GEMS 15 kVA UPS Technical Specifications - BR LS.xlsx
XLSX spreadsheet 15 KB Posted
- Attached to
- EMA - GEMS Facility UPS - 15KVA
- Solicitation number
- 26-588IEMA-MGMTA-B-52266
- Issued by
- Illinois
About this file
This document contains technical specifications for a 15 kVA Uninterruptible Power Supply (UPS) system procured by the State of Illinois for the GEMS Facility. The specification details call for an Eaton 9355 model UPS with a 3-high cabinet configuration and 64 battery capacity, rated at 15 KVA / 13.5 KW at 0.9 power factor. The unit operates using double conversion topology with input voltage of 208/120V AC, three-phase, four-wire configuration, and delivers sinewave output at the same voltage specifications with 91% efficiency at full load. The system includes two external battery cabinets (EBM 96 configuration) and features automatic bypass capability on overload or UPS failure, with an on-line transfer time of 1 millisecond. The installation location is specified as on-site at Braidwood and LaSalle Nuclear Generating Stations. This bid was cloned from a previous bid (B-51543) due to an administrative error and will be awarded to the lowest bidder meeting the specified technical requirements.
The vendor selected for this contract must be certified by the manufacturer to perform initial startup of the equipment per manufacturer requirements. The UPS system includes integrated communications capabilities with a graphical LCD display, RS-232 connectivity, and industrial gateway card functionality with factory-installed MS Network Card supporting SNMP protocols. The standard warranty includes one year of full parts and labor coverage with 24/7 on-site emergency response within eight hours of notification. Additionally, the selected vendor must provide unlimited 24/7 technical support availability. Quality certification to ISO 9001 standards is required, and the system operates at noise levels below 58 dBA at full load at one meter distance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| standard-terms-and-conditions 4~51.pdf | ||
| B-51543 Q and A.docx | DOCX document | |
| Standard Illinois Certifications v.26.2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 GEMS UPS Technical Specifications
| Tech Specs | |
| Model | Eaton 9355 |
| Cabinet Style | 3 High w/ 64 Battery |
| Power | |
| Ratings | 15 KVA / 13.5KW @ 0.9 P.F. |
| Topology | Double Conversion |
| Input | |
| Input Voltage | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Input Frequency | 60 Hz ± 5 Hz |
| Voltage Correction Range | 176-228.8V AC |
| Power Factor (Full Load) | 0.99 typical |
| Output | |
| Waveform (On-Line) | Sinewave |
| Waveform (On-Battery) | Sinewave |
| Output Voltage (RMS) | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Output Frequency | 60 Hz |
| Efficiency (Full Load / On-Line) | 91% typical |
| Voltage Regulation | ± 1% |
| Input Current Distortion | <= 5% THD |
| Overload Capabilities | 125% (1 min.) / 150% (5 sec.) / 110% (10 mins.) |
| Battery | |
| Battery Type | VRLA, 9AH, maintenance free (Field replacable) |
| Typical Backup Time (Full Load) | > 70 min @ full load (> 8 hours @ 15% full load) |
| External Battery Cabinet (EBM) Configuration | EBM 96 (Quantity 2) |
| Operation / General | |
| Diagnostics | Full system self-test @ startup |
| UPS Bypass | Automatic on overload or UPS failure |
| On-Line Transfer Time | 1 ms typical |
| Audible Noise (Full Load @ 1m) | < 58 dBA |
| Communications | |
| Minimum Requirements | Graphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card (P/N: 103003055), X-slot Industrial Gateway Card (P/N: INDGW-X2) |
| Network type | Factory Installed MS Network Card (SNMP) |
| Certifications | |
| Quality | ISO 9001 |
| Warranty | |
| Standard | 1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification. |
| Customer Service | |
| Initial Start Up | Vendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Braidwood and LaSalle Nuclear Generating Stations |
| Tech Support Availability | 24/7 (Unlimited) |