Floyd_Little_Moisture_Probing_Report.pdf

PDF 668 KB Posted

Attached to
Floyd Little Athletic Center - Removal and Replacement of Athletic Flooring
Solicitation number
2025-RFP-189
Issued by
New Haven County, Connecticut

About this file

This document is a Relative Humidity (RH) testing report from Materials Testing, Inc. for the Floyd Athletic Center Improvements project, commissioned by the City of New Haven Engineering Department. The report details an ASTM F2170 standard test method for determining relative humidity in concrete floor slabs, conducted on February 7, 2025, with measurements taken on February 10, 2025. Technicians placed 44 RH sleeves in pre-selected areas of the interior concrete slab, drilling to a depth of 4 inches in an approximately 10-inch thick slab.

The test results reveal varying relative humidity levels across the tested locations, ranging from 70% to 98%, with most readings between 78% and 95%. Several test points showed water-filled holes after drilling, and one sensor was noted as damaged. The ambient air temperature during testing was consistently around 70°F, with humidity at 41%. These moisture measurements are likely crucial for determining the suitability of future flooring installations, particularly in the context of the city's planned athletic flooring replacement project, which requires careful assessment of concrete slab conditions before new flooring can be installed.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MATERIALS TESTING, INC.

55 LAURA STREET • NEW HAVEN, CONNECTICUT 06512 • (203)468-5216

WWW.MTIES.COM

DATE: 02-10-2025

REPORT NO: S-1000

CLIENT: City of New Haven - Engineering Dept.

200 Orange Street, Room 504

New Haven, CT 06510

Attn: Mr. Zach Shapiro, PE

PROJECT: Floyd Athletic Center Improvements

PO No. 20251613-00

480 Sherman Parkway

New Haven, CT

SUBJECT: ASTM F2170 “STANDARD TEST METHOD FOR DETERMINING RELATIVE HUMIDITY IN

CONCRETE FLOOR SLABS USING IN SITU PROBES”

DATE OF DRILLING: 02-07-25 TIME OF DRILLING: 10:30 AM

DATE OF MEASUREMENT: 02-10-25 TIME OF MEASUREMENT: 11:00 AM

INSTRUMENT: RapidRH Model L6 LAST CALIBRATION: 10-01-2024

SLAB THICKNESS: approx. 10"

DEPTH OF DRILLING: 4"

AMBIENT AIR TEMPERATURE ABOVE THE PROBES: 71 EF

AMBIENT HUMIDITY ABOVE THE PROBES: 41 %

On 02-07-25 RH sleeves were placed in 44 pre-selected areas of the interior concrete slab of the Floyd

Athletic Center. The results were recorded and are listed on the next page.

Note: See attached drawing for location of RH sleeves (* Indicates ground water present)

Temperature Relative Humidity Observations 1 - - Water filled hole after drilling 2 - - Water filled hole after drilling

3 68 EF 71%

4 67 EF 78%

5 68 EF 78%

6 68 EF 79%

7 68 EF 78%

8 - - Water filled hole after drilling

9 68 EF 70%

10 - - Water filled hole after drilling 11 - - Water filled hole after drilling 12 - - Water filled hole after drilling 13 - - Water filled hole after drilling

14 70 EF 93%

15 70 EF 87%

16 69 EF 87%

17 70 EF 91%

18 70 EF 93%

19 71 EF 93%

20 70 EF 94%

21 68 EF 79%

22 68 EF 79%

23 71 EF 88%

24 70 EF 83%

25 70 EF 85%

26 71 EF 88%

27 70 EF 92%

28 71 EF 94%

29 - - Damaged sensor

30 71 EF 98%

31 71 EF 97%

32 71 EF 89%

33 71 EF 97%

34 - - Water filled hole after drilling 35 - - Water filled hole after drilling

36 71 EF 88%

37 70 EF 89%

38 70 EF 88%

39 70 EF 89%

40 71 EF 95%

41 71 EF 94%

42 71 EF 94%

43 71 EF 95%

44 - - Water filled hole after drilling

Test reports may not be reproduced, except in full, without the express permission of Materials Testing, Inc. Results only relate to items tested. When information is provided by others and included in the report, there is potential for affecting the validity of results.

Basketball court

22 21 20 19