This document is a detailed technical specification (Section 28 31 70) for an Interior Fire Alarm System at the Power Independence Mission Control Station located at Buckley Space Force Base in Colorado. The specification outlines comprehensive requirements for a fully addressable fire alarm system, including detailed provisions for system components such as fire alarm control units, remote annunciators, manual stations, smoke and heat detectors, carbon monoxide detectors, notification appliances, and associated equipment. Key technical requirements include compatibility with existing AES and EST systems, compliance with NFPA 72 and UFC standards, addressable device capabilities, synchronization of visual notification appliances, and specific installation, testing, and documentation protocols.

The specification mandates rigorous technical and documentation standards, including detailed pre-installation submittals, qualifications for fire alarm system designers and technicians, extensive testing procedures, and comprehensive training requirements for government personnel. The system must provide complete supervision of circuits, support multiple levels of alarm prioritization, and include features like history logging, battery backup, and integration with building management systems. The contractor must provide complete documentation, including as-built drawings, operation and maintenance manuals, spare parts, and deliver a fully functional system with a 10-year repair service commitment. The estimated system installation cost ranges between $50,000 to $150,000 as part of a larger $25-100 million construction project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Power Independence, Mission Control Station - Buckley SFB, CO BUCO00102

SECTION TABLE OF CONTENTS

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

SECTION 28 31 70

INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE

08/20

PART 1 GENERAL

1.1 REFERENCES

1.2 RELATED SECTIONS

1.3 SUMMARY

1.3.1 Scope

1.3.2 Qualified Fire Protection Engineer (QFPE)

1.4 DEFINITIONS

1.4.1 Interface Device

1.4.2 Fire Alarm Control Unit (FACU)

1.4.3 Remote Fire Alarm Control Unit

1.4.4 Terminal Cabinet

1.4.5 Control Module and Relay Module

1.4.6 Designated Fire Protection Engineer (DFPE)

1.4.7 Qualified Fire Protection Engineer (QFPE)

1.5 SUBMITTALS

1.6 SYSTEM OPERATION

1.6.1 Alarm Initiating Devices and Notification Appliances (Visual, Audible)

1.6.2 Functions and Operating Features

1.7 TECHNICAL DATA AND SITE-SPECIFIC SOFTWARE

1.8 QUALITY ASSURANCE

1.8.1 Submittal Documents

1.8.1.1 Preconstruction Submittals

1.8.1.2 Nameplates

1.8.1.3 Wiring Diagrams

1.8.1.4 System Layout

1.8.1.5 Notification Appliances

1.8.1.6 Initiating Devices

1.8.1.7 Battery Power

1.8.1.8 Voltage Drop Calculations

1.8.1.9 Product Data

1.8.1.10 Operation and Maintenance (O&M) Instructions

1.8.1.11 As-Built Drawings

1.8.2 Qualifications

1.8.2.1 Fire Alarm System Designer

1.8.2.2 Supervisor

1.8.2.3 Technician

1.8.2.4 Installer

1.8.2.5 Test Technician

1.8.2.6 Manufacturer

1.8.3 Regulatory Requirements

1.9 DELIVERY, STORAGE, AND HANDLING

1.10 MAINTENANCE

1.10.1 Spare Parts

1.10.2 Special Tools

SECTION 28 31 70 Page 1

PART 2 PRODUCTS

2.1 GENERAL PRODUCT REQUIREMENT

2.2 MATERIALS AND EQUIPMENT

2.2.1 Standard Products

2.2.2 Nameplates

2.2.3 Keys

2.2.4 Instructions

2.3 FIRE ALARM CONTROL UNIT

2.3.1 Cabinet

2.3.2 Silencing Switches

2.3.2.1 Alarm Silencing Switch

2.3.2.2 Supervisory/Trouble Silencing Switch

2.3.3 Non-Interfering

2.3.4 Memory

2.3.5 Field Programmability

2.3.6 Input/Output Modifications

2.3.7 Resetting

2.3.8 Walk Test

2.3.9 History Logging

2.3.10 Manual Access

2.4 RELEASING SERVICE FIRE ALARM CONTROL PANEL (RSCP)

2.4.1 Cabinet

2.4.2 Control Modules

2.4.3 Silencing Switches

2.4.3.1 Alarm Silencing Switch

2.4.3.2 Supervisory/Trouble Silencing Switch

2.4.4 Non-Interfering

2.4.5 Memory

2.4.6 Field Programmability

2.4.7 Input/Output Modifications

2.4.8 Resetting

2.4.9 Instructions

2.4.10 History Logging

2.4.11 Heat Detector Self-Test Routines

2.5 REMOTE ANNUNCIATOR

2.5.1 LCD Annunciator

2.6 MANUAL STATIONS

2.7 SMOKE DETECTORS

2.7.1 Spot Type Detectors

2.7.2 Duct Smoke Detectors

2.7.3 Smoke Sensor Testing

2.8 HEAT DETECTORS

2.8.1 Heat Detectors

2.8.1.1 Fixed Temperature Detectors

2.9 Hydrogen Detectors

2.10 Carbon Monoxide Detectors

2.11 MULTI SENSOR DETECTORS

2.12 MULTI CRITERIA DETECTORS

2.13 ADDRESSABLE INTERFACE DEVICES

2.14 ADDRESSABLE CONTROL MODULES

2.15 ISOLATION MODULES

2.16 NOTIFICATION APPLIANCES

2.16.1 Audible Notification Appliances

2.16.1.1 Horns

2.16.2 Visual Notification Appliances

2.17 ELECTRIC POWER

2.17.1 Primary Power

SECTION 28 31 70 Page 2

2.18 SECONDARY POWER SUPPLY

2.18.1 Batteries

2.18.1.1 Capacity

2.18.1.2 Battery Power Calculations

2.18.2 Battery Chargers

2.19 SURGE PROTECTIVE DEVICES

2.19.1 Signaling Line Circuit Surge Protection

2.19.2 Sensor Wiring Surge Protection

2.20 WIRING

2.20.1 Alarm Wiring

2.21 AUTOMATIC FIRE ALARM TRANSMITTERS

2.21.1 Radio Transmitter and Interface Panels

2.21.1.1 Operation

2.21.1.2 Battery Power

2.21.1.3 Transmitter Housing

2.21.1.4 Antenna

2.21.2 Signals to Be Transmitted to the Base Receiving Station

2.22 SYSTEM MONITORING

2.22.1 Valves

2.22.1.1 Tamper Switches

2.22.2 High/Low Nitrogen Supervisory Switches

2.22.3 Room Low Temperature Supervisory Switch

2.22.4 Diesel Fire Pump Tank Level Sensor

2.22.5 Pressure Switches

2.22.6 Waterflow Detectors

2.22.7 Solenoid Disconnect Switches

2.23 ENVIRONMENTAL ENCLOSURES OR GUARDS

PART 3 EXECUTION

3.1 VERIFYING ACTUAL FIELD CONDITIONS

3.2 INSTALLATION

3.2.1 Fire Alarm Control Unit (FACU)

3.2.2 Battery Cabinets

3.2.3 Manual Stations

3.2.4 Notification Appliances

3.2.5 Smoke and Heat Detectors

3.2.6 LCD REMOTE Annunciator

3.2.7 Ceiling Bridges

3.3 SYSTEM FIELD WIRING

3.3.1 Wiring within Cabinets, Enclosures, and Boxes

3.3.2 Terminal Cabinets

3.3.3 Alarm Wiring

3.3.4 Back Boxes and Conduit

3.3.5 Conductor Terminations

3.4 FIRESTOPPING

3.5 PAINTING

3.6 FIELD QUALITY CONTROL

3.6.1 Test Procedures

3.6.2 Pre-Government Testing

3.6.2.1 Verification of Compliant Installation

3.6.2.2 Request for Government Final Test

3.6.3 Correction of Deficiencies

3.6.4 Government Final Tests

3.7 MINIMUM SYSTEM TESTS

3.7.1 System Tests

3.7.2 Audibility Tests

3.8 SYSTEM ACCEPTANCE

3.9 INSTRUCTION OF GOVERNMENT EMPLOYEES

SECTION 28 31 70 Page 3

3.9.1 Instructor

3.9.2 Required Instruction Time

3.9.2.1 Technical Training

3.9.3 Training Documentation

3.9.4 Training Course Content

3.10 Technical Data and Computer Software

3.11 PASSWORDS

3.12 EXTRA MATERIALS

3.12.1 Repair Service/Replacement Parts

3.12.2 Spare Parts

3.12.3 Special Tools

3.12.4 Document Storage Cabinet

-- End of Section Table of Contents --

SECTION 28 31 70 Page 4

SECTION 28 31 70

INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE

08/20

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

FM GLOBAL (FM)

FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits

IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 4 (2018) Standard for Integrated Fire Protection and Life Safety System Testing

NFPA 20 (2022) Standard for the Installation of Stationary Pumps for Fire Protection

NFPA 70 (2023) National Electrical Code

NFPA 72 (2022; ERTA 22-1) National Fire Alarm and Signaling Code

NFPA 90A (2024) Standard for the Installation of Air Conditioning and Ventilating Systems

NFPA 170 (2021) Standard for Fire Safety and Emergency Symbols

U.S. DEPARTMENT OF DEFENSE (DOD)

UFC 3-600-01 (2016; with Change 6, 2021) Fire Protection Engineering for Facilities

UFC 3-601-02 (2021) Fire Protection Systems Inspection, Testing, and Maintenance

UFC 4-010-06 (2016; with Change 1, 2017) Cybersecurity of Facility-Related Control Systems

SECTION 28 31 70 Page 5

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

47 CFR 15 Radio Frequency Devices

47 CFR 90 Private Land Mobile Radio Services

UNDERWRITERS LABORATORIES (UL)UL SOLUTIONS (UL)

UL 268 (2023) UL Standard for Safety Smoke Detectors for Fire Alarm Systems

UL 268A (2008; Reprint Oct 2014) Smoke Detectors for Duct Application

UL 464 (2023) UL Standard for Safety Audible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories

UL 497A (2001; Bul. 2019) UL Standard for Safety Secondary Protectors for Communications Circuits

UL 497B (2004; Reprint Feb 2022) UL Standard for Safety Protectors for Data Communications and Fire Alarm Circuits

UL 521 (1999; Reprint Feb 2023) UL Standard for Safety Heat Detectors for Fire Protective Signaling Systems

UL 864 (2014; Reprint May 2020) UL Standard for Safety Control Units and Accessories for Fire Alarm Systems (2023) UL Standard for Safety Control Units and Accessories for Fire Alarm Systems

UL 1283 (2017) UL Standard for Safety Electromagnetic Interference Filters

UL 1449 (2021; Reprint Dec 2022) UL Standard for Safety Surge Protective Devices

UL 1480 (2023) UL Standard for Safety Speakers for Fire Alarm and Signaling Systems, Including Accessories

UL 1638 (2023) UL Standard for Safety Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories

UL 1971 (2002; Reprint Oct 2008) Signaling Devices for the Hearing Impaired (2002; Reprint Feb 2024) UL Standard for Safety Signaling Devices for the Deaf and Hard of Hearing

UL Fire Prot Dir (2012) Fire Protection Equipment Directory

SECTION 28 31 70 Page 6

1.2 RELATED SECTIONS

Section 25 05 11.03 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - FIRE ALARM 25 05 11 Cybersecurity for Facility-Related Control Systems , applies to this section, with the additions and modifications specified herein. In addition, refer to the following sections for related work and coordination:

Section 08 71 00 DOOR HARDWARE Section 21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION Section 21 13 18 PREACTION SPRINKLER SYSTEMS, FIRE PROTECTION Section 21 30 00 FIRE PUMPS Section 23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC Section 23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC Section 23 30 00 HVAC AIR DISTRIBUTION Section 25 05 11.01 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

- HVAC

Section 25 05 11.02 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

- FUEL CONTROL

Section 25 05 11.03 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

- FIRE ALARM

Section 25 05 11.04 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

- INTERCOM/PUBLIC ADDRESS

Section 25 05 11.05 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS

- GENERATOR/SWITCHGEAR SCADA

Section 26 24 13 SWITCHBOARDS and EP series sheets for shunt trip operation of circuit breakers.

Section 26 51 00 INTERIOR LIGHTING and EL series sheets for additional work related to egress lighting activation override.

Section 27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM Section 27 51 23 INTERCOMMUNICATION SYSTEM Section 33 56 10 FACTORY-FABRICATED FUEL STORAGE TANKS

[ Section 21 13 13 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION ] [ Section 21 30 00 FIRE PUMPS ] [ Section 21 23 00.00 20 WET CHEMICAL FIRE EXTINGUISHING for KITCHEN

CABINET]

[ Section 21 13 16 DRY PIPE FIRE SPRINKLER SYSTEMS ] [ Section 21 13 18 PREACTION FIRE SPRINKLER SYSTEMS] [ Section 21 13 19 DELUGE FIRE SPRINKLER SYSTEMS] [ Section 23 30 00 HVAC AIR DISTRIBUTION ] [ Section 21 13 24.00 10 AQUEOUS

FILM-FORMING FOAM (AFFF) FIRE PROTECTION SYSTEM ]

[ Section 21 13 25 HIGH-EXPANSION FOAM SYSTEM, FIRE PROTECTION ] [ Section

21 13 20.00 20 FOAM FIRE EXTINGUISHING FOR AIRCRAFT HANGARS ]

[ Section 21 13 21.00 20 FOAM FIRE EXTINGUISHING FOR FUEL TANK PROTECTION ] [ Section 21 13 22.00 20 FOAM FIRE EXTINGUISHING FOR HAZ/FLAM MATERIAL

FACILITY ]

[ Section 21 21 01.00 20 CARBON DIOXIDE FIRE EXTINGUISHING (HIGH

PRESSURE)] [ Section 21 21 02.00 20 CARBON DIOXIDE FIRE EXTINGUISHING

(LOW PRESSURE)]

[ Section 21 21 03.00 10 WET CHEMICAL FIRE EXTINGUISHING SYSTEM ] [ Section 08 71 00 DOOR HARDWARE for [door release][door unlocking] and additional work related to finish hardware. ]

[ Section[s] [ 14 21 13 ELECTRIC TRACTION FREIGHT ELEVATORS] [ 14 21 23 ELECTRIC TRACTION PASSENGER ELEVATORS] [and] [ 14 24 13 HYDRAULIC FREIGHT ELEVATORS] [ 14 24 23 HYDRAULIC PASSENGER ELEVATORS] for additional work related to elevators. ] [ Section 07 84 00 FIRESTOPPING for additional work related to firestopping. ]

SECTION 28 31 70 Page 7

1.3 SUMMARY

1.3.1 Scope

a. This work includes designing and [ providing a new, complete, ][modifying the existing] fire alarm system as described herein and on the contract drawings [ for the _____________] . Include system wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, initiating devices, notification appliances, supervising station fire alarm transmitters, and other accessories and miscellaneous items required for a complete operational system even though each item is not specifically mentioned or described. Provide system [ s] complete and ready for operation. [ Existing interior fire alarm system was manufactured by [_____].] Design and installation must comply with the drawings and this section, UFC 3-600-01 , NFPA 20 , NFPA 72 , UFGSSection 25 05 11 .03 , UFC 4-010-06 and AFGM 2019-320-02.

b. Provide equipment, materials, installation, workmanship, inspection, and testing in strict accordance with NFPA 72 , except as modified herein. [ The system layout on the drawings show the intent of coverage and suggested locations. Final quantity, system layout, and coordination are the responsibility of the Contractor. ]

[ c. Each remote fire alarm control unit must be powered from a wiring riser specifically for that use or from a local emergency power panel located on the same floor as the remote fire alarm control unit.

Where remote fire control units are provided, equipment for notification appliances may be located in the remote fire alarm control units. The "local emergency power panel" (also termed "Dedicated Emergency Panel Schedules" in the contract documents) for this building is designated as Panel NL3. ]

[ d. Where a fire pump (s) is (are) provided, the fire alarm system must monitor and transmit the fire pump controller signals in accordance with the provisions of NFPA 72 . ]

[e. Where an emergency generator provides standby power supply for life safety system circuits, the generator must be monitored by the Fire Alarm Control Unit (FACU) and transmit emergency generator signals in accordance with NFPA 72 .] f e. The fire alarm system must be independent of the building security, building management, and energy/utility monitoring systems other than for control functions.

1.3.2 Qualified Fire Protection Engineer (QFPE)

Services of the QFPE must include:

a. Reviewing SD-02, SD-03, and SD-05 submittal packages for completeness and compliance with the provisions of this specification.

Construction (shop) drawings and calculations must be prepared by, or prepared under the immediate supervision of, the QFPE. The QFPE must affix their professional engineering stamp with signature to the shop drawings, calculations, and material data sheets, indicating approval prior to submitting the shop drawings to the DFPE.

b. Providing a letter documenting that the SD-02, SD-03, and SD-05 submittal package has been reviewed and noting any outstanding

SECTION 28 31 70 Page 8 comments.

c. Performing in-progress construction surveillance prior to installation of ceilings (rough-in inspection).

d. Witnessing pre-Government [and final Government ] functional performance testing and performing a final installation review.

e. Signing applicable certificates under SD-07.

1.4 DEFINITIONS

Wherever mentioned in this specification or on the drawings, the equipment, devices, and functions must be defined as follows:

1.4.1 Interface Device

An addressable device that which interconnects hard wired systems or devices to an analog/addressable system.

1.4.2 Fire Alarm Control Unit (FACU)

A master control unit having the features of a fire alarm control unit

(FACU).

1.4.3 Remote Fire Alarm Control Unit

A control unit, physically remote from the fire alarm control unit, that which receives inputs from automatic and manual fire alarm devices; may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the fire alarm and mass notification control unit.

1.4.4 Terminal Cabinet

A steel cabinet with locking, hinge-mounted door where terminal strips are securely mounted inside the cabinet.

1.4.5 Control Module and Relay Module

Terms utilized to describe emergency control function interface devices as defined by NFPA 72 .

1.4.6 Designated Fire Protection Engineer (DFPE)

The DoD fire protection engineer that who oversees that the Area of Responsibility for that project. This is sometimes referred to as the "cognizant" fire protection engineer. Interpret reference to "authority having jurisdiction" and/or AHJ in referenced standards to mean the Designated Fire Protection Engineer (DFPE). The DFPE may be responsible for review of the contractor submittals having a "G" designation, and for witnessing final inspection and testing.

1.4.7 Qualified Fire Protection Engineer (QFPE)

A QFPE is an individual who is a licensed professional engineer (P.E.), who has passed the fire protection engineering written examination

SECTION 28 31 70 Page 9 administered by the National Council of Examiners for Engineering and Surveying (NCEES) and has relevant fire protection engineering experience.

1.5 SUBMITTALS

The Contractor shall submit the following submittals (and subsequent resubmittals) together:

21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION

21 13 18 PREACTION SPRINKLER SYSTEMS, FIRE PROTECTION

21 30 00 FIRE PUMPS

25 05 11.03 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - FIRE

ALARM

28 31 70 INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE

All submittals shall be stamped and sealed by the contractor's QFPE. See section on QFPE qualifications.

If submitted separately, the review period shall start upon receipt of the last submittal (or resubmittal) in the package. Allow a minimum of 40 calendar days exclusive of mailing for Government reviews and approvals.

Include in submittals the information required by the "CFCI Equipment Electrical Data" submittal in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. The basis of design is listed in the EP610 series Equipment Electrical Connection Schedules.

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are [for Contractor Quality Control approval.] [ for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. ]

Shop drawings (SD-02), product data (SD-03) and calculations (SD-05) must be prepared by the fire alarm designer and combined and submitted as one complete package. The QFPE must review the SD-02/SD-03/SD-05 submittal package for completeness and compliance with the Contract provisions prior to submission to the Government. The QFPE must provide a Letter of Confirmation that they have reviewed the submittal package for compliance with the contract provisions. This letter must include their registered professional engineer stamp and signature. Partial submittals and submittals not reviewed by the QFPE will be returned by the Government disapproved without review.

Submit the following in accordance with Section 01 33 00 SUBMITTAL

PROCEDURES:

SD-01 Preconstruction Submittals

Qualified Fire Protection Engineer (QFPE) ; G, DO [, [_____]]

Fire alarm system designer ; G, DO [, [_____]]

Supervisor ; G, DO [, [_____]]

Technician ; G, DO [, [_____]]

Installer ; G, DO [, [_____]]

SECTION 28 31 70 Page 10

Test Technician ; G, DO [, [_____]]

Fire Alarm System Site-Specific Software Acknowledgement ; G[, SD-02 Shop Drawings

Shop drawings shall not be smaller than the Contract Drawings.

Submit plan view drawing showing device locations, device addresses, terminal cabinet locations, junction boxes, other related equipment, conduit routing, wire counts, circuit identification in each conduit, and circuit layouts for all floors. Drawings shall comply with the requirements of NFPA 72 and NFPA 170 .

Nameplates ; G, DO [, [_____]]

Instructions ; G, DO [, [_____]]

Wiring Diagrams ; G, DO [, [_____]]

System Layout ; G, DO [, [_____]]

Notification Appliances ; G, DO [, [_____]]

Initiating devices ; G, DO [, [_____]]

Battery Power ; G, DO [, [_____]]

Voltage Drop Calculations ; G, DO [, [_____]]

Dedicated Emergency Panel Schedules ; G, DO

SD-03 Product Data

Fire Alarm Control Unit (FACU) ; G, DO [, [_____]]

Releasing Service Fire Alarm Control Panel (RSCP) ; G, DO

[ Video Display Unit (VDU) ; G[, [_____]] ]

LCD Annunciator ; G, DO [, [_____]]

Manual Stations ; G, DO [, [_____]]

Smoke Detectors ; G, DO [, [_____]]

Duct Smoke Detectors ; G, DO [, [_____]]

[ Projected Beam Smoke Detector ; G[, [_____]] ]

[ Air sampling smoke detectors ; G[, [_____]] ]

Heat Detectors ; G, DO [, [_____]]

[ Flame Detectors ; G[, [_____]] [ Multi-Criteria Detectors ; G[, [_____]] ]

SECTION 28 31 70 Page 11

Carbon monoxide detector ; G[, [_____]]

Addressable Interface Devices ; G, DO [, [_____]]

Addressable Control Modules ; G, DO [, [_____]]

Isolation Modules ; G, DO [, [_____]]

Notification Appliances ; G, DO [, [_____]]

Batteries ; G, DO [, [_____]]

Battery Chargers ; G, DO [, [_____]]

[ Supplemental Notification Appliance Circuit Panels ; G[, [_____]] ]

[ Auxiliary Power Supply Panels ; G[, [_____]] ]

Surge Protective Devices ; G, DO [, [_____]]

Alarm Wiring ; G, DO [, [_____]]

[ Back Boxes and Conduit ; G, DO [, [_____]] ]

[ Ceiling Bridges for Ceiling-Mounted Appliances; G, DO [, [_____]] ]

Terminal Cabinets ; G, DO [, [_____]]

Digital Alarm Communicator Transmitter (DACT) ; G[, [_____]]

[ Automatic Fire Alarm Transmitters (including housing); G, DO [, [ Radio Transmitter and Interface Panels ; G, DO [, [_____]] ]

Electromagnetic Door Holders ; G[, [_____]]

Environmental Enclosures or Guards ; G, DO [, [_____]]

[ Firefighter Telephone ; G[, [_____]] ]

[ Printer ; G[, [_____]] ]

Document Storage Cabinet ; G, DO [, [_____]]

Surge Protective Devices ; G, DO

Hydrogen Detectors ; G, DO

Carbon Monoxide Detectors ; G, DO

Low Temperature Sensors ; G, DO

Solenoid Disconnect Switches ; G, DO

Tamper Switches ; G, DO

Pressure Switches ; G, DO

SECTION 28 31 70 Page 12

Waterflow Detectors ; G, DO

Spare Parts ; G, DO

Preliminary Equipment List ; G, DO

Provide a preliminary Equipment List identifying the type, quantity, make, and model number of each piece of equipment to be provided under this submittal. The Equipment List shall include the type, quantity, make and model of spare equipment. Types and quantities of equipment submitted shall coincide with the types and quantities of equipment used in the battery calculations and those shown on the shop drawings.

SD-05 Design Data

[ Air Sampling Smoke Detection System Calculations ; G[, [_____]]

SD-06 Test Reports

Test Procedures ; G, RO [, [_____]]

SD-07 Certificates

Verification of Compliant Installation ; G, RO [, [_____]]

Request for Government Final Test ; G, RO [, [_____]]

SD-10 Operation and Maintenance Data

Operation and Maintenance (O&M) Instructions ; G, RO [, [_____]]

Instruction of Government Employees ; G, RO [, [_____]]

SD-11 Closeout Submittals

As-Built Drawings

Spare Parts

1.6 SYSTEM OPERATION

Fire alarm system components requiring power, except for the FACU(s) and RSCP(s) power supply supplies , must operate on 24 volts DC unless noted otherwise in this section.

The interior fire alarm system must be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to NFPA 20 , NFPA 72 , and UL 864 . Systems meeting UL 2017 only are not acceptable. The system must be activated into the alarm mode by actuation of an alarm initiating device. The system must remain in the alarm mode until the initiating device is reset and the control unit is reset and restored to normal.

[Provide the system with an interconnected riser loop or network having Class [A][X] supervision. Ensure that the return portion of the loop is remote from the supply portion of the loop.][ Where the building has two stairs for egress from floors above grade or floors below grade, ensure that a single impairment cannot adversely affect more than one floor.

Where three or more stairs are provided for egress from floors above grade

SECTION 28 31 70 Page 13 or below grade, ensure that a single impairment cannot adversely affect more than one-half of any floor. ][Ensure that any single impairment of the system does not affect the system on more than [one][one-half] of any floor.]

1.6.1 Alarm Initiating Devices and Notification Appliances (Visual, Audible)

a. Connect alarm initiating devices to initiating device circuits (IDC) [Class "A"] [ Class "B" ] , or to signaling line circuits (SLC) Class ["A"] [ "B" ]["X"] and installed in accordance with NFPA 72 , except IDC and SLC circuits for the RSCP(s) shall be Class "A" .

b. Connect notification appliances to notification appliance circuits (NAC) [Class "A] [ Class "B" ] .

1.6.2 Functions and Operating Features

The system must provide the following functions and operating features:

a. Power, annunciation, supervision, and control for the system.

Addressable systems must be microcomputer (microprocessor or microcontroller) based with a minimum word size of eight bits with sufficient memory to perform as specified.

b. Visual alarm notification appliances must be synchronized as required by NFPA 72 .

c. Electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control unit.

d. An audible and visual trouble signal to activate upon a single break or open condition, or ground fault [ (or short circuit for Class "X")] .

The trouble signal must also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory control unit modules. After the system returns to normal operating conditions, the trouble signal must again sound until the trouble is acknowledged. A smoke detector in the process of being verified for the actual presence of smoke must not initiate a trouble condition.

e. A trouble signal silence feature that must silence the audible trouble signal, without affecting the visual indicator.

f. Program capability via switches in a locked portion of the FACU to bypass the automatic notification appliance circuits, [ fire reporting system ][air handler shutdown] [smoke control operation] [elevator recall] [door release] [door unlocking] features. Operation of this programmed action must indicate on the FACU display [ and printer output] as a supervisory or trouble condition. [ Notification appliance bypass must be selectable by floor.]

g. Alarm functions must override trouble or supervisory functions.

Supervisory functions must override trouble functions.

h. The system must be capable of being programmed from the control unit keyboard. Programmed information must be stored in non-volatile memory.

SECTION 28 31 70 Page 14

i. The system must be capable of operating, supervising, and/or monitoring non-addressable alarm and supervisory devices.

j. There must be no limit, other than maximum system capacity, as to the number of addressable devices that may be in alarm simultaneously.

k. Where the fire alarm system is responsible for initiating an action in another emergency control device or system, such as HVAC or lighting, [HVAC, ][atrium exhaust, ][smoke control, ][elevator recall, ][releasing service, ] the addressable fire alarm relay must be located in the vicinity of the emergency control device.

l. An alarm signal must automatically initiate the following functions (in addition to the functions identified on the control matrices) :

(1) Transmission of an alarm signal to [ the fire department ][a remote supervising station] .

(2) Visual indication of the device operated on the FACU and RSCP , [Video Display unit (VDU),] [ and on the [ graphic ][remote ] annunciator ] . [ Indication on the graphic annunciator must be by floor, zone or circuit, and type of device.]

[(3) Record the event on the system printer.]

(4) Actuation of alarm notification appliances.

(5) Recording of the event electronically in the history log of the

FACU.

(6) Select actions also report to the building DDC system.

[(6) Release of doors held open by electromagnetic devices.]

[(7) Operation of the [smoke control system][atrium exhaust system].]

[(8) Release of power to electric locks (delayed egress locks) on doors that are part of the means of egress.]

[(9) Elevator recall as described in this section.]

[(10) Operation of [_____] must release the [_____] fire extinguishing system after a [_____] second time delay.]

[(11) Operation of a sprinkler waterflow switch serving an elevator machinery room or elevator shaft must operate shunt trip circuit breaker(s) to shut down power to the elevators in accordance with

ASME A17.1/CSA B44 .]

[(12) Operation of an interface that operates vibrating pagers worn by hearing-impaired occupants.]

m. A supervisory signal must automatically initiate the following functions (in addition to the functions identified on the control matrices) :

(1) Visual indication of the device operated on the FACU or RSCP (as assigned by functional matrix) , [Video Display unit (VDU),] [ and

SECTION 28 31 70 Page 15 on the [ graphic ][remote ] annunciator ] . [ Indication on the graphic annunciator must be by floor, zone or circuit, and type of device.]

[(2) Record the event on the system printer.]

(3) Transmission of a supervisory signal to [ the fire department ][a remote supervising station] .

(4) Operation of a duct smoke detector must shut down the appropriate air handler in accordance with NFPA 90A in addition to other requirements of this paragraph and as allowed by NFPA 72 .

(5) Recording of the event electronically in the history log of the

FACU.

(6) Select actions also report to the building DDC system.

n. A trouble condition must automatically initiate the following functions (in addition to the functions identified on the control matrices) :

(1) Visual indication of the device operated on the FACU or RSCP (as assigned by functional matrix) , [Video Display unit (VDU),] [ and on the [ graphic ][remote ] annunciator ] . [ Indication on the graphic annunciator must be by floor, zone or circuit, and type of device.]

[(2) Record the event on the system printer.]

(3) Transmission of a trouble signal to [ the fire department ][a remote supervising station] .

(4) Recording of the event electronically in the history log of the

FACU.

[o. Activation of a carbon monoxide alarm initiating device must automatically initiate the following functions:

(1) Visual indication of the device operated on the ,[ LCD, LED Display unit (VDU),][ and on the [graphic ][remote ]annunciator].[ Indication on the graphic annunciator must be by floor and room number, device address, and device type.]

(2) Transmission of a carbon monoxide alarm signal to [the fire department][a remote supervising station].

(3) Activation of all strobes and the carbon monoxide alarm signal throughout the building.

(4) Recording of the event electronically in the history log of the FACU.] (5) Select actions also report to the building DDC system.

p. System control equipment must be programmed to provide a 60-minute to 180-minute delay in transmission of trouble signals resulting from primary power failure.

q. Provide signaling line circuits for the network.

r. Provide notification appliance circuits. The visual alarm

SECTION 28 31 70 Page 16 notification appliances shall have the flash rates synchronized as required by NFPA 72 .

s. Silencing.

(1) Subsequent actuation of other initiating devices or supervisory signals after the initial alarm or supervisory signal has been silenced shall cause the notification appliances to reactivate.

(2) If an audible trouble signal has been silenced, it shall comply with the following:

(i) The audible trouble shall re-sound every 24 hours or less until fault conditions are restored to normal.

(ii) The re-sound audible trouble signal shall sound until it is manually silenced or acknowledged.

(iii) The re-sounded audible trouble signal shall also be automatically re-transmitted to the base fire department.

(3) When the silence switch is left in the active position and there is no alarm, supervisory, or trouble signal, an audible trouble signal and a visual indicator shall be activated until the switch is restored to its normal position.

Report supervisory alarms as independent addresses to the FACP, RSCP, or Energy Management Control System as indicated on the functional matrixes.

Grouped switches on common addresses are not permitted. Provide non-latching electronically supervisory devices unless otherwise indicated.

Alarm signals, supervisory signals, and trouble signals shall be clearly differentiated at the control panels and annunciators.

[ 1.6.3 Elevator Recall

Provide elevator recall in accordance with ASME A17.1/CSA B44 , Section [

14 21 13 ELECTRIC TRACTION FREIGHT ELEVATORS][ 14 21 23 ELECTRIC TRACTION

PASSENGER ELEVATORS][14 24 13 HYDRAULIC FREIGHT ELEVATORS][ 14 24 23

HYDRAULIC PASSENGER ELEVATORS], and as specified herein. Activation of any smoke detector in an elevator shaft, machine room, or lobby (except at designated recall level) must cause all elevators associated with that shaft, machine room, or lobby to return nonstop to the designated level.

Activation of a smoke detector in the lobby or machine room at the designated level must cause all elevators associated with that lobby to return nonstop to the assigned alternate level. Activation of a detector in an elevator shaft, machine room, or lobby must also cause illumination of elevator cab warning signal (fire hat) and complete operation of fire alarm system as specified in paragraph titled "Functions and Operating Features".

] 1.7 TECHNICAL DATA AND SITE-SPECIFIC SOFTWARE

Technical data and site-specific software (meaning technical data that relates to computer software) that are specifically identified in this project, and may be required in other specifications, must be delivered, strictly in accordance with the CONTRACT CLAUSES. The fire alarm system manufacturer must submit written confirmation of this contract provision as " Fire Alarm System Site-Specific Software Acknowledgement ". Identify data delivered by reference to the specification paragraph against which it is furnished. Data to be submitted must include complete system, equipment, and software descriptions. Descriptions must show how the

SECTION 28 31 70 Page 17 equipment will operate as a system to meet the performance requirements of this contract. The site-specific software data package must also include the following:

a. Items identified in NFPA 72, titled "Site-Specific Software".

b. Identification of programmable portions of the system equipment and capabilities.

c. Description of system revision and expansion capabilities and methods of implementation detailing both equipment and software requirements.

d. Provision of operational software data on all modes of programmable portions for fire alarm .

e. Description of Fire Alarm Control Unit equipment operation.

f. Description of auxiliary and remote equipment operations.

g. Library of application software.

h. Operation and maintenance manuals.

[ 1.8 EXISTING EQUIPMENT

a. Equipment and devices must be compatible and operable with the existing fire alarmmass notification system and must not impair reliability or operational functions of existing supervising station fire alarm system.[ The proprietary type supervising station (PSS) is located [in Building [_____].][_____].][ The supervising equipment is existing and consists of the following brands and models: [supervising station control unit [_____].][_____][signal reporting components [_____]], [annunciator [_____]][_____]].

[b. Equipment and devices must be compatible and operable with the existing building fire alarm system. Equipment must not impair reliability or operational functions of the existing system. The existing building system control unit is [_____].]

] 1.8 QUALITY ASSURANCE

1.8.1 Submittal Documents

1.8.1.1 Preconstruction Submittals

Within 36 days of contract award but not less than [ 14 days ][_____] prior to commencing any work on site, the Contractor must submit the following for review and approval. SD-02, SD-03 and SD-05 submittals received prior to the review and approval of the qualifications of the fire alarm subcontractor and QFPE must be returned disapproved without review. All resultant delays must be the sole responsibility of the Contractor.

1.8.1.2 Shop Drawings

Shop drawings must not be smaller than [ISO A1][ANSI D][the Contract Drawings]. Drawings must comply with the requirements of NFPA 72 and NFPA 170 . Minimum scale for floor plans must be 1/8"=1'.

SECTION 28 31 70 Page 18

1.8.1.2 Nameplates

Nameplate illustrations and data to obtain approval by the Contracting Officer before installation.

1.8.1.3 Wiring Diagrams

[_____] copies Copies of point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems that which are supervised or controlled by the system. Diagrams must show connections from field devices to the FACU and remote FACU, initiating circuits, switches, relays and terminals, including pathway diagrams between the control unit and shared communications equipment within the protected premises. Point-to-point wiring diagrams must be job specific and must not indicate connections or circuits not being utilized. Provide complete riser diagrams indicating the wiring sequence of all devices and their connections to the control equipment. Include a color-code schedule for the wiring.

Provide a schedule of connections for the fire alarm, intercom/public address, releasing service, HVAC system, power system, and any other connected systems and all associated interfaces.

1.8.1.4 System Layout

[_____] copies Copies of plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, conduit sizes, wire counts, conduit fill calculations, wire color-coding, circuit identification in each conduit, and circuit layouts for all floors , control equipment, alarm and supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, and other accessories and miscellaneous items required for a complete operating system even though each item is not specifically mentioned or described. Provide systems complete and ready for operation. . Indicate candela rating of each visual notification appliance and wattage and decibel rating of each audible notification appliance . Clearly identify the locations of isolation modules. Indicate the addresses of all devices, modules, relays, etc. Clearly identify the locations of isolation modules. Indicate the addresses of all devices, modules, relays, and similar. Indicate if the environment for the FACU is within its environmental listing (e.g. temperature/humidity).

Provide a complete description of the system operation in matrix format similar to the "Typical Input/Output Matrix" included in the Annex of NFPA 72 . Provide a complete description of the system operation in matrix format capturing the items identified in the (and of formatting similar to the) Functional Matrices and the requirements of the related specification sections listed herein.

[For air sampling smoke detection systems, provide floor plan layouts indicating location of fire alarm control unit, air sampling piping (lengths of pipe) and sampling ports (sizes and locations). Floor plan must also indicate geographic monitor zone boundaries, location of display control unit, bar level annunciation panels if separate, and all other associated equipment that is required to provide a complete operational system.]

SECTION 28 31 70 Page 19

1.8.1.5 Notification Appliances

Calculations and supporting data on each circuit to indicate that there is at least 25 percent spare capacity for notification appliances. Annotate data for each circuit on the drawings.

1.8.1.6 Initiating Devices

Calculations and supporting data on each circuit to indicate that there is at least [ 25][_____] percent spare capacity for initiating devices.

Annotate data for each circuit on the drawings.

1.8.1.7 Battery Power

Calculations and supporting data as required in paragraph Battery Power Calculations for alarm, alert, and supervisory power requirements.

Calculations including ampere-hour requirements for each system component and each control unit component, and the battery recharging period, must be included on the drawings.

1.8.1.8 Voltage Drop Calculations

Voltage drop calculations for each notification all circuit s indicating that sufficient voltage is available for proper operation of the system and all components, at a minimum rated voltage of the system operating on batteries. Identify on device data and calculations the minimum operable voltage per manufacturer recommendations for all devices requiring power, and identify special device features to be used where the delivered voltage does not satisfy the manufacturer's standard voltage range.

Include the calculations on the system layout drawings.

1.8.1.9 Product Data

[_____] copies of Provide annotated descriptive data to show the specific model, type, and size of each item. Catalog cuts must also indicate the NRTL listing. The data must be highlighted to show model, size, and options that are intended for consideration. Data must be adequate to demonstrate compliance with all contract requirements. Product data for all equipment must be combined into a single submittal.

Provide an equipment list identifying the type, quantity, make, and model number of each piece of equipment to be provided under this submittal.

The equipment list must include the type, quantity, make and model of spare equipment. Types and quantities of equipment submitted must coincide with the types and quantities of equipment used in the battery calculations and those shown on the shop drawings.

[ 1.8.1.10 Air Sampling Smoke Detection System Calculations

Submit air sampling detection system design analysis calculations consisting of battery capacity, loading calculations, and fan speed and air flow/transport calculations. Include schematic diagrams showing pipe segments, pipe diameters, lengths of pipe, node numbers, and sample port diameters to verify the requirements are met.

] 1.8.1.10 Operation and Maintenance (O&M) Instructions

[ Six ][_____] copies of the Operation and Maintenance Instructions. The O&M Instructions must be prepared in a single volume or in multiple

SECTION 28 31 70 Page 20 volumes, with each volume indexed, and may be submitted as a Technical Data Package. Manuals must be approved prior to training. The Interior Fire Alarm System Operation and Maintenance Instructions must include the following:

a. "Manufacturer Data Package [ five ][_____] " as specified in [ Section

01 78 23 OPERATION AND MAINTENANCE DATA][_____] .

b. Operating manual outlining step-by-step procedures required for system startup, operation, and shutdown. The manual must include the manufacturer's name, model number, service manual, parts list, and preliminary equipment list complete with description of equipment and their basic operating features.

c. Maintenance manual listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guide. The manuals must include conduit layout, equipment layout and simplified wiring, and control diagrams of the system as installed.

d. Complete procedures for system revision and expansion, detailing both equipment and software requirements.

e. Software submitted for this project on CD/DVD media utilized.

f. Printouts of configuration settings for all devices.

g. Routine maintenance checklist. The routine maintenance checklist must be arranged in a columnar format. The first column must list all installed devices, the second column must state the maintenance activity or state no maintenance required, the third column must state the frequency of the maintenance activity, and the fourth column provided for additional comments or reference. All data (devices, testing frequencies, and similar) must comply with UFC 3-601-02 .

h. A final Equipment List must be submitted with the Operating and Maintenance (O&M) manual.

1.8.1.11 As-Built Drawings

The drawings must show the system as installed, including deviations from both the project drawings and the approved shop drawings. These drawings must be submitted within two weeks after the final Government test of the system. At least one set of the as-built (marked-up) drawings must be provided at the time of, or prior to the final Government test.

1.8.2 Qualifications

1.8.2.1 Fire Alarm System Designer

The fire alarm system designer must be certified as a Level [III] [ IV ] (minimum) Technician by National Institute for Certification in Engineering Technologies (NICET) in the Fire Alarm Systems subfield of Fire Protection Engineering Technology or meet the qualifications for a

QFPE.

1.8.2.2 Supervisor

[ A NICET Level [III] [ or ] [ IV ] fire alarm technician must supervise the installation of the fire alarm system [, including the air sampling smoke

SECTION 28 31 70 Page 21 detection system] . ][A fire alarm technician with a minimum of eight years of experience must supervise the installation of the fire alarm system.] The fire alarm technicians supervising the installation of equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.

1.8.2.3 Technician

Fire alarm technicians with a minimum of four years of experience must be utilized to install and terminate fire alarm devices, cabinets and control units. The fire alarm technicians installing the equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings [ , and must be thoroughly experienced in the installation of air sampling detection systems ] .

1.8.2.4 Installer

[Fire alarm installer with a minimum of two years of experience utilized to assist in the installation of fire alarm devices, cabinets and control units] [ NICET Level II technician to assist in the installation of fire alarm devices, cabinets and control units ] . A licensed electrician must be allowed to install wire, cable, conduit and backboxes for the fire alarm system system. The fire alarm installer must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.

1.8.2.5 Test Technician

Fire alarm technicians with a minimum of eight years of experience and NICET Level [III] [ or ] [ IV ] utilized in testing and certification of the installation of the fire alarm devices, cabinets and control units. The fire alarm technicians testing the equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment installed as part of this project.

1.8.2.6 Manufacturer

Components must be of current design and must be in regular and recurrent production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system, complete, conforming to NFPA 72 , except as specified herein.

1.8.3 Regulatory Requirements

Equipment and material must be listed or approved. Listed or approved, as used in this Section, means listed, labeled or approved by a Nationally Recognized Testing Laboratory (NRTL) such as UL Fire Prot Dir or FM APP GUIDE. The omission of these terms under the description of any item of equipment described must not be construed as waiving this requirement. All listings or approvals by testing laboratories must be from an existing ANSI or UL published standard. The recommended practices stated in the manufacturer's literature or documentation must be considered as mandatory requirements.

1.9 DELIVERY, STORAGE, AND HANDLING

Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.

SECTION 28 31 70 Page 22

1.10 MAINTENANCE

1.10.1 Spare Parts

Furnish the following spare parts in the manufacturers original unopened containers:

a. [ Five ][_____] complete sets of system keys.

b. [ Two][_____] of each type of fuse required by the system.

c. [ One][_____] manual stations.

[ d. [ Two][_____] of each type of detector installed. ]

e. [ Two][_____] of each type of detector base and head installed.

[ f. [One][_____] electromagnetic door holders. ]

[ g. One smoke detector manufacturer's test screen, card or magnet for each ten beam smoke detectors, or fraction thereof, installed in the system. ]

[h. Two air sampling smoke detection system filter assemblies.]

i. [ Two][_____] of each type of audible and visual alarm device installed.

j. [Two][_____] of each type of addressable monitor module installed.

k. [Two][_____] of each type of addressable control module installed.

l. [ Two][_____] low voltage, [ one ][_____] [ telephone ][internet] [ethernet] , and [ one ][____] 120 VAC surge protective device.

[m. [Two][_____] spare reams of paper for the system printer, plus sufficient paper for testing.]

[n. [Two][_____] spare printer ribbons.]

1.10.2 Special Tools

Software, connecting cables and proprietary equipment, necessary for the maintenance, testing, and reprogramming of the equipment must be furnished to the Contracting Officer, prior to the instruction of Government employees.

PART 2 PRODUCTS

2.1 GENERAL PRODUCT REQUIREMENT

All fire alarm equipment must be listed for use under the applicable reference standards.

SECTION 28 31 70 Page 23

2.2 MATERIALS AND EQUIPMENT

2.2.1 Standard Products

Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory and listed for fire protection service when so required by NFPA 72 or this specification. Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular classification of materials. Material and equipment must be the standard products of a manufacturer regularly engaged in the manufacture of the products for at least [ 2][_____] years prior to bid opening.

2.2.2 Nameplates

Major components of equipment must have the manufacturer's name, address, type or style, model or serial number, catalog number, date of installation, installing Contractor's name and address, and the contract number provided on a new name plate permanently affixed to the item or equipment. Major components include, but are not limited to, the following:

a. FACU

b. Automatic transmitter/transceiver

c. Terminal Cabinet

d. RSCP

e. Fire Alarm Annunciators

f. Fire Pump Controllers

f. Diesel Fire Pump Remote Annunciators

Nameplates must be etched metal or plastic, permanently attached by screws to control units or adjacent walls.

2.2.3 Keys

Keys and locks for equipment, control units and devices must be identical. Provide note less than six keys of each type required. Master all keys and locks to a single key as required by the Installation Fire Department [Master all keys and locks to a single key as required by the [Installation Fire Department][_____]] . [Keys must be CAT [60][_____].]

2.2.4 Instructions

Provide a typeset printed or typewritten instruction card mounted…