This is a Pre-Demolition Hazardous Materials Survey Report prepared by NOVA Engineering and Environmental, LLC for Greene County Public Schools in Greensboro, Georgia. The survey was conducted on July 10 and July 15, 2021, to identify asbestos-containing material (ACM), lead-based paint (LBP), and hazardous building materials (HBM) at Greensboro Elementary School prior to its demolition. The 102,000 square-foot brick-framed school building was assessed in general accordance with AHERA guidelines and ASTM E2356-10 standards. Field services included bulk sampling of 92 samples containing 161 total layers of various building materials, including floor tile, mastic, caulking, insulation, and other components. Laboratory analysis using Polarized Light Microscopy (PLM) identified five samples indicating the presence of asbestos-containing material. The survey's findings and recommendations were prepared for the exclusive use of Greene County Public Schools and are intended to inform demolition planning and abatement procedures.
The survey identified three primary categories of asbestos-containing material requiring remediation: 9-inch floor tile containing 7 percent Chrysotile Asbestos, black mastic containing 5 percent Chrysotile Asbestos, and east hall door frame caulking containing 4 percent Chrysotile Asbestos. Lead-based paint and lead-containing paint were identified on painted surfaces of wood windows, trim, baseboards, and metal doors, frames, and beams throughout the facility. Additional hazardous building materials inventoried include fluorescent lighting with ballasts, emergency exit signs, fire extinguishers, HID and LED lighting, HVAC units, refrigeration units, water fountains, electric thermostats, and facility maintenance chemicals. The report notes that the survey represents a limited inquiry and does not wholly eliminate uncertainty regarding potential contamination. NOVA's assessment is based on visual evaluation of readily accessible areas, and the report may not be disclosed to or relied upon by third parties without express written consent from Greene County Public Schools.
Text of this file
REPORT OF PRE-DEMOLITION
ASBESTOS CONTAINING MATERIAL
SURVEY, LEAD BASED PAINT
SURVEY, AND HAZARDOUS
BUILDING MATERIAL INVENTORY
Greensboro Elementary School Greensboro, Greene County, Georgia
PREPARED FOR:
Greene County Public Schools 101 East Third Street Greensboro, Georgia 30642
NOVA Project Number: 3021105
August 23, 2021
P R O F E S S I O N A L | P R A C T I C A L | P R O V E N
3 9 0 0 K e n n e s a w 7 5 P a r k w a y , S u i t e 1 0 0 , K e n n e s a w , G e o r g i a 3 0 1 4 4 t . 7 7 0 . 4 2 5 . 0 7 7 7 / f . 7 7 0 . 4 2 5 . 1 1 1 3 / u s a n o v a . c o m
August 23, 2021
Greene County Public Schools 101 East Third Street Greensboro, Georgia 306420
Attention: Mr. Ralph Boswell
Construction Manager
Subject: Report of Environmental Services
GREENSBORO ELEMENTARY SCHOOL
Greensboro, Greene County, Georgia
NOVA Project Number 3021105
Mr. Boswell:
NOVA Engineering and Environmental, LLC (NOVA) has completed the Pre-Demolition Asbestos
Containing Material (ACM) Survey, Lead Based Paint (LBP) Survey, and Hazardous Building
Material Inventory (HBMI) for Greensboro Elementary School located at 2834, 1441 Martin Luther
King Jr. Drive in Greensboro, Greene County, Georgia. We appreciate your selection of NOVA and for the opportunity to be of service on this project. Please feel free to contact us if you have any questions or if we may be of further assistance.
Sincerely, NOVA Engineering and Environmental, LLC
Curtis Moses Nickolaus DaSantos
Staff Professional Business Unit Manager
Environmental Services Environmental Services AHERA No. 18456 AHERA No. 18557 EPA Lead Inspector No. 1969 EPA Lead Inspector No. 1892
TABLE OF CONTENTS
1.0 SUMMARY
1.1 ASBESTOS CONTAINING MATERIAL
1.2 LEAD BASED PAINT & LEAD CONTAINING PAINT
1.1 HAZARDOUS BUILDING MATERIAL
2.0 INTRODUCTION
2.1 DESCRIPTION OF SUBJECT PROPERTY
2.2 PURPOSE
2.3 LIMITATIONS
2.4 USER RELIANCE
3.0 ASBESTOS CONTAINING MATERIAL
3.1 FIELD AND LABORATORY SERVICES
3.2 ASBESTOS ABATEMENT
4.0 LEAD BASED PAINT & LEAD CONTAINING PAINT
4.1 DEFINITIONS
4.2 FIELD AND LABORATORY SERVICES
4.3 LEAD ABATEMENT ACTIVITIES
5.0 HAZARDOUS BUILDING MATERIAL INVENTORY
5.1 FIELD SERVICES
5.2 HAZARDOUS BUILDING MATERIAL INVENTORY
5.3 HAZARDOUS BUILDING MATERIAL INVENTORY CONCLUSIONS
LIST OF APPENDICES
APPENDIX A – SAMPLE LOCATION PLAN
APPENDIX B – LABORATORY ANALYTICAL DATA & XRF DATA
APPENDIX C – PERSONNEL QUALIFICATIONS
APPENDIX D – QUALIFICATIONS OF CONCLUSIONS
Greensboro Elementary School August 23, 2021
Greene County Public Schools NOVA Project Number 3021105
1.0 SUMMARY
NOVA Engineering and Environmental, LLC. (NOVA) has completed the Pre-Demolition Asbestos
Containing Material (ACM) Survey, Lead Based Paint (LBP) Survey, and Hazardous Building
Material Inventory (HBMI) for Greensboro Elementary School located at 2834, 1441 Martin
Luther King Jr. Drive in Greensboro, Greene County, Georgia (Subject Property). Field activities were performed on July 10 and July 15, 2021.
A brief summary of our findings is presented below. This summary is provided for convenience and should not be substituted for review of the full report, including all attachments as provided herein.
1.1 ASBESTOS CONTAINING MATERIAL
During this study, ninety-two (92) samples (containing 161 total layers) of floor tile, mastic, glue, cove base, joint compound, caulking material, grout, mortar, brick, Thermal System Insulation (TSI), cement, vapor barrier, plaster, ceiling tile, glue dots, leveler, fire curtains, tread glue, wallboard, fire stop, floor sheeting, roof field layers, roof flashing, and roof penetration cement were analyzed by NOVA using Polarized Light
Microscopy (PLM) with five (5) analyzed samples indicating Asbestos Containing
Material (ACM). A sample location plan is included in Appendix A of this Report.
Below is a summary of the Asbestos Containing Material identified at the Subject Property:
9-Inch Floor Tile
• A total of two (2) samples of the 9-inch floor tile located at the Subject Property indicated >1% asbestos (7% Chrysotile Asbestos). Consequently, we believe all of the 9-inch floor tile located at the Subject Property should be considered Asbestos
Containing Material (ACM).
Black Mastic
• A total of two (2) samples of the black mastic located at the Subject Property indicated >1% asbestos (5% Chrysotile Asbestos). Consequently, we believe all of the black mastic located at the Subject Property should be considered Asbestos
Greensboro Elementary School August 23, 2021
Frame Caulking
• A total of one (1) sample of the east hall door frame caulking located at the Subject
Property indicated >1% asbestos (4% Chrysotile Asbestos). Consequently, we believe all of the door frame caulking that has not been identified as non-asbestos containing located at the Subject Property, should be considered Asbestos
The Occupational Safety and Health Administration (OSHA) Asbestos Standard for
Construction Industry 29 CFR 1926.1101 regulates workplace exposure to asbestos.
OSHA does not define Asbestos Containing Material on asbestos content. Any detectable asbestos, even if <1%, makes it asbestos for purposes of complying with
OSHA regulations to determine worker exposure. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc). The OSHA standard classifies construction and maintenance activities, which could disturb ACM, and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. In addition to worker protection, the mean and methods necessary for ACM abatement are the sole responsibility of the abatement contractor.
A complete list of suspected ACM samples obtained is shown in the laboratory report
(included in Appendix B).
1.2 LEAD BASED PAINT & LEAD CONTAINING PAINT
One hundred thirty-six (136) X-ray fluorescence (XRF) analyzer readings were made by
NOVA throughout the interior of the Subject Property structure to determine the presence of Lead Based Paint (LBP).
Lead Based Paint
Lead Based Paint (LBP) is defined as a paint or varnish containing lead at a concentration >0.5% by weight when determined by laboratory analysis. LBP is also defined by HUD as 1.0 mg/cm2 when determined using an XRF analyzer.
• Painted surfaces of metal windows and columns between bricks located at the
Subject Property.
Greensboro Elementary School August 23, 2021
Lead Containing Paint
OSHA does not define Lead Based Paint based on lead content. Any detectable lead in a paint or varnish makes it lead paint for purposes of complying with OSHA regulations to determine worker exposure. Consequently, for purposes of this study, Lead
Containing Paint is considered any detectable level of lead.
The predominant LCP material identified by the NOVA survey include:
• Painted surfaces of wood windows, trim, and baseboards located at the Subject
Property.
• Painted surfaces of metal doors, frames, trim, and beams located at the Subject
1.1 HAZARDOUS BUILDING MATERIAL
NOVA surveyed potential Hazardous Building Material (HBM) that was reasonably observed at the Subject Property. Potential HBM observed at the Subject Property include fluorescent lighting, ballasts, emergency exit signs, fire extinguishers, HID lighting, LED
Lighting, HVAC units, Refrigeration unit, water fountains, electric thermostats, and miscellaneous facility cleaning/maintenance chemicals.
The names and locations of all the material identified in the HBMI are included in the table in Section 5.2 of this report.
Greensboro Elementary School August 23, 2021
2.0 INTRODUCTION
2.1 DESCRIPTION OF SUBJECT PROPERTY
The Subject Property is identified as Greensboro Elementary School located at 2834, 1441 Martin Luther King Jr. Drive in Greensboro, Greene County, Georgia (Subject
Property). Specifically, for the purposes of this Pre-Renovation Asbestos Containing
Material (ACM) Survey, Lead Based Paint (LBP) Survey, and Hazardous Building Material
Inventory (HBMI), the Subject Property consists of an approximately 102,000 square foot brick framed school building.
2.2 PURPOSE
As requested by Greene County Public Schools (CLIENT), the Pre-Demolition Asbestos
Containing Material Survey, Lead Based Paint Survey, and Hazardous Building Material
Inventory (HBMI) was performed in an effort to identify Asbestos-Containing Material
(ACM), Lead Based Paint (LBP), and Hazardous Building Material at the Subject
Property. This work has been performed in general accordance with applicable state and federal regulations, and routine industry practice.
ACM sampling was performed in general accordance with the Asbestos Hazard
Emergency Response Act (AHERA) guidelines and ASTM E2356-10,”Standard Practice for Comprehensive Building Asbestos Survey” as a Baseline Survey. Deviations from the Baseline Survey protocols include:
• Determination of ACM quantities were excluded from the scope of work
2.3 LIMITATIONS
NOVA has performed the Pre-Demolition Asbestos Containing Material Survey, Lead
Based Paint Survey, and Hazardous Building Material Inventory (HBMI), which is a limited inquiry into a property's environmental status and is not sufficient to discover every potential source of ACM, LBP, or Hazardous Building Material (HBM) of the property to be evaluated. No survey/sampling can wholly eliminate uncertainty regarding the potential ACM, LBP, or HBM in connection with a property. Performance of this practice is intended to reduce, but not eliminate, uncertainty regarding the potential for ACM, LBP, and HBM in connection with a property.
The level of inquiry is variable. Not every property will warrant the same level of assessment for ACM, LBP, and HBM.
Greensboro Elementary School August 23, 2021
Consistent with good commercial or customary practices, the appropriate level of assessment will be guided by the type of property subject to assessment, the intended use of the property, the expertise and risk tolerance of the CLIENT, and the information developed in the course of the assessment.
NOVA's findings, opinions, conclusions and recommendations are based on information obtained through visual assessment of surficial conditions in readily accessible areas.
It is possible that additional ACM, LBP, or HBM exist or may subsequently become known that may impact or change the assessment after NOVA's services are complete.
NOVA’s assessment represents our professional opinion, only. Therefore, NOVA cannot, under any circumstances, make a statement of warranty or guarantee, expressed or implied, that ACM, LBP, and HBM are limited to those that are discovered while we are performing the Sampling.
2.4 USER RELIANCE
NOVA’s Pre-Demolition Asbestos Containing Material Survey, Lead Based Paint Survey, and Hazardous Building Material Inventory, along with the findings and conclusions contained in the report, either in completed form, summary form, or by extraction, is prepared, and intended, for the sole use of Greene County Public Schools (CLIENT) and therefore may not contain sufficient information for other purposes or parties.
The CLIENT is the only intended beneficiary of this report. The contents of NOVA's report will continue to be the property of NOVA. NOVA's report may not be disclosed to, used by, or relied upon by, any person or entity other than the CLIENT without the express written consent of NOVA.
Authorization for disclosure to a third party or authorization for third-party reliance on a final report of any report will be considered by NOVA upon the written request of the
CLIENT. NOVA reserves the right to deny authorization to allow disclosure or reliance of
NOVA's report to third parties.
Greensboro Elementary School August 23, 2021
3.0 ASBESTOS CONTAINING MATERIAL
3.1 FIELD AND LABORATORY SERVICES
Mr. Curtis Moses, a NOVA professional and federal and state certified asbestos inspector, performed the field work for the Pre-Demolition Asbestos Containing Material
Survey at the Subject Property on July 10 and July 15, 2021.
3.1.1 ASBESTOS CONTAINING MATERIAL SAMPLING
The building area was visually assessed by NOVA to identify suspect ACM, which were then grouped into three categories according to their intended use:
• Surfacing Material such as sprayed-on or troweled fireproofing, acoustical and decorative insulation, textured “popcorn” finishes, paint, stucco, etc.
• Thermal System Insulation (TSI), such as pipe, boiler and storage tank insulation, and insulation on ducts, pumps, heat exchangers, and other equipment.
• Miscellaneous Material, such as floor and ceiling tiles, wallboard, asbestos-cement board, siding and other building material that did not fall into one of the previously mentioned categories.
Where applicable, material with similar texture, color and general appearance were considered homogeneous for sampling purposes, including visually similar material on different floors. NOVA’s assessment also included touching representative samples to determine friability, a mechanical classification defined as whether a material can be crumbled, pulverized, or reduced to powder by hand pressure.
Bulk samples were subsequently obtained in general accordance with the AHERA (40
CFR 763.86, Sampling) and ASTM E2356-10 procedures. The samples were placed in appropriate containers, and the containers sealed and labeled with a unique identification number. The samples were subsequently transported (following routine industry practices and chain-of-custody procedures) to EMSL Analytical, LLC (EMSL) for analysis.
The ACM samples were analyzed for asbestos using Polarized Light Microscopy (PLM) methods in accordance with EPA Method 600/R-93/116. Copies of the complete asbestos laboratory report and chain-of custody are included in Appendix B.
Using the results of the laboratory analysis and NOVA’s visual assessment, the asbestos containing building material can be further categorized into three groups:
Greensboro Elementary School August 23, 2021
• Friable ACM - Material means any material containing more than one percent (1%) asbestos as determined using the method specified in Appendix A, Subpart F, 40
CFR part 763 Section 1, Polarized Light Microscopy, that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.
• Category I Nonfriable ACM - Asbestos-containing packing, gaskets, resilient floor covering, and asphalt roofing products containing more than one percent (1%) asbestos as determined using the method specified in Appendix A, Subpart F, 40
CFR part 763, Section 1, Polarized Light Microscopy.
• Category II Nonfriable ACM - Any material, excluding Category I Nonfriable ACM, containing more than one percent (1%) asbestos as determined using the methods specified in Appendix A, Subpart F, 40 CFR part 763, Section 1, Polarized Light
Microscopy that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
During this study, ninety-two (92) samples (containing 161 total layers) of floor tile, mastic, glue, cove base, joint compound, caulking material, grout, mortar, brick, Thermal System Insulation (TSI), cement, vapor barrier, plaster, ceiling tile, glue dots, leveler, fire curtains, tread glue, wallboard, fire stop, floor sheeting, roof field layers, roof flashing, and roof penetration cement were analyzed by NOVA using Polarized Light
Microscopy (PLM) with five (5) analyzed samples indicating Asbestos Containing
Material (ACM). A sample location plan is included in Appendix A of this Report.
Below is a summary of the Asbestos Containing Material identified at the Subject Property:
9-Inch Floor Tile
• A total of two (2) samples of the 9-inch floor tile located at the Subject Property indicated >1% asbestos (7% Chrysotile Asbestos). Consequently, we believe all of the 9-inch floor tile located at the Subject Property should be considered Asbestos
Black Mastic
• A total of two (2) samples of the black mastic located at the Subject Property indicated >1% asbestos (5% Chrysotile Asbestos). Consequently, we believe all of the black mastic located at the Subject Property should be considered Asbestos
Greensboro Elementary School August 23, 2021
Frame Caulking
• A total of one (1) sample of the east hall door frame caulking located at the Subject
Property indicated >1% asbestos (4% Chrysotile Asbestos). Consequently, we believe all of the door frame caulking that has not been identified as non-asbestos containing located at the Subject Property, should be considered Asbestos
The Occupational Safety and Health Administration (OSHA) Asbestos Standard for
Construction Industry 29 CFR 1926.1101 regulates workplace exposure to asbestos.
OSHA does not define Asbestos Containing Material on asbestos content. Any detectable asbestos, even if <1%, makes it asbestos for purposes of complying with
OSHA regulations to determine worker exposure. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc). The OSHA standard classifies construction and maintenance activities, which could disturb ACM, and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. In addition to worker protection, the mean and methods necessary for ACM abatement are the sole responsibility of the abatement contractor.
A complete list of suspected ACM samples obtained is shown in the laboratory report
(included in Appendix B).
Determination of the actual quantities of ACM at all locations should be made by the abatement contractor during a site inspection prior to beginning abatement.
3.2 ASBESTOS ABATEMENT
Any component, which is similar in appearance to, and is in the general vicinity or similar application of samples identified as containing asbestos, as well as any other material not shown by proper sampling and analysis to be non-asbestos containing, should be handled as asbestos-containing material (ACM). As previously noted, determination of the actual quantities of ACM at all locations should be made by the contractor during a site inspection prior to beginning abatement.
ACM should be abated (removed) prior to disturbance by maintenance, renovation and/or demolition by a licensed asbestos abatement contractor and disposed at an approved solid waste disposal facility.
Abatement is highly regulated and consists of several parts. In addition to the demolition/renovation permit, a ten (10) day advance notification to the Georgia
Environmental Protection Division (GA-EPD) is required.
Greensboro Elementary School August 23, 2021
During abatement, third party monitoring is recommended to review if the asbestos is adequately managed and contained during the abatement process and to document clearance and re-occupancy criteria established for the project.
Most Clients also request an abatement management report. This report compiles pertinent data regarding the personnel, abatement, and asbestos disposal for liability management after the fact should there be concerns later from workers or others. The ten (10) day notice, abatement, third party oversight, and management report are not included with the authorized scope of work for this project, but we can provide these supplemental services, if desired. Please note that the means and methods necessary for ACM abatement, as well as worker protection and monitoring, are the sole responsibility of the abatement contractor.
Greensboro Elementary School August 23, 2021
4.0 LEAD BASED PAINT & LEAD CONTAINING PAINT
4.1 DEFINITIONS
concentration >0.5% by weight when determined by laboratory analysis, (1972, Lead
Based Paint Poison Prevention Act (LBPPPA)). LBP is also defined by HUD as 1.0 mg/cm2 when determined using x-ray fluorescence (XRF) analyzer. These concentrations are applicable for housing and child-care facilities; however, these concentration levels are also frequently used as targets in commercial projects to allow flexibility in future area usage.
Lead Containing Paint (LCP) was defined as a paint or varnish containing lead at a concentration >0.06% by weight (600 ppm) when determined by laboratory analysis, (1978, LBPPPA). In 2009, LCP was further defined as containing lead at a concentration
>0.009% by weight (90 ppm) for certain consumer products and residential use.
Please note that OSHA does not define Lead Based Paint based on lead content. Any detectable lead in a paint or varnish makes it lead paint for purposes of complying with
OSHA regulations to determine worker exposure. Consequently, for purposes of this study, Lead Containing Paint is considered any detectable lead.
4.2 FIELD AND LABORATORY SERVICES
Mr. Curtis Moses, a NOVA professional and EPA certified lead inspector, performed the field work for the Lead Based Paint Survey at the Subject Property on July 10 and
July 15, 2021.
One hundred thirty-six (136) X-ray fluorescence (XRF) analyzer readings were made by
NOVA throughout the interior of the Subject Property structure to determine the presence of Lead Based Paint (LBP).
4.2.1 LEAD BASED PAINT SAMPLING
Where applicable, material with similar texture, color and general appearance were considered homogeneous for sampling purposes, including visually similar material on different floors and/or different buildings.
NOVA’s XRF readings are presented below:
No. Time Units Component Substrate Side Condition Color Results Pb Error
1 7/10/2021 10:22 cps 7.42 0
2 7/10/2021 10:24 mg / cm ^2 calibration positive 1 0.1
Greensboro Elementary School August 23, 2021
No. Time Units Component Substrate Side Condition Color Results Pb Error
3 7/10/2021 10:24 mg / cm ^2 calibration positive 1.1 0.1
4 7/10/2021 10:25 mg / cm ^2 calibration positive 1 0.1
5 7/10/2021 10:26 mg / cm ^2 column metal A intact white negative <LOD 0.03
6 7/10/2021 10:27 mg / cm ^2 column metal A intact white negative <LOD 0.03
7 7/10/2021 10:27 mg / cm ^2 column metal A intact white negative <LOD 0.03
8 7/10/2021 10:27 mg / cm ^2 column concrete A intact white negative <LOD 0.03
9 7/10/2021 10:28 mg / cm ^2 column concrete A intact white negative <LOD 0.03
10 7/10/2021 10:28 mg / cm ^2 column concrete A intact white negative <LOD 0.03
11 7/10/2021 10:29 mg / cm ^2 door metal A intact black negative <LOD 0.03
12 7/10/2021 10:29 mg / cm ^2 door metal A intact black negative <LOD 0.03
13 7/10/2021 10:29 mg / cm ^2 window metal A intact black negative <LOD 0.03
14 7/10/2021 10:30 mg / cm ^2 wall brick A intact red negative <LOD 0.03
15 7/10/2021 10:30 mg / cm ^2 wall concrete A intact red negative <LOD 0.03
16 7/10/2021 10:31 mg / cm ^2 ceiling concrete A intact green negative <LOD 0.03
17 7/10/2021 10:31 mg / cm ^2 ceiling concrete A intact green negative <LOD 0.03
18 7/10/2021 10:33 mg / cm ^2 wall concrete D intact red negative <LOD 0.03
19 7/10/2021 10:33 mg / cm ^2 wall brick D intact red negative <LOD 0.03
20 7/10/2021 10:34 mg / cm ^2 door metal D intact brown negative <LOD 0.03
21 7/10/2021 10:34 mg / cm ^2 door metal D intact brown negative <LOD 0.03
22 7/10/2021 10:34 mg / cm ^2 ceiling metal D intact brown negative <LOD 0.03
23 7/10/2021 10:34 mg / cm ^2 ceiling metal D intact brown negative <LOD 0.03
24 7/10/2021 10:35 mg / cm ^2 riser metal C intact red negative <LOD 0.03
25 7/10/2021 10:36 mg / cm ^2 riser metal C intact red negative <LOD 0.68
26 7/10/2021 10:36 mg / cm ^2 rail metal C intact red negative <LOD 0.03
27 7/10/2021 11:44 mg / cm ^2 rail metal C intact red negative <LOD 0.03
28 7/10/2021 12:37 mg / cm ^2 wall brick C intact gray negative <LOD 0.03
29 7/10/2021 12:38 mg / cm ^2 wall brick C intact gray negative <LOD 0.03
30 7/10/2021 12:39 mg / cm ^2 door metal C intact blue negative <LOD 0.03
31 7/10/2021 12:39 mg / cm ^2 door metal C intact blue negative 0.1 0.04
32 7/10/2021 12:41 mg / cm ^2 door metal D intact blue negative <LOD 0.03
33 7/10/2021 12:41 mg / cm ^2 door metal D intact blue negative 0.11 0.07
34 7/10/2021 12:41 mg / cm ^2 window metal D intact blue negative <LOD 0.03
35 7/10/2021 12:42 mg / cm ^2 window metal D intact blue positive 3 0.4
36 7/10/2021 13:25 mg / cm ^2 window metal D intact blue positive 1.3 0.1
37 7/10/2021 13:33 mg / cm ^2 trim brick D intact pink negative <LOD 0.03
38 7/10/2021 13:33 mg / cm ^2 trim brick D intact pink negative <LOD 0.03
39 7/10/2021 13:33 mg / cm ^2 trim brick D intact pink negative <LOD 0.03
40 7/10/2021 13:46 mg / cm ^2 trim metal D intact yellow negative <LOD 0.6
41 7/10/2021 13:46 mg / cm ^2 trim metal D intact yellow negative <LOD 0.6
42 7/10/2021 13:47 mg / cm ^2 trim metal D intact yellow negative <LOD 0.03
43 7/10/2021 13:48 mg / cm ^2 trim metal D intact yellow negative <LOD 0.03
44 7/10/2021 14:24 mg / cm ^2 calibration metal D intact yellow positive 1 0.1
Greensboro Elementary School August 23, 2021
No. Time Units Component Substrate Side Condition Color Results Pb Error
45 7/10/2021 14:24 mg / cm ^2 calibration metal D intact yellow positive 1.1 0.1
46 7/10/2021 14:25 mg / cm ^2 calibration metal D intact yellow positive 1 0.1
47 7/15/2021 8:10 cps 6.2 0
48 7/15/2021 8:10 mg / cm ^2 calibration negative 0.9 0.1
49 7/15/2021 8:11 mg / cm ^2 calibration positive 1 0.1
50 7/15/2021 8:12 mg / cm ^2 calibration positive 1 0.1
51 7/15/2021 8:12 mg / cm ^2 calibration positive 1 0.1
52 7/15/2021 8:48 mg / cm ^2 door metal C intact white negative <LOD 0.03
53 7/15/2021 8:48 mg / cm ^2 door metal C intact white negative <LOD 0.03
54 7/15/2021 8:51 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
55 7/15/2021 8:51 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
56 7/15/2021 8:51 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
57 7/15/2021 8:52 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
58 7/15/2021 8:52 mg / cm ^2 door metal B intact white negative <LOD 0.03
59 7/15/2021 8:52 mg / cm ^2 door metal B intact white negative <LOD 0.03
60 7/15/2021 8:53 mg / cm ^2 door metal A intact white negative <LOD 0.03
61 7/15/2021 8:53 mg / cm ^2 door metal A intact white negative <LOD 0.03
62 7/15/2021 8:54 mg / cm ^2 wall concrete A intact white negative <LOD 0.03
63 7/15/2021 8:54 mg / cm ^2 wall concrete B intact blue negative <LOD 0.03
64 7/15/2021 8:55 mg / cm ^2 window metal B intact blue negative <LOD 0.03
65 7/15/2021 8:57 mg / cm ^2 window metal B intact blue negative <LOD 0.03
66 7/15/2021 9:05 mg / cm ^2 wall concrete B intact white negative <LOD 0.03
67 7/15/2021 9:05 mg / cm ^2 wall concrete B intact white negative <LOD 0.03
68 7/15/2021 9:06 mg / cm ^2 wall concrete B intact white negative <LOD 0.03
69 7/15/2021 9:06 mg / cm ^2 column metal B intact white positive 2.3 0.5
70 7/15/2021 9:09 mg / cm ^2 door metal B intact white negative 0.04 0.02
71 7/15/2021 9:09 mg / cm ^2 window metal B intact brown negative <LOD 0.03
72 7/15/2021 9:09 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
73 7/15/2021 9:10 mg / cm ^2 wall concrete B intact white negative <LOD 0.03
74 7/15/2021 9:10 mg / cm ^2 door metal B intact white negative 0.05 0.03
75 7/15/2021 9:11 mg / cm ^2 door wood B intact brown negative <LOD 0.03
76 7/15/2021 9:11 mg / cm ^2 door wood D intact brown negative <LOD 0.03
77 7/15/2021 9:11 mg / cm ^2 door wood D intact brown negative <LOD 0.03
78 7/15/2021 9:12 mg / cm ^2 wall wood B intact brown negative <LOD 0.03
79 7/15/2021 9:12 mg / cm ^2 door metal B intact white negative <LOD 0.03
80 7/15/2021 9:13 mg / cm ^2 door metal C intact white negative <LOD 0.03
81 7/15/2021 9:13 mg / cm ^2 wall concrete D intact white negative <LOD 0.03
82 7/15/2021 9:13 mg / cm ^2 wall concrete D intact white negative <LOD 0.03
83 7/15/2021 9:14 mg / cm ^2 wall concrete D intact white negative <LOD 0.03
84 7/15/2021 9:42 mg / cm ^2 wall concrete B intact white negative <LOD 0.03
85 7/15/2021 9:42 mg / cm ^2 wall concrete B intact white negative <LOD 0.03
86 7/15/2021 9:42 mg / cm ^2 wall concrete D intact white negative <LOD 0.03
Greensboro Elementary School August 23, 2021
No. Time Units Component Substrate Side Condition Color Results Pb Error
87 7/15/2021 9:43 mg / cm ^2 door metal D intact brown negative <LOD 0.03
88 7/15/2021 9:43 mg / cm ^2 door metal D intact yellow negative <LOD 0.03
89 7/15/2021 9:44 mg / cm ^2 door metal D intact yellow negative <LOD 0.03
90 7/15/2021 9:44 mg / cm ^2 door metal D intact yellow negative <LOD 0.03
91 7/15/2021 9:45 mg / cm ^2 door metal D intact yellow negative <LOD 0.03
92 7/15/2021 9:45 mg / cm ^2 door metal D intact yellow negative <LOD 0.03
93 7/15/2021 9:49 mg / cm ^2 wall concrete A intact white negative <LOD 0.03
94 7/15/2021 9:50 mg / cm ^2 wall concrete A intact white negative <LOD 0.03
95 7/15/2021 9:50 mg / cm ^2 door metal A intact brown negative <LOD 0.03
96 7/15/2021 9:50 mg / cm ^2 door metal A intact brown negative <LOD 0.03
97 7/15/2021 9:53 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
98 7/15/2021 9:54 mg / cm ^2 column metal C intact white positive 1.4 0.4
99 7/15/2021 10:09 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
100 7/15/2021 10:10 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
101 7/15/2021 10:10 mg / cm ^2 door concrete C intact white negative <LOD 0.03
102 7/15/2021 10:10 mg / cm ^2 door concrete C intact white negative <LOD 0.03
103 7/15/2021 10:11 mg / cm ^2 wall concrete A intact white negative <LOD 0.03
104 7/15/2021 10:11 mg / cm ^2 wall concrete A intact yellow negative <LOD 0.03
105 7/15/2021 10:23 mg / cm ^2 wall concrete B intact white negative <LOD 0.03
106 7/15/2021 10:24 mg / cm ^2 wall concrete C intact white negative <LOD 0.03
107 7/15/2021 10:24 mg / cm ^2 beams metal C intact blue negative 0.04 0.02
108 7/15/2021 10:25 mg / cm ^2 beams metal C intact white negative 0.06 0.03
109 7/15/2021 10:25 mg / cm ^2 beams metal C intact white negative 0.04 0.02
110 7/15/2021 10:25 mg / cm ^2 beams metal C intact white negative <LOD 0.12
111 7/15/2021 10:32 mg / cm ^2 wall concrete A intact green negative <LOD 0.03
112 7/15/2021 10:33 mg / cm ^2 wall concrete A intact beige negative <LOD 0.03
113 7/15/2021 10:34 mg / cm ^2 wall concrete A intact blue negative <LOD 0.03
114 7/15/2021 10:34 mg / cm ^2 wall concrete D intact pink negative <LOD 0.03
115 7/15/2021 10:35 mg / cm ^2 wall concrete D intact red negative <LOD 0.03
116 7/15/2021 10:36 mg / cm ^2 floor concrete D intact beige negative <LOD 0.03
117 7/15/2021 10:36 mg / cm ^2 wall concrete B intact beige negative <LOD 0.03
118 7/15/2021 10:37 mg / cm ^2 wall concrete B intact beige negative <LOD 0.03
119 7/15/2021 10:37 mg / cm ^2 window metal A intact black negative <LOD 0.03
120 7/15/2021 10:38 mg / cm ^2 window metal A intact black negative <LOD 0.03
121 7/15/2021 10:38 mg / cm ^2 door metal A intact black negative <LOD 0.03
122 7/15/2021 10:38 mg / cm ^2 door metal A intact black negative <LOD 0.03
123 7/15/2021 10:38 mg / cm ^2 door metal A intact black negative <LOD 0.03
124 7/15/2021 10:39 mg / cm ^2 door metal A intact black negative <LOD 0.03
125 7/15/2021 10:39 mg / cm ^2 door metal A intact black negative <LOD 0.03
126 7/15/2021 10:44 mg / cm ^2 wall wood A intact beige negative <LOD 0.03
127 7/15/2021 10:44 mg / cm ^2 wall wood A intact blue negative <LOD 0.03
128 7/15/2021 10:44 mg / cm ^2 wall wood A intact blue negative <LOD 0.03
Greensboro Elementary School August 23, 2021
No. Time Units Component Substrate Side Condition Color Results Pb Error
129 7/15/2021 10:45 mg / cm ^2 wall concrete B intact beige negative <LOD 0.03
130 7/15/2021 10:45 mg / cm ^2 wall concrete C intact blue negative <LOD 0.03
131 7/15/2021 10:45 mg / cm ^2 cabinet concrete C intact blue negative <LOD 0.03
132 7/15/2021 10:46 mg / cm ^2 door metal C intact white negative <LOD 0.03
133 7/15/2021 10:46 mg / cm ^2 door metal C intact brown negative <LOD 0.03
134 7/15/2021 10:59 mg / cm ^2 calibration positive 1 0.1
135 7/15/2021 11:00 mg / cm ^2 calibration positive 1 0.1
136 7/15/2021 11:01 mg / cm ^2 calibration positive 1 0.1
< LOD = below level of detection
Lead Based Paint concentration >0.5% by weight when determined by laboratory analysis. LBP is also defined by HUD as 1.0 mg/cm2 when determined using an XRF analyzer.
• Painted surfaces of metal windows and columns between bricks located at the
Subject Property.
Lead Containing Paint
OSHA does not define Lead Based Paint based on lead content. Any detectable lead in a paint or varnish makes it lead paint for purposes of complying with OSHA regulations to determine worker exposure. Consequently, for purposes of this study, Lead
Containing Paint is considered any detectable level of lead.
The predominant LCP material identified by the NOVA survey include:
• Painted surfaces of wood windows, trim, and baseboards located at the Subject
• Painted surfaces of metal doors, frames, trim, and beams located at the Subject
4.3 LEAD ABATEMENT ACTIVITIES
The US EPA has stated that solid architectural components coated with LBP are less likely to be hazardous because of the small ratio of lead paint to total waste mass (US
EPA, 1993, Applicability of RCRA Disposal Requirements to Lead-Based Paint
Abatement Wastes, Final Report, EPA 747-R-93-006 Technical Programs Branch, Office of Pollution Prevention and Toxics, March 1993).
Greensboro Elementary School August 23, 2021
The US Army conducted a study which concluded that whole-building demolition debris is not likely to exceed the toxicity characteristic standard for lead if it is handled as a single, whole waste stream and disposed of all together (US Dept. of the Army, US Army
Environmental Hygiene Agency, Interim Final Report, Lead-Based Paint Contaminated
Debris Waste Characterization Study No. 27-26-JK44-92. May 1993). Consequently, whole-building demolition debris is typically considered a non-hazardous waste with regard to lead under RCRA.
We believe the greatest impact of LBP and/or LCP may be on the contractor’s salvage activities of railing, doorframes, etc.., particularly activities that include cutting, grinding, sanding or scraping. As previously noted, OSHA does not define lead paint based on content. Any detectable lead in paint makes it lead paint for purposes of complying with
OSHA regulations to determine worker exposure.
• The contractor must conduct an initial exposure assessment of all workplaces and operations where lead or lead-containing material is being used, disturbed or removed to determine whether any employee may be exposed to lead at or above the action level.
• Personnel involved in LBP or LCP must be monitored and directed by a Competent
Person who will determine appropriate compliance controls and procedures.
• The Lead in Construction standard's action level is 30 ug/m3 calculated as an 8-hour time-weighted average.
In addition, on April 22, 2008, EPA issued a rule requiring the use of lead-safe practices and other actions aimed at preventing lead poisoning. Under the rule, beginning April
22, 2010, contractors performing abatement, renovation, repair and painting projects that disturb lead-based paint in homes, child-care facilities, and schools (K-12) built before 1978 must be certified by EPA and must follow specific lead-safe work practices to prevent lead contamination.
Persons performing lead-based paint (LBP) abatement activities must:
• Be certified
• Work for a Certified Lead Firm
Persons performing renovation work must:
• Be a certified Renovator
• Work for a Certified Renovation Firm
Greensboro Elementary School August 23, 2021
The EPA and the also regulate the LBP and LCP waste stream resulting from abatement and renovation activities. A potential lead waste material must be analyzed for toxicity using the Toxicity Characteristic Leachate Procedure (TCLP).
• If TCLP results from waste stream of paint chips, dust (including dust from floor refinishing operations), soil, and/or stripper sludge are less than 5 milligrams per liter (5 parts per million or ppm), the waste may usually go to a municipal solid waste
(MSW) or construction debris (CD) landfill, depending on concentrations and landfill operator requirements.
• If greater than 5 milligrams per liter (5 ppm) must comply with Georgia State Rules for Hazardous Waste Management.
Please note that the means and methods necessary for LBP and/or LCP abatement or demolition, as well as worker protection and monitoring, are the sole responsibility of the contractor.
Greensboro Elementary School August 23, 2021
5.0 HAZARDOUS BUILDING MATERIAL INVENTORY
5.1 FIELD SERVICES
Mr. Curtis Moses, a NOVA Professional, performed the field work for the Hazardous
Building Material Inventory (HBMI) for the Subject Property on June 29, 2021.
5.2 HAZARDOUS BUILDING MATERIAL INVENTORY
fluorescent lighting, ballasts, emergency exit signs, fire extinguishers, HID lighting, LED
The materials identified are listed below:
SUMMARY OF HAZARDOUS BUILDING MATERIAL FINDINGS
MATERIAL / EQUIPMENT LOCATION ESTIMATED QUANTITY
LED Lighting Poll Mounted 8
HVAC Units Mechanical Rooms &
Exterior
Emergency Exit Signs Doorways 15
Score Board Gymnasium 2
4’ Fluorescent Ballast Throughout 790
4’ Curved Fluorescent Bulbs Throughout 3,160
Pod Lights Gymnasium 50
Fire Extinguishers Throughout 8
HID Lighting Throughout 20
Electric Thermostats Throughout 49
Refrigeration Units Cafeteria 1
Water Fountains Hallways 6
Additionally, small batteries and chemicals associated with cleaning/maintenance were observed throughout the facility.
It should be noted that the above list is an approximation of what was observed by NOVA at the time of the site reconnaissance.
Based on the findings of random checks, the majority of ballasts at the Subject Property are labeled as “Non-PCB” containing.
Greensboro Elementary School August 23, 2021
Ballasts that are not labeled as Non-PCB containing should be assumed to be PCB-containing. Emergency exit signs and exit lighting units are assumed to contain nickel-cadmium batteries.
Electronic equipment such as cell phones, smoke detectors, laptop computers can contain batteries. Additional batteries are stored throughout the building and likely associated with the fire, emergency lighting, and security alarm systems. These batteries should be disposed in accordance with applicable regulations.
5.3 HAZARDOUS BUILDING MATERIAL INVENTORY CONCLUSIONS
fluorescent lighting, ballasts, emergency exit signs, fire extinguishers, HID lighting, LED
The removal and proper disposal of the HBM identified within this report should be managed in accordance with the following rules:
• Solid Waste Management – Georgia Environmental Rule 391-3-4
• Hazardous Waste Management – Georgia Environmental Rule 391-3-11
Batteries: All batteries should be removed from equipment and transported for recycling in accordance with applicable regulations. Additional batteries likely associated with the security, emergency lighting, and fire warning systems should be disposed properly.
PCB-Containing Ballasts: Ballasts should be removed and disposed in accordance with
40 CFR 761.62 and all other applicable regulations.
Fluorescent and Incandescent Light Bulbs: Bulbs should be disposed in accordance with Resource Conservation & Recovery Act (RCRA):
• Subtitle C: Hazardous Waste (40 CFR Parts 261, 262), or if found to be non-hazardous;
• Subtitle D: Municipal & Other Non-Hazardous Waste (40 CFR 258).
Chemical Waste: All chemicals, including cleaning/maintenance chemicals, should be removed, transported and disposed in accordance with applicable regulations.
Fire Extinguishers: All chemical containing fire extinguishers should be removed, transported and disposed in accordance with applicable regulations.
Greensboro Elementary School August 23, 2021
High-Intensity-Discharge (HID) Lighting & Light Emitting Diode (LED) Lighting: Should be disposed in accordance with the federal Universal Waste Rule (see 40 CFR 273).
Electronic devices: Computer monitors, computer hard drives, printers, telephones, refrigerators, LED lighting, thermostats, and microwave ovens can contain chemicals such as lead, cadmium, chromium, mercury and copper. Caution should be used during the removal of these devices, and they should be disposed in accordance with applicable regulations.
APPENDIX A
SAMPLE LOCATION PLANS
SAMPLE LOCATION PLAN
Common Areas and Offices
GREENSBORO ELEMENTARY SCHOOL
GREENSBORO, GREENE COUNTY, GEORGIA
NOVA Project Number 3021105
Asbestos Containing Material Non Asbestos Containing Material Asbestos Containing Material
Non-Asbestos Containing Material
Lead Based Paint
Lead Containing Paint
No Detect
C-FT-1
C-FT-2
C-FT-3
C-FT-4
C-FT-5
C-CB-7
C-JC-8
C-C-17
C-C-14
C-C-16
C-CM-24
C-JC-9
C-JC-10
G-C-25G-G-39
G-V-26
G-V-27
G-FT-59
G-F-60 G-F-61
G-C-62 G-G-63
G-W-64
G-W-65
G-JC-66
G-JC-67
G-JC-68
G-F-74
G-F-75
G-CB-76
G-FT-77 G-FT-78
G-FT-79
G-FT-80
G-C-81
G-CB-82
G-CT-83
G-F-FT-84
G-F-FT-85
118119
129 130
Classrooms
GREENSBORO ELEMENTARY SCHOOL
GREENSBORO, GREENE COUNTY, GEORGIA
NOVA Project Number 3021105
Asbestos Containing Material Non Asbestos Containing Material Asbestos Containing Material
Non-Asbestos Containing Material
Lead Based Paint
Lead Containing Paint
No Detect
C-CM-23
G-M-34
G-M-35
C-FT-6
C-C-15
C-C-11
C-C-13
C-C-12
C-P-28
G-GM-18
G-GM-19G-TSI-20
G-TSI-21
G-TSI-22
G-P-29
G-TSI-31
G-TSI-32
G-TSI-33
G-GM-36
G-CT-40
G-GM-37G-GM-38 G-FT-44
G-CT-42
G-CT-43
G-CT-41
G-G-46
G-G-47
G-CB-45
G-C-48
G-FT-49
G-G-50 G-C-51
G-CB-52
G-GD-53
G-GD-54
G-GD-55
G-GM-56G-L-57G-L-58
G-FT-69
G-FS-70
G-FS-71
G-CT-72
G-C-73
3231 34 35
373839
60 61
67 68
69 68
74 75
76 77
87 88 89 90
Roof
GREENSBORO ELEMENTARY SCHOOL
GREENSBORO, GREENE COUNTY, GEORGIA
NOVA Project Number 3021105
G-R-86
G-R-87
G-R-88
G-R-89
G-R-93
G-R-91
G-R-94
G-R-92
G-R-90
Asbestos Containing Material Non Asbestos Containing Material Asbestos Containing Material
Non-Asbestos Containing Material
APPENDIX B
LABORATORY ANALYTICAL DATA
XRF RESULTS
EMSL Analytical, Inc.
2205 Corporate Plaza Parkway SE, Suite 200 Smyrna, GA 30080
Tel/Fax: (770) 956-9150 / (770) 956-9181 http://www.EMSL.com / atlantalab@emsl.com
072105173EMSL Order:
Customer ID: NOVA30
Customer PO:
Project ID:
Attention: Phone:Curtis Moses (678) 982-5576
Fax:Nova Engineering & Environmental, Inc. (770) 425-1113
Received Date:3900 Kennesaw 75 Parkway 07/16/2021 8:00 AM
Analysis Date:Suite 100 07/18/2021 - 07/22/2021
Collected Date:Kennesaw, GA 30144
Project: 3021105
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
G-FT-1-Floor Tile
072105173-0001
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
White/Blue 12 X 12
W/Glue - Lobby
G-FT-1-Mastic
072105173-0001A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
White/Blue 12 X 12
W/Glue - Lobby
G-FT-2-Floor Tile
072105173-0002
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
White/Blue 12 X 12
W/Glue - Office
G-FT-2-Mastic
072105173-0002A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
White/Blue 12 X 12
W/Glue - Office
G-FT-3-Floor Tile
072105173-0003
None DetectedNon-fibrous (Other)100%Beige
Non-Fibrous
Homogeneous
Tan/Blue 12 X 12
W/Glue - Reception
G-FT-3-Mastic
072105173-0003A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Tan/Blue 12 X 12
W/Glue - Reception
G-FT-3-Leveler
072105173-0003B
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Tan/Blue 12 X 12
W/Glue - Reception
G-FT-4-Floor Tile 1
072105173-0004
None DetectedNon-fibrous (Other)100%Beige
Non-Fibrous
Homogeneous
Tan/Blue 12 X 12
W/Glue - Offices
G-FT-4-Mastic 1
072105173-0004A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Tan/Blue 12 X 12
W/Glue - Offices
G-FT-4-Floor Tile 2
072105173-0004B
None DetectedNon-fibrous (Other)100%Blue
Non-Fibrous
Homogeneous
Tan/Blue 12 X 12
W/Glue - Offices
G-FT-4-Mastic 2
072105173-0004C
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Tan/Blue 12 X 12
W/Glue - Offices
G-FT-5-Floor Tile 1
072105173-0005
None DetectedNon-fibrous (Other)100%Blue
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby
G-FT-5-Mastic 1
072105173-0005A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby
G-FT-5-Floor Tile 2
072105173-0005B
None DetectedNon-fibrous (Other)100%Purple
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby
G-FT-5-Mastic 2
072105173-0005C
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby
G-FT-6-Floor Tile 1
072105173-0006
None DetectedNon-fibrous (Other)100%Blue
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby Hall
Bend
Initial report from: 07/22/2021 15:31:20
Page 1 of 10ASB_PLM_0008_0001 - 1.78 Printed: 7/22/2021 3:31 PM
Tel/Fax: (770) 956-9150 / (770) 956-9181 http://www.EMSL.com / atlantalab@emsl.com
072105173EMSL Order:
Customer ID: NOVA30
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
G-FT-6-Mastic 1
072105173-0006A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby Hall
Bend
G-FT-6-Floor Tile 2
072105173-0006B
None DetectedNon-fibrous (Other)100%Purple
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby Hall
Bend
G-FT-6-Mastic 2
072105173-0006C
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Purple/Blue 12 X 12
W/Glue - Lobby Hall
Bend
G-CB-7-Cove Base
072105173-0007
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Covebase Glue -
Offices
G-CB-7-Glue
072105173-0007A
None DetectedNon-fibrous (Other)100%Yellow
Non-Fibrous
Homogeneous
Covebase Glue -
Offices
G-JC-8
072105173-0008
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Joint Compound -
Addition Trim - Entry
G-JC-9
072105173-0009
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Joint Compound -
Addition Trim - End
G-JC-10
072105173-0010
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Joint Compound -
Addition Trim - Mid
G-C-11
072105173-0011
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Caulking - Back Door
- Original
G-C-12
072105173-0012
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Caulking - Window -
Original
G-C-13-Caulk 1
072105173-0013
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Caulking - Door - Far
East - Class Hall
G-C-13-Caulk 2
072105173-0013A
4% ChrysotileNon-fibrous (Other)96%Tan
Non-Fibrous
Homogeneous
Caulking - Door - Far
East - Class Hall
G-C-14
072105173-0014
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Caulking - Door -
Front - New Structure
G-C-15
072105173-0015
None DetectedNon-fibrous (Other)100%Brown
Non-Fibrous
Homogeneous
Caulking - Window -
Fornt - New Structure
G-C-16
072105173-0016
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Caulking - HVAC At
Café
G-C-17
072105173-0017
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Caulking - At
Cafeteria
G-GM-18-Grout
072105173-0018
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Grout/Mortar/Brick -
Exterior Center
G-GM-18-Mortar
072105173-0018A
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Grout/Mortar/Brick -
Exterior Center
G-GM-18-Brick
072105173-0018B
None DetectedNon-fibrous (Other)100%Red
Non-Fibrous
Homogeneous
Grout/Mortar/Brick -
Exterior Center
Page 2 of 10ASB_PLM_0008_0001 - 1.78 Printed: 7/22/2021 3:31 PM
Tel/Fax: (770) 956-9150 / (770) 956-9181 http://www.EMSL.com / atlantalab@emsl.com
072105173EMSL Order:
Customer ID: NOVA30
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
G-GM-19-Grout
072105173-0019
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Grout/Mortar/Brick -
Exterior End/Back
G-GM-19-Mortar
072105173-0019A
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Grout/Mortar/Brick -
Exterior End/Back
G-GM-19-Brick
072105173-0019B
None DetectedNon-fibrous (Other)100%Red
Non-Fibrous
Homogeneous
Grout/Mortar/Brick -
Exterior End/Back
G-TSI-20-Brown layer
072105173-0020
None DetectedNon-fibrous (Other)20%Cellulose80%Brown
Fibrous
Homogeneous
Insulation Between
Metal Panels Below
Windows - Mid
G-TSI-20-White layer
072105173-0020A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Insulation Between
Metal Panels Below
Windows - Mid
G-TSI-21-Brown layer
072105173-0021
None DetectedNon-fibrous (Other)20%Cellulose80%Brown
Fibrous
Homogeneous
Insulation Between
Metal Panels Below
Windows - Side
G-TSI-21-White layer
072105173-0021A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Insulation Between
Metal Panels Below
Windows - Side
G-TSI-22-Brown layer
072105173-0022
None DetectedNon-fibrous (Other)20%Cellulose80%Brown
Fibrous
Homogeneous
Insulation Between
Metal Panels Below
Windows - Back
G-TSI-22-White layer
072105173-0022A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Insulation Between
Metal Panels Below
Windows - Back
G-CM-23
072105173-0023
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Cement On Exterior -
HVAC Units
G-CM-24
072105173-0024
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Cement On Exterior -
HVAC Units
G-C-25
072105173-0025
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Caulking OnHVAC To
Building - Old Units
G-V-26
072105173-0026
None DetectedNon-fibrous (Other)20%Cellulose80%Black
Fibrous
Homogeneous
Vapor Barrier Behind
Metal Siding
G-V-27
072105173-0027
None DetectedNon-fibrous (Other)20%Cellulose80%Black
Fibrous
Homogeneous
Vapor Barrier Behind
Metal Siding
G-P-28
072105173-0028
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Plaster - At HVAC
G-P-29
072105173-0029
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Plaster - At Hall
HVAC
G-P-30
072105173-0030
G-TSI-31-Wrap
072105173-0031
None DetectedNon-fibrous (Other)10%Cellulose
Glass
80%
10%
Various
Fibrous
Homogeneous
TSI - Run - Mech
G-TSI-31-Mastic
072105173-0031A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
TSI - Run - Mech
Initial report from: 07/22/2021 15:31:20
Page 3 of 10ASB_PLM_0008_0001 - 1.78 Printed: 7/22/2021 3:31 PM
See Above
Tel/Fax: (770) 956-9150 / (770) 956-9181 http://www.EMSL.com / atlantalab@emsl.com
072105173EMSL Order:
Customer ID: NOVA30
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
G-TSI-32-Wrap
072105173-0032
None DetectedNon-fibrous…
This is the start of the file's text. The full file is on GovTribe.
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .