Generator_Relocation_Site_Plans_and_Specifications.pdf
PDF 6 MB Posted
- Attached to
- Generator Relocation
- Solicitation number
- 2024-08-21
- Issued by
- Ellis County, Texas
About this file
These are comprehensive construction documents and site plans for the Waxahachie City Hall Generator Relocation Project prepared by Architexas and Conquest Engineering for the City of Waxahachie, Texas, dated May 30, 2024. The project involves relocating an existing 80kW Kohler Power Systems standby generator from the current City Hall location at 401 S. Rogers Street to the new City Hall Annex across the street. The detailed plans include site layouts, electrical site plans, power distribution diagrams, and specific relocation instructions encompassing the generator's physical move, electrical reconnection, and system integration.
The documents specify extensive technical requirements for the generator relocation, including providing a new concrete housekeeping pad, rerouting underground conduits, reconnecting electrical systems, and performing comprehensive generator system inspection and maintenance. The project requires the contractor to service the generator, test all safety and control systems, replace batteries and filters, and ensure full operational compliance with local building codes. The electrical plans detail precise routing of power feeders, grounding systems, and panel relocations, with specific notes about coordinating exact locations with the owner and maintaining existing electrical infrastructure during the transition.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Generator_Relocation.pdf | ||
| Picture_of_Generator_at_Current_Location.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Waxahachie City Hall Renovation401 S. Rogers Street, Waxahachie, TX 75165
May 30, 2024
Generator Relocation Package
STREET MAPVICINITY MAPSYMBOL LEGEND
Room name
150 SF
1t
1i
A101
SIM
BROKEN SECTION
A101
SIM
WALL SECTION
DETAIL SECTION
DETAIL KEY
DETAIL KEY
BUILDING ELEVATION KEY
COLUMN CENTER LINE
FLOOR LEVEL
CHANGE
CENTER LINE
DOOR TYPE
WINDOW TYPE
WALL TYPE
ROOM NAME,
NUMBER, & SQUARE
FOOTAGE
BREAK LINE
A101
SIM
A101
SIM
A101
SIM
A101
SIM
MATERIAL LEGEND
EARTH/COMPACT
FILL
GRAVEL FILL
SAND FILL
CAST-IN-PLACE
CONC.
LIGHTWEIGHT
CONC.
FACE BRICK
COMMON BRICK
CMU
CAST STONE
GLASS
STEEL
ALUMINUM
SHEET METAL
FRT ROUGH WOOD
FRT BLOCKING
FINISH WOOD
PLYWOOD
RIGID INSULATION
THERMAL/ ACOUSTIC INSULATION
SPRAYED FIRE INSULATION
CERAMIC TILE
TYPE 'X' GYP.
BOARD
METAL LATH & PLASTER
CARPET
HOLLOW CLAY TILE
WAXAHACHIE CITY HALL ANNEX
CITY OF WAXAHACHIE CITY OF WAXAHACHIE
WAXAHACHIE CITY HALL ANNEX
WAXAHACHIE CITY HALL
WAXAHACHIE CITY HALL
1. THE WORK SHALL CONFORM WITH THE CURRENT EDITION OF THE FOLLOWING REGULATIONS AS ADOPTED BY THE
CITY OF WAXAHACHIE:
-2018 INTERNATIONAL BUILDING CODE W/ NCTCOG AMENDMENTS
-2018 INTERNATIONAL EXISTING BUILDING CODE W/ NCTCOG AMENDMENTS
-2018 INTERNATIONAL FIRE CODE W/ WAXAHACHIE AMENDMENTS
-2018 INTERNATIONAL PLUMBING CODE W/ NCTCOG AMENDMENTS
-2018 INTERNATIONAL MECHANICAL CODE W/ NCTCOG AMENDMENTS
-2017 NATIONAL ELECTRICAL CODE W/ NCTCOG AMENDMENTS
-2018 INTERNAL ENERGY CONSERVATION CODE W/ NCTCOG AMENDMENTS
-U.S. DEPARTMENT OF LABOR, OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
2. THE CONTRACTOR SHALL VISIT THE SITE TO REVIEW AND SURVEY EXISTING CONDITIONS TO FULLY
UNDERSTAND SCOPE OF WORK.
3. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND INSPECTIONS AND PAY ALL APPLICATION FEES.
4. IF THE CONTRACTOR PERFORMS OR PROCEEDS WITH ANY WORK, CONTRARY TO APPLICABLE LAWS, ORDINANCES, RULES AND REGULATIONS WITHOUT GIVING PRIOR WRITTEN NOTICE TO THE ARCHITECT, HE/SHE SHALL ASSUME
FULL RESPONSIBILITY THEREFORE AND SHALL BEAR ALL COST ATTRIBUTABLE.
5. THE CONTRACTOR SHALL CAREFULLY STUDY THE CONTRACT DOCUMENTS PRIOR TO CONSTRUCTION AND SHALL
REPORT TO THE ARCHITECT ANY ERROR, INCONSISTENCY OR OMISSION DISCOVERED AND SHALL NOT PROCEED
WITH THE WORK UNTIL THE INTENT OF THE DOCUMENTS IS VERIFIED BY THE ARCHITECT.
6. ALL DRAWINGS AND SPECIFICATIONS FORMING PART OF THE CONSTRUCTION DOCUMENTS ARE COMPLEMENTARY, AND WHAT IS CALLED FOR BY ONE WILL BE BINDING AS IF CALLED FOR BY ALL; ANY WORK SHOWN OR REFERRED TO
ON ANY ONE DOCUMENT SHALL BE PROVIDED AS THOUGH SHOWN ON ALL DOCUMENTS.
7. THE CONTRACT DOCUMENTS SHALL BE INTERPRETED WITH THE FOLLOWING ORDER OF PRECEDENCE:
SPECIFICATIONS, DETAILS, ENLARGEMENTS, OVERALL DRAWINGS, AND SUBSEQUENT CLARIFICATIONS. ADDENDA
SHALL OVERRIDE THE AFFECTED COMPONENTS IN ALL OF THE ABOVE. ALL VERBAL CLARIFICATIONS ARE TO BE
RECORDED BY THE CONTRACTOR AND SENT TO THE ARCHITECT WITHIN SEVEN DAYS OF THE OCCURRENCE.
8. THE STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND AUDIO/VISUAL DOCUMENTS ARE SUPPLEMENTARY
TO THE ARCHITECTURAL DOCUMENTS. SHOULD THERE BE A DISCREPANCY BETWEEN THE ARCHITECTURAL
DOCUMENTS AND THE STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL, AND AUDIO/VISUAL DOCUMENTS, SUCH DISCREPANCY IS TO BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. THE CONTRACTOR SHALL RECEIVE
INSTRUCTIONS PRIOR TO INSTALLATION OR PERFORMANCE OF SAID WORK. ANY WORK PERFORMED OR INSTALLED
IN CONFLICT WITH THE DOCUMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE.
9. INFORMATION CONTAINED ON THESE DRAWINGS WITH REGARD TO EXISTING CONDITIONS OF CONSTRUCTION IS
PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR EXECUTING THE WORK. EVERY ATTEMPT HAS BEEN MADE
TO PROVIDE COMPLETE AND ACCURATE REPRESENTATIONS OF SUCH EXISTING CONDITIONS. THIS
INTERPRETATION HAS BEEN TAKEN BY FIELD MEASUREMENT AND OBSERVATION. THE ARCHITECT HAS
ENDEAVORED TO IDENTIFY AS COMPLETELY AS POSSIBLE IN THE CONSTRUCTION DOCUMENTS, EXISTING ITEMS OF
EQUIPMENT AND CONSTRUCTION THAT ARE REQUIRED TO BE REMOVED OR OTHERWISE DEMOLISHED. THIS
INFORMATION IS PROVIDED FOR THE CONVENIENCE OF THE CONTRACTOR AND IS IN NO WAY INTENDED TO MEAN
THAT DEMOLITION IS LIMITED ONLY TO THOSE ITEMS SPECIFICALLY IDENTIFIED. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO EXECUTE DEMOLITION WORK AS REQUIRED TO REMOVE ELEMENTS AND SYSTEMS IDENTIFIED
IN THE CONSTRUCTION DOCUMENTS, ALONG WITH THEIR ASSOCIATED PARTS.
10. ALL AREAS AND ITEMS INDICATING CONTRACT LIMITS AND LINES OF DEMARCATION ARE SHOWN FOR THE
CONVENIENCE OF THE CONTRACTOR AND ARE NOT TO BE TAKEN LITERALLY. ACTUAL CONTRACT LIMITS ARE TO BE
DETERMINED PRIOR TO CONSTRUCTION BY FIELD VERIFICATION.
11. CONTRACTOR TO ASSIST THE ARCHITECT IN MAKING THEIR EVALUATIONS AND RECOMMENDATIONS BY PROVIDING
IN A TIMELY MANNER, AT NO ADDITIONAL COST TO THE OWNER, ACCURATE AND COMPLETE DRAWINGS, SKETCHES, AND PHOTOGRAPHS, SUFFICIENT TO CLEARLY DESCRIBE DISCREPANCIES, CONFLICTS, AND CONCEALED OR
OTHERWISE UNANTICIPATED CONDITIONS AFFECTING NEW CONSTRUCTION.
12. FIELD VERIFICATIONS OF EXISTING CONDITIONS RELATED TO SPECIFIC PORTIONS OF THE WORK SHALL BE
UNDERTAKEN IN ADVANCE TO ALLOW FOR THE TIMELY IDENTIFICATION OF EXISTING CONDITIONS THAT MAY AFFECT
THE SCHEDULED INSTALLATION OF NEW WORK AS DESIGNED AND DETAILED, AND TO AVOID UNDUE AND
UNREASONABLE DELAYS TO THE PROJECT SHOULD SUCH CONDITIONS BE DISCOVERED. TIMELY IDENTIFICATION OF
SUCH CONDITIONS SHALL PROVIDE FOR A MINIMUM PERIOD OF 10 (TEN) WORKING DAYS DURING WHICH TIME THE
ARCHITECT WILL EVALUATE THE CONDITION AND MAKE RECOMMENDATIONS FOR ACCOMMODATING NEW WORK.
13. CONTRACTOR IS TO PROVIDE AND INSTALL ALL ACCESS PANELS, RATED OR OTHERWISE, SIZE AS REQUIRED, AT ALL
CONCEALED MECHANICAL AND PLUMBING ITEMS WHICH REQUIRE SERVICE OR ACCESS (VALVES, FIE DAMPERS, DUCT HEATERS, ETC.). ACCESS PANELS IN RATED CEILINGS AND PARTITIONS SHALL HAVE THE APPROPRIATE UL
LABELS.
14. THE CONTRACTOR SHALL COORDINATE ALL WORK WITH ALL EQUIPMENT MANUFACTURER'S ROUGH-IN
REQUIREMENTS.
15. NOTIFY CITY OF WAXAHACHIE WHEN IT IS NECESSARY TO AFFECT UTILITIES BEFORE PROCEEDING WITH THE WORK.
ALL EXISTING UTILITIES MUST BE CHECKED BY THE CONTRACTOR PRIOR TO THE COMMENCEMENT OF DEMOLITION
WORK. ANY DAMAGES RESULTING FROM LACK OF COMPLIANCE WITH THE PROVISIONS SHOULD BE CORRECTED BY
THE CONTRACTOR AT HIS OR HER OWN EXPENSE.
GENERAL NOTES
COPYRIGHT
Dallas | Austin | San Antonio www.architexas.com
1907 Marilla St.
Second Floor
Dallas, Texas 75201 p 214.748.4561
The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.
Reproduction or use for any purpose other than that authorized by Architexas is forbidden.
REVISION HISTORY
#9409
Architexas No.
Sheet Name
Date
Sheet Number
5/30/2024
City of Waxahachie
Waxahachie City Hall
A0.00
401 S. Rogers St., Waxahachie, TX
75165
CONSTRUCTION DOCUMENTS
2407 05/30/2024
Cover Sheet
DN
DN
DN
DNDNDN
DN
TRASH
BRIDGE ABOVE
S Rogers St
RETAIL
CITY HALL ANNEX
CITY HALL
PLAZA
A
R C
A D
E
7 10
VAN14
UP
A1.00
LIMIT OF WORK
RELOCATE GENERATOR FROM
EXISTING LOCATION AT CITY HALL, REF. MEP
6" CONC. CURB, MATCH EXISTING
(REF. P1/C11.00 FROM WAXAHACHIE CITY HALL
ANNEX PROJECT)
8'-0" HEIGHT ALUM. PERFORATED MECH. FENCE,
BASIS OF DESIGN: POLARIS ALUMINUM FENCE
DESIGN SYSTEM, MANUFACTURED BY AMETCO
PROVIDE SLAB FOR GENERATOR
R
' - 0
/4
/4
PROVIDE IRRIGATION FOR
PLANTINGS BY OWNER.
COORDINATE EXACT
LOCATIONS W/ OWNER
DEMO PAVING AS REQ'D TO INSTALL NEW
LANDSCAPE AREA FOR GENERATOR
6" DIA X 36" H BOLLARD
@ 4' - 0" O.C., MAX., PAINT
DEMO AND REPLACE FULL
CONCRETE PANEL
PATH OF CONDUIT
UNDERGROUND, REF. MEP
RUN FEEDERS TIGHT TO
BUILDING, PAINT TO
MATCH BRICK AND STONE
FIRE CAULK CONDUIT AT ALL
PENETRATIONS THROUGH
WALLS OF RISER ROOM
TO ELECTRICAL ROOM
3' - 0"
15' - 0" 4' - 8"
DEMO EXISTING CURB
COPYRIGHT
Dallas | Austin | San Antonio www.architexas.com
1907 Marilla St.
Second Floor
Dallas, Texas 75201 p 214.748.4561
The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.
Reproduction or use for any purpose other than that authorized by Architexas is forbidden.
REVISION HISTORY
#9409
Architexas No.
Sheet Name
Date
Sheet Number
5/30/2024
City of Waxahachie
Waxahachie City Hall
A1.00
401 S. Rogers St., Waxahachie, TX
75165
CONSTRUCTION DOCUMENTS
2407 05/30/2024
Site Plan
N
PLAN NORTH
N
TRUE NORTH
1" = 20'-0"
Site Plan
1/8" = 1'-0"
Enlarged Site Plan
UP
UP
UP
X
UP
(E) GENERATOR
ENLARGED PLAN
E2.00 - 2
(E) MDP
(E) PANEL NQ
(E) PANEL NF
(E) TRANSFER SWITCH
(E) TRANSFORMER
N
PLAN NORTH
N
TRUE NORTH
1" = 20'-0"
Site Plan
Dallas | Austin | San Antonio www.architexas.com
1907 Marilla St.
Second Floor
Dallas, Texas 75201 p 214.748.4561
City of Waxahachie
Waxahachie City Hall
401 S. Rogers St., Waxahachie, TX
75165
COPYRIGHT
The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.
Reproduction or use for any purpose other than that authorized by Architexas is forbidden.
REVISION HISTORY
CONSTRUCTION DOCUMENTS
Architexas No.
Sheet Name
Sheet Number
Date
05/30/2024
Engineering Firm : F-23407 Conquest Engineering, LLC 14901 Quorum Dr, Ste 300
Dallas, Texas 75254 gclaussen@conquestddg.com
NOTES BY SYMBOL
1. EXISTING KOHLER POWER SYSTEMS STANDBY GENERATOR,
480Y/277V, 80KW, 80 AMP MCB WITH KOHLER DECISION-MAKER 3000.
UNIT TO BE RELOCATED TO NEW ANNEX BUILDING ACROSS THE
STREET. ENTIRE STANDBY GENERATOR SYSTEM AND ATS TO BE
FULLY SERVICED AND IN GOOD WORKING CONDITION.
2. ALL EQUIPMENT IN THIS AREA, PART OF THE EMERGENCY POWER
DISTRIBUTION SYSTEM TO BE REMOVED, SERVICED, CLEANED,
RELOCATED AND REINSTALLED AT ANNEX BUILDING ACROSS THE
STREET.
3. EXISTING 480Y/277V, EMERGENCY POWER PANELBOARD, SQUARE
D, TYPE NF, 125A BUS, 3PH, 4W, MLO, PROTECTED UPSTREAM AT
THE GENERATOR BY AN 80A/3PH CIRCUIT BREAKER. EXISTING
50A/3P, 20A/3P, AND (2) 20A/1P CIRCUIT BREAKERS TO REMAIN.
4. EXISTING 30KVA, 480 DELTA / 208Y/120V, 150 DEGREE C, TYPE 2
ENCLOSURE, DRY-TYPE TRANSFORMER HUNG FROM STRUCTURE
TO BE RELOCATED. SQUARE D, CAT NO: 30T3H
5. EXISTING KOHLER DECISION-MAKER MPAC 1200, AUTOMATICE
TRANSFER SWITCH TO BE RELOCATED. SYSTEM AT TIME OF
INSPECTION HAD A WARNING MESSAGE. SYSTEM TO BE FULL
SERVICED TO GOOD WORKING CONDITION.
N
PLAN NORTH
N
TRUE NORTH
1/4" = 1'-0"
Enlarged Site Plan
Electrical Site Plan - City Hall
E2.00
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text 118281
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text
GRANT CLAUSSEN
AutoCAD SHX Text 05/30/24
AutoCAD SHX Text X
R e f r i g e r a t o r
DN
DN
DN
DNDNDN
DN
UP
ENLARGED PLAN
E2.01 - 2
RELOCATED GENERATOR
(E) TRANSFORMER
(E) SD-2
(E) SD-1
NEW LB'S
EXISTING
PANEL "MSB-1"
NEW PATH OF CONDUIT
UNDERGROUND
N
PLAN NORTH
N
TRUE NORTH
1/32" = 1'-0"
Site Plan
Dallas | Austin | San Antonio www.architexas.com
1907 Marilla St.
Second Floor
Dallas, Texas 75201 p 214.748.4561
City of Waxahachie
Waxahachie City Hall
401 S. Rogers St., Waxahachie, TX
75165
COPYRIGHT
The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.
Reproduction or use for any purpose other than that authorized by Architexas is forbidden.
REVISION HISTORY
CONSTRUCTION DOCUMENTS
Architexas No.
Sheet Name
Sheet Number
Date
05/30/2024
Engineering Firm : F-23407 Conquest Engineering, LLC 14901 Quorum Dr, Ste 300
Dallas, Texas 75254 gclaussen@conquestddg.com
NOTES BY SYMBOL
1. NEW LOCATION FOR RELOCATED GENERATOR. EXACT LOCATION
SHALL BE COORDINATED WITH THE OWNER PRIOR TO ANY
ROUGH-IN. PROVIDE NEW HOUSE KEEPING PAD WITH 6IN APRON ON
ALL FOUR SIDES OF THE GENERATOR SET. COORDINATE WITH CIVIL
ENGINEER AS REQUIRED FOR EXACT CONCRETE REQUIREMENTS,
PAD THICKNESS, AND INSTALLATION REQUIREMENTS. COORDINATE
WITH KOHLER POWER FOR FOUNDATION ROUGH-IN AND BLOCKOUT
REQUIREMENTS FOR ALL REQUIRED UTILITY ENTRANCES THROUGH
SLAB.
2. EXISTING SERVICE DISCONNECT "SD-1". 208Y/120V, 1200A/3P, NEMA
3R. FIELD VERIFY EXACT LOCATION.
3. EXISTING SERVICE DISCONNECT "SD-2". 208Y/120V, 800A/3P, NEMA
3R. FIELD VERIFY EXACT LOCATION.
4. EXISTING UNDERGROUND 4"C ROUTED FROM BELOW EXISTING
SERVICE DISCONNECT TO EXISTING ELECTRICAL ROOM AS
INDICATED. FIELD VERIFY EXACT ROUTING UNDERGROUND AND
CONDUIT STUB LOCATIONS AT BOTH ENDS.
5. INTERCEPT EXISTING 4"C AT THIS APPROXIMATE LOCATION AND
REROUTE, UNDERGROUND, TO NEW GENERATOR LOCATION.
PROVIDE ANY NEW 4"C AS REQUIRED TO NEW GENERATOR
LOCATION. PROVIDE ALL HANDHOLES AND PULL BOXES AS
REQUIRED.
6. FIELD VERIFY EXACT LOCATION OF EXISTING 4" CONDUIT STUB.
PROVIDE NEW JUNCTION BOX, SIZE AS REQUIRED, FOR
CONNECTION TO NEW 1.5"C. PROVIDE NEW 1.5"C FROM JUNCTION
BOX TO NEW LOCATION OF RELOCATED TRANSFER SWITCH
LOCATED IN THE SECOND FLOOR ELECTRICAL ROOM. SEE
ENLARGED PLANS FOR LOCATIONS. CONDUIT SHALL BE ROUTED
CONCEALED THROUGH THE BUILDING AS REQUIRED. PROVIDE ALL
PULL BOXES AS REQUIRED BY THE NEC.
7. PROVIDE ONE(1) 1"C ROUTED UNDERGROUND FROM NEW
GENERATOR LOCATION TO EXTERIOR OF EXISTING WALL AS
INDICATED. CUT EXISTING CONCRETE AS RQUIRED FOR NEW
CONDUIT INSTALLATION. PATCH AND REPAIR CONCRETE TO MATCH
EXISTING. ROUTE CONDUIT UP EXISTING WALL TO NEW LB. TURN
CONDUIT THROUGH WALL AND ROUTE THROUGH BUILDING AS
REQUIRED TO NEW LOCATION OF RELOCATED GENERATOR PANEL
LOCATED IN THE SECOND FLOOR TELECOM ROOM. SEE ENLARGED
PLANS FOR LOCATIONS. PROVIDE ALL PULL BOXES AS RQUIRED BY
THE NEC. GENERATOR CIRCUITS NQ-2,4,6 SHALL BE ROUTED
THROUGH THIS SINGLE PIPE. MINIMUM WIRE SIZE SHALL BE
#10AWG. CONTRACTOR SHALL FIELD MARK ALL ASSOCIATED
JUNCTION AND PULL BOX COVERS WITH ALL ASSOCIATED CIRCUIT
NUMBERS AND THEIR SERVING PANELBOARD.
8. PROVIDE ONE(1) 3/4"C WITH PULL STRING ROUTED UNDERGROUND
FROM NEW GENERATOR LOCATION TO EXTERIOR OF EXISTING
WALL AS INDICATED. CUT EXISTING CONCRETE AS REQUIRED FOR
NEW CONDUIT INSTALLATION. PATCH AND REPAIR CONCRETE TO
MATCH EXISTING. ROUTE CONDUIT UP EXISTING WALL TO NEW LB.
TURN CONDUIT THROUGH WALL AND ROUTE THROUGH BUILDING
AS REQUIRED TO NEW LOCATION OF RELOCATED TRANSFER
SWITCH LOCATED IN THE SECOND FLOOR ELECTRICAL ROOM. SEE
ENLARGED PLANS FOR LOCATIONS. PROVIDE ALL PULL BOXES AS
REQUIRED BY THE NEC.
N
PLAN NORTH
N
TRUE NORTH
1/8" = 1'-0"
Enlarged Power Plan
CONTRACTOR SHALL PROVIDE A COMPREHENSIVE INSPECTION OF THE
EXISTING GENERATOR SYSTEM AND FUEL TANK. PROVIDE ALL
NECESSARY REPAIRS AND MAINTENANCE TO ENSURE THE GENERATOR
IS IN OPTIMAL WORKING CONDITION. REPAIR AND REPLACE ANY WORN
OR DAMAGED PARTS. SERVICE THE ENGINE, FUEL SYSTEM, AND
ELECTRICAL COMPONENTS. TEST AND REPLACE BATTERIES, FILTERS,
AND FLUIDS. ENSURE ALL SAFETY AND CONTROL SYSTEMS ARE
FUNCTIONING CORRECTLY. CONDUCT A THROUGH TEST TO CONFIRM
THE GENERATOR IS FULLY OPERATIONAL AND MEETS PERFORMANCE
SPECIFICATIONS. PERFORM LOAD TESTS AND ENSURE ALL SAFETY
SYSTEMS ARE FUNCTIONING CORRECTLY. ALL WORK MUST COMPLY
WITH LOCAL BUILDING CODES AND REGULATIONS. ENSURE ALL
NECESSARY PERMITS AND INSPECTIONS ARE OBTAINED AND
DOCUMENTED.
Electrical Site Plan - Annex
E2.01
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text 118281
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text
GRANT CLAUSSEN
AutoCAD SHX Text 05/30/24
U C
R e f r
U P
DN
UP
D N
City Engineer
CH208
Work Room
CH210
Asst. City Mgr
CH229
Exec. Conf.
CH202
Balcony
Arcade Roof Below
Asst. Director
CH225
Asst. P.W. Dir. /
Engi.
CH215
F. Asst. Dir.
CH214
Public Counter
Jan.
CH205
Printer
Asst. Director
CH227
Public Works
Director
CH209
E. I. T
CH206
E
Director
CH226
Stor.
CH213
Ice
C o f f e e
Stor.
CH218
C r o s s o v e r
6 11
Future Engineer
CH207
Chief Inspector
CH216
Asst. to City Mgr
CH228
A
Engineering
CH204
Stair #1
CHST1
Public Works
CH219
Stair #2
CHST2
Public Lobby
CH201
Utilities
CH221
Reception
CH220
R T
A
C H
A
E.1
8 9 107
B
D
E L E V
T V
C o f f e e
Ref.
Storage
CH232
Staff Bath
CH230
C o f f e e
S t o r
S t o r
S h e l v e s
Printer
R e f
OPEN
TO
BELOW
C
Corridor
CH203
Women
CH212
Men
CH211
P
Break Room
CH231
FIRE RISER
Electrical
CH223
ER-Equipment
CH222
8.2 8.8
B.1
LINE OF DOME ABOVE
5.1
Inspector Sup.
CH217
Utility Engineer
CH224
S t o r
S t o r
E.2
SF4
SF5
SF4
ENLARGED PLAN
E2.00 - 2
U P
D N
C r o s s o v e r
Stair #2
CHST2
FIRE RISER
Electrical
CH223
ER-Equipment
CH222
(E) PANEL 2LC
(E) PANEL 2LB
(E) PANEL 2LA
RELOCATED
PANEL NQ
RELOCATED
PANEL NF
RELOCATED
TRANSFORMER
RELOCATED
TRANSFER SWITCH
NQ-8
NQ-10
NQ-16
NQ-18
NQ-20
NQ-22
EXISTING FCU-5
EXISTING CU-5
ON ROOF
NQ-11,13
NQ-12,14
NQ-24,26
NQ-28,30
NQ-17,19
NQ-21,23
NQ-15
N
PLAN NORTH
N
TRUE NORTH
1" = 20'-0"
2nd Floor Power Plan
Dallas | Austin | San Antonio www.architexas.com
1907 Marilla St.
Second Floor
Dallas, Texas 75201 p 214.748.4561
City of Waxahachie
Waxahachie City Hall
401 S. Rogers St., Waxahachie, TX
75165
COPYRIGHT
The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing. Any errors or omissions shall be reported to Architexas without delay. The Copyrights to all designs and drawings are the property of Architexas.
Reproduction or use for any purpose other than that authorized by Architexas is forbidden.
REVISION HISTORY
CONSTRUCTION DOCUMENTS
Architexas No.
Sheet Name
Sheet Number
Date
05/30/2024
Engineering Firm : F-23407 Conquest Engineering, LLC 14901 Quorum Dr, Ste 300
Dallas, Texas 75254 gclaussen@conquestddg.com
N
PLAN NORTH
N
TRUE NORTH
1/4" = 1'-0"
2nd Floor Enlarged Power Plan
NOTES BY SYMBOL
1. APPROXIMATE ROUTING FOR NEW PANELBOARD FEEDER. NEW
FEEDER SHALL BE ROUTED ABOVE THE CORRIDOR CEILING.
COORDINATE EXACT ROUTING WITH SITE CONDITIONS. PROVIDE
ALL PULL BOXES AS REQUIRED BY THE NEC.
2. EXISTING ABANDONED CABLE TRAY IN THIS AREA TO BE REMOVED
TO ACCOMMODATE NEW PANEL INSTALLATION. COORDINATE
DEMOLITION SCOPE WITH THE OWNER PRIOR TO BEGINNING ANY
WORK.
3. ALL EQUIPMENT SHOWN IN THIS ROOM IS EXISTING TO REMAIN.
EXISTING CIRCUITS SHALL BE REROUTED TO PANEL NQ AS
INDICATED. PROVIDE ALL NEW CONDUIT AND WIRE AS REQUIRED,
SIZE AND TYPE TO MATCH EXISTING. CONTRACTOR SHALL FIELD
VERIFY THE SERVING CIRCUIT BREAKER LOCATIONS FOR ALL
EQUIPMENT SHOWN. EXISTING BREAKERS SHALL BE RELABELED AS
"SPARE" AND SET TO THE "OFF" POSITION.
N.T.S.
ONE-LINE DIAGRAM
NOTES BY SYMBOL
1. PROVIDE #8G TO NEW 3/4"X20' COPPER CLAD GROUND ROD.
PROVIDE BURNDY HYGROUND DIRECT BURIAL HIGH COMPRESSION
CLAMPS.
2. NEW 4#4,#8G ROUTED IN NEW 4" UNDERGROUND CONDUIT.
3. NEW 4#4,#8G ROUTED IN EXISTING 4" UNDERGROUND CONDUIT.
4. NEW 4#4,#8G ROUTED IN NEW 1.5" CONDUIT.
5. EXISTING 4"C TO BE ABANDONED IN PLACE. FIELD VERIFY EXACT
LOCATION.
6. INTERCEPT EXISTING 4"C AND PROVIDE NEW 4"C TO NEW
GENERATOR LOCATION. SEE SHEET E2.01 FOR ADDITIONAL
REQUIREMENTS.
7. NEW JUNCTION BOX, SIZE AS REQUIRED.
8. NEW 4#4,#8G,1.5"C
9. NEW 3#8,#10G,3/4"C
10. NEW 4#3,#8G,1.25"C
11. PROVIDE #8G TO BUILDING GROUNDING ELECTRODE SYSTEM.
PROVIDE HIGH COMPRESSION CLAMPS OR EXOTHERMIC WELDS.
Electrical 2nd Floor - Power
- Annex
E2.02
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text J
AutoCAD SHX Text 1st FLOOR ELECTRICAL ROOM
AutoCAD SHX Text
RELOCATED GENERATOR
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
EXISTING SD-1
AutoCAD SHX Text
EXISTING SD-2
AutoCAD SHX Text 2nd FLOOR ELECTRICAL ROOM
AutoCAD SHX Text 2nd FLOOR ER-EQUIPMENT ROOM
AutoCAD SHX Text
RELOCATED TRANSFER SWITCH
AutoCAD SHX Text
RELOCATED TRANSFERFORMER
AutoCAD SHX Text
RELOCATED PANEL "NF" 125A 480Y/277V 3PH/4W
AutoCAD SHX Text
AutoCAD SHX Text
RELOCATED PANEL "NQ" 225A 208Y-120V 3PH/4W
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW 80A/3P 65,00 AIC
AutoCAD SHX Text
EXISTING PANEL "MSB-1" 1200A M.C.B. 208Y/120V QED SQ-D SWITCHBOARD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text L
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text X
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text 118281
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text
GRANT CLAUSSEN
AutoCAD SHX Text 05/30/24
AutoCAD SHX Text
| Sheets |
| A0.00 - Cover Sheet |
| A1.00 - Site Plan |
File details come from the government source that posted it. Updated .