FLOOR TRUSS.pdf
PDF 142 KB Posted
- Attached to
- TRUSSES FOR HOMES FOR IOWA PROGRAM
- Solicitation number
- RFB 913
- Issued by
- Jones County, Iowa
About this file
The document provided contains a detailed drawing and specifications for floor trusses, as well as information about a related state and local contract opportunity. The floor truss drawing was prepared by Alpine Engineering for the "Governor's Housing" project and includes comprehensive technical details such as material specifications, load calculations, and installation requirements. The related state and local contract opportunity is for the procurement of 35 sets of trusses for the Homes for Iowa program, which is a project located in Jones County, Iowa. The contract opportunity does not provide a specific response deadline, award date, or contract term.
The floor truss drawing outlines the structural design and engineering requirements, including the type of wood, load capacities, and deflection limits. It also provides detailed instructions for handling, shipping, installation, and bracing of the trusses. The technical specifications and drawings must be closely followed by all contractors and installers involved in the project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB913INSTR.dat | — | |
| RFB913PRICE.dat | — | |
| ROOF TRUSS.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TC LL REF
TC DL DATE
BC DL DRWG
BC LL
TOT.LD. O/A LEN.
DUR.FAC.
TYPE
**WARNING!** READ AND FOLLOW ALL NOTES ON THIS DRAWING! **WARNING!** READ AND FOLLOW ALL NOTES ON THIS DRAWING! **WARNING!** READ AND FOLLOW ALL NOTES ON THIS DRAWING!
**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS.**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS.**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS.
Trusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building Component Safety Information, by TPI and WTCA) for safety practices prior to performing these functions. Installers shall provide temporary bracing per BCSI.
Unless noted otherwise, top chord shall have properly attached structural sheathing and bottom chord shall have a properly attached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10, as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise.
Refer to drawings 160A-Z for standard plate positions.
ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing, any failure to build the truss in conformance with ANSI/TPI 1, or for handling, shipping, installation & bracing of trusses.
A seal on this drawing or cover page listing this drawing, indicates acceptance of professionalA seal on this drawing or cover page listing this drawing, indicates acceptance of professionalA seal on this drawing or cover page listing this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitability and use of this drawingengineering responsibility solely for the design shown. The suitability and use of this drawingengineering responsibility solely for the design shown. The suitability and use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job’s general notes page and these web sites:
ITWBCG: www.itwbcg.com; TPI: www.tpinst.org; WTCA: www.sbcindustry.com; ICC: www.iccsafe.org
TAG = T6
LEFT JIG = 23'8"9 RIGHT JIG = 23'8"9
DESIGN CRIT=IBC2006/TPI-2002 FT/RT=12%(0%)/10(0)PLT. TYP.-WAVE
40.0psf 10.0psf 5.0psf 0.0psf 55.0psf 1.00
SPACING 24.0" SY42
JOB #: Q21-1036
231100
KJK
03-05-2021
REV. 19.02.02C.1006.11QTY= 25 TOTAL= 25
SEQ = 81625
23'11"
4"8
7"8
2'8"4 2'3"12
11"8
5' 5' 11"8
2'3"12
2'8"4
7"8
4"8
1"8
3"
10"8 4'9" 3'4"12
1"8 4'10"8
1"8 3'4"12 4'9"
10"8
3"
1"8
1'1"8 4'10"8 11'11" 4'10"8
1'1"8
'6
T1 T2
B1 B2
W1 W2
W2
W3 W2
W2 W4 W5 W2
W2 W6
W4 W2 W4
W4 W2 W4
W6 W2 W2
W5 W4 W2
W2 W3
W2 W2
W1
2'5"4
2X4(R) 2X4(R)
4X5
4X5
5X8
4X12
4X12
3X8
W=SS0312 3X8
W=3X6 3X4
3X8
3X8
4X12
4X12
5X8
4X5
4X5
2X4(R) 2X4(R)
R=1302# W=5"8 (Rigid Surface)
R=1302# W=5"8 (Rigid Surface)
Top chord 4x2 SPF 2400f-2.0E Bot chord 4x2 SPF 2400f-2.0E Webs 4x2 SPF #1/#2
All plates are 2X4 except as noted.
+ 2x6 continuous strongback. See detail STRBRIBR1014 for bracing and bridging recommendations.
Deflection estimate assumes composite action with single layer of the appropriate span rated glue-nailed wood sheathing.Max JT VERT DEFL: LL: 0.42" DL: 0.16". See detail DEFLCAMB1014 for camber recommendations.
Bottom chord checked for 10.00 psf non-concurrent bottom chord live load applied per IBC-06 section 1607.Deflection meets L/480 live and L/360 total load.
Truss must be installed as shown with top chord up.
Job:(Q21-1036) /GOVERNOR'S HOUSING (IWOA / 23'-11 THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
SCALE =0.3285
TC LL REF
TC DL DATE
BC DL DRWG
BC LL
TOT.LD. O/A LEN.
DUR.FAC.
TYPE
**WARNING!** READ AND FOLLOW ALL NOTES ON THIS DRAWING! **WARNING!** READ AND FOLLOW ALL NOTES ON THIS DRAWING! **WARNING!** READ AND FOLLOW ALL NOTES ON THIS DRAWING!
**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS.**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS.**IMPORTANT** FURNISH THIS DRAWING TO ALL CONTRACTORS INCLUDING THE INSTALLERS.
Trusses require extreme care in fabricating, handling, shipping, installing and bracing. Refer to and follow the latest edition of BCSI (Building Component Safety Information, by TPI and WTCA) for safety practices prior to performing these functions. Installers shall provide temporary bracing per BCSI.
Unless noted otherwise, top chord shall have properly attached structural sheathing and bottom chord shall have a properly attached rigid ceiling. Locations shown for permanent lateral restraint of webs shall have bracing installed per BCSI sections B3, B7 or B10, as applicable. Apply plates to each face of truss and position as shown above and on the Joint Details, unless noted otherwise.
Refer to drawings 160A-Z for standard plate positions.
ITW Building Components Group Inc. shall not be responsible for any deviation from this drawing, any failure to build the truss in conformance with ANSI/TPI 1, or for handling, shipping, installation & bracing of trusses.
A seal on this drawing or cover page listing this drawing, indicates acceptance of professionalA seal on this drawing or cover page listing this drawing, indicates acceptance of professionalA seal on this drawing or cover page listing this drawing, indicates acceptance of professional engineering responsibility solely for the design shown. The suitability and use of this drawingengineering responsibility solely for the design shown. The suitability and use of this drawingengineering responsibility solely for the design shown. The suitability and use of this drawing for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.for any structure is the responsibility of the Building Designer per ANSI/TPI 1 Sec.2.
For more information see this job’s general notes page and these web sites:
ITWBCG: www.itwbcg.com; TPI: www.tpinst.org; WTCA: www.sbcindustry.com; ICC: www.iccsafe.org
TAG = T2
LEFT JIG = 17'7"2 RIGHT JIG = 23'8"9
DESIGN CRIT=IBC2018/TPI-2014 FT/RT=12%(0%)/10(0)PLT. TYP.-WAVE
40.0psf 10.0psf 5.0psf 0.0psf 55.0psf 1.00
SPACING 24.0" SY42
JOB #: Q21-1036
231100
KJK
03-05-2021
REV. 19.02.02C.1006.11QTY= 1 TOTAL= 1
SEQ = 81628
4'11"
14'5"4 4"8
9'1"4
23'11"
4"8
7"8
2'8"4 3'3"4 5'4"12 7'10"8 3'3"12 3"
1"8
1"8
3"
10"8 5' 3'3"4 5'11"8 2'2"4
4"8
4'7"8 10"8
1'1"8 4'11"4 8'4"8
4"8 3'0"8
2"4
3" 4'6"
1'1"8
'6
1'4"8
T1 T2T3
B1 B2
W1 W2
W2
W3 W2
W2 W4 W5 W5
W2
W2
W2
W6 W4
W2 W4 W7 W8
W8
W9
W8W10 W2 W2
W2 W5 W5 W4
W2 W2 W3
W2
W2
W1
2'5"4
2X4(R) 2X4(R)
2X4
5X8
4X12
4X12
3X8
W=SS0312
2X4
4X8
W=3X6 3X4
3X8
3X4
3X6
2X4
3X6(R)
3X4(R)
6X8 4X12
4X12
4X12
5X8
2X4 2X4(R)
2X4(R)
R=1302# W=5"8 (Rigid Surface)
R=1302# W=5"8 (Rigid Surface)
Top chord 4x2 SPF 2400f-2.0E Bot chord 4x2 SPF 2400f-2.0E Webs 4x2 SPF #1/#2
All plates are 4X5 except as noted.
+ 2x6 continuous strongback. See detail STRBRIBR1014 for bracing and bridging recommendations.
Deflection estimate assumes composite action with single layer of the appropriate span rated glue-nailed wood sheathing.Max JT VERT DEFL: LL: 0.40" DL: 0.17". See detail DEFLCAMB1014 for camber recommendations.
Bottom chord checked for 10.00 psf non-concurrent live load.Deflection meets L/480 live and L/360 total load. Creep increase factor for dead load is 2.00.
Truss must be installed as shown with top chord up.
Job:(Q21-1036) /GOVERNOR'S HOUSING (IWOA / 14.6 CUTAWAY THIS DWG. PREPARED BY THE ALPINE JOB DESIGNER PROGRAM FROM TRUSS MFR'S LAYOUT
SCALE =0.3285