This file describes a federal contract opportunity for expansion of the Meds by Mail program at the Murfreesboro Consolidated Mail Outpatient Pharmacy facility. The solicitation number is 36C77023R0003 for project 764-21-101 to expand Meds by Mail operations. The opportunity is being offered by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. The attached floor plan PDF provides details on the required expansion for the Meds by Mail program at the Murfreesboro, Tennessee CMOP facility to increase pharmaceutical mail order operations capacity. Responses to the solicitation are due on the date specified in the opportunity notice.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C77023R0003 0003.docx | DOCX document | |
| Pre-Bid_Questions with Photos.pdf | ||
| Pre-Bid_Sign-In.pdf | ||
| 36C77023R0003 0002.docx | DOCX document | |
| 36C77023R0003 0001.docx | DOCX document | |
| Attachment_3_Past_Performance_Questionnaire.pdf | ||
| 36C77023R0003_1.docx | DOCX document | |
| Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NUMBER
WHERE DRAWN
SECTION LETTER
SECTIONS DETAILS
FT-1
TYPICAL
EQUIPMENT
NUMBER
UNIQUE I.D.
(FAN TERMINAL NO. 1)
EQUIPMENT TYPE
(FT=FAN TERMINAL)
DRAWING SYMBOLSGENERAL NOTES
B
M2.1 M3.6
M3.6
B
M2.1 M3.6
M3.6
1. VERIFY JOB SITE CONDITIONS AND DIMENSIONS BEFORE BEGINNING WORK. PLANS ARE SCHEMATIC IN NATURE. LAYOUT IS BASED ON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS AND DIMENSIONS.
2. NO PIPING, DUCTWORK, ETC. SHALL PENETRATE STRUCTURAL MEMBERS.
3. PROVIDE MISCELLANEOUS CUTTING, PATCHING AND REPAIRING OF FINISHES, ROOF, WALLS, ETC., AS
REQUIRED TO ACCOMMODATE THE NEW WORK.
4. G.C. IS TO PATCH ANY OPENINGS IN CORRIDORS REQUIRED TO BE CONSTRUCTED TO LIMIT THE TRANSFER OF
SMOKE AND IN SMOKE BARRIERS AS REQUIRED TO MEET CODE REQUIREMENTS. SEE ARCHITECTURAL
DRAWINGS FOR LOCATIONS.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY EXACT LOCATION, CONFIGURATION AND ROUTING OF EXISTING SYSTEMS REQUIRED TO REMAIN IN OPERATION DURING THE PROJECT TO PREVENT DAMAGE
DURING DEMOLITION AND PHASING.
6. REMOVE ALL EXISTING EQUIPMENT, DUCTWORK AND PIPING THAT IS NOT REQUIRED FOR A WORKING
INSTALLATION.
7. COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO INSTALLATION.
8. UNLESS OTHERWISE INDICATED, INSTALL ALL SPACE THERMOSTATS AND OTHER OCCUPANT ADJUSTABLE
CONTROL DEVICES SAME HEIGHT AS ADJACENT LIGHT SWITCHES, BUT IN NO CASE HIGHER THAN 48 INCHES ABOVE FINISHED FLOOR PER ADA REQUIREMENTS. COORDINATE EXACT HEIGHT WITH ARCHITECT PRIOR TO
INSTALLATION.
9. ALL CUTTING AND PATCHING SHALL BE CLOSELY COORDINATED WITH THE G.C.
10. COORDINATE ROUTING OF PLUMBING, AND HVAC PIPING WITH DUCTWORK, LIGHTS, ARCHITECTURAL CEILING
AND STRUCTURAL ELEMENTS. PIPING SHALL RISE AND DROP, JOG OR OFFSET AS REQUIRED TO AVOID CONFLICTS. DUCTWORK SHALL TAKE PRECEDENCE OVER ALL PIPING, EXCEPT WHERE GRADE MUST BE MAINTAINED FOR DRAINAGE. REWORK OF INSTALLED WORK TO RESOLVE CONFLICTS RISING FROM LACK OF
COORDINATION SHALL NOT JUSTIFY AN INCREASE IN THE CONTRACT AMOUNT.
11. ALL DIFFUSERS ARE 4-WAY BLOW UNLESS INDICATED OTHERWISE ON THE DRAWINGS.
12. FLEXIBLE DUCTWORK IS ALLOWED ON RUNOUTS TO SUPPLY DIFFUSERS ONLY. UTILIZE ONLY ABOVE LAY-IN
ACCESSIBLE CEILINGS. DO NOT INSTALL FLEX DUCT ABOVE HARD CEILINGS OR WHERE EXPOSED. A MAXIMUM
LENGTH OF 6'-0" MAY BE USED AT EACH CONNECTION.
13. SEAL DUCTWORK AS CALLED OUT BELOW USING HARDCAST DT TAPE AND FTA-20 ADHESIVE OR HARDCAST
AFG-1402 "FOIL GRIP" PER MANUFACTURERS INSTRUCTIONS.
TYPE OF DUCT APPLY TO JOINTS
EXHAUST DUCT (ROUND OR RECT) TRANSVERSE AND LONGITUDINAL
MEDIUM VELOCITY (ROUND) TRANSVERSE AND LONGITUDINAL
MEDIUM VELOCITY (RECTANGULAR) TRANSVERSE AND LONGITUDINAL
LOW VELOCITY SUPPLY AND RETURN (RECT) TRANSVERSE AND LONGITUDINAL
LOW VELOCITY SUPPLY (ROUND) TRANSVERSE AND LONGITUDINAL
14. INSTALL BALANCE DAMPER WITH STANDOFF AND LOCKING QUADRANT IN AN ACCESSIBLE LOCATION AT EACH RUNOUT TO SUPPLY DIFFUSERS, EXHAUST GRILLES, AND RETURN GRILLES WHERE AIRFLOW IS INDICATED, OR
AS INDICATED OTHERWISE.
15. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE FIRE STOPPED BY THE TRADE MAKING THE PENETRATION. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR REQUIREMENTS.
16. DO NOT ROUTE PIPING OR DUCTWORK OVER ELECTRICAL PANELS OR EQUIPMENT. PIPING OR DUCTWORK SHALL NOT BE ROUTED THROUGH ELECTRICAL ROOMS, TELECOM ROOMS OR ELEVATOR EQUIPMENT ROOMS UNLESS SPECIFICALLY SERVING THAT ROOM. COORDINATE WITH E.C. PROVIDE WATERTIGHT DRIP PAN WITH
DRAIN TO NEAREST APPROVED RECEPTOR WHERE REQUIRED.
17. COORDINATE SIZE AND LOCATION OF ACCESS DOORS IN CONSTRUCTION REQUIRED FOR ACCESS TO
MECHANICAL EQUIPMENT WITH G.C.
18. ALL WORK IS TO CONFORM WITH APPLICABLE CODES AND STANDARDS.
19. DUCT SIZES SHOWN ARE ACTUAL INSIDE CLEAR DIMENSIONS. INCREASE SHEET METAL DIMENSIONS AS
REQUIRED TO ACCOMMODATE DUCT LINER WHERE LINER IS SPECIFIED.
20. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING MOUNTED AIR
DISTRIBUTION DEVICES.
21. PAINT INSIDE OF DUCTWORK BLACK ANYWHERE VISIBLE THROUGH FACE OF GRILLE OR DIFFUSER.
22. TEMPERATURE CONTROLS CONTRACTOR (T.C.C.) SHALL FURNISH AND INSTALL ALL LOW VOLTAGE WIRING AND
ASSOCIATED CONDUIT REQUIRED FOR MECHANICAL CONTROL SYSTEM. WIRING SHALL BE IN CONDUIT INSIDE WALLS, IN ROOMS WITH EXPOSED CEILINGS, AND ABOVE HARD CEILINGS. LINE VOLTAGE WIRING AND ASSOCIATED CONDUIT SHALL BE PROVIDED AND INSTALLED BY E.C. CONTROL SYSTEM SHALL BE INSTALLED
IN ACCORDANCE WITH SPECIFICATIONS.
23. COORDINATE ACCESS TO EQUIPMENT AND VALVES INSTALLED ABOVE 'HARD' CEILINGS AND IN MASONRY
CHASES WITH GENERAL CONTRACTOR. PROVIDE LOCKING ACCESS DOORS FOR INSTALLATION BY
CONTRACTOR AS REQUIRED TO SERVICE CONCEALED DAMPERS, VALVES AND EQUIPMENT. CEILING ACCESS DOORS FOR FIRE DAMPERS, SMOKE DAMPERS AND FIRE SMOKE DAMPERS FURNISHED AND INSTALLED BY
CONTRACTOR.
24. CONTRACTOR TO INSTALL TEMPORARY FILTERS OVER ALL RETURN AND EXHAUST GRILLES IN WORK AREA
DURING CONSTRUCTION.
25. THESE DRAWINGS ARE ACCOMPANIED BY SPECIFICATIONS. REFER TO SPECIFICATIONS FOR FURTHER
INFORMATION.
26. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF TEMPORARY PARTITIONS.
27. SQUARE THROAT NOT ALLOWED ON RADIUS ELBOWS.
28. TERMINAL UNITS, MANUAL BALANCE DAMPERS, HYDRONIC AND PLUMBING VALVES, CIRCUIT SETTERS AND
OTHER ACCESSORIES REQUIRING ACCESS SHALL BE ACCESSIBLE VIA A STANDARD LADDER SO COMPONENTS MAY BE REPLACED, REPAIRED, OR UTILIZED WITHOUT THE NEED FOR EXTENSIVE CEILING REMOVAL, SCAFFOLDING OR A MAN LIFT. WHERE POSSIBLE NO MORE THAN 48” ABOVE THE FINISHED CEILING.
SHEET NUMBER
WHERE REFERENCED
SHEET NUMBER
WHERE DRAWN
DETAIL NUMBER
SHEET NUMBER
WHERE DRAWN
DETAIL NUMBER
SHEET NUMBER
WHERE REFERENCED
EQUIPMENT
CALLOUT
SHEET NUMBER
WHERE DRAWN
SECTION LETTER
REFER TO PLAN NOTES# ROOM CALLOUT
DEMOLITION PEN WEIGHT - COMPONENT MAY ALSO BE SHADED
CONNECT NEW TO EXISTING. VERIFY EXACT LOCATION.
REVISION NUMBER
EXISTING COMPONENT PEN WEIGHT
EXISTING EQUIPMENT OR MATERIAL DESIGNATION(E)
DISCONNECT FROM EXISTING. VERIFY EXACT LOCATION.
EC ELECTRICAL CONTRACTOR
GENERAL CONTRACTORGC
PC PLUMBING CONTRACTOR
MC MECHANICAL CONTRACTOR
TEMPERATURE CONTROL CONTRACTORTCC
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
HVAC & PLUMBING SYMBOL SCHEDULE
GAS COCK / GLOBE VALVE
GATE VALVE - SHUT OFF VALVE
VALVE IN DROP / VALVE IN RISER
BUTTERFLY VALVE
2-WAY / 3-WAY CONTROL VALVE (PNEUMATIC)
BALL VALVE
PLUG VALVE
STRAINER / UNION OR FLANGE CONNECTION
THERMOMETER / PRESSURE GAUGE
CHECK VALVE3 PIECE BALL VALVE / HYDRAULIC VALVE
EMERGENCY VALVE WITH FIRE LINK
2-WAY / 3-WAY CONTROL VALVE (ELECTRIC)
PRESSURE REDUCING VALVE (PRV) / WAFER CHECK VALVE
CIRCUIT SETTER - CALIBRATED BALANCE VALVE
CALIBRATED ORIFICE PLATE FLOW METER
AUTOMATIC FLOW CONTROL VALVE
SPRING HANGER / PIPE HANGER
DOUBLE CHECK BACKFLOW ASSEMBLY
REDUCED PRESSURE ZONE BACKFLOW ASSEMBLY
CAP / CAPPED OUTLET
PIPE DROP / PIPE RISE TOP CONNECTION, 45° OR 90° / BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTIONDIRECTION OF FLOW / ANCHOR
CONCENTRIC REDUCER OR INCREASER / ECCENTRIC REDUCER
DOMESTIC COLD WATER LINE (CW) ABOVE FLOOR WASTE LINE (W)
BELOW FLOOR WASTE LINE (W)DOMESTIC HOT WATER LINE (HW)
HOT WATER RECIRC LINE (HWC) PLUMBING VENT LINE (V)
F RL RAIN LEADER (RL) / OVERFLOW RAIN LEADER (ORL)FIRE PROTECTION LINE (F)
CA COMPRESSED AIR (CA) SWS
TW DOMESTIC TEMPERED WATER LINE (TW)
STORM SEWER (SWS)
FCW FILTERED COLD WATER LINE (FCW)
CD COOLING COIL CONDENSATE DRAIN LINE (CD)
WCO
CO CO
CO
FLOOR DRAIN / TRENCH DRAIN
PLUMBING FIXTURE CALLOUT
WATER HAMMER ARRESTOR - PDI SIZE
P-#
WHA#
F FLOW LINE ELEVATION
DOMESTIC HOT WATER PUMPDHWP
VTR VENT THROUGH ROOF
L
WALL CLEANOUT / END OF LINE CLEANOUT
CLEANOUT (FLOOR) / 2-WAY CLEANOUT (FLOOR)
HOSE REEL / HOSE BIBB
DI
RO
ROR
SCW
IW
G
INDUSTRIAL WASTE
NATURAL GAS LINE (G)
SOFT COLD WATER LINE (SCW)
REVERSE OSMOSIS PURE WATER SUPPLY LINE (RO)
REVERSE OSMOSIS PURE WATER RETURN LINE (ROR)
DEIONIZED PURE WATER SUPPLY (DI)
TOP / BOP TOP OF PIPE / BOTTOM OF PIPE ELEVATION ABOVE FLOOR
ROOF DRAIN / OVERFLOW ROOF DRAIN
VITRIFIED CLAY PIPE / POLYVINYL CHLORIDE PIPE
CI CAST IRON
F/S
WH-#
FILTER-SEPARATOR
WATER HEATER CALLOUT
WALL HYDRANTWH
FS FLOOR SINK
FHC FIRE HOSE CABINET
FS
FOR
FOG
FUEL SUPPLY / UNUSABLE FUEL
FUEL OIL SUPPLY / FUEL OIL RETURN
FUEL OIL GAUGE
TYP. / (TYP) TYPICAL ALL INSTANCES
NOT ALL MAY BE USED ON PROJECT
THERMOSTATIC MIXING VALVETMV
SR SUPPLY REGISTER
MAKE-UP AIR UNITMAU
HUMIDIFIERH
DP DIFFERENTIAL PRESSURE UH UNIT HEATER
COMPUTER ROOM AIR CONDITIONING UNITCRAC
ULTRAVIOLET STERILE CONDITIONERUV
24x12
24x12
24x12
RETURN DUCT RISER
SUPPLY DUCT DROP / RETURN DUCT DROP
SUPPLY DUCT RISER
FLEXIBLE DUCT
TURNING VANES
(UP)DUCT SEC., POSITIVE PRESSURE-FIRST SIZE IS TOP DIM.(TYP.)
(DOWN) DUCT SECTION, POSITIVE PRESSURE
(UP) DUCT SECTION, NEGATIVE PRESSURE
R
24x12
18x12
BALANCING DAMPER W/ MANUAL LOCKING QUADRANT
SIDE WALL SUPPLY REGISTER
(DOWN) DUCT SECTION, NEGATIVE PRESSURE
DUCT SIZE, FIRST FIGURE IS SIDE SHOWN-CLEAR INSIDE DIM.
DUCT CHANGE OF ELEVATION RISE(R) DROP(D)
FLEXIBLE CONNECTION
BALANCING DAMPER W/ MOTORIZED LOCKING QUADRANT
T
TH
H ELECTRIC OR DDC THERMOSTAT (TSTAT)
FIRE DAMPER IN WALLFD
SD SMOKE DAMPER
PNEUMATIC THERMOSTATPNEUMATIC HUMIDISTAT
FD FIRE DAMPER IN FLOOR
ELECTRIC OR DDC HUMIDISTAT (HSTAT)
T
M
H
TEMPERATURE SENSOR
MOTOR
HUMIDITY SENSOR
R RADIATION DAMPER
COMBINATION FIRE/SMOKE DAMPER IN WALLFSD
FSD COMBINATION FIRE/SMOKE DAMPER IN FLOOR
OPPOSED BLADE DAMPEROBD
TOP OF DUCT ELEVATION ABOVE FLOOR
BOD
TOD
FTU / FCU
SF SUPPLY AIR FAN
FAN POWERED TERMINAL UNIT / FAN COIL UNIT
ROOFTOP UNIT / AIR HANDLING UNITRTU / AHU
F FURNACE
SA / OA SUPPLY AIR / OUTSIDE AIR
RETURN AIR / EXHAUST AIRRA / EA
DH DUCT HEATER
BOTTOM OF DUCT ELEVATION ABOVE FLOOR
BOS BOTTOM OF STEEL EF / RG EXHAUST FAN / RETURN GRILLE
VAV VARIABLE AIR VOLUME UNIT
CVR CONSTANT VOLUME REHEAT UNIT
V V R VARIABLE VOLUME REHEAT UNIT
VARIABLE VOLUME VARIABLE TEMPERATUREV V T
RECTANGULAR - OPPOSED BLADE / ROUND - BUTTERFLY
RECTANGULAR - OPPOSED BLADE / ROUND - BUTTERFLY
VARIABLE FREQUENCY DRIVEVFD
FOS
UF
ORL
FD / TD
RD / ORD
VCP / PVC
HR / HB
UNO UNLESS NOTED OTHERWISE ETR EXISTING TO REMAIN
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 www.pec1.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
/2
/2
:2
:1
P
M B
IM
/1
R
A tr ia x M u rf re e s b o ro
C M
O P
/2
-0
-M E
C H
-R
.r v t
M-001
MECHANICAL COVER SHEET MEDS BY MAIL OFFICE
EXPANSION AT THE
MID-SOUTH CMOP
3209 ELAM FARMS PKWY, MURFREESBORO, TN 67127
764-21-101
N/A
03/25/2022 TJS KWP 10 17
PRESSURE CLASS SCHEDULE
AIR SYSTEM PRESSURE CLASS
SEAL
CLASS
LEAKAGE CLASS
ROUND RECT
GENERAL EXHAUST 2 INCH WG (500 PA) A 3 6
LOW-PRESSURE SUPPLY 2 INCH WG (500 PA) A 6 12
MEDIUM PRESSURE SUPPLY (UPSTREAM OF
VAV & CV BOXES)
6 INCH WG (1500 PA) A 3 6
RETURN AND RELIEF 2 INCH WG (500 PA) A 6 12
1.
REMARKS:
HVAC DESIGN CONDITIONS
SPACE OR AREA
OUTDOOR AIR INDOOR
HEATING
°F
INDOOR
COOLING
°F
RELATIVE
HUMIDITY
%RH
REMARKSSUMMER
DB/WB °F
WINTER
DB °F
MEDS BY MAIL EXPANSION 95/76 15 70 75 50 --
SHEET LIST
M-001 MECHANICAL COVER SHEET
M-101 HVAC & PLUMBING PLAN
M-201 MECHANICAL DETAILS & SCHEDULES
Revisions: Date:
T
T
T
T
T
OFFICE
OFFICE
OFFICE
COFFEE
SCANNER/MAIL
PROCESSING
RECORDS ROOM
SUPPLY ROOM
RETURN MEDS ROOM
(E) HSK
(E) SWITCH ROOM
CUBICLES
CORRIDOR
HALLWAY
HALLWAY
(E) COMPUTER TRAINING
(E) GROUP FITNESS
(E) STOR
(E) WORKOUT ROOM
(E) WOMEN
(E) MEN
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OCCUPATIONAL HEALTH
(E) STORAGE
(E) STAIR
E ( )56x30 E ( )82x36
E x2
E ( )6"ø
( ) E 1/2"
( ) E 1/2"
(E)1/2"HW &
1 1/4"CW DN
(E)WH-4
( ) E 1/2"
( ) E 1/2"
( ) E 1"
(E)4"VTR
AND 4"W DN
( ) E 1/2"
( ) E 1"
(E)-245 (E)-245
E ( )12"ø
(E)22x22
(E)VAV
) 1 0" ø
E ( )10"ø
P02P02
2"W
1/2"1/2"
P03 x2
36x24
SJ8
SL8
SL8
SJ8
SJ8
SJ8
SJ8
SJ8
SJ8
SJ8
SJ8
SJ8
SJ8
SJ8
SJ8
100 SJ8
SJ8
SJ8
PL22x10
PL22x10
PO22x10 PO22x10
PM22x22
PL22x10
PL22x10PL22x10 PL22x10
EXISTING AIR VOLUME SERVED = 7740 CFM.
VAV-13
(575)
VAV-14
(550)
VAV-15
(700)
VAV-16
(1000)
VAV-17A
(600)
EXISTING MEDIUM VELOCITY DUCT SIZED FOR
APPROXIMATE MAXIMUM 12,500 CFM TOTAL @ 0.3"/100'
MAXIMUM FRICTION LOSS, 2500 FPM MAXIMUM VELOCITY.
EXISTING UTILIZED AIR VOLUME = 7,740 CFM.
NEW UTILIZED AIR VOLUME = 10,565 CFM.
FD
H01
H02
SK-1
SY16x4
SY16x4
SY16x4
SY16x4
RW22x10
SL8
8x8
12x12
8x
8"ø
10"ø
10"ø
10"ø x1
12x12
8x
12x12 10x10
10"ø x1
26x20
H03
NEW SYSTEMS SHALL BE COMPATIBLE WITH EXISTING
HONEYWELL "NIAGARA WEB-600" CONTROLS AS INSTALLED BY
C-TECH CONTROLS (888-868-1688, ctechcontrols.com). NEW
THERMOSTATS SHALL MATCH EXISTING BUILDING STANDARD.
ALL LOW VOLTAGE HVAC CONTROLS CABLING SHALL BE
PROVIDED AND INSTALLED BY TCC. COORDINATE WITH TCC.
1-1/2''
2"CO
(E)FD
(E)FD
"ø
(OBD) (OBD)
H04
P01
EXISTING FIRE SPRINKLER SYSTEM SERVING THE OPEN
MEZZANINE SHALL BE MODIFIED TO SERVE ALL SPACES UNDER
THE SCOPE OF THIS PROJECT. EXISTING SPRINKLER SYSTEM
IS HIGH IN SPACE AND WILL NEED TO BE REROUTED DOWN TO
PROJECT CEILING LEVEL..
VAV-13
8x
H05
H06
"ø
SW12x8
SW12x8
"ø
H07
(10x10) (8x8)
H05
(1 0x
(8")
H08 H08
H07 H07
H07
VAV-17 AND ALL ASSOCIATED
DUCTWORK AND EQUIPMENT
SHOWN WITH A DARK GREY
FILL ARE TO BE PART OF
ALTERNATE #1.
H09H09
MECHANICAL GENERAL NOTES
1. DUCT SIZES SHOWN ARE ACTUAL INSIDE CLEAR
DIMENSIONS. INSULATION THICKNESS HAS NOT BEEN
ACCOUNTED FOR. DUCTWORK EXPOSED TO SPACE
SHALL NOT HAVE EXTERIOR INSULATION.
2. THE SPACE ABOVE THE CEILING IS BEING UTILIZED AS A
RETURN AIR PLENUM. ALL RETURN GRILLES SHALL BE
PROVIDED WITH SOUND BOOTS AND A DIRECT PATH TO
THE AIR HANDLING SYSTEM RETURN AIR DUCT SHALL BE
PROVIDED. WHERE FULL HEIGHT WALLS ARE BEING USED
AND THE RETURN AIR PATH IS COMPROMISED, THE
SOUND BOOT SHALL EXTEND THROUGH THE WALL OR
TRANSFER DUCTS SHALL BE PROVIDED.
3. AVOID ROUTING DUCTWORK OVER ELECTRICAL ROOMS
AND ELECTRICAL PANELS. MAINTAIN N.E.C.
CLEARANCES. COORDINATE ROUTING WITH ELECTRICAL
CONTRACTOR.
4. ALL SUPPLY AIR BRANCHES FOR SUPPLY DIFFUSERS TO
HAVE MANUAL BALANCE DAMPERS, ALL MAY NOT BE
SHOWN FOR CLARITY.
5. PROVIDE FLEXIBLE DUCT AND PIPE CONNECTIONS TO
ALL MOTORIZED EQUIPMENT.
6. REFER TO GRD SCHEDULE FOR DUCT CONNECTION
SIZES. REFER TO TERMINAL BOX SCHEDULE FOR INLET
DUCT SIZES.
7. CEILING COORDINATION OF ALL MEP SYSTEMS
(LIGHTING, DUCTWORK, DIFFUSERS, ELECTRICAL, ETC.)
MUST BE COMPLETED BY THE CONTRACTOR PRIOR TO
THE START OF ANY NEW INSTALLATION.
8. REFER TO THE PLUMBING FIXTURE SCHEDULE FOR PIPE
SIZES TO INDIVIDUAL FIXTURES.
9. NOT ALL REQUIRED CLEANOUTS ARE NECESSARILY
SHOWN ON THESE PLANS. PROVIDE CLEANOUTS ON
WASTE, VENT AND STORM PIPING AS REQUIRED BY CODE
AND FOR REASONABLE MAINTENANCE BASED ON ACTUAL
FIELD INSTALLATION.
10. ALL VALVES SHALL BE INSTALLED ABOVE DROP-IN
CEILINGS IN ACCESSIBLE LOCATIONS, OR WITH ACCESS
PANELS IN HARD LID CEILINGS.
11. PROVIDE ACCESSIBLE SHUT-OFF VALVES TO ALL
APPLIANCES AND EQUIPMENT.
12. CEILING PLENUM IS USED AS A RETURN AIR PATH. KEEP
PLENUM FREE OF COMBUSTIBLES, PVC PIPING AND ANY
OTHER MATERIALS NOT ALLOWED BY THE IFC.
13. VERIFY AND REFER TO ARCHITECTURAL DIMENSIONAL
FLOOR PLAN FOR EXACT LOCATIONS OF ALL FIXTURES
AND EQUIPMENT.
14. NEW THERMOSTATS SHALL MATCH EXISTING BUILDING
STANDARD THERMOSTAT. COORDINATE WITH BUILDING
OWNER AND TCC.
FIRE PROTECTION NOTES
1. PIPING TO BE BLACK IRON WITH SCREWED MALLEABLE
IRON FITTINGS OR MECHANICAL GROOVE FITTINGS. SEE
SPECIFICATIONS FOR DETAILS AND APPLICATIONS.
2. PIPE HANGERS TO BE U.L. LISTED AND MOUNTED IN
ACCORDANCE WITH NFPA-13.
3. DO NOT OBSTRUCT SPRINKLERS WITH OTHER UTILITIES.
4. SEE SPECIFICATIONS FOR SPRINKLER HEAD TYPES AND
APPLICATIONS. ALL SPRINKLER HEADS TO BE QUICK-
RESPONSE TYPE. ALL SPRINKLER HEADS SHALL BE
LOCATED IN EXACT CENTER OF CEILING TILES.
5. FIRE SPRINKLER DESIGN IS THE RESPONSIBILITY OF
THE FIRE SPRINKLER CONTRACTOR. FINAL DESIGN
SHALL BE SEALED BY A REGISTERED LICENSED
ENGINEER IN THIS STATE. FIRE MARSHALL APPROVED
SHOP DRAWINGS SHALL BE SUBMITTED TO THE DESIGN
ENGINEER FOR APPROVAL.
6. COORDINATE PIPE ROUTING AND HEAD LOCATIONS
WITH OTHER TRADES. PIPING AND HEADS NOT
COORDINATED SHALL BE MOVED AT THE
CONTRACTOR'S EXPENSE TO ACCOMPLISH CEILING
HEIGHTS AS CALLED OUT ON THE ARCHITECT'S
DRAWINGS.
7. COORDINATE CLOSELY WITH ALL OTHER TRADES PRIOR
TO CONSTRUCTION AND PROVIDE BIM MODEL TO
CONSTRUCTION MANAGER FOR COORDINATION AMONG
DISCIPLINES IF APPLICABLE.
8. FIRE PROTECTION ENGINEER OF RECORD SHALL
DETERMINE HAZARD CLASSIFICATIONS.
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 www.pec1.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
AREA OF CONSTRUCTION
/2
/2
:2
:2
P
M B
IM
/1
R
A tr ia x M u rf re e s b o ro
C M
O P
/2
-0
-M E
C H
-R
.r v t
M-101
HVAC & PLUMBING PLAN MEDS BY MAIL OFFICE
EXPANSION AT THE
MID-SOUTH CMOP
3209 ELAM FARMS PKWY, MURFREESBORO, TN 67127
764-21-101
N/A
03/25/2022 TJS KWP 11 17
0' 8' 12'4' 1/4" = 1'-0"
HVAC & PLUMBING PLAN
A
PLAN NOTES
H01 36x24 RETURN AIR TRANSFER DUCT TURNED UP.
REFER TO RETURN AIR TRANSFER DUCT DETAIL.
H02 TEST AND BALANCE CONTRACTOR TO PROVIDE
PRE-CONSTRUCTION READING OF TOTAL AIRFLOW
FROM EXISTING ROOFTOP UNIT. UNIT SHALL BE
REBALANCED AT CONCLUSION OF PROJECT TO
PROVIDE AN ADDITIONAL 2,825 CFM BASED ON NEW
WORK. COORDINATE REQUIREMENTS WITH
TEMPERATURE CONTROLS CONTRACTOR.
H03 26x20 RETURN AIR TRANSFER DUCT TURNED UP.
H04 MOUNT BOTTOM OF GRILLE @ APPROXIMATELY 10'-6".
COORDINATE EXACT HEIGHT WITH ARCHITECT.
H05 VAV-17 AND ALL ASSOCIATED DUCTWORK, DIFFUSERS,
ETC SHOWN WITH A DARK GREY FILL ARE TO BE PART
OF ALTERNATE #1. REFER TO SPECIFICATIONS AND
ADDITIONAL NOTES ON VAV-16 FOR FURTHER
ALTERNATE INFORMATION.
H06 IF TAKING ALTERNATE #1, USE VAV-16A SCHEDULED
DATA. OTHERWISE USE VAV-16 SCHEDULED DATA.
REFER TO DUCT SIZE NOTES IF TAKING ALTERNATE
#1.
H07 SIZE INDICATED IN PARENTHESIS INDICATES DUCT
SIZE IF TAKING ALTERNATE #1.
H08 DUCTWORK TO BE OMITTED IF TAKING ALTERNATE #1.
H09 GRILLE MOUNTED WITH BOTTOM @ APPROXIMATELY
11'-0". COORDINATE EXACT HEIGHT WITH ARCHITECT.
ORIENT BLADES IN DOWNWARD DIRECTION.
P01 CONNECT 2" WASTE TO EXISTING WASTE LINE
SERVING EXISTING FD & MOP BASIN IN FIRST FLOOR
CEILING PLENUM.
P02 CONNECT 1/2" CW, 1/2" HW TO EXISTING 3/4" CW, 3/4"
HW ABOVE EXISTING WATER HEATER.
P03 CONNECT 1-1/2" VENT TO EXISTING VENT LINE NEAR
THIS LOCATION.
N
CEILING GRID
LAY - IN RETURN
AIR GRILLE
SHEET METAL DUCT
WITH 1/2" ACOUSTICAL
DUCT LINER
HANGER STRAP
OPENING TO RETURN
AIR PLENUM, SAME SIZE
AS GRILLE NECK.
NECK SIZE 18"
DIMENSION AS REQUIRED
TO CLEAR BUILDING
CONSTRUCTION (8" MIN)
COMPLETELY SEAL WALL
AROUND DUCT PENETRATION
FULL HEIGHT
PARTITION WALL
END OF DUCT OPEN TO CEILING
PLENUM (TYPICAL BOTH ENDS)
DOUBLE WALL PERFORATED
GALVANIZED SHEET METAL
TURNING VANES WITH ANGULAR
SPACE PACKED WITH FIBERGLASS
SHEET METAL DUCT
(REFER TO PLANS OR
TRANSFER CALLOUT FOR SIZE)
NOTES:
1. INSTALL RETURN AIR TRANSFER
DUCT ABOVE CEILING.
2. LOCATE SO THAT OPEN ENDS OF
DUCT ARE NOT OBSTRUCTED BY
OTHER DUCTS OR PIPING WITHIN
12" OF DUCT.
3. INSTALL FIRE DAMPERS OR FIRE/
SMOKE DAMPERS AS SHOWN
ON PLANS.
PLAN VIEW
24" MIN.
STRAIGHT GALV.
INSULATED DUCT MINIMUM
DISTANCE OF 3.0 TIMES
BOX INLET DUCT DIAMETER
AIRFLOW SENSOR
HEATING COIL
TRANSITION TO LOW
VELOCITY DUCTWORK
LOW VELOCITY SUPPLY AIR DUCT
SEE FLOOR PLANS FOR SIZE AND
ROUTING. TRANSITION AS REQUIRED
TO MATCH BOX OUTLET SIZE
MIN. 36" CLEAR
CONTROL BOX
SHEET METAL TRANSITION
AS REQUIRED (REFER TO
ACTUAL SUBMITTAL)
HIGH EFFICIENCY TAKEOFF
MEDIUM VELOCITY
TRUNK DUCT
FLOW FLOW
MINIMUM OF 12" STRAIGHT DUCT,
SAME AS VAV BOX OUTLET, OR AS
REQUIRED BY MFR PRIOR TO
TAKEOFFS, ELBOWS, OR FITTINGS.
HANGER ROD TO STRUCTURE
ANVIL FIG 260 OR EQUAL HEAVY
DUTY CLEVIS HANGER SIZED FOR
INSULATION THICKNESS
PIPE INSULATION W/ VAPOR
BARRIER. REFER TO
SPECIFICATIONS FOR
INSULATION THICKNESS.
FOAM GLASS HIGH DENSITY
INSERT W/ VAPOR BARRIER
ANVIL FIG 167 INSULATION SADDLE SHIELD
14 GA GALVANIZED x 24" LONG
NOTE:
OMIT FOAM GLASS INSERT ON
PIPES 3" AND LARGER
DIRECTION OF AIRFLOW. RECTANGULAR MAIN
OR TRUNK DUCT
MANUAL OPPOSED BLADE
BALANCING DAMPER WITH
LOCKING QUADRANT, ON BRANCH
DUCT OR WHERE INDICATED. NO
OBD ON MEDIUM PRESSURE DUCTS
BEFORE VAVs. TYPICAL.
STANDOFF FOR INSULATION
THICKNESS. TYPICAL.
SUPPLY
EXHAUST
RETURN
L=4" MINIMUM OR 1/4 OF "W"
W
45° L
ROUND MAIN OR
TRUNK DUCT
"LOW-LOSS" 45°F
ENTRY FITTING
GASKET
HIGH EFFICIENCY
TAKEOFF (HETO).
SUPPLY
EXHAUST
RETURN
45°
HIGH EFFICIENCY
TAKEOFF (HETO)
ROUND BRANCH DUCT
GASKET
MANUAL BUTTERFLY BALANCE
DAMPER WITH LOCKING QUADRANT
STANDOFF FOR
INSULATION THICKNESS
LOW VELOCITY
SUPPLY DUCT
SHORT RADIUS RIGID METAL ELBOW
WHERE 1.5D FLEX ELBOW CAN NOT BE
MAINTAINED
DUCT WRAP INSULATION
PER SPECIFICATIONS
REFER TO SURFACE-MOUNTED
DIFFUSER DETAIL FOR INSTALLATION
REQUIREMENTS
LAY-IN CEILING
TILE, TYPICALTEE-BAR
GRID, TYPICAL
NYLON STRAP
FASTENER, TYPICAL
STRAP HANGER
INSULATED FLEX DUCT, 6'-0"
MAXIMUM LENGTH, ALLOWED
ABOVE LAY-IN CEILINGS AT SUPPLY
DIFFUSERS ONLY, TYPICAL
SUPPLY DIFFUSER
AS SCHEDULED,
TYPICAL
1.5DM
AX
DIRECTION OF AIRFLOW
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 www.pec1.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
/2
/2
:2
:2
P
M B
IM
/1
R
A tr ia x M u rf re e s b o ro
C M
O P
/2
-0
-M E
C H
-R
.r v t
M-201
MECHANICAL DETAILS & SCHEDULES MEDS BY MAIL OFFICE
EXPANSION AT THE
MID-SOUTH CMOP
3209 ELAM FARMS PKWY, MURFREESBORO, TN 67127
764-21-101
N/A
03/25/2022 TJS KWP 12 17
1.
2.
3.
4.
ALL TERMINAL UNITS SHALL BE PROVIDED WITH FLOW-RING SERVICE 'T'.
ALL ELECTRIC TERMINAL UNITS SHALL BE PROVIDED WITH INDEPENDENT DISCONNECT SWITCH AND FUSE BLOCK BY EQUIPMENT MANUFACTURER.
PROVIDE THERMOSTAT COMPATIBLE WITH EXISTING DDC SYSTEM. NEW SYSTEMS SHALL BE COMPATIBLE WITH EXISTING HONEYWELL "NIAGARA WEB-600" CONTROLS AS INSTALLED BY C-TECH CONTROLS (888-868-1688, ctechcontrols.com). ALL LOW VOLTAGE HVAC CONTROLS CABLING SHALL BE PROVIDED AND INSTALLED BY TCC. COORDINATE WITH TCC.
TERMINAL UNIT TO BE PROVIDED BY ALTERNATE #1. VAV-16 TO BE OMITTED IF TAKING ALTERNATE #1.
REMARKS:
TERMINAL UNIT SCHEDULE
MARK
BASED ON
UNIT
SIZE
INLET
SIZE
(INCH)
PRIMARY AIRFLOW
OP SP
(IN WC)
MAX
NC
RAD
HEATING COIL
EMERGENCY
POWER
LINER
TYPE
REMARKS
MFR MODEL
MAX
(CFM)
MIN
(CFM)
AIR ELECTRIC COIL
CFM
EAT
(°F)
LAT
(°F)
CAP
(KW)
VOLT PHASE STEPS MCA MOP
VAV-13 TITUS DESV 8 8" 575 175 1 30 320 55 89.6 3.5 277 1 SCR 15.8 20 No FIBER FREE 1-3
VAV-14 TITUS DESV 8 8" 550 175 1 30 275 55 89.5 3 277 1 SCR 13.5 15 No FIBER FREE 1-3
VAV-15 TITUS DESV 8 8" 700 225 1 30 350 55 86.6 3.5 277 1 SCR 15.8 20 No FIBER FREE 1-3
VAV-16 TITUS DESV 10 10" 1000 300 1 30 550 55 86.6 6.5 277 1 SCR 29.3 30 No FIBER FREE 1-3
VAV-16A TITUS DESV 6 6" 400 125 1 30 200 55 92.3 2 277 1 SCR 9.0 15 No FIBER FREE 1-4
VAV-17A TITUS DESV 8 8" 600 200 1 30 300 55 86.6 3 277 1 SCR 13.5 15 No FIBER FREE 1-4
S R P E L M C U
SUPPLY DIFFUSER
RETURN GRILLE
PLENUM RETURN GRILLE
EXHAUST GRILLE
SLOT DIFFUSER
LAMINAR FLOW SUPPLY DIFFUSER
SECURITY GRILLE
FLOOR MOUNTED SUPPLY GRILLE
1.
2.
3.
4.
5.
6.
7.
8.
PROVIDE SQUARE TO ROUND ADAPTERS AS REQUIRED TO ACCOMODATE ROUND RUNOUTS.
PROVIDE ALL LAY-IN GRDs WITH 24x24 LAY-IN PANEL AS REQUIRED.
FINISH TO BE WHITE UNLESS OTHERWISE SPECIFIED. COORDINATE AND VERIFY ALL FINISHES WITH ARCHITECT.
ALL SELECTIONS ARE BASED ON A MAXIMUM NC OF 25 UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL VERIFY ALL CEILING TYPES AND ASSOCIATED BORDER TYPES.
MARKS USED MAY NOT BE IN SEQUENCE.
LOUVERED GRILLES TO HAVE FRONT BLADES PARALLEL TO LONG DIMENSION UNLESS WALL MOUNTED.
WALL MOUNTED LOUVERED GRILLES TO HAVE FRONT BLADES PARALLEL TO FLOOR.
FIRST LETTER IN MARK: NOTES:
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
MARK TYPE IMAGE
BASED ON
MOUNT PANEL SIZE
(FACE SIZE)
MATERIAL
BLADE SPACING /
SLOT WIDTH
DEFLECTION COLOR REMARKS
MFR MODEL
SJ SUPPLY DIFFUSER TITUS OMNI-AA LAY-IN 24x24 ALUMINUM -- -- WHITE --
SL SUPPLY DIFFUSER TITUS OMNI-AA SURFACE 24x24 ALUMINUM -- -- WHITE --
SW WALL SUPPLY TITUS 300FS WALL SEE PLANS ALUMINUM 3/4" DOUBLE
MATCH
WALL
SY
DUCT MOUNTED
SUPPLY
TITUS S300FS DUCT SEE PLANS ALUMINUM 3/4" DOUBLE
MATCH
DUCT
AIR SCOOP DAMPER
PL
RETURN GRILLE
(PLENUM RETURN)
TITUS 45F LAY-IN
24x12 (22x10)
ALUMINUM -- 45° WHITE REFER TO SOUND TRAP DETAIL
PM
RETURN GRILLE
(PLENUM RETURN)
TITUS 45F LAY-IN
24x24 (22x22)
ALUMINUM -- 45° WHITE REFER TO SOUND TRAP DETAIL
PO
RETURN GRILLE
(PLENUM RETURN)
TITUS 45F SURFACE
24x12 (22x10)
ALUMINUM -- 45° WHITE REFER TO SOUND TRAP DETAIL
RW WALL RETURN TITUS 350FL/S WALL SEE PLANS ALUMINUM 3/4" 35°
MATCH
WALL
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION MANUFACTURER MODEL DIMENSIONS
ADA
COMPLIANT
MATERIAL DESCRIPTION &
FINISH
TRIM
FLOW
FIXTURE
FLUSH
FIXTURE
PIPE RUNOUT SIZES
SPECIFICATION
MANUFACTURER MODEL
CONTROL
TYPE
POWER FLOW (GPM)
VOLUME
PER FLUSH
(GAL)
COLD
WATER
HOT
WATER
WASTE VENT
SK-1 SINK - SINGLE BOWL ELKAY LRAD191865
19" x 18" x 6-1/2" (16" x
11-1/2" BOWL)
Yes STAINLESS STEEL ELKAY "AVADO" LKAV3031LS MANUAL -- 1.8 -- 1/2" 1/2" 2" 1-1/2"
SINGLE HOLE DRILLING - FAUCET WITH PULL DOWN SPRAY, LEVER HANDLE, CERAMIC DISC VALVE, LESS ESCUTCHEON - LEONARD 170-OF ASSE 1070 THERMOSTATIC MIXING VALVE IN HOT WATER SUPPLY SET TO 105°F - GRID DRAIN - WALL SUPPLIES WITH QUARTER TURN STOPS - LKAD35 OR EQUAL OFFSET DRAIN WITH GRID STRAINER - 1-1/2" CHROME PLATED CAST BRASS P-TRAP. INSULATE AS REQUIRED FOR ADA COMPLIANCE.
NO SCALE
RETURN GRILLE SOUND TRAP DETAIL
NO SCALE
RETURN AIR TRANSFER DUCT
NO SCALE
TERMINAL UNIT REHEAT DETAIL
NO SCALE
PIPE HANGER DETAIL
NO SCALE
DUCT TAKEOFF DETAILS
NO SCALE
DIFFUSER INSTALLATION DETAIL - SLOT
ONE-LINE
LSIG = LONG TIME, SHORT TIME,
INSTANTANEOUS, GROUND FAULT
GFI = GROUND FAULT
DISCONNECT SWITCH (SEE EQUIP
CONN SCHED)
CIRCUIT BREAKER
OVERLOADS
FUSE
INDICATOR LIGHT(G=GREEN, R=RED)
CIRCUIT BREAKER ACCESSORIES:
CONTACTS (N.O., N.C.)
K = KIRK KEY INTERLOCK
(CIRCUIT NUMBER / SWITCH SIZE
/ FUSE SIZE / # OF POLES) (# OF
POLES IF OTHER THAN 3)
FUSIBLE SWITCH
ST = SHUNT TRIP
DRAWOUT CONTACTS
G
A
A
A A
AT
AFA
PANEL
M M
VFD AT
RV
SPD
LSIG
GFI
ST
K
'1'
HP KW
N
ATS
E
'1'
(VOLTAGE / SWITCH SIZE / FUSE
SIZE / # OF POLES - NOTED IF
EQUIPMENT NOT SCHEDULED)
STARTER (SEE EQUIP CONN SCHED)
(VOLTAGE / STARTER SIZE /
# OF POLES - NOTED IF
EQUIPMENT NOT SCHEDULED)
GROUND CONNECTION
LIGHTNING ARRESTOR
FEEDER DESIGNATION
SURGE PROTECTIVE DEVICE
(CIRCUIT NUMBER / SWITCH
SIZE / FUSE SIZE / # OF POLES
/ STARTER SIZE) (# OF POLES
IF OTHER THAN 3)
STARTER WITH FUSIBLE SWITCH
2P
2P
(CIRCUIT NUMBER / TRIP SIZE / #
OF POLES) (FRAME SIZE / TRIP
SIZE) (# OF POLES IF OTHER
THAN 3)
CIRCUIT BREAKER (MOLDED CASE
NON-ADJUSTABLE TRIP /
ADJUSTABLE TRIP)
2P 2P
3Ø TRANSFORMER (DELTA PRIMARY
/ WYE SECONDARY)
1Ø TRANSFORMER
METER (UTILITY / PANEL MOUNTED)
EQUIPMENT (SINGLE MOTOR / MULTI-
MOTOR OR OTHER TYPE AS NOTED)
VARIABLE FREQUENCY DRIVE
(HP SIZE IF NOT SCHEDULED)
PANELBOARD
(BUILT-IN SPD)
SPD
TRANSFER SWITCH (ATS =
AUTOMATIC, MTS = MANUAL)
MOTOR STARTER [SINGLE SPEED
ACROSS-THE-LINE (UON)]
(AMP SIZE / VOLTAGE / POLES
/ AIC RATING / NEMA RATING)
(NEMA RATING IF OTHER
THAN NEMA-1)
(NEMA SIZE /
RV AT= REDUCED VOLTAGE /
AUTO-TRANSFORMER /
SS = SOLID STATE)
T1. EACH DATA, TELEPHONE, VIDEO, OR OTHER SYSTEMS
OUTLET REQUIRES 1"C. WITH PULL ROPE STUBBED 6"
ABOVE NEAREST ACCESSIBLE CEILING UNLESS
OTHERWISE NOTED ON PLANS. CONDUITS STUBBED
UP ABOVE CEILINGS SHALL BE TURNED OUT 90
DEGREES. PROVIDE INSULATED BUSHINGS ON ALL
CONDUITS. LABEL CONDUIT TO IDENTIFY ITS
INTENDED USE (I.E. TELEPHONE, DATA, ETC.).
COMMUNICATION / DATA
F1. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED
PER THE REQUIREMENTS OF NFPA 72, 2013 EDITION.
DEVICES SHOWN INDICATE DESIGN INTENT AND SHALL
BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER SHALL
PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR
DEVICES REQUIRED BY THE AUTHORITY HAVING
JURISDICTION.
F2. FIELD VERIFY LOCATIONS OF AREA SMOKE DETECTORS
AND HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF
A HVAC DIFFUSER (SUPPLY OR RETURN), IN A DIRECT
AIR FLOW, WITHIN 36" OF A SPRINKLER HEAD, OR WITHIN
36" OF THE TIP OF A CEILING FAN BLADE. SMOKE
DETECTORS FOR DOOR RELEASE SHALL BE LOCATED
ON THE CENTER LINE OF THE DOOR AND A MAXIMUM OF
5 FEET FROM THE DOOR. THE MINIMUM DISTANCE FROM
THE DOOR IS THE DEPTH OF THE WALL SECTION ABOVE
THE DOOR, BUT NOT LESS THAN 12".
F4. LABEL REMOTE ALARM INDICATOR FOR DUCT
MOUNTED SMOKE DETECTORS (I.E. RTU-=1 SUPPLY,
RTU-2 RETURN, FIRE/SMOKE DAMPER, ETC.). DUCT
DETECTORS SHOULD BE LOCATED IN THE AREA
BETWEEN 6 AND 10 DUCT EQUIVALENT DIAMETERS
OF STRAIGHT, UNITERRUPTED DUCTWORK. DUCT
DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD
BE LOCATED BETWEEN THE LAST INLET OR OUTLET
UPSTREAM OF THE DAMPER AND THE FIRST INLET
OR OUTLET DOWNSTREAM OF THE DAMPER.
F3. FAN SHUTDOWN RELAY WIRING SHALL BE LOCATED
WITHIN 3 FEET OF THE FAN CONTROLS AND THE WIRING
TO THE RELAY SHALL BE MONITORED.
F5. PROVIDE 120V POWER AND FUSTAT FOR EACH
FIRE/SMOKE DAMPER. INTERLOCK WITH FIRE ALARM
CONTROL PANEL TO CLOSE THE FIRE/SMOKE DAMPER
UPON ANY ALARM AT THE FIRE ALARM CONTROL PANEL
AND TO SHUTDOWN THE ASSOCIATED MECHANICAL UNIT.
FIRE ALARM
1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE
LATEST EDITION OF THE NATIONAL ELECTRICAL CODE
(NEC) & THE AMERICANS WITH DISABILITIES ACT (ADA).
2. REFER TO RELATED ARCHITECTURAL, MECHANICAL,
STRUCTURAL, AND CIVIL DRAWINGS FOR RELATED
INFORMATION.
3. REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE
DRAWINGS.
4. E.C. SHALL REFER TO MECHANICAL DRAWINGS AND
SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED
WITH WIRING AND CONNECTION OF INTERLOCKING AND
CONTROLS OF MECHANICAL UNITS AND THERMOSTAT
LOCATIONS.
5. COORDINATE OUTLET BOX LOCATIONS WITH MASONRY TO
MINIMIZE CUTTING OF BRICK OR BLOCK.
6. ALL MOUNTING HEIGHTS TO CENTERLINE OF ITEM UNLESS
OTHERWISE NOTED. VERIFY ALL OUTLET LOCATIONS ON
THE JOB PRIOR TO ROUGH-IN.
7. CONDUIT RUN W/CONDUCTORS AS INDICATED & GROUND
WIRE SIZED PER N.E.C. 250.122. CONDUIT SIZE AS
REQUIRED.
8. WHEN INCREASED CONDUCTOR SIZES ARE SHOWN ON
THE PLANS, THE LARGER CONDUCTOR SIZE SHALL BE
USED THROUGHOUT THE LENGTH OF THE CIRCUIT,
INCLUDING NEUTRAL AND GROUND.
9. "CT" INDICATED ADJACENT TO DEVICE INDICATES DEVICE
MOUNTED ABOVE BACKSPLASH OF COUNTER TOP.
VERIFY EXACT HEIGHT WITH ARCHITECTURAL PLANS AND
ELEVATIONS.
10. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME
RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE
CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY
BE GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE
CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE
MARKED OR LABELED TO INDICATE WHICH CIRCUIT THEY
ARE ASSOCIATED WITH. SEE SPECIFICATION SECTION
"LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND
CABLES" FOR ADDITIONAL INFORMATION.
12. LABEL THE FRONT OF EACH RECEPTACLE COVERPLATE
WITH PANEL DESIGNATION AND CIRCUIT NUMBER
USING CLEAR THERMAL TRANSFER (ELECTRONIC
DYMO) LABELS WITH 1/8" HIGH BLACK LETTERS (OR
CONTRASTING COLOR IF COVERPLATES ARE BLACK OR
BROWN). LABELS SHALL BE SUITABLE FOR
INDOOR/OUTDOOR USE. LABEL THE BACK OF EACH
LIGHT SWITCH COVERPLATE WITH PANEL DESIGNATION
AND CIRCUIT NUMBER USING A FINE BLACK
PERMANENT MARKER.
11. JUNCTION BOX OR RECEPTACLE FOR DRINKING FOUNTAINS
SHALL BE LOCATED BEHIND THE EQUIPMENT SKIRT UNLESS
OTHERWISE NOTED. COORDINATE CONNECTION TYPE AND
LOCATION WITH EQUIPMENT PROVIDED.
13. PROVIDE 18" LONG (MIN.) CONDUIT SLEEVES THRU ALL
WALLS WHERE CABLES ARE INDICATED OR REQUIRED TO
PASS THRU WALLS. PROVIDE BUSHINGS ON BOTH ENDS.
SIZE CONDUIT FOR CABLES INSTALLED. AT CABLE TRAYS,
PROVIDE ONE 4" CONDUIT SLEEVE FOR EACH 4" WIDTH OF
CABLE TRAY. MAXIMUMS SHALL BE:
1"C. = 10 CABLES
2 1/2"C. = 20 CABLES
3"C. = 30 CABLES
4"C. = 50 CABLES
14. LOCATE CABLE TRAYS 6" ABOVE CEILING. OFFSET TRAY
UP AND OVER LIGHT FIXTURES AND DUCTWORK (FIELD
VERIFY AND PROVIDE AS REQUIRED). IF PHYSICALLY
IMPOSSIBLE TO RUN CABLE TRAY UP AND OVER, THEN
PROVIDE CABLE SUPPORT HOOKS FROM STRUCTURE
ABOVE, SIZED AND RATED FOR INSTALLED CABLES PLUS
25% SPARE.
15. PROVIDE DIMMER PER THE SPECIFICATIONS.
COORDINATE DIMMER TYPE AND WIRING WITH
ASSOCIATED LIGHT FIXTURE DIMMING REQUIREMENTS (I.E.
3-WIRE, O-10V, ELECTRONIC OR MAGNETIC LOW VOLTAGE,
ETC.) OR WITH LIGHTING CONTROL SYSTEM PROPRIETARY
REQUIREMENTS (I.E. LUTRON, nLIGHT, DALI, ETC.) AS
NECESSARY. 3-WIRE DIMMERS SHALL BE PROVIDED WITH
A DEDICATED NEUTRAL FOR EACH CONTROL ZONE. 0-10V
DIMMERS SHALL BE PROVIDED WITH DIM/ON/OFF
CONTROL. COORDINATE PHASE CONTROL OF LED
DRIVERS (I.E. REVERSE PHASE, FORWARD PHASE, ETC.)
WITH LIGHT FIXTURE MANUFACTURER'S
RECOMMENDATIONS. LOW VOLTAGE CONTROL WIRING IS
NOT SHOWN ON PLANS FOR CLARITY, BUT SHALL BE
PROVIDED AS REQUIRED.
- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -
- - - SYMBOL LIST IS FOR REFERENCE ONLY. ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT. - - -
PEN WEIGHT LEGEND
LIGHT FIXTURE TO BE REMOVED
EXISTING LIGHT FIXTURE TO REMAIN
NEW LIGHT FIXTURE
DUPLEX GROUNDED REC TO BE REMOVED
EXISTING DUPLEX GROUNDED REC TO REMAIN
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK
SOLID LINES ARE NEW TO BE INSTALLED
NEW DUPLEX GROUNDED RECEPTACLE
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN HALFTONE
SOLID LINES ARE EXISTING TO REMAIN
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK
DASHED LINES ARE EXISTING TO BE REMOVED
LIGHT FIXTURE TO BE RELOCATED
DUPLEX GROUNDED REC TO BE RELOCATED
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT
DASHED LINES ARE EXISTING TO BE RELOCATED
SECURITY
WALL M
E
W
W
K KEY PAD
SECURITY BEAM DETECTOR
GLASS BREAK SENSOR
CARD READER
MAGNETIC LOCK
ELECTRIC DOOR STRIKE
DOOR POSITION SWITCH
DOOR LOCK & POSITION SWITCHDOOR RELEASE BUTTON
CCTV CAMERA - FIXED
CCTV CAMERA - FIXED
CCTV CAMERA - PAN/TILT/ZOOM
DURESS
CCTV CAMERA - PAN/TILT/ZOOM
SEC ROOM MOTION DETECTOR
SEC ROOM MOTION DETECTOR
WALL
CEILING
CEILING
REQUEST TO EXIT DEVICE (MOTION)ED
WALL/CLG
SEC CORRIDOR MOTION DETECTOR
CEILING
B
CR
RE REQUEST TO EXIT DEVICE (PSHBTN) WALL
CONDUIT AND WIRING
PHASE CONDUCTORS/
NEUTRAL CONDUCTOR (#12 UON)
EMERGENCY CIRCUIT
CONDUIT RUN PARTIAL CIRCUIT.
2#12 & 1#12 GRD. - 1/2"C.
CDT RUN 2#12 & 1#12 GRD.- 1/2"C.
OR CDT RUN AS NOTED ON PLAN
CDT RUN 2#12 & 1#12 GRD.- 3/4"C.
OR CDT RUN AS NOTED ON PLAN
CLG/WALL
MASTER/SLAVE FIXTURE WHIP
CONDUIT HOME RUN, 2 CIRCUITS.
4#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 1 CIRCUIT.
2#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 3 CIRCUITS.
6#12 & 1#12 GRD. - 1/2"C.
CONDUIT HOME RUN, 1 CIRCUIT.
2#10 & 1#10 GRD. (GEN. NOTES 7 & 8)
#10
GROUND CONDUCTOR (#12 UON)
CONDUIT HOME RUN, 2 CIRCUITS
SWITCH LEGS (#12 UON)
CEILING
CLG/WALL
CLG/WALL
EARTH/
FLOOR
CLG/WALL
CLG/WALL
CLG/WALL
CLG/WALL
CLG/WALL
LOW VOLTAGE WIRING CLG/WALL
MISC. EQUIPMENT CONNECTION
CONDUIT SEAL OFF
FIRE ALARM
46"AFFFIRE ALARM MANUAL STATION
DUCT SMOKE DETECTOR &
FIRE/ SMOKE DAMPER (GEN
NOTES F4 & F5)
FIRE ALARM VISUAL SIGNAL
FIRE ALARM HORN
DUCT SMOKE DETECTOR
(GEN NOTE F4)
IONIZATION AREA SMOKE
DETECTOR (GEN NOTE F2)
PHOTO ELECTRIC AREA SMOKE
DETECTOR (GEN NOTE F2)
F.A. RELAY (GEN NOTE F3)R
CH CHIME
DUCTWORK
CEILING
FIRE ALARM CONTROL PANEL'FACP'
FIRE SPRINKLER ALARM BELL
WALL
BOTTOM 80"
COMB. F.A. HORN & VISUAL SIGNAL
BOTTOM 80"
BOTTOM 80"
FIRE ALARM SPEAKER
COMB FA SPEAKER & VISUAL SIGNAL
FIRE ALARM REMOTE ANNUNCIATOR'FAAP' WALL
COMB FA HORN & VISUAL SIGNAL
FSD DUCTWORK
WALL
WALL
WALL
BOTTOM 80"
FIRE SPRINKLER TAMPER SWITCH
ELECTROMAGNETIC DOOR HOLDER
FIRE SPRINKLER WATER FLOW SW
HEAT DETECTOR (GEN NOTE F2)
SPRKLR RSR
C FIRE ALARM CONTROL MODULE
FIRE ALARM MONITOR MODULE
FIRE ALARM SPEAKER
FIRE SPRINKLER PRESSURE SWITCH
FIRE ALARM SPEAKER
CEILING
WALL
WALL
SPRKLR RSR
CEILINGFIRE ALARM VISUAL SIGNAL
M
P
H
T
W
DH
1-VOICE OUTLET & JACK (GEN
NOTE T1)
1-VOICE/1-DATA OUTLET &
JACKS (GEN NOTE T1)
1-DATA OUTLET & JACK (GEN
NOTE T1)
18"AFF
CABLE TV OR VIDEO OUTLET &
CONNECTOR (GEN NOTE T1)
1-VOICE/2-DATA OUTLETS &
JACKS (GEN NOTE T1)
2-VOICE/2-DATA OUTLETS & JACKS
(GEN NOTE T1)
1-VOICE/3-DATA OUTLETS &
JACKS (GEN NOTE T1)
4-DATA OUTLETS & JACKS (GEN
NOTE T1)
2-DATA OUTLETS & JACKS (GEN
NOTE T1)
3-DATA OUTLETS & JACKS (GEN
NOTE T1)
18"AFF
18"AFF
18"AFF
18"AFF
18"AFF
18"AFF 18"AFF
18"AFF
18"AFF
COMMUNICATION / DATA
POWER
DUPLEX GROUNDED RECEPTACLE
FUSTAT BUSS #SSY
SPECIAL DEVICE (AS NOTED)
JUNCTION BOX - 1-GANG
DOUBLE DUPLEX GROUNDED REC
GROUND FAULT DUPLEX REC
DUPLEX GROUNDED RECEPTACLE
SINGLE GROUNDED RECEPTACLE
DUPLEX GRD REC BOTTOM SWITCHD
GRD FAULT DOUBLE DUPLEX REC
18" AFF
A
ELECTRICAL DISTRIBUTION EQUIP
EQUIPMENT - SEE EQUIPMENT
CONNECTION SCHEDULE
x-x x-x
CONDUIT SLEEVE (GEN NOTE 13)
CABLE TRAY (GEN NOTE 14)
FEEDER DESIGNATION
M MANUAL STARTER
CIRCUIT BREAKER
DISCONNECT SWITCH
M MOTOR
PLUGMOLD SURFACE RACEWAY
S
18" AFF
18" AFF
CEILING
18" AFF
18" AFF
18" AFF
FLOOR/WALL
72" TO TOP
WALL
JUNCTION BOX - 2-GANG
PLUG LOAD SENSOR CEILING
HANDICAP DOOR PUSHBUTTON 36" AFF
RELAY
PUSHBUTTON (1-BUTTON, 2-BUTTON)
BOX MOUNTED TRANSFORMER
46" AFF
CONTACTOR
METER
STARTER OR ATS (AS NOTED)
COMBINATION STARTER/DISC
BUSDUCT PLUG
THERMOSTAT/TEMP SENSOR 46" AFF
SPECIAL OUTLET (SEE
SCHEDULE OR AS NOTED)
BRANCH CIRCUIT PANEL AND
PANEL DESIGNATION
AA
TS
H
P
R
TAMPER-PROOF DUPLEX REC 18" AFF
TAMPER-PROOF GFCI DUPLEX REC 18" AFF
T
C
1J
J
F
1D
2M
SWITCHES (KEYED, PILOT, TIMER)
INDICATES SWITCHING SCHEME
EMERGENCY BATTERY LIGHT FIXT
LIGHT FIXTURE & FIXTURE LETTER
46" AFF
A
A
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
STRIP LIGHT FIXTURE & FIXT LETTERA
A
A
A
1 RELAY OCCUPANCY SENSOR SW
2 RELAY OCCUPANCY SENSOR SW
OCCUPANCY SENSOR
1 RELAY OCCUPANCY SENSOR/
DIMMER SWITCH (GEN NOTE 15)
M
D DIMMER SWITCH (GEN NOTE 15)
ON/OFF SWITCH
S
DS DAYLIGHT SENSOR
CLG/WALL
46" AFF
46" AFFSSS
SSS
S a, b, c
CLG SURF/
RECESSED
CEILING
WALL
CEIL/WALL
WALL
CEIL/WALL
46" AFF
46" AFF
46" AFF
46" AFF
2 3 4
K P T
LIGHTING, SWITCHES AND SENSORS
SWITCHES (1-POLE, 2-POLE,
3-WAY, 4-WAY)
EXIT SIGN (SHADING DENOTES
EXIT FACE SIDE)
FIXTURE WITH SHADED LAMP(S)
ON EMERGENCY POWER
WALLCOMB EXIT SIGN/EM BATTERY LIGHT
LP LIGHTING CONTROL POWER PACK
EP UL-924 LISTED POWER PACK
46" AFF
ON/OFF/0-10V DIMMING SWITCH
S
46" AFF
DUAL TECH ON/OFF SENSOR
S
46" AFF
16-SCENE WALL CONTROLLER
S
46" AFF
DUAL TECH ON/OFF/0-10V DIM SW
S
46" AFF
LOW VOLTAGE SWITCH
S
A
A
A
A A
LIGHT FIXTURE & FIXTURE LETTERA POLEA
AV AV SYSTEM/LIGHTING INTERFACE
A
A CLG SURF/
RECESSED
A
CLG SURF/
RECESSED
A A
A
A
LIGHTING TRACK, TRACK FIXTURES,
& FIXTURE LETTERS CEILING
A AA
A A T
CEILING
PC PHOTOCELL
NIGHT LIGHT - WIRE AHEAD OF
ABBREVIATIONS
NL
EM
WP
CT
UON
ON EMERGENCY POWER
WEATHERPROOF
COUNTERTOP (SEE GEN. NOTE 9)
UNLESS OTHERWISE NOTED
ABOVE FINISHED FLOORAFF
AFG ABOVE FINISHED GRADE
WALLW
CONTROLS
DRINKING FOUNTAIN -
SEE GENERAL NOTE 11
DF
GAP GENERATOR ANNUNCIATOR PANEL
GENERAL NOTES
SYMBOL
SYMBOL LIST
DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING SYMBOL
SYMBOL LIST
DESCRIPTION MOUNTINGDESCRIPTIONSYMBOLMOUNTING
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 www.pec1.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
/2
/2
:0
:0
P
M B
IM
/1
R
A tr ia x
M u rf re e s b o ro C
M O
P /2
-0
E
L E
C R
.r v t
E-001
ELECTRICAL GENERAL NOTES AND
SYMBOLS
MEDS BY MAIL OFFICE
EXPANSION AT THE
MID-SOUTH CMOP
3209 ELAM FARMS PKWY, MURFREESBORO, TN 67127
764-21-101
N/A
03/25/2022 DDC KTN 13 17
ELECTRICAL SHEET INDEX
SHEET NO. SHEET TITLE
E-001 ELECTRICAL GENERAL NOTES AND SYMBOLS
E-101 POWER & SYSTEMS PLAN
E-102 LIGHTING PLAN
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES
SPECIAL OUTLETS
MARK DESCRIPTION
SF1 SYSTEM FURNITURE WALL OUTLET: CONNECT SYSTEM FURNITURE PER DETAIL 7/E501.
VERIFY EXACT LOCATION WITH FURNITURE PROVIDER PRIOR TO ROUGH-IN.
CT
CT
J
J
J J
J J
J
J
E
E
E
E
E
E
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED
U.L. ASSEMBLY NUMBERS.
5. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE
WITH THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS
AND SPECIFICATIONS.
6. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
7. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
8. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE
MOLDABLE FIRE BARRIER.
9. FIELD VERIFY THE EXACT LOCATION OF ALL FLOOR BOXES AND POKE
THROUGHS WITH ARCHITECT PRIOR TO ROUGH-IN.
10. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED PER THE
REQUIREMENTS OF NFPA 72. DEVICES SHOWN INDICATE THE DESIGN
INTENT AND SHALL BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER SHALL
PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR DEVICES
REQUIRED BY THE AUTHORITY HAVING JURISDICTION.
11. ALL DATA CABLING SHALL BE CAT. 6A WITH BLUE COLORED JACKET. VERIFY
WITH OWNER PRIOR TO INSTALLATION.
OFFICE
OFFICE
OFFICE
COFFEE
SCANNER/MAIL
PROCESSING
RECORDS ROOM
SUPPLY ROOM
RETURN MEDS ROOM
(E) HSK
(E) SWITCH ROOM
CUBICLES
CORRIDOR
HALLWAY
HALLWAY
(E) COMPUTER TRAINING
(E) GROUP FITNESS
(E) STOR
(E) WORKOUT ROOM
(E) WOMEN
(E) MEN
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OCCUPATIONAL HEALTH
(E) STORAGE
(E) STAIR
(E) ELEV. MACHINE
(E) STAIR
(E) OPEN SPACE
(E) ELEV
HOB-1
EXISTING 75kVA
TRANSFORMER
LOB-1
LOB-2
TX-LOB-2
VAV-16
VAV-14
VAV-13
VAV-17A
SF1
SF1
S1S1
LOB-2:1
LOB-2:3
LOB-2:5
LOB-2:7
LOB-2:9
LOB-2:11
LOB-2:13
LOB-2:17
LOB-2:15
LOB-2:37
LOB-2:21
LOB-2:23
LOB-2:25
LOB-2:27
LOB-2:31
LOB-2:33
LOB-2:35
COPIER
LOB-2:19
LOB-2:29
P1
P1
P1
P1 P1
P1
P2
P2
VAV-15
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 www.pec1.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
AREA OF CONSTRUCTION
/2
/2
:0
:1
P
M B
IM
/1
R
A tr ia x
M u rf re e s b o ro C
M O
P /2
-0
E
L E
C R
.r v t
E-101
POWER & SYSTEMS PLAN MEDS BY MAIL OFFICE
EXPANSION AT THE
MID-SOUTH CMOP
3209 ELAM FARMS PKWY, MURFREESBORO, TN 67127
764-21-101
N/A
03/25/2022 DDC KTN 14 17
KEYED NOTES
P1 ACCESS CONTROL ROUGH-IN. VERIFY ALL SYSTEM REQUIREMENTS WITH
MANUFACTURER PRIOR TO ROUGH-IN. REFER TO DETAIL 8/E-501 FOR
ADDITIONAL INFORMATION.
P2 IF TAKING ALTERNATE #1, USE VAV-16A AND VAV-17A SCHEDULED DATA.
OTHERWISE, USE VAV-16 SCHEDULED DATA ONLY AND OMIT VAV-16A AND
VAV-17A.
S1 PROVIDE JUNCTION BOX AND CONDUIT ABOVE ACCESSIBLE CEILING FOR
SIX (6) CAT. 6A CABLES WITH BLUE COLORED JACKET FOR SYSTEMS
FURNITURE. VERIFY LOCATION AND ALL REQUIREMENTS WITH SYSTEMS
FURNITURE PRIOR TO ROUGH-IN.
0' 8' 12'4' 1/8" = 1'-0"
POWER & SYSTEMS PLAN
A
1D
1D 1D
1D 1D
1D
1D 1D
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR LABELED
TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH. SEE
SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
CONDUITS.
3. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
LOCATIONS OF FIRE RATED WALLS AND CEILINGS AND THE ASSOCIATED U.L.
ASSEMBLY NUMBERS.
4. FOR ALL PENETRATIONS IN FIRE RATED WALLS AND CEILINGS, PROVIDE AN
ASTM E814 COMPLIANT, U.L. LISTED THROUGH PENETRATION FIRE
STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL OR CEILING
CONSTRUCTION ASSEMBLY. INSTALL SYSTEM IN STRICT COMPLIANCE WITH
THE U.L. ASSEMBLY INDICATED IN THE ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN FIRE RATED WALLS OR CEILINGS SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON OPPOSITE
SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A HORIZONTAL
DISTANCE OF 24 INCHES OR PROTECTED BY OTHER MEANS ALLOWED BY
THE SPECIFIC U.L. ASSEMBLY.
7. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF STC RATED
WALLS. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) ON
OPPOSITE SIDES OF STC RATED WALLS SHALL BE LIMITED TO TWO OUTLET
BOXES PER STUD SPACE AND COVERED WITH "PUTTY PAD" TYPE MOLDABLE
FIRE BARRIER.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LIGHT
FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH ARCHITECT PRIOR
TO ROUGH-IN.
9. OCCUPANCY SENSORS SHALL MATCH EXISTING FACILITY STANDARDS.
VERIFY WITH OWNER PRIOR TO INSTALLATION.
OFFICE
OFFICE
OFFICE
COFFEE
SCANNER/MAIL
PROCESSING
RECORDS ROOM
SUPPLY ROOM
RETURN MEDS ROOM
(E) HSK
(E) SWITCH ROOM
CUBICLES
CORRIDOR
HALLWAY
HALLWAY
(E) COMPUTER TRAINING
(E) GROUP FITNESS
(E) STOR
(E) WORKOUT ROOM
(E) WOMEN
(E) MEN
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OFFICE
(E) OCCUPATIONAL HEALTH
(E) STORAGE
(E) STAIR
(E) ELEV. MACHINE
(E) STAIR
(E) OPEN SPACE
(E) ELEV
HOB-1
LOB-1
LOB-2
TX-LOB-2
EXISTING 75kVA
TRANSFORMER
K2 K2
K2 K2
K2K2
X1L3L3
L3 L3
K3 K3
L3 L3
K3
K3
K3 K3
K3
K3
X1
X1
K2 K2 K2 K2 K2 K2 K3
X1
X1
F4 F4 F4 F4
F4
K3 K3 K3 K3
K3K3
K3 K3
K3
K3HOB-1:12
HOB-1:14
L1
L2
L2
L2
L2
L2
X1
X1
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number:
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
Dwg. of o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Veterans Health
Administration GLMV Architecture Architect 1525 E. Douglas, Wichita, KS 67211
Phone: 316-265-9367 www.glmv.com
Professional Engineering Consultants (PEC) MEP Engineers 623 Massachusetts Street, Suite 200, Lawrence, KS 66044
Phone: 785-842-6464 www.pec1.com
Atriax, pllc 102 3rd Avenue NE, Hickory, NC 28601 PO Box 1629, Hickory, NC 28603
Phone: 828-315-9962 www.atriaxgroup.com
KEYPLAN
AREA OF CONSTRUCTION
/2
/2
:0
:1
P
M B
IM
/1
R
A tr ia x
M u rf re e s b o ro C
M O
P /2
-0
E
L E
C R
.r v t
E-102
LIGHTING PLAN MEDS BY MAIL OFFICE
EXPANSION AT THE
MID-SOUTH CMOP
3209 ELAM FARMS PKWY, MURFREESBORO, TN 67127
764-21-101
N/A
03/25/2022 DDC KTN 15 17
KEYED NOTES
L1 EXISTING WALL MOUNTED EXIT SIGN TO BE DEMOLISHED. INSTALL NEW
CEILING MOUNTED EXIT SIGN AS INDICATED.
L2 INTERLOCK OCCUPANCY SENSORS PER MANUFACTURER'S
REQUIREMENTS. ALL NEW SENSORS TO MATCH EXISTING
MANUFACTURER AND TYPE.
0' 8' 12'4' 1/8" = 1'-0"
LIGHTING PLAN
A
PANEL
HOB-1
TX-LOB-2
75 KVA
PANEL
LOB-2
(E) STORAGE 206
TO "EDP"6"(MIN.)
46" AFF TO CENTERLINE, TOP OF
DEVICE SHALL NOT BE MORE THAN 48" AFF
MAGNETIC HOLD OPEN
OR CLOSURE/HOLD
OPEN. COORDINATE
WITH HARDWARE
SPECIFICATIONS.
(TYP.)
DETECTOR
SMOKE
FIRE ALARM DEVICE MOUNTING CRITERIA
THESE GUIDELINES SHALL BE USED
UNLESS MOUNTING HEIGHTS HAVE BEEN
SPECIFIED OTHERWISE ON THE DRAWINGS.
GENERAL NOTE
PULL STATION
REFER TO THE VISUAL UNIT.
AUDIO/VISUAL UNIT
AUDIO UNIT
VISUAL UNIT
TOP OF DETECTOR
ACCEPTABLE HERE
DO NOT PLACE DETECTOR
IN THIS AREA
MAINTAIN 36" BETWEEN SMOKE DETECTOR
AND AIR DIFFUSER/REGISTER/GRILL
PULL
STATION
12" 4"
90"
80"
46"
AUDIO/VISUAL
80" TO BOTTOM
AUDIO ONLY
6"(MIN.)
6"(MIN.)
AUDIO ONLY
90" TO TOP
VISUAL ONLY
80" TO BOTTOM
FINISH FLOOR
CEILING
MAX. OF 5'-0", MIN. OF "d"
BUT NOT LESS THAN 12"
DETECTORS ON ONE SIDE
OR BOTH SIDES OF DOOR
AS REQUIRED BY NFPA 72.
HEIGHT OF
DOOR HEADER "d"
AIR DIFFUSER
TOP OF DEVICE 90"…