and IEC 60529 IP66/67/68/69(1)

Paint Polyurethane coat (1.8 to 2.2 mils thick) Cover gasket Aluminum housing: Buna-N

(1) For applications where the transmitter may be submerged, even temporarily, contact Emerson Flow Technical Support for details.

Electrical connections Conduit entries Available in ½ inch NPT or M20. See ordering table footnotes for details.

Terminal block screws 6-32 (No. 6) suitable for up to 14 AWG wire Safety grounding screws External stainless assembly, M5; internal 8-32 (No. 8)

Vibration rating Integral mount 2G per IEC 61298 Remote mount 5G per IEC 61298

Rosemount 8750W Magnetic Flowmeter System 27

Dimensions See Dimensional drawings.

Weight Field mount transmitter only Aluminum Approximately 7 lbs. (3.2 kg)

Add 1 pound (0.5 kg) for LOI/Display.

Sensor specifications

Functional specifications Service Conductive liquids and slurries Line sizes ½ inch to 48 inch (15 mm to 1200 mm) Sensor coil resistance 2 - 20 Ω Interchangeability Rosemount 8750W sensors are interchangeable with 8750W transmitters. System accuracy is maintained regardless of line size or optional features. Each sensor nameplate has a sixteen-digit calibration number that can be entered into a transmitter during configuration.

Upper range limit

39.37 ft/s (12 m/s) Ambient temperature limits

■ –20 to 140 °F (–29 to 60 °C) standard carbon steel housing design Pressure limits See Process temperature limits.

Vacuum limits PTFE lining Full vacuum to +248 °F (+120 °C) through 4-in. (100 mm) line sizes.

Consult an Emerson Flow representative for vacuum applications with line sizes of 6 inches (150

mm) or larger.

All other standard sensor lining materials

Full vacuum to maximum material temperature limits for all available line sizes.

28 Emerson.com/Rosemount

Submergence protection IP68 The remote mount sensor is rated IP68 for continuous submergence. Tested to a depth of 33 ft. (10 m) for a period of 48 hours. IP68 rating requires that the transmitter must be remote mount. Installer must use IP68 approved cable glands, conduit connections, and/or conduit plugs.

Conductivity limits Process liquid must have a conductivity of 100 microSiemens/cm or greater. Consult an Emerson Flow representative for conductivity less than 100 microSiemens/cm.

Process temperature limits PTFE lining 0 to +248 °F (–18 to +120 °C) Polyurethane lining 0 to +140 °F (–18 to +60 °C) Neoprene lining 0 to +176 °F (–18 to +80 °C)

Notes

■ Carbon steel flanges for PED have a minimum process temperature limit of 32 °F (0 °C).

■ Sensors ordered with hazardous location ratings may have different maximum process temperature limits. The sensors must be installed and used as directed by the installation drawing number noted on the serial nameplate.

Table 18: Temperature vs. Pressure Limits for ASME B16.5 class flanges (1) Sensor temperature vs. pressure limits for ASME B16.5 class flanges ( ½ -in. to 24-in. line sizes)(2)

Flange material Flange rating Pressure @ -20 to 100 °F (-29 to 38 °C)

@ 200 °F (93 °C) @ 300 °F (149 °C) @ 350 °F (177 °C)

Carbon Steel Class 150 285 psi 260 psi 230 psi 215 psi Class 300 740 psi 680 psi 655 psi 645 psi

304 Stainless Steel Class 150 275 psi 235 psi 205 psi 190 psi Class 300 720 psi 620 psi 530 psi 500 psi

(1) Liner temperature limits must also be considered.

(2) 30-in. and 36-in. AWWA C207 Class D rated to 150 psi at atmospheric temperature.

Table 19: Temperature vs. Pressure Limits for AS2129 Table D and E flanges (1) Sensor temperature vs. pressure limits for AS2129 Table D and E flanges (4 inch to 24 inch line sizes) Flange Material Flange Rating Pressure

@ -29 to 50 °C (-20 to 122 °F)

@ 100 °C (212 °F) @ 150 °C (302 °F) @ 200 °C (392 °F)

Carbon Steel D 101.6 psi 101.6 psi 101.6 psi 94.3 psi E 203.1 psi 203.1 psi 203.1 psi 188.6 psi

(1) Liner temperature limits must also be considered.

Rosemount 8750W Magnetic Flowmeter System 29

Table 20: Temperature vs. Pressure Limits for EN 1092-1 flanges (1) Sensor temperature vs. pressure limits for EN 1092-1 flanges (15 mm to 600 mm line sizes) Flange material Flange rating Pressure

@ -29 to 50 °C (-20 to 122 °F)

@ 100 °C (212 °F) @ 150 °C (302 °F) @ 175 °C (347 °F)

Carbon Steel PN 10 10 bar 10 bar 9.7 bar 9.5 bar PN 16 16 bar 16 bar 15.6 bar 15.3 bar PN 40 40 bar 40 bar 39.1 bar 38.5 bar

304 Stainless Steel PN 10 9.1 bar 7.5 bar 6.8 bar 6.5 bar PN 16 14.7 bar 12.1 bar 11.0 bar 10.6 bar PN 40 36.8 bar 30.3 bar 27.5 bar 26.5 bar

(1) Liner temperature limits must also be considered.

Table 21: Temperature vs. Pressure Limits for GB/T 9119 Flanges (1) Temperature vs. Pressure Limits for GB/T 9119 Flanges Flange material Flange rating Pressure (Mpa)

≤ 20 °C @ 100 °C (212 °F) @ 150 °C (302 °F) Carbon steel Group 3E0 PN 10 1.00 0.92 0.88

PN 16 1.60 1.48 1.40

PN 40 4.00 3.71 3.52

304 SST Group 11E0 PN 10 1.00 0.90 0.81

PN 16 1.60 1.45 1.31

PN 40 4.00 3.63 3.27

(1) Liner temperature limits must also be considered.

Table 22: Temperature vs. Pressure Limits for JIS B2220 Flanges (1) Temperature vs. Pressure Limits for JIS B2220 Flanges Flange material Flange rating Pressure (Mpa)

≤ 50 °C (122 °F) @ 120 °C (248 °F) Carbon steel 10K 1.4 1.4 Carbon steel 10K 1.4 1.4 Carbon steel 10K 1.4 1.4

(1) Liner temperature limits must also be considered.

Physical specifications Emerson Rosemount magnetic flow meters are designed to the standards defined in ASME B31.3. This standard is used as the basis for all of our other pressure vessel certifications such as CRN and PED.

Non-wetted materials Sensor Pipe Type 304/304L SST Flanges A105 Carbon steel, Type 304/304L SST(1)

Coil housing Rolled carbon steel or 300 series stainless steel

30 Emerson.com/Rosemount

Paint Polyurethane coat (2.6 mils or greater)

(1) Ambient temperature low limit for A105 carbon steel is –20 °F (–29 °C) per ANSI B16.5. For colder ambient environments, stainless steel flanges must be used.

Process-wetted materials Lining PTFE, Polyurethane, Neoprene Electrodes 316L SST, Nickel Alloy 276 (UNS N10276)

Flat-faced flanges Flat-faced flanges are manufactured with full-face liners. Available in Neoprene only.

Process connections ASME B16.5 ■ Class 150 and Class 300: ½ inch to 24 inch (15 mm to 600 mm)

AWWA C207 ■ Class D: 30 inch to 48 inch (750 mm to 1200 mm)

■ Class E: 30 inch to 48 inch (750 mm to 1200 mm)

EN 1092-1 ■ PN10: 200 mm to 900 mm (8 inch to 36 inch)

■ PN16: 100 mm to 900 mm (4 inch to 36 inch)

■ PN16: 50 mm to 900 mm (2 inch to 36 inch)

■ PN25: 200 mm to 900 mm (8 inch to 36 inch)

■ PN40: 15 mm to 900 mm (½ inch to 36 inch)

AS2129 ■ Table D and Table E: 15 mm to 900 mm (½ inch to 36 inch)

AS4087 ■ PN16, PN21: 2 inch to 40 inch, 48 inch (8 inch excluded) (50 mm to 1000 mm, 1200 mm)

■ PN35: 2 inch to 36 inch (8 inch excluded) (50 mm to 900 mm)

GB/T9119 ■ PN10: 8 and 24, 36, 40, 48 inch (200 mm to 600 mm, 900 mm, 1000 mm, 1200 mm)

■ PN16: 4 and 24, 36, 40 inch (100 mm to 600 mm, 900 mm, 1000 mm)

■ PN40: ½ to 24 inch (15 mm to 600 mm)

JIS B2220 ■ 10K, 20K: ½ to 24 inch (15 mm to 600 mm)

Electrical connections Conduit entries Available with ½ inch NPT and M20 Terminal block screws 6-32 (No. 6) suitable for up to 14 AWG wire Safety grounding screws External stainless assembly, M5; internal 8-32 (No. 8)

Process reference electrode (optional) A process reference electrode can be installed similarly to the…