Q&A’s for HQ Air Force Security Forces Center
1. Please verify the ceiling fans are to be provided by end user - (We provide fans, you provide drop down poles)
2. Will any modifications be required to existing ceiling for placement of new ceiling fans - i.e., movement of lights, speakers, alarm systems, fire sprinklers etc.,- (No, center as best as you can)
3. Please verify/clarify that no switch (shut off device) will be required for new ceiling fans and power for ceiling fans can come from any existing power source - (We desire to have a wall switch provided to shut off device, use existing power source)
4. Will a load calculation will be required for new ceiling fan circuits?
(No load calculation needed)
5. Will only the recessed can fixtures that are currently inoperable and or flickering will require new ballast? ( Yes)
6. Please verify type F1 and F2 fixtures are dual ballast ( Yes)
7. Please verify no lamps need replacing - only ballast all fixtures to be corrected ( Yes)
8. Will all F1 and F2 fixture ballast be replaced or only the fixtures that are in-operable? (Only the bad ones)
9. Do they need to be the same manufacturer/ballast type as what's already in place? If so, please provide info (No, any equivalent)