Generator_Relocation_Site_Plans_and_Specifications.pdf

PDF 6 MB Posted

Attached to
Generator Relocation
Solicitation number
2024-08-21
Issued by
Ellis County, Texas

About this file

These are comprehensive construction documents and site plans for the Waxahachie City Hall Generator Relocation Project prepared by Architexas and Conquest Engineering for the City of Waxahachie, Texas, dated May 30, 2024. The project involves relocating an existing 80kW Kohler Power Systems standby generator from the current City Hall location at 401 S. Rogers Street to the new City Hall Annex across the street. The detailed plans include site layouts, electrical site plans, power distribution diagrams, and specific relocation instructions encompassing the generator's physical move, electrical reconnection, and system integration.

The documents specify extensive technical requirements for the generator relocation, including providing a new concrete housekeeping pad, rerouting underground conduits, reconnecting electrical systems, and performing comprehensive generator system inspection and maintenance. The project requires the contractor to service the generator, test all safety and control systems, replace batteries and filters, and ensure full operational compliance with local building codes. The electrical plans detail precise routing of power feeders, grounding systems, and panel relocations, with specific notes about coordinating exact locations with the owner and maintaining existing electrical infrastructure during the transition.

View the file

Other files

File Type Posted
Generator_Relocation.pdf PDF
Picture_of_Generator_at_Current_Location.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Waxahachie City Hall Renovation401 S. Rogers Street, Waxahachie, TX 75165

May 30, 2024

Generator Relocation Package

STREET MAPVICINITY MAPSYMBOL LEGEND

Room name

150 SF

1t

1i

A101

SIM

BROKEN SECTION

A101

SIM

WALL SECTION

DETAIL SECTION

DETAIL KEY

DETAIL KEY

BUILDING ELEVATION KEY

COLUMN CENTER LINE

FLOOR LEVEL

CHANGE

CENTER LINE

DOOR TYPE

WINDOW TYPE

WALL TYPE

ROOM NAME,

NUMBER, & SQUARE

FOOTAGE

BREAK LINE

A101

SIM

A101

SIM

A101

SIM

A101

SIM

MATERIAL LEGEND

EARTH/COMPACT

FILL

GRAVEL FILL

SAND FILL

CAST-IN-PLACE

CONC.

LIGHTWEIGHT

CONC.

FACE BRICK

COMMON BRICK

CMU

CAST STONE

GLASS

STEEL

ALUMINUM

SHEET METAL

FRT ROUGH WOOD

FRT BLOCKING

FINISH WOOD

PLYWOOD

RIGID INSULATION

THERMAL/ ACOUSTIC INSULATION

SPRAYED FIRE INSULATION

CERAMIC TILE

TYPE 'X' GYP.

BOARD

METAL LATH & PLASTER

CARPET

HOLLOW CLAY TILE

WAXAHACHIE CITY HALL ANNEX

CITY OF WAXAHACHIE CITY OF WAXAHACHIE

WAXAHACHIE CITY HALL ANNEX

WAXAHACHIE CITY HALL

WAXAHACHIE CITY HALL

1. THE WORK SHALL CONFORM WITH THE CURRENT EDITION OF THE FOLLOWING REGULATIONS AS ADOPTED BY THE

CITY OF WAXAHACHIE:

-2018 INTERNATIONAL BUILDING CODE W/ NCTCOG AMENDMENTS

-2018 INTERNATIONAL EXISTING BUILDING CODE W/ NCTCOG AMENDMENTS

-2018 INTERNATIONAL FIRE CODE W/ WAXAHACHIE AMENDMENTS

-2018 INTERNATIONAL PLUMBING CODE W/ NCTCOG AMENDMENTS

-2018 INTERNATIONAL MECHANICAL CODE W/ NCTCOG AMENDMENTS

-2017 NATIONAL ELECTRICAL CODE W/ NCTCOG AMENDMENTS

-2018 INTERNAL ENERGY CONSERVATION CODE W/ NCTCOG AMENDMENTS

-U.S. DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

2. THE CONTRACTOR SHALL VISIT THE SITE TO REVIEW AND SURVEY EXISTING CONDITIONS TO FULLY

UNDERSTAND SCOPE OF WORK.

3. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND INSPECTIONS AND PAY ALL APPLICATION FEES.

4. IF THE CONTRACTOR PERFORMS OR PROCEEDS WITH ANY WORK, CONTRARY TO APPLICABLE LAWS, ORDINANCES, RULES AND REGULATIONS WITHOUT GIVING PRIOR WRITTEN NOTICE TO THE ARCHITECT, HE/SHE SHALL ASSUME

FULL RESPONSIBILITY THEREFORE AND SHALL BEAR ALL COST ATTRIBUTABLE.

5. THE CONTRACTOR SHALL CAREFULLY STUDY THE CONTRACT DOCUMENTS PRIOR TO CONSTRUCTION AND SHALL

REPORT TO THE ARCHITECT ANY ERROR, INCONSISTENCY OR OMISSION DISCOVERED AND SHALL NOT PROCEED

WITH THE WORK UNTIL THE INTENT OF THE DOCUMENTS IS VERIFIED BY THE ARCHITECT.

6. ALL DRAWINGS AND SPECIFICATIONS FORMING PART OF THE CONSTRUCTION DOCUMENTS ARE COMPLEMENTARY, AND WHAT IS CALLED FOR BY ONE WILL BE BINDING AS IF CALLED FOR BY ALL; ANY WORK SHOWN OR REFERRED TO

ON ANY ONE DOCUMENT SHALL BE PROVIDED AS THOUGH SHOWN ON ALL DOCUMENTS.

7. THE CONTRACT DOCUMENTS SHALL BE INTERPRETED WITH THE FOLLOWING ORDER OF PRECEDENCE:

SPECIFICATIONS, DETAILS, ENLARGEMENTS, OVERALL DRAWINGS, AND SUBSEQUENT CLARIFICATIONS. ADDENDA

SHALL OVERRIDE THE AFFECTED COMPONENTS IN ALL OF THE ABOVE. ALL VERBAL CLARIFICATIONS ARE TO BE

RECORDED BY THE CONTRACTOR AND SENT TO THE ARCHITECT WITHIN SEVEN DAYS OF THE OCCURRENCE.

8. THE STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND AUDIO/VISUAL DOCUMENTS ARE SUPPLEMENTARY

TO THE ARCHITECTURAL DOCUMENTS. SHOULD THERE BE A DISCREPANCY BETWEEN THE ARCHITECTURAL

DOCUMENTS AND THE STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND AUDIO/VISUAL DOCUMENTS, SUCH DISCREPANCY IS TO BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. THE CONTRACTOR SHALL RECEIVE

INSTRUCTIONS PRIOR TO INSTALLATION OR PERFORMANCE OF SAID WORK. ANY WORK PERFORMED OR INSTALLED

IN CONFLICT WITH THE DOCUMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE.

9. INFORMATION CONTAINED ON THESE DRAWINGS WITH REGARD TO EXISTING CONDITIONS OF CONSTRUCTION IS

PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR EXECUTING THE WORK. EVERY ATTEMPT HAS BEEN MADE

TO PROVIDE COMPLETE AND ACCURATE REPRESENTATIONS OF SUCH EXISTING CONDITIONS. THIS

INTERPRETATION HAS BEEN TAKEN BY FIELD MEASUREMENT AND OBSERVATION. THE ARCHITECT HAS

ENDEAVORED TO IDENTIFY AS COMPLETELY AS POSSIBLE IN THE CONSTRUCTION DOCUMENTS, EXISTING ITEMS OF

EQUIPMENT AND CONSTRUCTION THAT ARE REQUIRED TO BE REMOVED OR OTHERWISE DEMOLISHED. THIS

INFORMATION IS PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR AND IS IN NO WAY INTENDED TO MEAN

THAT DEMOLITION IS LIMITED ONLY TO THOSE ITEMS SPECIFICALLY IDENTIFIED. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO EXECUTE DEMOLITION WORK AS REQUIRED TO REMOVE ELEMENTS AND SYSTEMS IDENTIFIED

IN THE CONSTRUCTION DOCUMENTS, ALONG WITH THEIR ASSOCIATED PARTS.

10. ALL AREAS AND ITEMS INDICATING CONTRACT LIMITS AND LINES OF DEMARCATION ARE SHOWN FOR THE

CONVENIENCE OF THE CONTRACTOR AND ARE NOT TO BE TAKEN LITERALLY. ACTUAL CONTRACT LIMITS ARE TO BE

DETERMINED PRIOR TO CONSTRUCTION BY FIELD VERIFICATION.

11. CONTRACTOR TO ASSIST THE ARCHITECT IN MAKING THEIR EVALUATIONS AND RECOMMENDATIONS BY PROVIDING

IN A TIMELY MANNER, AT NO ADDITIONAL COST TO THE OWNER, ACCURATE AND COMPLETE DRAWINGS, SKETCHES, AND PHOTOGRAPHS, SUFFICIENT TO CLEARLY DESCRIBE DISCREPANCIES, CONFLICTS, AND CONCEALED OR

OTHERWISE UNANTICIPATED CONDITIONS AFFECTING NEW CONSTRUCTION.

12. FIELD VERIFICATIONS OF EXISTING CONDITIONS RELATED TO SPECIFIC PORTIONS OF THE WORK SHALL BE

UNDERTAKEN IN ADVANCE TO ALLOW FOR THE TIMELY IDENTIFICATION OF EXISTING CONDITIONS THAT MAY AFFECT

THE SCHEDULED INSTALLATION OF NEW WORK AS DESIGNED AND DETAILED, AND TO AVOID UNDUE AND

UNREASONABLE DELAYS TO THE PROJECT SHOULD SUCH CONDITIONS BE DISCOVERED. TIMELY IDENTIFICATION OF

SUCH CONDITIONS SHALL PROVIDE FOR A MINIMUM PERIOD OF 10 (TEN) WORKING DAYS DURING WHICH TIME THE

ARCHITECT WILL EVALUATE THE CONDITION AND MAKE RECOMMENDATIONS FOR ACCOMMODATING NEW WORK.

13. CONTRACTOR IS TO PROVIDE AND INSTALL ALL ACCESS PANELS, RATED OR OTHERWISE, SIZE AS REQUIRED, AT ALL

CONCEALED MECHANICAL AND PLUMBING ITEMS WHICH REQUIRE SERVICE OR ACCESS (VALVES, FIE DAMPERS, DUCT HEATERS, ETC.). ACCESS PANELS IN RATED CEILINGS AND PARTITIONS SHALL HAVE THE APPROPRIATE UL

LABELS.

14. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH ALL EQUIPMENT MANUFACTURER'S ROUGH-IN

REQUIREMENTS.

15. NOTIFY CITY OF WAXAHACHIE WHEN IT IS NECESSARY TO AFFECT UTILITIES BEFORE PROCEEDING WITH THE WORK.

ALL EXISTING UTILITIES MUST BE CHECKED BY THE CONTRACTOR PRIOR TO THE COMMENCEMENT OF DEMOLITION

WORK. ANY DAMAGES RESULTING FROM LACK OF COMPLIANCE WITH THE PROVISIONS SHOULD BE CORRECTED BY

THE CONTRACTOR AT HIS OR HER OWN EXPENSE.

GENERAL NOTES

COPYRIGHT

Dallas | Austin | San Antonio www.architexas.com

1907 Marilla St.

Second Floor

Dallas, Texas 75201 p 214.748.4561

The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.

Reproduction or use for any purpose other than that authorized by Architexas is forbidden.

REVISION HISTORY

#9409

Architexas No.

Sheet Name

Date

Sheet Number

5/30/2024

City of Waxahachie

Waxahachie City Hall

A0.00

401 S. Rogers St., Waxahachie, TX

75165

CONSTRUCTION DOCUMENTS

2407 05/30/2024

Cover Sheet

DN

DN

DN

DNDNDN

DN

TRASH

BRIDGE ABOVE

S Rogers St

RETAIL

CITY HALL ANNEX

CITY HALL

PLAZA

A

R C

A D

E

7 10

VAN14

UP

A1.00

LIMIT OF WORK

RELOCATE GENERATOR FROM

EXISTING LOCATION AT CITY HALL, REF. MEP

6" CONC. CURB, MATCH EXISTING

(REF. P1/C11.00 FROM WAXAHACHIE CITY HALL

ANNEX PROJECT)

8'-0" HEIGHT ALUM. PERFORATED MECH. FENCE,

BASIS OF DESIGN: POLARIS ALUMINUM FENCE

DESIGN SYSTEM, MANUFACTURED BY AMETCO

PROVIDE SLAB FOR GENERATOR

R

' - 0

/4

/4

PROVIDE IRRIGATION FOR

PLANTINGS BY OWNER.

COORDINATE EXACT

LOCATIONS W/ OWNER

DEMO PAVING AS REQ'D TO INSTALL NEW

LANDSCAPE AREA FOR GENERATOR

6" DIA X 36" H BOLLARD

@ 4' - 0" O.C., MAX., PAINT

DEMO AND REPLACE FULL

CONCRETE PANEL

PATH OF CONDUIT

UNDERGROUND, REF. MEP

RUN FEEDERS TIGHT TO

BUILDING, PAINT TO

MATCH BRICK AND STONE

FIRE CAULK CONDUIT AT ALL

PENETRATIONS THROUGH

WALLS OF RISER ROOM

TO ELECTRICAL ROOM

3' - 0"

15' - 0" 4' - 8"

DEMO EXISTING CURB

COPYRIGHT

Dallas | Austin | San Antonio www.architexas.com

1907 Marilla St.

Second Floor

Dallas, Texas 75201 p 214.748.4561

The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.

Reproduction or use for any purpose other than that authorized by Architexas is forbidden.

REVISION HISTORY

#9409

Architexas No.

Sheet Name

Date

Sheet Number

5/30/2024

City of Waxahachie

Waxahachie City Hall

A1.00

401 S. Rogers St., Waxahachie, TX

75165

CONSTRUCTION DOCUMENTS

2407 05/30/2024

Site Plan

N

PLAN NORTH

N

TRUE NORTH

1" = 20'-0"

Site Plan

1/8" = 1'-0"

Enlarged Site Plan

UP

UP

UP

X

UP

(E) GENERATOR

ENLARGED PLAN

E2.00 - 2

(E) MDP

(E) PANEL NQ

(E) PANEL NF

(E) TRANSFER SWITCH

(E) TRANSFORMER

N

PLAN NORTH

N

TRUE NORTH

1" = 20'-0"

Site Plan

Dallas | Austin | San Antonio www.architexas.com

1907 Marilla St.

Second Floor

Dallas, Texas 75201 p 214.748.4561

City of Waxahachie

Waxahachie City Hall

401 S. Rogers St., Waxahachie, TX

75165

COPYRIGHT

The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.

Reproduction or use for any purpose other than that authorized by Architexas is forbidden.

REVISION HISTORY

CONSTRUCTION DOCUMENTS

Architexas No.

Sheet Name

Sheet Number

Date

05/30/2024

Engineering Firm : F-23407 Conquest Engineering, LLC 14901 Quorum Dr, Ste 300

Dallas, Texas 75254 gclaussen@conquestddg.com

NOTES BY SYMBOL

1. EXISTING KOHLER POWER SYSTEMS STANDBY GENERATOR,

480Y/277V, 80KW, 80 AMP MCB WITH KOHLER DECISION-MAKER 3000.

UNIT TO BE RELOCATED TO NEW ANNEX BUILDING ACROSS THE

STREET. ENTIRE STANDBY GENERATOR SYSTEM AND ATS TO BE

FULLY SERVICED AND IN GOOD WORKING CONDITION.

2. ALL EQUIPMENT IN THIS AREA, PART OF THE EMERGENCY POWER

DISTRIBUTION SYSTEM TO BE REMOVED, SERVICED, CLEANED,

RELOCATED AND REINSTALLED AT ANNEX BUILDING ACROSS THE

STREET.

3. EXISTING 480Y/277V, EMERGENCY POWER PANELBOARD, SQUARE

D, TYPE NF, 125A BUS, 3PH, 4W, MLO, PROTECTED UPSTREAM AT

THE GENERATOR BY AN 80A/3PH CIRCUIT BREAKER. EXISTING

50A/3P, 20A/3P, AND (2) 20A/1P CIRCUIT BREAKERS TO REMAIN.

4. EXISTING 30KVA, 480 DELTA / 208Y/120V, 150 DEGREE C, TYPE 2

ENCLOSURE, DRY-TYPE TRANSFORMER HUNG FROM STRUCTURE

TO BE RELOCATED. SQUARE D, CAT NO: 30T3H

5. EXISTING KOHLER DECISION-MAKER MPAC 1200, AUTOMATICE

TRANSFER SWITCH TO BE RELOCATED. SYSTEM AT TIME OF

INSPECTION HAD A WARNING MESSAGE. SYSTEM TO BE FULL

SERVICED TO GOOD WORKING CONDITION.

N

PLAN NORTH

N

TRUE NORTH

1/4" = 1'-0"

Enlarged Site Plan

Electrical Site Plan - City Hall

E2.00

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text X

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text 118281

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text

GRANT CLAUSSEN

AutoCAD SHX Text 05/30/24

AutoCAD SHX Text X

R e f r i g e r a t o r

DN

DN

DN

DNDNDN

DN

UP

ENLARGED PLAN

E2.01 - 2

RELOCATED GENERATOR

(E) TRANSFORMER

(E) SD-2

(E) SD-1

NEW LB'S

EXISTING

PANEL "MSB-1"

NEW PATH OF CONDUIT

UNDERGROUND

N

PLAN NORTH

N

TRUE NORTH

1/32" = 1'-0"

Site Plan

Dallas | Austin | San Antonio www.architexas.com

1907 Marilla St.

Second Floor

Dallas, Texas 75201 p 214.748.4561

City of Waxahachie

Waxahachie City Hall

401 S. Rogers St., Waxahachie, TX

75165

COPYRIGHT

The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.

Reproduction or use for any purpose other than that authorized by Architexas is forbidden.

REVISION HISTORY

CONSTRUCTION DOCUMENTS

Architexas No.

Sheet Name

Sheet Number

Date

05/30/2024

Engineering Firm : F-23407 Conquest Engineering, LLC 14901 Quorum Dr, Ste 300

Dallas, Texas 75254 gclaussen@conquestddg.com

NOTES BY SYMBOL

1. NEW LOCATION FOR RELOCATED GENERATOR. EXACT LOCATION

SHALL BE COORDINATED WITH THE OWNER PRIOR TO ANY

ROUGH-IN. PROVIDE NEW HOUSE KEEPING PAD WITH 6IN APRON ON

ALL FOUR SIDES OF THE GENERATOR SET. COORDINATE WITH CIVIL

ENGINEER AS REQUIRED FOR EXACT CONCRETE REQUIREMENTS,

PAD THICKNESS, AND INSTALLATION REQUIREMENTS. COORDINATE

WITH KOHLER POWER FOR FOUNDATION ROUGH-IN AND BLOCKOUT

REQUIREMENTS FOR ALL REQUIRED UTILITY ENTRANCES THROUGH

SLAB.

2. EXISTING SERVICE DISCONNECT "SD-1". 208Y/120V, 1200A/3P, NEMA

3R. FIELD VERIFY EXACT LOCATION.

3. EXISTING SERVICE DISCONNECT "SD-2". 208Y/120V, 800A/3P, NEMA

3R. FIELD VERIFY EXACT LOCATION.

4. EXISTING UNDERGROUND 4"C ROUTED FROM BELOW EXISTING

SERVICE DISCONNECT TO EXISTING ELECTRICAL ROOM AS

INDICATED. FIELD VERIFY EXACT ROUTING UNDERGROUND AND

CONDUIT STUB LOCATIONS AT BOTH ENDS.

5. INTERCEPT EXISTING 4"C AT THIS APPROXIMATE LOCATION AND

REROUTE, UNDERGROUND, TO NEW GENERATOR LOCATION.

PROVIDE ANY NEW 4"C AS REQUIRED TO NEW GENERATOR

LOCATION. PROVIDE ALL HANDHOLES AND PULL BOXES AS

REQUIRED.

6. FIELD VERIFY EXACT LOCATION OF EXISTING 4" CONDUIT STUB.

PROVIDE NEW JUNCTION BOX, SIZE AS REQUIRED, FOR

CONNECTION TO NEW 1.5"C. PROVIDE NEW 1.5"C FROM JUNCTION

BOX TO NEW LOCATION OF RELOCATED TRANSFER SWITCH

LOCATED IN THE SECOND FLOOR ELECTRICAL ROOM. SEE

ENLARGED PLANS FOR LOCATIONS. CONDUIT SHALL BE ROUTED

CONCEALED THROUGH THE BUILDING AS REQUIRED. PROVIDE ALL

PULL BOXES AS REQUIRED BY THE NEC.

7. PROVIDE ONE(1) 1"C ROUTED UNDERGROUND FROM NEW

GENERATOR LOCATION TO EXTERIOR OF EXISTING WALL AS

INDICATED. CUT EXISTING CONCRETE AS RQUIRED FOR NEW

CONDUIT INSTALLATION. PATCH AND REPAIR CONCRETE TO MATCH

EXISTING. ROUTE CONDUIT UP EXISTING WALL TO NEW LB. TURN

CONDUIT THROUGH WALL AND ROUTE THROUGH BUILDING AS

REQUIRED TO NEW LOCATION OF RELOCATED GENERATOR PANEL

LOCATED IN THE SECOND FLOOR TELECOM ROOM. SEE ENLARGED

PLANS FOR LOCATIONS. PROVIDE ALL PULL BOXES AS RQUIRED BY

THE NEC. GENERATOR CIRCUITS NQ-2,4,6 SHALL BE ROUTED

THROUGH THIS SINGLE PIPE. MINIMUM WIRE SIZE SHALL BE

#10AWG. CONTRACTOR SHALL FIELD MARK ALL ASSOCIATED

JUNCTION AND PULL BOX COVERS WITH ALL ASSOCIATED CIRCUIT

NUMBERS AND THEIR SERVING PANELBOARD.

8. PROVIDE ONE(1) 3/4"C WITH PULL STRING ROUTED UNDERGROUND

FROM NEW GENERATOR LOCATION TO EXTERIOR OF EXISTING

WALL AS INDICATED. CUT EXISTING CONCRETE AS REQUIRED FOR

NEW CONDUIT INSTALLATION. PATCH AND REPAIR CONCRETE TO

MATCH EXISTING. ROUTE CONDUIT UP EXISTING WALL TO NEW LB.

TURN CONDUIT THROUGH WALL AND ROUTE THROUGH BUILDING

AS REQUIRED TO NEW LOCATION OF RELOCATED TRANSFER

SWITCH LOCATED IN THE SECOND FLOOR ELECTRICAL ROOM. SEE

ENLARGED PLANS FOR LOCATIONS. PROVIDE ALL PULL BOXES AS

REQUIRED BY THE NEC.

N

PLAN NORTH

N

TRUE NORTH

1/8" = 1'-0"

Enlarged Power Plan

CONTRACTOR SHALL PROVIDE A COMPREHENSIVE INSPECTION OF THE

EXISTING GENERATOR SYSTEM AND FUEL TANK. PROVIDE ALL

NECESSARY REPAIRS AND MAINTENANCE TO ENSURE THE GENERATOR

IS IN OPTIMAL WORKING CONDITION. REPAIR AND REPLACE ANY WORN

OR DAMAGED PARTS. SERVICE THE ENGINE, FUEL SYSTEM, AND

ELECTRICAL COMPONENTS. TEST AND REPLACE BATTERIES, FILTERS,

AND FLUIDS. ENSURE ALL SAFETY AND CONTROL SYSTEMS ARE

FUNCTIONING CORRECTLY. CONDUCT A THROUGH TEST TO CONFIRM

THE GENERATOR IS FULLY OPERATIONAL AND MEETS PERFORMANCE

SPECIFICATIONS. PERFORM LOAD TESTS AND ENSURE ALL SAFETY

SYSTEMS ARE FUNCTIONING CORRECTLY. ALL WORK MUST COMPLY

WITH LOCAL BUILDING CODES AND REGULATIONS. ENSURE ALL

NECESSARY PERMITS AND INSPECTIONS ARE OBTAINED AND

DOCUMENTED.

Electrical Site Plan - Annex

E2.01

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text X

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text 118281

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text

GRANT CLAUSSEN

AutoCAD SHX Text 05/30/24

U C

R e f r

U P

DN

UP

D N

City Engineer

CH208

Work Room

CH210

Asst. City Mgr

CH229

Exec. Conf.

CH202

Balcony

Arcade Roof Below

Asst. Director

CH225

Asst. P.W. Dir. /

Engi.

CH215

F. Asst. Dir.

CH214

Public Counter

Jan.

CH205

Printer

Asst. Director

CH227

Public Works

Director

CH209

E. I. T

CH206

E

Director

CH226

Stor.

CH213

Ice

C o f f e e

Stor.

CH218

C r o s s o v e r

6 11

Future Engineer

CH207

Chief Inspector

CH216

Asst. to City Mgr

CH228

A

Engineering

CH204

Stair #1

CHST1

Public Works

CH219

Stair #2

CHST2

Public Lobby

CH201

Utilities

CH221

Reception

CH220

R T

A

C H

A

E.1

8 9 107

B

D

E L E V

T V

C o f f e e

Ref.

Storage

CH232

Staff Bath

CH230

C o f f e e

S t o r

S t o r

S h e l v e s

Printer

R e f

OPEN

TO

BELOW

C

Corridor

CH203

Women

CH212

Men

CH211

P

Break Room

CH231

FIRE RISER

Electrical

CH223

ER-Equipment

CH222

8.2 8.8

B.1

LINE OF DOME ABOVE

5.1

Inspector Sup.

CH217

Utility Engineer

CH224

S t o r

S t o r

E.2

SF4

SF5

SF4

ENLARGED PLAN

E2.00 - 2

U P

D N

C r o s s o v e r

Stair #2

CHST2

FIRE RISER

Electrical

CH223

ER-Equipment

CH222

(E) PANEL 2LC

(E) PANEL 2LB

(E) PANEL 2LA

RELOCATED

PANEL NQ

RELOCATED

PANEL NF

RELOCATED

TRANSFORMER

RELOCATED

TRANSFER SWITCH

NQ-8

NQ-10

NQ-16

NQ-18

NQ-20

NQ-22

EXISTING FCU-5

EXISTING CU-5

ON ROOF

NQ-11,13

NQ-12,14

NQ-24,26

NQ-28,30

NQ-17,19

NQ-21,23

NQ-15

N

PLAN NORTH

N

TRUE NORTH

1" = 20'-0"

2nd Floor Power Plan

Dallas | Austin | San Antonio www.architexas.com

1907 Marilla St.

Second Floor

Dallas, Texas 75201 p 214.748.4561

City of Waxahachie

Waxahachie City Hall

401 S. Rogers St., Waxahachie, TX

75165

COPYRIGHT

The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.

Reproduction or use for any purpose other than that authorized by Architexas is forbidden.

REVISION HISTORY

CONSTRUCTION DOCUMENTS

Architexas No.

Sheet Name

Sheet Number

Date

05/30/2024

Engineering Firm : F-23407 Conquest Engineering, LLC 14901 Quorum Dr, Ste 300

Dallas, Texas 75254 gclaussen@conquestddg.com

N

PLAN NORTH

N

TRUE NORTH

1/4" = 1'-0"

2nd Floor Enlarged Power Plan

NOTES BY SYMBOL

1. APPROXIMATE ROUTING FOR NEW PANELBOARD FEEDER. NEW

FEEDER SHALL BE ROUTED ABOVE THE CORRIDOR CEILING.

COORDINATE EXACT ROUTING WITH SITE CONDITIONS. PROVIDE

ALL PULL BOXES AS REQUIRED BY THE NEC.

2. EXISTING ABANDONED CABLE TRAY IN THIS AREA TO BE REMOVED

TO ACCOMMODATE NEW PANEL INSTALLATION. COORDINATE

DEMOLITION SCOPE WITH THE OWNER PRIOR TO BEGINNING ANY

WORK.

3. ALL EQUIPMENT SHOWN IN THIS ROOM IS EXISTING TO REMAIN.

EXISTING CIRCUITS SHALL BE REROUTED TO PANEL NQ AS

INDICATED. PROVIDE ALL NEW CONDUIT AND WIRE AS REQUIRED,

SIZE AND TYPE TO MATCH EXISTING. CONTRACTOR SHALL FIELD

VERIFY THE SERVING CIRCUIT BREAKER LOCATIONS FOR ALL

EQUIPMENT SHOWN. EXISTING BREAKERS SHALL BE RELABELED AS

"SPARE" AND SET TO THE "OFF" POSITION.

N.T.S.

ONE-LINE DIAGRAM

NOTES BY SYMBOL

1. PROVIDE #8G TO NEW 3/4"X20' COPPER CLAD GROUND ROD.

PROVIDE BURNDY HYGROUND DIRECT BURIAL HIGH COMPRESSION

CLAMPS.

2. NEW 4#4,#8G ROUTED IN NEW 4" UNDERGROUND CONDUIT.

3. NEW 4#4,#8G ROUTED IN EXISTING 4" UNDERGROUND CONDUIT.

4. NEW 4#4,#8G ROUTED IN NEW 1.5" CONDUIT.

5. EXISTING 4"C TO BE ABANDONED IN PLACE. FIELD VERIFY EXACT

LOCATION.

6. INTERCEPT EXISTING 4"C AND PROVIDE NEW 4"C TO NEW

GENERATOR LOCATION. SEE SHEET E2.01 FOR ADDITIONAL

REQUIREMENTS.

7. NEW JUNCTION BOX, SIZE AS REQUIRED.

8. NEW 4#4,#8G,1.5"C

9. NEW 3#8,#10G,3/4"C

10. NEW 4#3,#8G,1.25"C

11. PROVIDE #8G TO BUILDING GROUNDING ELECTRODE SYSTEM.

PROVIDE HIGH COMPRESSION CLAMPS OR EXOTHERMIC WELDS.

Electrical 2nd Floor - Power

- Annex

E2.02

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text J

AutoCAD SHX Text 1st FLOOR ELECTRICAL ROOM

AutoCAD SHX Text

RELOCATED GENERATOR

AutoCAD SHX Text

FLOOR

AutoCAD SHX Text

EXTERIOR

AutoCAD SHX Text

EXISTING SD-1

AutoCAD SHX Text

EXISTING SD-2

AutoCAD SHX Text 2nd FLOOR ELECTRICAL ROOM

AutoCAD SHX Text 2nd FLOOR ER-EQUIPMENT ROOM

AutoCAD SHX Text

RELOCATED TRANSFER SWITCH

AutoCAD SHX Text

RELOCATED TRANSFERFORMER

AutoCAD SHX Text

RELOCATED PANEL "NF" 125A 480Y/277V 3PH/4W

AutoCAD SHX Text

AutoCAD SHX Text

RELOCATED PANEL "NQ" 225A 208Y-120V 3PH/4W

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NEW 80A/3P 65,00 AIC

AutoCAD SHX Text

EXISTING PANEL "MSB-1" 1200A M.C.B. 208Y/120V QED SQ-D SWITCHBOARD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text L

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text X

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text 118281

AutoCAD SHX Text F

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text

GRANT CLAUSSEN

AutoCAD SHX Text 05/30/24

AutoCAD SHX Text

Sheets
A0.00 - Cover Sheet
A1.00 - Site Plan

File details come from the government source that posted it. Updated .