GEMS 15 kVA UPS Technical Specifications - BR LS.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
EMA - GEMS Facility UPS - 15KVA
Solicitation number
26-588IEMA-MGMTA-B-52266
Issued by
Illinois

About this file

This document contains technical specifications for a 15 kVA Uninterruptible Power Supply (UPS) system procured by the State of Illinois for the GEMS Facility. The specification details call for an Eaton 9355 model UPS with a 3-high cabinet configuration and 64 battery capacity, rated at 15 KVA / 13.5 KW at 0.9 power factor. The unit operates using double conversion topology with input voltage of 208/120V AC, three-phase, four-wire configuration, and delivers sinewave output at the same voltage specifications with 91% efficiency at full load. The system includes two external battery cabinets (EBM 96 configuration) and features automatic bypass capability on overload or UPS failure, with an on-line transfer time of 1 millisecond. The installation location is specified as on-site at Braidwood and LaSalle Nuclear Generating Stations. This bid was cloned from a previous bid (B-51543) due to an administrative error and will be awarded to the lowest bidder meeting the specified technical requirements.

The vendor selected for this contract must be certified by the manufacturer to perform initial startup of the equipment per manufacturer requirements. The UPS system includes integrated communications capabilities with a graphical LCD display, RS-232 connectivity, and industrial gateway card functionality with factory-installed MS Network Card supporting SNMP protocols. The standard warranty includes one year of full parts and labor coverage with 24/7 on-site emergency response within eight hours of notification. Additionally, the selected vendor must provide unlimited 24/7 technical support availability. Quality certification to ISO 9001 standards is required, and the system operates at noise levels below 58 dBA at full load at one meter distance.

View the file

Other files

File Type Posted
standard-terms-and-conditions 4~51.pdf PDF
B-51543 Q and A.docx DOCX document
Standard Illinois Certifications v.26.2.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 GEMS UPS Technical Specifications

Tech Specs
ModelEaton 9355
Cabinet Style3 High w/ 64 Battery
Power
Ratings15 KVA / 13.5KW @ 0.9 P.F.
TopologyDouble Conversion
Input
Input Voltage208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Input Frequency60 Hz ± 5 Hz
Voltage Correction Range176-228.8V AC
Power Factor (Full Load)0.99 typical
Output
Waveform (On-Line)Sinewave
Waveform (On-Battery)Sinewave
Output Voltage (RMS)208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Output Frequency60 Hz
Efficiency (Full Load / On-Line)91% typical
Voltage Regulation± 1%
Input Current Distortion<= 5% THD
Overload Capabilities125% (1 min.) / 150% (5 sec.) / 110% (10 mins.)
Battery
Battery TypeVRLA, 9AH, maintenance free (Field replacable)
Typical Backup Time (Full Load)> 70 min @ full load (> 8 hours @ 15% full load)
External Battery Cabinet (EBM) ConfigurationEBM 96 (Quantity 2)
Operation / General
DiagnosticsFull system self-test @ startup
UPS BypassAutomatic on overload or UPS failure
On-Line Transfer Time1 ms typical
Audible Noise (Full Load @ 1m)< 58 dBA
Communications
Minimum RequirementsGraphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card (P/N: 103003055), X-slot Industrial Gateway Card (P/N: INDGW-X2)
Network typeFactory Installed MS Network Card (SNMP)
Certifications
QualityISO 9001
Warranty
Standard1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification.
Customer Service
Initial Start UpVendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Braidwood and LaSalle Nuclear Generating Stations
Tech Support Availability24/7 (Unlimited)

File details come from the government source that posted it. Updated .