FY26 HVAC B469 Cooling Tower Salient Characteristics.pdf

PDF 108 KB Posted

Attached to
HVAC Cooling Tower Federal contract opportunity
Solicitation number
FA441826Q0008
Issued by
Department of the Air Force Air Mobility Command

About this file

This document is a Salient Characteristics specification for a federal cooling tower procurement issued by the Department of the Air Force, Headquarters 628th Air Base Wing (AMC) at Joint Base Charleston, South Carolina, dated 11 December 2025.

The requirement is for an open circuit induced-draft vertical discharge cooling tower, specified as EVAPCO MODEL AT 29-4K21 or equivalent, to be delivered for Government installation. The cooling tower must meet specific design and operational parameters: design conditions of 95°F dry bulb / 80.7°F wet bulb, water inlet/outlet temperatures of 95°F / 85°F, and water flow capacity of 1,418.1 gpm. The equipment must feature 316 stainless steel construction for both the cold water basin and upper components, a 5-probe electronic water level control package, stainless steel basin heaters with contactor and transformer rated to 0°F, fan vibration switch, sump sweeper piping with high flow eductors, fan motor shaft grounding rings, and VFD service-rated fan motors (Variable Frequency Drives not included). The maximum footprint dimension is 9' x 23'. The contractor must include a 5-year Parts/Labor Warranty and provide factory start-up and commissioning services through a manufacturer representative.

View the file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CUI

CUI

DEPARTMENT OF THE AIR FORCE

HEADQUARTERS 628TH AIR BASE WING (AMC)

JOINT BASE CHARLESTON SC

Salient characteristics

FY26 HVAC(AB) B469 Cooling Tower

Joint Base Charleston Air Base

South Carolina

11 December 2025

Salient characteristics:

Open Circuit Induced-draft Vertical Discharge Cooling Tower, EVAPCO MODEL AT 29-4K21 or equivalent

Delivered for Government installation.

Include 5 year Parts/Labor Warranty, Factory Start-up and Commissioning from Manufacturer Rep.

Equipment Requirements:

-Design conditions: 95°F db / 80.7°F wb -Water in/out: 95°F / 85°F -Water Flow: 1,418.1 gpm -316 stainless steel cold water basin -316 stainless steel upper -5-probe electronic water level control package -Stainless steel basin heaters, heater package contactor w/ transformer and disconnect (rated to 0°F) -Fan vibration switch -Sump sweeper piping (high flow eductors) -Fan motor shaft grounding rings -VFD service-rated fan motors (VFDs NOT included) -9’ x 23’ MAX DIMENSION footprint

Equipment Requirements: