Final Drawings Electrical.pdf
PDF 5 MB Posted
- Solicitation number
- 89-20251028-CCC
- Issued by
- Chatham County, North Carolina
About this file
This document is a set of mechanical and electrical engineering plans prepared by Brittain Engineering, Inc., for a 2018 Appendix B Building Code Summit project involving site lighting and electrical systems installation. The project includes comprehensive specifications for LED area lighting fixtures, power distribution systems, and electrical infrastructure throughout a facility site. The plans detail multiple lighting fixture types (designated A through I), pole mounting configurations, and electrical service requirements including panel layouts and power riser diagrams. The scope encompasses installation of approximately 16 area lighting fixtures of varying specifications, complete with foundation details, cable routing systems, and control mechanisms. The documentation includes detailed schedules specifying fixture types, mounting heights, wattage requirements, and electrical connections, along with site plan layouts indicating placement of all lighting elements around perimeter parking areas and facility grounds.
The technical specifications indicate lighting fixtures ranging from standard to specialized LED configurations with total wattage loads documented in the electrical panels and schedules. Foundation requirements, bearing plates, and material specifications are provided for pole installation in various soil conditions. The electrical systems are designed to operate through designated power panels (Panel A and Power Riser systems) with specified voltage, amperage, and breaker configurations. All construction work is indicated to comply with current building codes, and special inspection services are scheduled for structural, mechanical, and electrical components. The project appears designed for commercial or institutional facility use with emphasis on efficient LED lighting technology and standardized electrical infrastructure capable of supporting the specified illumination requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 89-20251028-CCC.pdf | ||
| ADDENDUM 01.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PO BOX 939
HICKORY, NC 28603
CONSULTING MECHANICAL AND ELECTRICAL ENGINEERS
BRITTAIN ENGINEERING, INC.
C O
N S
U L T
I N
G
M
E C
H A
N I C
A L
A
N D
E
L E
C T
R I C
A L
E
N G
I N
E E
R S
B R
I T
T A
I
G
I N
E E
R I N
G
I N
C
P O
B
X
H I C
K O
R Y
N
C
AutoCAD SHX Text
ONE (1)
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text 10,700
AutoCAD SHX Text 9,000
AutoCAD SHX Text N/A
AutoCAD SHX Text 18,000
AutoCAD SHX Text N/A
AutoCAD SHX Text 27,000
AutoCAD SHX Text
SCHEDULE OF SPECIAL INSPECTION SERVICES
AutoCAD SHX Text No Special Inspection Required for this Project
AutoCAD SHX Text The following sheets comprise the required schedule of special inspections for this project.
AutoCAD SHX Text The construction divisions which require special inspections for this project are as follows.
AutoCAD SHX Text IT-1 Verification of Soils IT-10 Inspection of Structural Steel
AutoCAD SHX Text Fabricators
AutoCAD SHX Text IT-2 Excavation and Fill IT-11 Structural Masonry
AutoCAD SHX Text IT-3 Piling and Drilling Piers IT-12 Welding
AutoCAD SHX Text IT-4 Modular Retaining Walls IT-13 High Strength Bolts & Steel Framing Inspection
AutoCAD SHX Text IT-5 Reinforced Concrete IT-14 Sprayed Fire-Resistance Materials
AutoCAD SHX Text IT-6 Post Tension Slab IT-15 Exterior Insulation and Finish System
AutoCAD SHX Text IT-7 Pre-cast Concrete Erection IT-16 Seismic Resistance
AutoCAD SHX Text IT-8 Pre-stressed Concrete IT-17 Smoke Control
AutoCAD SHX Text IT-9 Inspection of Pre-Cast IT-18 Detention Basin
AutoCAD SHX Text Fabrication IT-19 Special Cases
AutoCAD SHX Text Check the above boxes for the special inspection required for this project and list below
AutoCAD SHX Text
THERMAL ENVELOPE
AutoCAD SHX Text Prescriptive
AutoCAD SHX Text ROOF/CEILING ASSEMBLY (each assembly)
AutoCAD SHX Text Method of Compliance:
AutoCAD SHX Text
ENERGY REQUIREMENTS:
AutoCAD SHX Text budget versus allowable annual energy cost budget.
AutoCAD SHX Text The following data shall be considered minimum and any special attribute required to meet the
AutoCAD SHX Text energy code shall also be provided. Each Designer shall furnish the required portions of the project
AutoCAD SHX Text information for the plan data sheet. If energy cost budget method, state the annual energy cost
AutoCAD SHX Text Performance
AutoCAD SHX Text Energy Cost Budget
AutoCAD SHX Text
2018 APPENDIX B
AutoCAD SHX Text
BUILDING CODE SUMMARY
AutoCAD SHX Text
FOR ALL COMMERCIAL PROJECTS
AutoCAD SHX Text (Except 1 & 2-Family Dwellings and Townhouses)
AutoCAD SHX Text
PROJECT NAME:
AutoCAD SHX Text
PROJECT ADDRESS:
AutoCAD SHX Text
PROPOSED USE:
AutoCAD SHX Text
OWNER/AUTHORIZED AGENT:
AutoCAD SHX Text
OWNED BY:
AutoCAD SHX Text
CODE ENFORCEMENT JURISDICTION:
AutoCAD SHX Text
ZIP CODE:
AutoCAD SHX Text
PHONE #:
AutoCAD SHX Text
CITY/COUNTY
AutoCAD SHX Text
STATE
AutoCAD SHX Text
CITY
AutoCAD SHX Text
STATE
AutoCAD SHX Text
LEAD DESIGN PROFESSIONAL:
AutoCAD SHX Text
%%UDESIGNER
AutoCAD SHX Text
%%UFIRM
AutoCAD SHX Text
%%UNAME
AutoCAD SHX Text
%%ULICENSE #
AutoCAD SHX Text
%%UTELEPHONE #
AutoCAD SHX Text
ARCHITECTURAL:
AutoCAD SHX Text
CIVIL:
AutoCAD SHX Text
ELECTRICAL:
AutoCAD SHX Text
FIRE ALARM:
AutoCAD SHX Text
PLUMBING:
AutoCAD SHX Text
MECHANICAL:
AutoCAD SHX Text
SPRINKLER-STANDPIPE:
AutoCAD SHX Text
STRUCTURAL:
AutoCAD SHX Text
RETAINING WALLS <5'H:
AutoCAD SHX Text
OTHER:
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
PRIVATE
AutoCAD SHX Text
2018 EDITION OF NC CODE FOR:
AutoCAD SHX Text
NEW CONSTRUCTION
AutoCAD SHX Text
ADDITION
AutoCAD SHX Text
UPFIT
AutoCAD SHX Text
EXISTING:
AutoCAD SHX Text
RECONSTRUCTION
AutoCAD SHX Text
ALTERATION
AutoCAD SHX Text
REPAIR
AutoCAD SHX Text
CONSTRUCTED
AutoCAD SHX Text
ORIGINAL USE
AutoCAD SHX Text
RENOVATED
AutoCAD SHX Text
CURRENT USE
AutoCAD SHX Text
BUILDING DATA:
AutoCAD SHX Text
CONSTRUCTION TYPE:
AutoCAD SHX Text
II-A
AutoCAD SHX Text I-A
AutoCAD SHX Text I-B
AutoCAD SHX Text
II-B
AutoCAD SHX Text
III-A
AutoCAD SHX Text
III-B
AutoCAD SHX Text
IV
AutoCAD SHX Text V-A
AutoCAD SHX Text V-B
AutoCAD SHX Text
MIXED CONSTRUCTION:
AutoCAD SHX Text
YES
AutoCAD SHX Text
NO
AutoCAD SHX Text
%%UTYPE
AutoCAD SHX Text N/A
AutoCAD SHX Text
SPRINKLERS:
AutoCAD SHX Text
PARTIAL
AutoCAD SHX Text
NO
AutoCAD SHX Text
YES
AutoCAD SHX Text
NFPA13
AutoCAD SHX Text
NFPA13R
AutoCAD SHX Text
NFPA13D
AutoCAD SHX Text
STANDPIPES:
AutoCAD SHX Text
YES
AutoCAD SHX Text
NO
AutoCAD SHX Text
CLASS I
AutoCAD SHX Text
II
AutoCAD SHX Text
III
AutoCAD SHX Text
WET
AutoCAD SHX Text
DRY
AutoCAD SHX Text
FIRE DISTRICT:
AutoCAD SHX Text
YES
AutoCAD SHX Text
NO
AutoCAD SHX Text
FLOOD HAZARD AREA:
AutoCAD SHX Text
YES
AutoCAD SHX Text
NO
AutoCAD SHX Text
BUILDING HEIGHT:
AutoCAD SHX Text
FEET:
AutoCAD SHX Text
AutoCAD SHX Text
NUMBER OF STORIES:
AutoCAD SHX Text
AutoCAD SHX Text
MEZZANINE:
AutoCAD SHX Text
YES
AutoCAD SHX Text
NO
AutoCAD SHX Text
GROSS BUILDING AREA:
AutoCAD SHX Text
FLOOR:
AutoCAD SHX Text
EXISTING (SQ FT)
AutoCAD SHX Text
NEW (SQ FT)
AutoCAD SHX Text
SUB-TOTAL
AutoCAD SHX Text
6TH FLOOR
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
5TH FLOOR
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
4TH FLOOR
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
3RD FLOOR
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
2ND FLOOR
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
MEZZANINE
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
UPPER FLOOR
AutoCAD SHX Text
LOWER FLOOR
AutoCAD SHX Text
TOTAL:
AutoCAD SHX Text
ALLOWABLE AREA:
AutoCAD SHX Text
PRIMARY OCCUPANCY:
AutoCAD SHX Text
ASSEMBLY
AutoCAD SHX Text A1
AutoCAD SHX Text A2
AutoCAD SHX Text A3
AutoCAD SHX Text A4
AutoCAD SHX Text A5
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text
EDUCATIONAL
AutoCAD SHX Text
FACTORY
AutoCAD SHX Text
F1 MODERATE
AutoCAD SHX Text
F2 LOW
AutoCAD SHX Text
HAZARDOUS
AutoCAD SHX Text
H1 DETONATE
AutoCAD SHX Text
H2 DEFLAGRATE
AutoCAD SHX Text
H3 COMBUST
AutoCAD SHX Text
H4 HEALTH
AutoCAD SHX Text
H5 HPM
AutoCAD SHX Text
INSTITUTIONAL
AutoCAD SHX Text I-1
AutoCAD SHX Text I-2
AutoCAD SHX Text I-3
AutoCAD SHX Text I-4
AutoCAD SHX Text
I-3 CONDITION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MERCANTILE
AutoCAD SHX Text
RESIDENTIAL
AutoCAD SHX Text R1
AutoCAD SHX Text R2
AutoCAD SHX Text R3
AutoCAD SHX Text R4
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
S1 MODERATE
AutoCAD SHX Text
S2 LOW
AutoCAD SHX Text
HIGH-PILED
AutoCAD SHX Text
UTILITY & MISCELLANEOUS
AutoCAD SHX Text
PARKING GARAGE
AutoCAD SHX Text
OPEN
AutoCAD SHX Text
ENCLOSED
AutoCAD SHX Text
REPAIR GARAGE
AutoCAD SHX Text
SECONDARY OCCUPANCY:
AutoCAD SHX Text
S-1 (STORAGE)
AutoCAD SHX Text
SPECIAL USES:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SPECIAL PROVISIONS:
AutoCAD SHX Text 508.2
AutoCAD SHX Text 508.3
AutoCAD SHX Text 508.4
AutoCAD SHX Text 508.5
AutoCAD SHX Text 508.6
AutoCAD SHX Text 508.7
AutoCAD SHX Text 508.5
AutoCAD SHX Text 508.8
AutoCAD SHX Text
MIXED OCCUPANCY:
AutoCAD SHX Text
NO
AutoCAD SHX Text
YES
AutoCAD SHX Text
SEPARATION:
AutoCAD SHX Text N/A
AutoCAD SHX Text
EXCEPTION:
AutoCAD SHX Text
INCIDENTAL USE SEPARATION:
AutoCAD SHX Text
THIS USE IS NOT EXEMPT AS A NON-SEPARATED USE (SEE EXCEPTIONS)
AutoCAD SHX Text
NON-SEPARATED USE (302.3.1)
AutoCAD SHX Text THE REQUIRED TYPE OF CONSTRUCTION FOR THE BUILDING SHALL BE DETERMINED BY APPLYING THE HEIGHT
AutoCAD SHX Text AND AREA LIMITATIONS FOR EACH OF THE APPLICABLE OCCUPANCIES TO THE ENTIRE BUILDING. THE MOST
AutoCAD SHX Text RESTRICTIVE TYPE OF CONSTRUCTION, SO DETERMINED, SHALL APPLY TO THE ENTIRE BUILDING.
AutoCAD SHX Text
SEPARATED USE (302.3.2) - SEE BELOW FOR AREA CALCULATIONS
AutoCAD SHX Text FOR EACH STORY, THE AREA OF THE OCCUPANCY SHALL BE THAT THE SUM OF THE RATIOS OF THE ACTUAL
AutoCAD SHX Text FLOOR AREA OF EACH USE DIVIDED BY THE ALLOWABLE FLOOR AREA FOR EACH USE SHALL NOT EXCEED 1.
AutoCAD SHX Text
%%UACTUAL AREA OF OCCUPANCY "A"
AutoCAD SHX Text
ALLOWABLE AREA OF OCCUPANCY "A"
AutoCAD SHX Text
AutoCAD SHX Text
%%UACTUAL AREA OF OCCUPANCY "B"
AutoCAD SHX Text
ALLOWABLE AREA OF OCCUPANCY "B"
AutoCAD SHX Text %%U<
AutoCAD SHX Text
AutoCAD SHX Text %%U %%U + %%U %%U + =%%U %%U %%U<%%U 1.00
AutoCAD SHX Text
AutoCAD SHX Text
FRONTAGE AREA INCREASES FROM SECTION 506.2 ARE COMPUTED THUS:
AutoCAD SHX Text
a. PERIMETER WHICH FRONTS A PUBLIC WAY OR OPEN SPACE HAVING 20 FEET MINIMUM WIDTH = %%U %%U (F)
AutoCAD SHX Text
b. TOTAL BUILDING PERIMETER = %%U %%U (P)
AutoCAD SHX Text
c. RATIO (F/P) = %%U %%U (F/P)
AutoCAD SHX Text
d. W = MINIMUM WIDTH OF PUBLIC WAY
AutoCAD SHX Text
e. PERCENT OF FRONTAGE INCREASE I = 100[F/P - 0.25] x W/30 = %%U %%U (%%%)
AutoCAD SHX Text f
AutoCAD SHX Text
AutoCAD SHX Text
THE SPRINKLER INCREASE PER SECTION 506.3 IS AS FOLLOWS:
AutoCAD SHX Text
a. MULTI-STORY BUILDING I = 200 PERCENT
AutoCAD SHX Text
b. SINGLE STORY BUILDING I = 300 PERCENT
AutoCAD SHX Text s
AutoCAD SHX Text s
AutoCAD SHX Text
AutoCAD SHX Text
UNLIMITED AREA APPLICABLE UNDER CONDITIONS OF SECTIONS GROUP B,F,M,S,A4 (507);
AutoCAD SHX Text GROUP A MOTION PICTURE (507.9); MALLS (402.6); AND H2 AIRCRAFT PAINT HANGERS (507.7).
AutoCAD SHX Text
AutoCAD SHX Text MAXIMUM BUILDING AREA = TOTAL NUMBER OF STORIES IN THE BUILDING x E (506.4).
AutoCAD SHX Text
AutoCAD SHX Text THE MAXIMUM AREA OF PARKING GARAGES MUST COMPLY WITH 406.3.5. THE MAXIMUM AREA OF AIR TRAFFIC
AutoCAD SHX Text
CONTROL TOWERS MUST COMPLY WITH 412.1.2.
AutoCAD SHX Text
TYPE OF CONSTRUCTION
AutoCAD SHX Text
BUILDING HEIGHT (FEET)
AutoCAD SHX Text
BUILDING HEIGHT (STORIES)
AutoCAD SHX Text
TYPE VB
AutoCAD SHX Text
FEET 40
AutoCAD SHX Text
ALLOWABLE
AutoCAD SHX Text
(TABLE 503)
AutoCAD SHX Text
INCREASE FOR SPRINKLERS
AutoCAD SHX Text
FEET = H+20 = 60
AutoCAD SHX Text
STORIES + 1 = 3
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
ON PLANS
AutoCAD SHX Text
CODE
AutoCAD SHX Text
REFERENCE
AutoCAD SHX Text
FEET 35
AutoCAD SHX Text
STORIES 3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ALLOWABLE HEIGHT
AutoCAD SHX Text
FIRE PROTECTION REQUIREMENTS
AutoCAD SHX Text
LIFE SAFETY PLAN #, IF PROVIDED N/A
AutoCAD SHX Text
BUILDING ELEMENT
AutoCAD SHX Text
FIRE
AutoCAD SHX Text
SEPARATION
AutoCAD SHX Text
DISTANCE
AutoCAD SHX Text
(FEET)
AutoCAD SHX Text
RATING
AutoCAD SHX Text
REQ'D
AutoCAD SHX Text
PROVIDED
AutoCAD SHX Text w/ XXX
AutoCAD SHX Text
REDUCTION
AutoCAD SHX Text
DETAIL #
AutoCAD SHX Text
AND
AutoCAD SHX Text
SHEET #
AutoCAD SHX Text
DESIGN #
AutoCAD SHX Text
FOR
AutoCAD SHX Text
RATED
AutoCAD SHX Text
ASSEMBLY
AutoCAD SHX Text
DESIGN #
AutoCAD SHX Text
FOR
AutoCAD SHX Text
RATED
AutoCAD SHX Text
PENETRATION
AutoCAD SHX Text
DESIGN #
AutoCAD SHX Text
FOR
AutoCAD SHX Text
RATED
AutoCAD SHX Text
JOINTS
AutoCAD SHX Text
STRUCTURAL FRAME, INCLUDING
AutoCAD SHX Text
COLUMNS, GIRDERS, TRUSSES
AutoCAD SHX Text
BEARING WALLS
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
EAST
AutoCAD SHX Text
WEST
AutoCAD SHX Text
SOUTH
AutoCAD SHX Text
INTERIOR
AutoCAD SHX Text
NONBEARING WALLS AND
AutoCAD SHX Text
PARTITIONS
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
EAST
AutoCAD SHX Text
WEST
AutoCAD SHX Text
SOUTH
AutoCAD SHX Text
INTERIOR WALLS & PARTITIONS
AutoCAD SHX Text
FLOOR CONSTRUCTION
AutoCAD SHX Text
INCLUDING SUPPORTING BEAMS
AutoCAD SHX Text
AND JOISTS
AutoCAD SHX Text
ROOF CONSTRUCTION
AutoCAD SHX Text
INCLUDING SUPPORTING BEAMS
AutoCAD SHX Text
AND JOISTS
AutoCAD SHX Text
SHAFT ENCLOSURES - EXIT
AutoCAD SHX Text
SHAFT ENCLOSURES - OTHER
AutoCAD SHX Text
CORRIDOR SEPARATION
AutoCAD SHX Text
OCCUPANCY SEPARATION
AutoCAD SHX Text
PARTY/FIRE WALL SEPARATION
AutoCAD SHX Text
SMOKE BARRIER SEPARATION
AutoCAD SHX Text
TENANT SEPARATION
AutoCAD SHX Text
INCIDENTAL USE SEPARATION
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
* INDICATE SECTION NUMBER PERMITTING REDUCTION
AutoCAD SHX Text
EMEGENCY LIGHTING:
AutoCAD SHX Text
NO
AutoCAD SHX Text
YES
AutoCAD SHX Text
EXIT SIGNS:
AutoCAD SHX Text
NO
AutoCAD SHX Text
YES
AutoCAD SHX Text
FIRE ALARM:
AutoCAD SHX Text
NO
AutoCAD SHX Text
YES
AutoCAD SHX Text
SMOKE DETECTION SYSTEMS:
AutoCAD SHX Text
NO
AutoCAD SHX Text
YES
AutoCAD SHX Text
PANIC HARDWARE:
AutoCAD SHX Text
NO
AutoCAD SHX Text
YES
AutoCAD SHX Text
LIFE SAFETY REQUIREMENTS
AutoCAD SHX Text
FLOOR, ROOM OR
AutoCAD SHX Text
SPACE DESIGNATION
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
NUMBER OF EXITS
AutoCAD SHX Text
AutoCAD SHX Text
TRAVEL DISTANCE
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
SHOWN
AutoCAD SHX Text
ON PLANS
AutoCAD SHX Text
ALLOWABLE TRAVEL
AutoCAD SHX Text
DISTANCE
AutoCAD SHX Text
(TABLE 1015.1)
AutoCAD SHX Text
ARRANGEMENT MEANS OF
AutoCAD SHX Text
EGRESS (SECTION 1014.2)
AutoCAD SHX Text 1,3
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
DISTANCE
AutoCAD SHX Text
BETWEEN
AutoCAD SHX Text
EXIT DOORS
AutoCAD SHX Text
ACTUAL
AutoCAD SHX Text
DISTANCE
AutoCAD SHX Text
SHOWN ON
AutoCAD SHX Text
PLANS
AutoCAD SHX Text
ACTUAL TRAVEL
AutoCAD SHX Text
DISTANCE
AutoCAD SHX Text
SHOWN ON PLANS
AutoCAD SHX Text
CORRIDOR DEAD ENDS (SECTION 1016.3)
AutoCAD SHX Text
SINGLE EXITS (TABLE 1018.2)
AutoCAD SHX Text
COMMON PATH OF TRAVEL (SECTION 1013.3)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIT WIDTH
AutoCAD SHX Text
EXIT REQUIREMENTS
AutoCAD SHX Text
NUMBER AND ARRANGEMENT OF EXITS
AutoCAD SHX Text
USE GROUP OR
AutoCAD SHX Text
SPACE DESIGNATION
AutoCAD SHX Text (A)
AutoCAD SHX Text
AREA
AutoCAD SHX Text
SQ. FT.
AutoCAD SHX Text (B)
AutoCAD SHX Text
AREA
AutoCAD SHX Text
PER
AutoCAD SHX Text
OCCUPANT
AutoCAD SHX Text
(TABLE
AutoCAD SHX Text 1004.1.2)
AutoCAD SHX Text
CALCULATED
AutoCAD SHX Text
OCCUPANT
AutoCAD SHX Text
LOAD
AutoCAD SHX Text (C)
AutoCAD SHX Text
EGRESS WIDTH
AutoCAD SHX Text
PER OCCUPANT
AutoCAD SHX Text
(TABLE 1005.1)
AutoCAD SHX Text EXIT WIDTH (in)
AutoCAD SHX Text 2,3,4,5,6
AutoCAD SHX Text
REQUIRED WIDTH
AutoCAD SHX Text
(SECTION 1005.1)
AutoCAD SHX Text A/B x C
AutoCAD SHX Text
ACTUAL WIDTH
AutoCAD SHX Text
SHOWN ON PLANS
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
LEVEL
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
LEVEL
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
LEVEL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLUMBING FIXTURE REQUIREMENTS
AutoCAD SHX Text
USE
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
NEW
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
WATERCLOSETS
AutoCAD SHX Text
URINALS
AutoCAD SHX Text
LAVATORIES
AutoCAD SHX Text
SHOWERS/
AutoCAD SHX Text
DRINKING FOUNTAINS
AutoCAD SHX Text
MALE
AutoCAD SHX Text
FEMALE
AutoCAD SHX Text
MALE
AutoCAD SHX Text
FEMALE
AutoCAD SHX Text
REGULAR
AutoCAD SHX Text
ACCESSIBLE
AutoCAD SHX Text
ACCESSIBLE PARKING
AutoCAD SHX Text
LOT OR
AutoCAD SHX Text
PARKING AREA
AutoCAD SHX Text
ASSEMBLY
AutoCAD SHX Text
TOTAL # OF PARKING SPACES
AutoCAD SHX Text
# OF ACCESSIBLE SPACES PROVIDED
AutoCAD SHX Text
TOTAL # OF
AutoCAD SHX Text
ACCESSBILE PROVIDED
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
PROVIDED
AutoCAD SHX Text REGULAR w/ 5'
AutoCAD SHX Text
ACCESS AISLE
AutoCAD SHX Text VAN SPACES w/
AutoCAD SHX Text
8' ACCESS AISLE
AutoCAD SHX Text
TOTAL:
AutoCAD SHX Text
SPECIAL APPROVALS
AutoCAD SHX Text SPECIAL APPROVAL: (LOCAL JURISDICTION, DEPARTMENT OF INSURANCE, OSC, DPI, DFS, ICC, etc., DESCRIBE BELOW)
AutoCAD SHX Text
TUBS
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
ENEGY SUMMARY
AutoCAD SHX Text
ELECTRICAL SUMMARY
AutoCAD SHX Text
(SEE ELECTRICAL DRAWINGS FOR BUILDING SUMMARY)
AutoCAD SHX Text
MECHANICAL SUMMARY
AutoCAD SHX Text N/A
AutoCAD SHX Text
AutoCAD SHX Text
SEE TABLE 1004.1.2 TO DETERMINE WHETHER NET OR GROSS AREA IS APPLICABLE.
AutoCAD SHX Text
SEE DEFINITION "AREA, GROSS" AND "AREA, NET" (SECTION 1002).
AutoCAD SHX Text MIN. STAIRWAY WIDTH(SECTION 1005.1);MIN. CORRIDOR WIDTH(SECTION 1016.2);MIN. DOOR WIDTH(SECTION 1018.1)
AutoCAD SHX Text
MIN. WIDTH OF EXIT PASSAGEWAY (SECTION 1020.2)
AutoCAD SHX Text
SEE SECTION 1004.5 FOR CONVEGING EXITS.
AutoCAD SHX Text THE LOSS OF ONE MEANS EGRESS SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50%%% OF THE
AutoCAD SHX Text
TOTAL REQUIRED (SECTION 1005.1).
AutoCAD SHX Text
ASSEMBLY OCCUPANCIES (SECTION 1024).
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COUNTY
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
STRUCTURAL DESIGN
AutoCAD SHX Text N/A
AutoCAD SHX Text
TYPE VB
AutoCAD SHX Text
STORY NO.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AND USE
AutoCAD SHX Text "A"
AutoCAD SHX Text
BLDG AREA
AutoCAD SHX Text
PER STORY
AutoCAD SHX Text
(ACTUAL)
AutoCAD SHX Text "B"
AutoCAD SHX Text
TABLE 503
AutoCAD SHX Text
AREA
AutoCAD SHX Text
AutoCAD SHX Text "C"
AutoCAD SHX Text
AREA FOR
AutoCAD SHX Text
FRONTAGE
AutoCAD SHX Text
INCREASE
AutoCAD SHX Text "D"
AutoCAD SHX Text
AREA FOR
AutoCAD SHX Text
SPRINKLER
AutoCAD SHX Text
INCREASE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text "E"
AutoCAD SHX Text
ALLOWABLE
AutoCAD SHX Text
AREA OR
AutoCAD SHX Text
UNLIMITED
AutoCAD SHX Text
AutoCAD SHX Text "F"
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
AREA OR
AutoCAD SHX Text
UNLIMITED
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text >5
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
2018 N.C. REHAB CODE
AutoCAD SHX Text Work area must be delineated on the submitted plans.
AutoCAD SHX Text Information:
AutoCAD SHX Text
RENOVATION
AutoCAD SHX Text
ALTERATION
AutoCAD SHX Text
REPAIR
AutoCAD SHX Text Check all that apply:
AutoCAD SHX Text
RECONSTRUCTION
AutoCAD SHX Text
CHANGE OF USE
AutoCAD SHX Text
ADDITON
AutoCAD SHX Text Describe scope of work based on code sections of the rehab code
AutoCAD SHX Text Last known legal Occupancy
AutoCAD SHX Text History Property:
AutoCAD SHX Text
YES
AutoCAD SHX Text
NO
AutoCAD SHX Text
ORIGINAL BUILDING CONSTRUCTION DATE
AutoCAD SHX Text Consideration for review under the Rehab Code based on code section as follows:
AutoCAD SHX Text Reviewers Notes for Field Inspector:
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
AutoCAD SHX Text 21.4
AutoCAD SHX Text N/A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text .15
AutoCAD SHX Text 16.1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text specific special inspections required under Chapter 17.
AutoCAD SHX Text Special Inspections Needed
AutoCAD SHX Text
TWO (2)
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text 10,700
AutoCAD SHX Text 9,000
AutoCAD SHX Text 18,000
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text 27,000
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text >5
AutoCAD SHX Text <5
AutoCAD SHX Text
1 HR
AutoCAD SHX Text
ARCH
AutoCAD SHX Text U419
AutoCAD SHX Text
1 HR
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
STORIES 2
AutoCAD SHX Text
LOWER FLOOR PLAN
AutoCAD SHX Text
UPPER FLOOR PLAN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LOWER FLOOR PLAN
AutoCAD SHX Text
UPPER FLOOR PLAN
AutoCAD SHX Text 10,700
AutoCAD SHX Text 10,700
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text .15
AutoCAD SHX Text .2
AutoCAD SHX Text N/A
AutoCAD SHX Text 16.1
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 109'
AutoCAD SHX Text 109'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text
PERCENTAGE OF OPENINGS
AutoCAD SHX Text
(TABLE 704.8)
AutoCAD SHX Text
TOTAL BUILDING ELEVATION AREA = 3,317 SQ. FT.
AutoCAD SHX Text
TOTAL SQUARE FOOTAGE OF OPENINGS = 366 SQ. FT.
AutoCAD SHX Text
TOTAL = 366/3,317 = 11%%% < 15%%%
AutoCAD SHX Text
NORTH ELEVATION
AutoCAD SHX Text
(SEE STRUCTURAL DRAWINGS FOR BUILDING SUMMARY)
AutoCAD SHX Text
AutoCAD SHX Text R-Value of Insulation
AutoCAD SHX Text WALLS BELOW GRADE (each assembly)
AutoCAD SHX Text WALLS ADJACENT TO UNCONDITIONED SPACE (each assembly)
AutoCAD SHX Text Openings (windows or doors glazing)
AutoCAD SHX Text Low E required (if applicable)
AutoCAD SHX Text total sq ft of skylights in each assembly
AutoCAD SHX Text Skylights in each assembly
AutoCAD SHX Text U-Value of assembly
AutoCAD SHX Text Door R-Value
AutoCAD SHX Text U-Value of skylight
AutoCAD SHX Text (Veritcal N / A )
AutoCAD SHX Text 2.0
AutoCAD SHX Text N / A
AutoCAD SHX Text .49
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text U-Value of total assembly
AutoCAD SHX Text Suspended Ceiling
AutoCAD SHX Text Interior Air Film
AutoCAD SHX Text Rigid Insulation
AutoCAD SHX Text Exterior Air Film
AutoCAD SHX Text Air Space
AutoCAD SHX Text Single Ply Membrane
AutoCAD SHX Text 1/22.38= 0.04468
AutoCAD SHX Text .68
AutoCAD SHX Text .68
AutoCAD SHX Text
AutoCAD SHX Text .34
AutoCAD SHX Text .34
AutoCAD SHX Text .34
AutoCAD SHX Text Horizontal-Vertical requirement
AutoCAD SHX Text Slab heated
AutoCAD SHX Text R-Value of insulation
AutoCAD SHX Text N / A
AutoCAD SHX Text N / A
AutoCAD SHX Text (Vertical @ Perimeter)
AutoCAD SHX Text (Horizontal N/A)
AutoCAD SHX Text
FLOORS SLAB ON GRADE
AutoCAD SHX Text Concrete block
AutoCAD SHX Text Rigid Perimeter (2"x24")
AutoCAD SHX Text U-Value of total assembly
AutoCAD SHX Text FLOORS OVER UNCONDITIONED SPACE (each assembly)
AutoCAD SHX Text Interior Air Film
AutoCAD SHX Text Vapor Barrier
AutoCAD SHX Text N / A
AutoCAD SHX Text .24
AutoCAD SHX Text .34
AutoCAD SHX Text .68
AutoCAD SHX Text 1 / 1.26 = 0.793
AutoCAD SHX Text N / A
AutoCAD SHX Text
NONE
AutoCAD SHX Text 5/8" Fire Code Gypsum Board
AutoCAD SHX Text .68
AutoCAD SHX Text Openings (window or doors glazing)
AutoCAD SHX Text U-Value of total assembly
AutoCAD SHX Text EXTERIOR WALLS (4" brick and metal studs)
AutoCAD SHX Text Door R-Value
AutoCAD SHX Text Projection factor
AutoCAD SHX Text Shading coefficient
AutoCAD SHX Text U-Value of assembly
AutoCAD SHX Text R-Value of insulation
AutoCAD SHX Text Interior Air Film
AutoCAD SHX Text Low E (If required)
AutoCAD SHX Text 2" Air Space
AutoCAD SHX Text Exterior Air Film
AutoCAD SHX Text 2.0
AutoCAD SHX Text 1 / 22.39 = 0.74
AutoCAD SHX Text "0"
AutoCAD SHX Text N / A
AutoCAD SHX Text "0"
AutoCAD SHX Text .57
AutoCAD SHX Text .68
AutoCAD SHX Text .45
AutoCAD SHX Text .34
AutoCAD SHX Text Face Brick
AutoCAD SHX Text .7
AutoCAD SHX Text 6" batt insulation
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1/2" exterior sheathing
AutoCAD SHX Text .54
AutoCAD SHX Text
NORTH CAMPUS SITE LIGHTING FOR CLEVELAND COMMUNITY COLLEGE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DONALD R. BRITTAIN, P.E.
AutoCAD SHX Text
BRITTAIN ENGINEERING, INC.
AutoCAD SHX Text
DONALD R. BRITTAIN
AutoCAD SHX Text
AutoCAD SHX Text
(828) 328-1813
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
831 NORTH POST ROAD
AutoCAD SHX Text
SHELBY, NORTH CAROLINA
AutoCAD SHX Text 28152
AutoCAD SHX Text
JEFF LEDFORD
AutoCAD SHX Text
BUSINESS
AutoCAD SHX Text
(704) 669-4268
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text N/A
AutoCAD SHX Text 20'
AutoCAD SHX Text
DWN BY:
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text 218400
AutoCAD SHX Text 10/24/25
AutoCAD SHX Text 10/24/25
AutoCAD SHX Text
CLEVELAND COMMUNITY COLLEGE
AutoCAD SHX Text
NORTH CAMPUS SITE LIGHTING FOR
AutoCAD SHX Text
831 NORTH POST ROAD, SHELBY, NC 28152
AutoCAD SHX Text
101625MW
AutoCAD SHX Text C-1
AutoCAD SHX Text
DGR
AutoCAD SHX Text
C
N S
U L T
I N
G
M
E C
H A
N I C
A L
A
E
C T
R I C
A L
E
N G
I N
E E
R S
B R
I T
T A
G
I N
E E
R I N
G
I N
C
H I C
K O
R Y
N
C
AutoCAD SHX Text See Fixture Schedule
AutoCAD SHX Text N/A
AutoCAD SHX Text See Fixture Schedule
AutoCAD SHX Text See Fixture Schedule
AutoCAD SHX Text See Fixture Schedule
AutoCAD SHX Text See Fixture Schedule
AutoCAD SHX Text
METHOD OF COMPLIANCE:
AutoCAD SHX Text total wattage per fixture
AutoCAD SHX Text Prescriptive Performance
AutoCAD SHX Text number of ballasts in fixture
AutoCAD SHX Text ballast type used in the fixture
AutoCAD SHX Text number of lamps in fixture
AutoCAD SHX Text lamp type required in fixture
AutoCAD SHX Text
ELECTRICAL SYSTEM AND EQUIPMENT
AutoCAD SHX Text total exterior wattage specified vs allowed
AutoCAD SHX Text total interior wattage specified vs allowed
AutoCAD SHX Text Lighting schedule
AutoCAD SHX Text 12,700/16,400
AutoCAD SHX Text Prescriptive Performance
AutoCAD SHX Text
ASHRAE 90.1:
AutoCAD SHX Text Energy Code:
AutoCAD SHX Text Additional Prescriptive Compliance
AutoCAD SHX Text C406.2 More Efficient Mechanical Equipment
AutoCAD SHX Text C406.3 Reduced Lighting Power Density
AutoCAD SHX Text C406.4 Enhanced Lighting Controls
AutoCAD SHX Text C406.5 On-Site Supply of Renewable Energy
AutoCAD SHX Text C406.6 Dedicated Outdoor Air System
AutoCAD SHX Text C406.7 High-Efficiency Service Water Heating
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
MANUFACTURER **
AutoCAD SHX Text
CATALOG NO.
AutoCAD SHX Text
LIGHTING FIXTURE SCHEDULE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
MARK
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
LAMPS
AutoCAD SHX Text
QTY/TYPE
AutoCAD SHX Text
VOLTAGE
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
LIGHT FIXTURES - AS NOTED ON FIXTURE SCHEDULE.
AutoCAD SHX Text
WALL SWITCHES - 4'-0" OR TO NEAREST MASONRY COURSE JOINT.
AutoCAD SHX Text
RECEPTACLES - 1'-6" OR TO NEAREST MASONRY COURSE JOINT.
AutoCAD SHX Text
%%UDETAILED ELECTRICAL SPECIFICATIONS
AutoCAD SHX Text SCOPE: FURNISH ALL MATERIALS, LABOR, TOOLS, EQUIPMENT AND SUPERVISION NECESSARY TO INSTALL COMPLETE FURNISH ALL MATERIALS, LABOR, TOOLS, EQUIPMENT AND SUPERVISION NECESSARY TO INSTALL COMPLETE ELECTRICAL POWER AND LIGHTING SYSTEM IN THE BUILDING AS FURTHER DESCRIBED ON THE ELECTRICAL CONTRACT DRAWINGS.
AutoCAD SHX Text SUPPLY ALL MATERIALS, FITTINGS AND HARDWARE NECESSARY FOR COMPLETE OPERATING SYSTEMS WITHIN THE OBVIOUS INTENT OF THE DRAWINGS. NO ATTEMPT HAS BEEN MADE TO DETAIL OR LIST EACH AND EVERY ITEM OF MATERIAL. THE ELECTRICAL CONTRACTOR IS CAUTIONED TO READ THE ENTIRE PROJECT DRAWINGS AND SPECIFICATIONS TO ASSURE HIMSELF OF A THOROUGH KNOWLEDGE OF BUILDING CONSTRUCTION, STRUCTURAL RESTRICTIONS TO ELECTRICAL CONTRACT WORK AND TO ASSURE THAT NO REFERENCE ANYWHERE IN THE PROJECT DRAWINGS AND SPECIFICATIONS TO WORK BY THE ELECTRICAL CONTRACTOR IS OVERLOOKED.
AutoCAD SHX Text CODES, PERMITS AND INSPECTIONS: THE LATEST EDITION OF THE STATE OF NORTH CAROLINA BUILDING CODE THE LATEST EDITION OF THE STATE OF NORTH CAROLINA BUILDING CODE WHICH INCLUDES THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE IS HEREBY MADE A PART OF THIS SPECIFICATION. CODE REQUIREMENTS SHALL TAKE PRECEDENCE OVER THESE SPECIFICATIONS WHERE THE CODE REQUIREMENTS EXCEED THAT OF THE SPECIFICATIONS. HOWEVER, THE SPECIFICATIONS SHALL BE FOLLOWED WHERE THEY EXCEED CODE REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL, AT NO ADDITIONAL COST TO THE OWNER, OBTAIN THE SERVICES OF THE LOCAL ELECTRICAL INSPECTOR TO MAKE ALL REQUIRED DURING CONSTRUCTION AND COMPLETED ELECTRICAL SYSTEM INSPECTIONS.
AutoCAD SHX Text MATERIALS AND WORKMANSHIP: ALL MATERIAL BUILT INTO THIS PROJECT SHALL BE NEW OF EQUIVALENT OR BETTER ALL MATERIAL BUILT INTO THIS PROJECT SHALL BE NEW OF EQUIVALENT OR BETTER QUALITY THAN THAT SPECIFIED. SPECIFIC NAMES AND CATALOG NUMBERS USED HEREIN ARE TO ESTABLISH THE ITEM FUNCTION, ARRANGEMENT AND QUALITY REQUIRED AND IS IN NO WAY TO RESTRICT COMPETITION. ALL MATERIALS SHALL BE UL APPROVED/LABELED AND/OR BE APPROVED BY A THIRD PARTY TESTING AGENCY IN THE STATE OF NORTH CAROLINA FOR THE PARTICULAR APPLICATION AS USED ON THIS PROJECT.
AutoCAD SHX Text CONDUCTORS: ALL CONDUCTORS SHALL BE COPPER (#10 AWG AND SMALLER SHALL BE SOLID, AND #8 AWG AND LARGER : ALL CONDUCTORS SHALL BE COPPER (#10 AWG AND SMALLER SHALL BE SOLID, AND #8 AWG AND LARGER STRANDED) WITH THHN/THWN INSULATION, INSTALLED IN CONDUIT. CONDUCTORS SHALL BE #12 AWG MINIMUM EXCEPT WITHIN LIGHT FIXTURES, LOW VOLTAGE CONTROLS OR COMMUNICATION/FIRE ALARM EQUIPMENT. CONDUCTOR COLOR CODE SHALL CONFORM TO THE NEC. CONDUCTORS SHALL BE CONTINUOUS FROM TERMINAL TO TERMINAL OR PULL BOX TO PULL BOX. JOINTS SHALL BE MADE WITH IDEAL "WIRENUTS." WIRING TERMINATIONS FOR ALL ELECTRICAL EQUIPMENT SHALL BE TESTED AND APPROVED FOR USE WITH 75°C RATED CONDUCTORS.
AutoCAD SHX Text RACEWAYS: RACEWAYS SHALL BE UL APPROVED RIGID GALVANIZED STEEL WITH THREADED JOINTS OR METALLIC RACEWAYS SHALL BE UL APPROVED RIGID GALVANIZED STEEL WITH THREADED JOINTS OR METALLIC TUBING (EMT) WITH THREADED STEEL HEXAGONAL COMPRESSION FITTINGS - NEITHER INDENTOR TYPE OR DIE METAL FITTING WILL BE ACCEPTED. CONDUIT UNDER THE FLOOR SLAB AND UNDER GROUND OUTSIDE THE BUILDING MAY BE PVC. FITTINGS IN EMT SHALL BE WEATHER TIGHT (THOMAS AND BETTS SERIES #5123 WITH NYLON INSULATED THROATS), BENDS SHALL BE FACTORY FABRICATED OR MADE "COLD" WITH BENDING TOOL, FREE OF KINKS OR RESTRICTIONS. NO SINGLE BEND SHALL BE IN EXCESS OF 90 DEGREES. THERE SHALL BE NO MORE THAN THE EQUIVALENT OF THREE (3) 90 DEGREE BENDS IN A GIVEN RACEWAY FROM PULL BOX TO PULL BOX. RIGID RACEWAY THREADS SHALL BE CUT STRAIGHT AND TRUE - PIPE ENDS SHALL BE REAMED AND SMOOTHED INSIDE AND OUT. SUPPORT 1-1/2 INCH AND LARGER CONDUIT 10 FEET O/C OR LESS, AND 1 INCH AND SMALLER 6 FEET O/C MAXIMUM. RACEWAYS SHALL BE SUPPORTED DIRECTLY FROM BUILDING STRUCTURE WITH BOLTS, SCREWS, STRAPS, HANGER RODS AND BRACKETS. ALL METALLIC HARDWARE SHALL BE GALVANIZED OR CADMIUM PLATED. NAILS, WIRE AND/OR PERFORATED STRAPS WILL NOT BE ACCEPTED. USE THREADED LOCKNUTS OUTSIDE AND THREADED LOCKNUT AND BUSHING INSIDE ALL RACEWAY CONNECTIONS TO BOXES, DEVICES, PANELS AND GUTTERS. USE NON-METALLIC BUSHINGS ON ALL 1-1/4 INCH AND LARGER CONDUIT. EXPOSED CONDUIT SHALL BE RUN STRAIGHT AND TRUE PARALLEL AND PERPENDICULAR TO PRIMARY BUILDING LINES.
AutoCAD SHX Text BOXES AND DEVICES: ALL BOXES, PANELS AND EQUIPMENT SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING ALL BOXES, PANELS AND EQUIPMENT SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING STRUCTURE AND SHALL NOT DEPEND ON THE FEEDER RACEWAYS FOR SUPPORT. ALL ITEMS SHALL BE CAREFULLY ALIGNED SO THAT COVERS WILL FINISH FLUSH AND STRAIGHT. ALL UNUSED KNOCKOUTS SHALL BE CLOSED WITH BLANKING DEVICES. BOXES IN CONCRETE OR MASONRY SHALL BE 3-1/2 INCH DEEP (MINIMUM) SQUARE 16 GAUGE GALVANIZED STEEL - STEEL CITY SERIES GW. BOXES INSTALLED IN WOOD PARTITIONS SHALL BE STEEL CITY 3-1/2 INCH DEEP GANGABLE SQUARE CORNER TYPE. SURFACE MOUNTED BOXES SHALL BE STEEL CITY #52151 AND/OR #52171 OR EQUAL. RECEPTACLES SHALL BE PASS & SEYMOUR 5362 SERIES OR EQUAL. SWITCHES SHALL BE PASS & SEYMOUR CBS20AC SERIES OR EQUAL. COVER PLATES SHALL BE STAINLESS STEEL (COORDINATE W/ OWNER). PULL BOXES SHALL BE 14 GAUGE GALVANIZED STEEL WITH BLANK COVER SIZED AS REQUIRED BY NATIONAL ELECTRICAL CODE. LOCATE DEVICES AND EQUIPMENT ABOVE FINISHED FLOOR AS FOLLOWS UNLESS OTHERWISE SPECIFICALLY NOTED ON PLANS:
AutoCAD SHX Text GROUNDING: THE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH THE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. GREEN EQUIPMENT GROUND WIRE SHALL BE INSTALLED WITH ALL FEEDERS AND BRANCH CIRCUITS AND IT SHALL BE SIZED PER NEC 250.122. WHERE ONLY ONE GROUND ROD IS DRIVEN AS ALLOWED BY THE EXCEPTION IN NEC ARTICLE 250.53(A)(2), THE CONTRACTOR SHALL SUBMIT A TESTING REPORT SHOWING THE ROD PROVIDES A RESISTANCE OF 25 OHMS OR LESS TO THE ENGINEER.
AutoCAD SHX Text LIGHTING FIXTURES: LIGHTING FIXTURES AND LAMPS SHALL BE PROVIDED AND INSTALLED AS PER SCHEDULE. CATALOG LIGHTING FIXTURES AND LAMPS SHALL BE PROVIDED AND INSTALLED AS PER SCHEDULE. CATALOG NUMBERS GIVEN IN THE FIXTURE SCHEDULE INDICATE THE MINIMUM QUALITY AND PERFORMANCE REQUIRED. EQUAL FIXTURES WILL BE ALLOWED ONLY UPON APPROVAL BY ENGINEER; EQUAL FIXTURES SHALL MEET THE MINIMUM QUALITY AND PERFORMANCE OF THE SPECIFIED FIXTURE. EQUAL FIXTURES BY HUBBELL, COOPER, PHILIPS OR ACUITY SHALL BE ALLOWED. ALL FIXTURES SHALL BE CLEANED ON COMPLETION OF INSTALLATION. BALLASTS AND/OR THE FIXTURE UNIT IN WHICH THEY ARE INSTALLED SHALL HAVE UL APPROVAL FOR DIRECT CONTACT MOUNTING TO COMBUSTIBLE CEILING MATERIAL. ALL FLUORESCENT FIXTURES SHALL BE SUPPLIED WITH ELECTRONIC BALLASTS AND LED FIXTURES SHALL BE SUPPLIED WITH DIMMABLE LED DRIVERS. THE FIXTURES SHALL BE COMPLETE IN ALL RESPECTS INCLUDING PLASTER RINGS WHERE REQUIRED, END PLATES AND OTHER APPURTENANCES NECESSARY FOR THE COMPLETE INSTALLATION. ALL LIGHTING FIXTURES SHALL BE SECURED TO THE CEILING STRUCTURE PER THE NEC. ADDITIONAL SUPPORT WIRES (TIE WIRES) SHALL BE INSTALLED FOR EACH LAY-IN TYPE FIXTURE. THERE SHALL BE TWO STEEL WIRES OF THE SAME TYPE AS USED TO SUPPORT THE LAY-IN CEILING TRACK. ONE WIRE AT EACH OPPOSITE CORNER OF THE FIXTURE. THE WIRES SHALL BE FASTENED TO THE BUILDING STRUCTURE. FOR FIRE RATED CEILING, FIXTURE SHALL BE SUPPORTED ON ALL FOUR CORNERS AND AS PER THE CEILING DESIGN CRITERIA, TO THE BUILDING STRUCTURE.
AutoCAD SHX Text PANELBOARDS: PROVIDE PANELBOARDS RATED AND SIZED AS INDICATED IN THE SCHEDULE AND SHOWN ON THE PLANS EQUAL PROVIDE PANELBOARDS RATED AND SIZED AS INDICATED IN THE SCHEDULE AND SHOWN ON THE PLANS EQUAL TO SQUARE D COMPANY MODEL NQ FOR SERVICES UP TO 240 VOLTS; MODEL NF FOR SERVICES UP TO 480 VOLTS; AND "I-LINE" FOR POWER DISTRIBUTION PANELS. ALL PANELBOARDS SHALL BE SUPPLIED WITH A COPPER EQUIPMENT GROUNDING BUS. CONSTRUCTION FEATURES SHALL INCLUDE MINIMUM 5" WIDE GUTTERS, DEAD FRONT CONSTRUCTION, ELECTROPLATED COPPER CURRENT CARRYING PARTS; UL LISTED TERMINALS SUITABLE FOR CONDUCTORS SPECIFIED; FLUSH FRONT HINGED "DOOR IN DOOR" WITH CYLINDER TUMBLER TYPE LOCKS (ALL KEYS ALIKE); CIRCUIT DIRECTORY AND FRAME, CODE GAUGE STEEL, GALVANIZED AND BAKED ENAMEL FINISHED. CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE QOB (NQ PANELBOARDS), TYPE EDB (NF PANELBOARDS), AND TYPE FA AND FH (I-LINE PANELBOARDS). BREAKERS SHALL BE TOGGLE ACTION WITH QUICK-MAKE, QUICK-BREAK MECHANISM. TRIP INDICATION SHALL BE BY BREAKER HANDLE TAKING A POSITION BETWEEN ON AND OFF. ALL MULTI-POLE BREAKERS SHALL BE COMMON TRIP WITH A SINGLE HANDLE. ACCEPTABLE MANUFACTURERS: SQUARE D, GENERAL ELECTRIC, SIEMENS, CUTLER-HAMMER
AutoCAD SHX Text SAFETY SWITCHES: SWITCHES SHALL BE EQUAL TO SQUARE D TYPE HD WITH RATINGS AND FUSING PROVISIONS AS INDICATED. SWITCHES SHALL BE EQUAL TO SQUARE D TYPE HD WITH RATINGS AND FUSING PROVISIONS AS INDICATED.
AutoCAD SHX Text IDENTIFICATION AND NAMEPLATES: PROVIDE ENGRAVED, LAMINATED BAKELITE (WHITE LETTERS ON BLACK SURFACE) PROVIDE ENGRAVED, LAMINATED BAKELITE (WHITE LETTERS ON BLACK SURFACE) NAMEPLATES SCREWED TO EACH PIECE OF ELECTRICAL DISTRIBUTION EQUIPMENT AS FOLLOWS:
AutoCAD SHX Text A. PANELBOARDS, SWITCHBOARDS - DESIGNATION L1, P1, ETC.,VOLTAGE, PHASE NUMBER OF WIRES, ETC.; WORDING EXAMPLE: PANEL L1-208V-3 PHASE, 4 WIRE.
AutoCAD SHX Text B. MOTOR STARTERS, DISCONNECT SWITCHES - UNLESS MOUNTED DIRECTLY ON OR ADJACENT TO IDENTIFY EQUIPMENT: WORDING EXAMPLE: EXHAUST FAN 1, MAKE-UP AIR UNIT.
AutoCAD SHX Text PROVIDE TYPED DIRECTORIES FOR PANELBOARD BRANCH CIRCUIT IDENTIFICATION. IDENTIFY EACH CIRCUIT BREAKER AS TO THE EXACT ROOM NUMBERS OR AREA SERVED AND THE TYPE OF CIRCUIT, I.E. "ROOMS 101-104 LIGHTS" OR "CAFETERIA EXHAUST FAN". PROVIDE ALL ADDITIONAL LABELING AS REQUIRED BY NEC ARTICLES 110.16 (ARC FLASH HAZARD) & 110.24 (AVAILABLE FAULT CURRENT).
AutoCAD SHX Text EQUIPMENT CONNECTIONS: THIS CONTRACTOR SHALL BRING ALL REQUIRED ELECTRICAL SERVICE TO ALL EQUIPMENT ITEMS THIS CONTRACTOR SHALL BRING ALL REQUIRED ELECTRICAL SERVICE TO ALL EQUIPMENT ITEMS FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS OR BY THE OWNER, MAKE FINAL CONNECTIONS, AND LEAVE EQUIPMENT READY FOR OPERATION. THIS CONTRACTOR SHALL COORDINATE WITH ANY AFFECTED TRADE TO ASSURE CORRECT OPERATION OF THE EQUIPMENT ITEM.
AutoCAD SHX Text CONTROL AND INTERLOCK WIRING: EXCEPT AS OTHERWISE INDICATED ON THE DRAWINGS, ALL CONTROL AND EXCEPT AS OTHERWISE INDICATED ON THE DRAWINGS, ALL CONTROL AND INTERLOCK WIRING SHALL BE PERFORMED BY THE RESPECTIVE CONTRACTORS. THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL ALL STARTERS, PILOT SWITCHES, CONTROL DEVICES AND MISCELLANEOUS ITEMS OF ELECTRICAL EQUIPMENT FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS THAT ARE NOT INTEGRALLY MOUNTED WITH THEIR ASSOCIATED EQUIPMENT.
AutoCAD SHX Text DRY TYPE DISTRIBUTION TRANSFORMERS: TRANSFORMERS TO BE DRY-TYPE WITH NATURAL DRAFT VENTILATION. UNITS TRANSFORMERS TO BE DRY-TYPE WITH NATURAL DRAFT VENTILATION. UNITS TO BE RATED FOR 480 VOLTS, 3 PHASE, 3 WIRE PRIMARY, AND 120/208 VOLTS, 3 PHASE, 4 WIRE SECONDARY, UNLESS OTHERWISE INDICATED. UNITS TO BE DESIGNED FOR 60 HERTZ OPERATION, WITH KVA CAPACITIES AS SHOWN ON DRAWINGS. TRANSFORMERS TO CONFORM WITH APPLICABLE NEMA AND ANSI STANDARDS, INCLUDING NEMA TP-1 ENERGY EFFICIENT STANDARDS AND BE UL LISTED. TRANSFORMERS TO HAVE CLASS H INSULATION, HIGH GRADE SILICONE STEEL CORES, AND BE RATED FOR A MAXIMUM TEMPERATURE RISE OF 115 DEGREES C. UNITS RATED 30 KVA AND LARGER TO HAVE FOUR 2 1/2% TAPS BELOW NORMAL AND TWO 2 1/2% TAPS ABOVE NORMAL. UNITS RATED LESS THAN 30 KVA TO HAVE TWO 5% TAPS BELOW NORMAL. SOUND LEVELS GENERATED BY TRANSFORMERS ARE NOT TO EXCEED THE FOLLOWING VALUES: 9 KVA AND LESS -40 DB, 10 TO 45 KVA -42 DB, 50 TO 150 KVA -45 DB.
AutoCAD SHX Text SERVICE: THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING SERVICE WITH THE UTILITY COMPANY. ALL THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING SERVICE WITH THE UTILITY COMPANY. ALL CHARGES ASSOCIATED WITH SERVICE SHALL BE PAID BY THE E.C. PROVIDE UTILITY REQUIRED METERING PROVISIONS. PROVIDE CT CAN OR CONCRETE PAD FOR TRANSFORMER AS REQUIRED. PROVIDE CONDUIT FOR UTILITY PRIMARY IF REQUIRED. EC SHALL WORK DIRECTLY WITH THE UTILITY AND SHALL COMPLETE AND SUBMIT ALL LOAD DATA SHEETS REQUIRED FOR SERVICE APPLICATION. WHERE A NEW SERVICE IS NOT REQUIRED, BUT LOADS ARE ADDED TO AN EXISTING SERVICE, E.C. SHALL NOTIFY UTILITY OF ADDITIONAL LOADS E.C. SHALL PROVIDE THIS INFORMATION AT BEGINNING OF PROJECT TO ALLOW TIME FOR A TRANSFORMER CHANGE OUT IF NECESSARY.
AutoCAD SHX Text VIBRATION ISOLATION AND SEISMIC RESTRAINT: ALL EQUIPMENT AND CONDUIT FURNISHED AND INSTALLED UNDER THIS ALL EQUIPMENT AND CONDUIT FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE SEISMICALLY RESTRAINED BY CHAPTER 16 OF THE INTERNATIONAL BUILDING CODE, VOL. 1 - GENERAL CONSTRUCTION.
AutoCAD SHX Text SUBMITTALS: SHOP DRAWING SUBMITTALS WILL BE REQUIRED FOR THIS PROJECT. SUBMIT ELECTRONIC COPIES OF ALL LIGHT SHOP DRAWING SUBMITTALS WILL BE REQUIRED FOR THIS PROJECT. SUBMIT ELECTRONIC COPIES OF ALL LIGHT FIXTURES AND MAJOR SPECIFIED EQUIPMENT TO THE ENGINEER FOR APPROVAL. THE ELECTRICAL CONTRACTOR SHALL REVIEW ALL SUBMITTALS AND MAKE CORRECTIONS AS REQUIRED PRIOR TO SUBMITTING TO ENGINEER FOR APPROVAL. THE CONTRACTOR SHALL ALSO AFFIX HIS STAMP TO THE SUBMITTALS INDICATING THAT HIS REVIEW HAS BEEN COMPLETED. IT IS UNDERSTOOD THAT PROOF OF EQUALITY IS THE RESPONSIBILITY OF THE CONTRACTOR AND/OR SUPPLIER AND THAT IT IS NOT THE RESPONSIBILITY OF THE ENGINEER TO PROVE THE INEQUALITY OF THE PROPOSED SUBSTITUTIONS. FURTHERMORE THE DECISION OF THE ENGINEER IS FINAL. SHOULD ANY SUBSTITUTE ITEMS BE SUBMITTED AND DISAPPROVED, THEN THOSE ITEMS MUST BE FURNISHED EXACTLY AS DESCRIBED HEREIN. THE ENGINEER'S REVIEW OF SHOP DRAWINGS AND/OR SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE CONTRACT DRAWINGS OR SPECIFICATIONS.
AutoCAD SHX Text TESTING: CABLE INSULATION TESTING: THE CONTRACTOR SHALL MEGGER ALL BUSWAYS, CABLES AND CONTROL CABLE INSULATION TESTING: THE CONTRACTOR SHALL MEGGER ALL BUSWAYS, CABLES AND CONTROL CONNECTIONS TO PROVE INSULATION RESISTANCE IS OF ACCEPTABLE VALUE. EMERGENCY LIGHT TESTING: CONTRACTOR SHALL PERFORM A TEST ON EACH UNIT AFTER IT IS PERMANENTLY INSTALLED AND CHARGED FOR A MINIMUM OF 24 HOURS. BATTERY SHALL BE TESTED FOR 90 MINUTES AND IT SHALL MEET THE REQUIREMENTS OF NEC 700.12 (A). ANY UNIT WHICH FAILS THE TEST MUST BE REPAIRED OR REPLACED, AND TESTED AGAIN. A COPY OF THE TEST REPORT SHALL BE PRESENTED TO THE ENGINEER PRIOR TO FINAL INSPECTION. TESTING DOCUMENTATION: ALL TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE DOCUMENTATION: ALL TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE DOCUMENTATION: ALL TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE ALL TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE ALL TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE ALL TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE TESTS SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE SPECIFIED SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE SHALL BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE BE COMPLETELY DOCUMENTED AND TURNED OVER TO THE COMPLETELY DOCUMENTED AND TURNED OVER TO THE COMPLETELY DOCUMENTED AND TURNED OVER TO THE DOCUMENTED AND TURNED OVER TO THE DOCUMENTED AND TURNED OVER TO THE AND TURNED OVER TO THE AND TURNED OVER TO THE TURNED OVER TO THE TURNED OVER TO THE OVER TO THE OVER TO THE TO THE TO THE THE THE ENGINEER WHERE REQUIRED IN THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, WHERE REQUIRED IN THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, WHERE REQUIRED IN THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, REQUIRED IN THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, REQUIRED IN THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, IN THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, IN THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, THESE SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, SPECIFICATIONS. THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, THE TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, TEST CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, CERTIFICATIONS SHALL IDENTIFY THE TEST VALUES, SHALL IDENTIFY THE TEST VALUES, SHALL IDENTIFY THE TEST VALUES, IDENTIFY THE TEST VALUES, IDENTIFY THE TEST VALUES, THE TEST VALUES, THE TEST VALUES, TEST VALUES, TEST VALUES, VALUES, VALUES, EQUIPMENT TESTED, TIME OF DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TESTED, TIME OF DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TESTED, TIME OF DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TIME OF DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TIME OF DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE OF DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE OF DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE DAY AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE AND DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE DATE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE OF TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TESTING, TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TEMPERATURE AT TIME OF TESTING, THE NAME OF THE TEMPERATURE AT TIME OF TESTING, THE NAME OF THE AT TIME OF TESTING, THE NAME OF THE AT TIME OF TESTING, THE NAME OF THE TIME OF TESTING, THE NAME OF THE TIME OF TESTING, THE NAME OF THE OF TESTING, THE NAME OF THE OF TESTING, THE NAME OF THE TESTING, THE NAME OF THE TESTING, THE NAME OF THE THE NAME OF THE THE NAME OF THE NAME OF THE NAME OF THE OF THE OF THE THE THE ELECTRICIAN THAT CONDUCTED THE TEST, AND SIGNATURE OF PERSON RESPONSIBLE FOR THE TEST.
AutoCAD SHX Text PROJECT CLOSE-OUT: DEMONSTRATION OF COMPLETE ELECTRICAL SYSTEMS: AFTER INSTALLATION HAS BEEN COMPLETED, DEMONSTRATION OF COMPLETE ELECTRICAL SYSTEMS: AFTER INSTALLATION HAS BEEN COMPLETED, EQUIPMENT HAS BEEN TESTED, SYSTEMS PLACED IN PERMANENT OPERATION, AND ALL ADJUSTMENTS MADE, THIS CONTRACTOR SHALL DEMONSTRATE THE PROPER OPERATION AND MAINTENANCE OF ALL EQUIPMENT HE HAS INSTALLED TO THE OWNER'S REPRESENTATIVE.
AutoCAD SHX Text OPERATING AND MAINTENANCE MANUALS: THIS CONTRACTOR SHALL PROVIDE THE OWNER WITH A SET OF OPERATION AND THIS CONTRACTOR SHALL PROVIDE THE OWNER WITH A SET OF OPERATION AND MAINTENANCE MANUALS FOR THE EQUIPMENT HE HAS PROVIDED AND INSTALLED ON THE PROJECT. THE FIRST PAGE OF THE MANUALS SHALL IDENTIFY PROJECT AND GIVE NAME, ADDRESS AND PHONE NUMBER OF ARCHITECT, ENGINEER, MECHANICAL AND ELECTRICAL SUB-CONTRACTORS AND ANY SERVICE COMPANIES INVOLVED AND GIVE NAME AND NIGHT PHONE NUMBERS OF EACH PARTY REPRESENTING THE ELECTRICAL CONTRACTOR RESPONSIBLE FOR SERVICE DURING WARRANTY PERIOD.
AutoCAD SHX Text WARRANTIES / GUARANTEE: THIS CONTRACTOR SHALL DELIVER TO THE OWNER ALL WARRANTIES FOR EQUIPMENT HE HAS THIS CONTRACTOR SHALL DELIVER TO THE OWNER ALL WARRANTIES FOR EQUIPMENT HE HAS PURCHASED AND INSTALLED. THIS CONTRACTOR SHALL ALSO GUARANTEE THAT ALL WORK PERFORMED AND/OR MATERIALS INSTALLED UNDER HIS CONTRACT IS OF THE QUALITY THAT COMPLIES WITH ALL SPECIFIC REQUIREMENTS OF THE PROJECT DOCUMENTS AND INSURES THE OWNER AGAINST ALL DEFECTS OF MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE.
AutoCAD SHX Text FINAL CLEAN UP: DURING CONSTRUCTION THIS CONTRACTOR SHALL KEEP THE SITE CLEAR OF DEBRIS AND UPON COMPLETION DURING CONSTRUCTION THIS CONTRACTOR SHALL KEEP THE SITE CLEAR OF DEBRIS AND UPON COMPLETION OF CONSTRUCTION HE SHALL CLEAN UP THE PREMISES AND REMOVE ALL EVIDENCE OF HIS WORK. RECORD DRAWINGS: AT THE END OF THE PROJECT, THE CONTRACTOR SHALL SUBMIT ONE SET OF THE ELECTRICAL DRAWINGS, AT THE END OF THE PROJECT, THE CONTRACTOR SHALL SUBMIT ONE SET OF THE ELECTRICAL DRAWINGS, UPDATED TO REFLECT CHANGES THAT HAVE TAKEN PLACE DURING THE CONSTRUCTION PERIOD, TO THE OWNER FOR THEIR USE. THE CORRECTED PLANS SHALL INDICATE ALL CHANGES AND DEVIATIONS FROM THE ORIGINAL CONTRACT DOCUMENTS.
AutoCAD SHX Text
WEATHERPROOF, GROUND FAULT, USB
AutoCAD SHX Text
DUPLEX RECEPT , ABOVE COUNTER
AutoCAD SHX Text
DISCONNECT SWITCH; FUSED; NONFUSED
AutoCAD SHX Text
SINGLE POLE SWITCH , 3 WAY, 4 WAY
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
QUAD-PLEX RECEPTACLE
AutoCAD SHX Text
GFI,
AutoCAD SHX Text
WP,
AutoCAD SHX Text
AFF
AutoCAD SHX Text
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
MOTOR TOGGLE SWITCH
AutoCAD SHX…