Final Drawings.pdf
PDF 3 MB Posted
- Solicitation number
- 27-350SOS-PHYSE-B-54614
- Issued by
- Sangamon County, Illinois
About this file
These are final construction drawings for a fire pump system replacement project at the Stratton Building (401 South Spring Street, Springfield, Illinois) prepared by the Illinois Secretary of State. The project involves replacing the existing fire pump and fire pump controller with a new horizontal split case pump (Aurora Pump Model No. 6-81-15E or pre-approved equal) rated at 1500 GPM flow at 90.0 PSI with a 100HP-480V-3PH-60HZ motor, installing a new fire pump controller (Tornatech Model GPS or pre-approved equal), and related piping, valves, and plumbing work in the partial basement. The scope of work includes demolition of existing equipment, installation of new sprinkler piping with gate valves and check valves, installation of a 10-inch RPZ (reduced pressure zone) backflow preventer assembly manufactured by Watts (Model No. 909-FAE or pre-approved equal), and installation of new domestic cold water piping with two new Read-O-Matic water meters. All work must comply with the 2018 International Building, Mechanical, Fuel Gas, and Fire Codes; 2021 International Energy Conservation Code; 2014 Illinois State Plumbing Code; 2017 National Electrical Code; and applicable Springfield ordinances. The construction documents reference a project number 25-081 with revisions dated August 5, 2026 and November 30, 2026.
The specifications require contractors to comply with NFPA 13 standards for sprinkler system installation, perform hydrostatic testing at minimum 200 psi for two hours or 50 psi in excess of maximum static pressure when exceeding 150 psi, and flush all piping to remove foreign substances before placing the system in service. Each trade contractor is responsible for obtaining all permits and inspections, paying applicable fees, and providing a one-year written guarantee covering all labor and materials from the date of substantial completion. Steel pipe connections up to 1.5 inches diameter shall be screwed or welded, while piping 2.5 inches diameter and larger shall be welded. Valve manufacturers must be pre-approved and include American Flow Controller, Kennedy Valve (ITT Grinnell), Mueller, or equivalents. The specifications establish detailed requirements for pipe and tube materials, fittings, unions, flanges, hangers, and valve installations consistent with ANSI/ASME standards. All work shall conform to prevailing wage requirements and OSHA regulations, with the contractor responsible for verifying all field dimensions and notifying the architect of any discrepancies.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Vendor Disclosure v 24.1 Formerly Forms A~33.docx | DOCX document | |
| IPG Active Registered Vendor Disclosure formerly Forms B v.23.1~56.docx | DOCX document | |
| Stratton Fire Pump IFB 27PS779008.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
401 SOUTH SPRING STREET
SPRINGFIELD, ILLINOIS
ARCHITECT:
GENERAL NOTES
1. EACH TRADE CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN
THE FIELD AND SHALL NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES. ALL WORK REQUIRING MEASURING SHALL
BE DONE ACCORDING TO FIGURES ON THE DRAWINGS AND
NOT SCALED FROM DRAWINGS. THE ARCHITECT WILL FURNISH
ANY ADDITIONAL DIMENSIONS UPON REQUEST.
2. ALL WORK SHALL CONFORM TO PREVAILING CODE,
ORDINANCES, AND REQUIREMENTS.
3. EACH TRADE CONTRACTOR SHALL BE RESPONSIBLE TO
OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED FOR THEIR
WORK AND SHALL PAY ALL APPLICABLE FEES.
4. EACH TRADE CONTRACTOR SHALL PROVIDE OWNER WITH
WRITTEN ONE (1) YEAR GUARANTEE COVERING ALL LABOR
AND MATERIALS FURNISHED AND INSTALLED AS PART OF THIS
PROJECT. GUARANTEE SHALL COMMENCE FROM THE DATE OF
SUBSTANTIAL COMPLETION.
5. EACH TRADE CONTRACTORS SHALL COMPLY WITH ALL
PREVAILING O.S.H.A. REQUIREMENTS.
INDEX OF DRAWINGS
G-1 COVER SHEET
FP-1 SPRINKLER PLAN
FP-2 SPRINKLER SPECIFICATIONS
P-1 PLUMBING PLAN
P-2 PLUMBING SPECIFICATIONS
E-1 ELECTRICAL PLAN
FIRE PUMP SYSTEM REPLACEMENT
STRATTON BUILDING
BUILDING DESIGN CRITERIA
ALL WORK SHALL BE CONSTRUCTED IN ACCORD WITH:
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL FUEL GAS CODE
2018 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2018 ILLINOIS ACCESSIBILITY CODE
2015 NFPA 101 LIFE SAFETY CODE
2014 ILLINOIS STATE PLUMBING CODE
2017 NATIONAL ELECTRICAL CODE
2005 SPRINGFIELD ZONING ORDINANCE,
SPRINGFIELD FIRE SAFETY ORDINANCE, CHAPTER 94
SPRINGFIELD BUILDING ORDINANCE, CHAPTER 170
SPRINGFIELD PLUMBING ORDINANCE, CHAPTER 171
SPRINGFIELD ELECTRICAL ORDINANCE, CHAPTER 172
SPRINGFIELD MECHANICAL ORDINANCE, CHAPTER 173
USE GROUP CLASSIFICATION B
CONSTRUCTION CLASSIFICATION 2A
ABBREVIATIONS
A.D.A.
A.F.F.
ALUM.
CLG.
CONC.
CONT.
C.T.
CPT.
DIA.
DN.
EA.
EL.
ELEC.
FL.
FIN.
GA.
G.B. or GYP. BD.
HT.
MANUF.
MAT'L
AT
AMERICANS WITH DISABILITIES ACT
ABOVE FINISH FLOOR
ALUMINUM
CEILING
CONCRETE
CONTINUOUS
CERAMIC TILE
CARPET
DIAMETER
DOWN
EACH
ELEVATION
ELECTRICAL
FLOOR
FINISH
GALVANIZED
GYPSUM BOARD
HEIGHT
MANUFACTURER or MANUFACTURED
MATERIAL
MAX.
MIN.
N.I.C.
O.C.
PLAM.
PT.
PREFIN.
REQ'D.
S.A.T.
S.F.
SHT.
S.S.
STL.
SUSP.
TEMP.
TYP.
U.N.O.
V.
V.A.T.
VERT.
WD.
MAXIMUM
MINIMUM or MINUTE
NOT-IN-CONTRACT
ON-CENTER
PLASTIC LAMINATE
PAINT
PREFINISHED
REQUIRED
SUSPENDED ACOUSTICAL TILE
SQUARE FEET
SHEET
STAINLESS STEEL
STEEL
SUSPENDED
TEMPERED
TYPICAL
UNLESS NOTED OTHERWISE
VOLT
VINYL FACED ACOUSTICAL TILE
VERTICAL
WOOD
G-1
1630 South Sixth Street Springfield, Illinois 62703 Phone 217.789.7011
© Evan Lloyd Associates, Inc.
TC
S
E
CRADE
ION
AT
TIMOTHY
B. SMITH
L
SNE
IC
S
TIH
F
TE
O ILIL
001-017445
Date:
Drawn By:
Revised:
Revised:
Project No.
SHEET
OF SHEETS.
Date Signed:
Expiration Date:
S ou th Six th St re et
Sp rin gfi eld
, Il lin ois
Ph on e
7.7
.70
FI
RE
P
UM
P
SY
ST
EM
R
EP
LA
CE
ME
NT
ST
RA
TT
ON
B
UI
LD
IN
G
1 S
OU
TH
S
PR
IN
G
ST
RE
ET
SP
RI
NG
FI
EL
D, IL
LIN
OI
S
AutoCAD SHX Text
BRH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text 25-081
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text
NOV. 30, 2026
FP-1PARTIAL BASEMENT SPRINKLER PLAN
NORTH
© Evan Lloyd Associates, Inc.
TC
S
E
CRADE
ION
AT
TIMOTHY
B. SMITH
L
SNE
IC
S
TIH
F
TE
O ILIL
001-017445
Date:
Drawn By:
Revised:
Revised:
Project No.
SHEET
OF SHEETS.
Date Signed:
Expiration Date:
S ou th Six th St ree t
Sp rin gfi eld
, Il lin ois
Ph on e
7.7
.70
FI
RE
P
UM
P
SY
ST
EM
R
EP
LA
CE
ME
NT
ST
RA
TT
ON
B
UI
LD
IN
G
1 S
OU
TH
S
PR
IN
G
ST
RE
ET
SP
RI
NG
FI
EL
D, IL
LIN
OI
S
KEY PLAN
NORTHPARTIAL BASEMENT SPRINKLER DEMOLITION PLAN
NORTH
PLUMBING SYMBOLS LISTINDEX OF DRAWINGS
FP-1 INDEX OF DRAWINGS, PARTIAL BASEMENT
PARTIAL BASEMENT SPRINKLER DEMOLITION PLAN,
PARTIAL BASEMENT SPRINKLER PLAN
FP-2 FIRE SUPPRESSION SYSTEM SPECIFICATIONS
P-1 PARTIAL BASEMENT PLUMBING DEMOLITION PLAN,
PARTIAL BASEMENT PLUMBING PLAN
P-2 PLUMBING SPECIFICATIONS
E-1 PARTIAL ELECTRICAL DEMOLITION PLAN, PARTIAL
ELECTRICAL PLAN
AutoCAD SHX Text
BRH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: " = 14" = 1'-0"
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text 25-081
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text
NOV. 30, 2026
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
SCALE: " = 14" = 1'-0"
AutoCAD SHX Text
EXISTING FDC TO REMAIN.
AutoCAD SHX Text
DISCONNECT AND REMOVE THE EXISTING FIRE PUMP & FIRE PUMP CONTROLLER.
AutoCAD SHX Text
INDICATES NEW CONNECTION
AutoCAD SHX Text
NEW SPRINKLER PIPING
AutoCAD SHX Text
NOTE: ALL THE EXISTING GAUGES SHALL BE REPLACED WITH SAME OR APPROVED EQUAL
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
EXISTING PLUMBING
AutoCAD SHX Text
DEPARTMENT
AutoCAD SHX Text
EXISTING STORAGE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
THE EXISTING CHECK VALVE, SHUT-OFF VALVE AND PIPING SHALL REMAIN.
AutoCAD SHX Text
REMOVE JOCKEY PUMP
AutoCAD SHX Text
EXISTING CHECK VALVE SHALL REMAIN (TYPICAL).
AutoCAD SHX Text
INDICATES NEW FLANGE FITTING
AutoCAD SHX Text
EXISTING SPRINKLER PIPING
AutoCAD SHX Text
EF
AutoCAD SHX Text F
AutoCAD SHX Text
EF
AutoCAD SHX Text
EF
AutoCAD SHX Text
EF
AutoCAD SHX Text
EF
AutoCAD SHX Text
EF
AutoCAD SHX Text
EF
AutoCAD SHX Text PROVIDE A NEW FIRE PUMP (HORIZONTAL SPLIT CASE SERIES) "AURORA PUMP MODEL NO. 6-81-15E", AURORA PUMP MODEL NO. 6-81-15E", PUMP MODEL NO. 6-81-15E", OR PRE-APPROVED EQUAL. 1500 GPM FLOW AT 90.0 PSI, RIGHT HAND ROTATION COMPLETE W/ A 100HP-480V-3PH-60HZ MOTOR. PROVIDE NEW CONCRETE BASE OR REUSE EXISTING AS NEEDED.
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER TORNATECH MODEL GPS MODEL GPS OR PRE-APPROVED EQUAL.
AutoCAD SHX Text
10" RPZ BY PLUMBING CONTRACTOR.
AutoCAD SHX Text
REMOVE THE EXISTING FIRE PUMP AND PORTION OF CONCRETE BASE. (AS REQUIRED).
AutoCAD SHX Text
FIRE PROTECTION CONTRACTOR STARTS HERE.
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
EXISTING PLUMBING
AutoCAD SHX Text
DEPARTMENT
AutoCAD SHX Text
EXISTING STORAGE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
EF
AutoCAD SHX Text
EF
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
REMOVE PORTIONS THE EXISTING PIPING FOR THE NEW GATE & CHECK VALVES.
AutoCAD SHX Text
EXISTING (6) TESTING OUTLETS TO REMAIN.
AutoCAD SHX Text
THE (6) EXISTING TESTING VALVES SHALL REMAIN.
AutoCAD SHX Text
PROVIDE A NEW GATE VALVE IN THE VERTICAL POSITION.
AutoCAD SHX Text
REMOVE VALVES AND PORTIONS OF THE EXISTING PIPING AS SHOWN.
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
STORAGE
INSTALL 2HP JOCKEY PUMP WITH NEW PIPE AND FITTINGS
FP-2
© Evan Lloyd Associates, Inc.
TC
S
E
CRADE
IO
N
AT
TIMOTHY
B. SMITH
L
SN
E
IC
S
TIH
F
TE
O ILIL
001-017445
Date:
Drawn By:
Revised:
Revised:
Project No.
SHEET
OF SHEETS.
Date Signed:
Expiration Date:
S ou th Six th St ree t
Sp rin gfi eld
, Il lin ois
Ph on e
7.7
.70
FI
RE
P
UM
P
SY
ST
EM
R
EP
LA
CE
ME
NT
ST
RA
TT
ON
B
UI
LD
IN
G
1 S
OU
TH
S
PR
IN
G
ST
RE
ET
SP
RI
NG
FI
EL
D, IL
LIN
OI
S
SPECIFICATIONS
AutoCAD SHX Text
BRH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text 25-081
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text
NOV. 30, 2026
AutoCAD SHX Text DIVISION 21 - FIRE SUPPRESSION Section 21 13 00 - Fire Suppression Sprinkler System PART 1 - GENERAL GENERAL 1.1 WORK INCLUDES WORK INCLUDES A. Base Bid: Base Bid: 1. Contractor provide: Contractor provide: a. Valves. Valves. b. Piping and fittings. Piping and fittings. c. Fire Pump. Fire Pump. d. Fire Pump Controller. Fire Pump Controller. e. Demolition of the existing as shown. Demolition of the existing as shown. 1.2 RELATED WORK RELATED WORK A. Specified elsewhere: Specified elsewhere: 1. Section 22 05 00 - Basic Plumbing Materials and Methods. Section 22 05 00 - Basic Plumbing Materials and Methods. 2. Section 22 05 23 - General duty valves for plumbing piping. Section 22 05 23 - General duty valves for plumbing piping. 1.3 REFERENCES REFERENCES A. ANSI/ASME B16.1 - Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 ANSI/ASME B16.1 - Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 B16.1 - Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 B16.1 - Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 - Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 - Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 Cast Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 Iron Pipe Flanges and Flanged Fittings, Class 25, 125, 250 Pipe Flanges and Flanged Fittings, Class 25, 125, 250 Pipe Flanges and Flanged Fittings, Class 25, 125, 250 Flanges and Flanged Fittings, Class 25, 125, 250 Flanges and Flanged Fittings, Class 25, 125, 250 and Flanged Fittings, Class 25, 125, 250 and Flanged Fittings, Class 25, 125, 250 Flanged Fittings, Class 25, 125, 250 Flanged Fittings, Class 25, 125, 250 Fittings, Class 25, 125, 250 Fittings, Class 25, 125, 250 Class 25, 125, 250 Class 25, 125, 250 25, 125, 250 25, 125, 250 125, 250 125, 250 250 250 and 800. B. ANSI/ASME B16.5 - Pipe Flanges and flanged fittings. ANSI/ASME B16.5 - Pipe Flanges and flanged fittings. 1.4 QUALITY ASSURANCE QUALITY ASSURANCE A. Regulatory Requirements: Regulatory Requirements: 1. Factory Mutual, FM: Factory Mutual, FM: a. Comply with FM approval guide. Comply with FM approval guide. b. Products labeled by FM. Products labeled by FM. 2. National Fire Protection Association, NFPA: National Fire Protection Association, NFPA: a. NFPA 13: Installation of Sprinkler Systems. NFPA 13: Installation of Sprinkler Systems. 3. Underwriter's Laboratories, UL: Underwriter's Laboratories, UL: a. Products listed and labeled by UL. Products listed and labeled by UL. b. UL 199: Automatic Sprinklers for fire protection service. UL 199: Automatic Sprinklers for fire protection service. c. UL 203: Pipe Hanger Equipment for fire protection service. UL 203: Pipe Hanger Equipment for fire protection service. d. UL 864: Control units for fire protection signaling service. UL 864: Control units for fire protection signaling service. 4. Local Fire Department/Illinois State Fire Marshal Regulations: Local Fire Department/Illinois State Fire Marshal Regulations: a. Comply with governing regulations for fire sprinkler systems. Comply with governing regulations for fire sprinkler systems. b. Comply with local fire department/marshal regulations for sizes, threading Comply with local fire department/marshal regulations for sizes, threading with local fire department/marshal regulations for sizes, threading with local fire department/marshal regulations for sizes, threading local fire department/marshal regulations for sizes, threading local fire department/marshal regulations for sizes, threading fire department/marshal regulations for sizes, threading fire department/marshal regulations for sizes, threading department/marshal regulations for sizes, threading department/marshal regulations for sizes, threading regulations for sizes, threading regulations for sizes, threading for sizes, threading for sizes, threading sizes, threading sizes, threading threading threading and arrangement of connections for fire department equipment to standpipe arrangement of connections for fire department equipment to standpipe arrangement of connections for fire department equipment to standpipe of connections for fire department equipment to standpipe of connections for fire department equipment to standpipe connections for fire department equipment to standpipe connections for fire department equipment to standpipe for fire department equipment to standpipe for fire department equipment to standpipe fire department equipment to standpipe fire department equipment to standpipe department equipment to standpipe department equipment to standpipe equipment to standpipe equipment to standpipe to standpipe to standpipe standpipe standpipe systems. 5. State of Illinois, Part 175 "Efficient and Adequate Standards for Building State of Illinois, Part 175 "Efficient and Adequate Standards for Building of Illinois, Part 175 "Efficient and Adequate Standards for Building of Illinois, Part 175 "Efficient and Adequate Standards for Building Illinois, Part 175 "Efficient and Adequate Standards for Building Illinois, Part 175 "Efficient and Adequate Standards for Building Part 175 "Efficient and Adequate Standards for Building Part 175 "Efficient and Adequate Standards for Building 175 "Efficient and Adequate Standards for Building 175 "Efficient and Adequate Standards for Building "Efficient and Adequate Standards for Building "Efficient and Adequate Standards for Building and Adequate Standards for Building and Adequate Standards for Building Adequate Standards for Building Adequate Standards for Building Standards for Building Standards for Building for Building for Building Building Building Specifications for the Construction of Schools", February 1989. 6. Employ certified welders and conform to ANSI/ASME Code. Employ certified welders and conform to ANSI/ASME Code. 7. 2014 Illinois State Plumbing Code. 2014 Illinois State Plumbing Code. 8. 2023 National Electrical Code. 2023 National Electrical Code. 1.5 SUBMITTALS SUBMITTALS A. Certificate of Installation: 1. Submit certificate from installer upon completion of fire sprinkler piping work stating that work has been installed, completed and tested in accordance with NFPA No. 13, that there are no defects in system and it is operations. B. Product data on all equipment. Product data on all equipment. C. Provide valve data and ratings. Provide valve data and ratings. 1.6 SYSTEM DESCRIPTION SYSTEM DESCRIPTION A. Interface system with building fire alarm system. Interface system with building fire alarm system. B. Provide system to NFPA 13 light hazard and ordinary hazard, Group 1 occupancy Provide system to NFPA 13 light hazard and ordinary hazard, Group 1 occupancy system to NFPA 13 light hazard and ordinary hazard, Group 1 occupancy system to NFPA 13 light hazard and ordinary hazard, Group 1 occupancy to NFPA 13 light hazard and ordinary hazard, Group 1 occupancy to NFPA 13 light hazard and ordinary hazard, Group 1 occupancy NFPA 13 light hazard and ordinary hazard, Group 1 occupancy NFPA 13 light hazard and ordinary hazard, Group 1 occupancy 13 light hazard and ordinary hazard, Group 1 occupancy 13 light hazard and ordinary hazard, Group 1 occupancy light hazard and ordinary hazard, Group 1 occupancy light hazard and ordinary hazard, Group 1 occupancy hazard and ordinary hazard, Group 1 occupancy hazard and ordinary hazard, Group 1 occupancy and ordinary hazard, Group 1 occupancy and ordinary hazard, Group 1 occupancy ordinary hazard, Group 1 occupancy ordinary hazard, Group 1 occupancy hazard, Group 1 occupancy hazard, Group 1 occupancy Group 1 occupancy Group 1 occupancy 1 occupancy 1 occupancy occupancy occupancy requirements to conform to occupancy rating of space to be served. PART 2 - PRODUCTS PRODUCTS 2.1 PIPE AND TUBE - ABOVE GROUND PIPE AND TUBE - ABOVE GROUND A. Steel Pipe: ASTM A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; Steel Pipe: ASTM A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; Pipe: ASTM A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; Pipe: ASTM A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; ASTM A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; ASTM A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; ASTM A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; A53; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; ASTM A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; A795; ANSI/ASTM A135; ANSI/ASME B36.10; black; ANSI/ASTM A135; ANSI/ASME B36.10; black; ANSI/ASTM A135; ANSI/ASME B36.10; black; A135; ANSI/ASME B36.10; black; A135; ANSI/ASME B36.10; black; ANSI/ASME B36.10; black; ANSI/ASME B36.10; black; B36.10; black; B36.10; black; black; black; Schedule 40 or light wall pipe in accord with NFPA requirements. B. Iron Pipe: ANSI/AWWA C151, ductile iron. Iron Pipe: ANSI/AWWA C151, ductile iron. 2.2 PIPE FITTINGS PIPE FITTINGS A. Steel Fittings: ANSI/ASME B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, Steel Fittings: ANSI/ASME B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, Fittings: ANSI/ASME B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, Fittings: ANSI/ASME B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, ANSI/ASME B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, ANSI/ASME B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, ANSI/ASME B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, B16.9, wrought steel, buttwelded, ANSI/ASME B16.25, wrought steel, buttwelded, ANSI/ASME B16.25, wrought steel, buttwelded, ANSI/ASME B16.25, steel, buttwelded, ANSI/ASME B16.25, steel, buttwelded, ANSI/ASME B16.25, buttwelded, ANSI/ASME B16.25, buttwelded, ANSI/ASME B16.25, ANSI/ASME B16.25, ANSI/ASME B16.25, B16.25, B16.25, buttweld ends, ASTM A234, wrought carbon steel and alloy steel, ANSI/ASME B16.5, ends, ASTM A234, wrought carbon steel and alloy steel, ANSI/ASME B16.5, ends, ASTM A234, wrought carbon steel and alloy steel, ANSI/ASME B16.5, ASTM A234, wrought carbon steel and alloy steel, ANSI/ASME B16.5, ASTM A234, wrought carbon steel and alloy steel, ANSI/ASME B16.5, A234, wrought carbon steel and alloy steel, ANSI/ASME B16.5, A234, wrought carbon steel and alloy steel, ANSI/ASME B16.5, wrought carbon steel and alloy steel, ANSI/ASME B16.5, wrought carbon steel and alloy steel, ANSI/ASME B16.5, carbon steel and alloy steel, ANSI/ASME B16.5, carbon steel and alloy steel, ANSI/ASME B16.5, steel and alloy steel, ANSI/ASME B16.5, steel and alloy steel, ANSI/ASME B16.5, and alloy steel, ANSI/ASME B16.5, and alloy steel, ANSI/ASME B16.5, alloy steel, ANSI/ASME B16.5, alloy steel, ANSI/ASME B16.5, steel, ANSI/ASME B16.5, steel, ANSI/ASME B16.5, ANSI/ASME B16.5, ANSI/ASME B16.5, B16.5, B16.5, steel flanges and fittings, ANSI/ASME B16.11, forged steel socket welded and threaded. B. Cast Iron Fittings: ANSI/ASME B16.1, flanges and fittings, B16.4, screwed fittings. Cast Iron Fittings: ANSI/ASME B16.1, flanges and fittings, B16.4, screwed fittings. C. Malleable Iron Fittings: ANSI/ASME B16.3, screwed type, ANSI/ASTM A47. Malleable Iron Fittings: ANSI/ASME B16.3, screwed type, ANSI/ASTM A47. D. Ductile Iron Fittings: ANSI/AWWA C110. Ductile Iron Fittings: ANSI/AWWA C110. 2.3 JOINT MATERIALS JOINT MATERIALS A. Threaded Joint Compound: Non-toxic joint compound. Threaded Joint Compound: Non-toxic joint compound. 2.4 UNIONS, FLANGES AND COUPLINGS UNIONS, FLANGES AND COUPLINGS A. Unions: 150 psi malleable iron for threaded piping. Unions: 150 psi malleable iron for threaded piping. B. Flanges: 150 psi forged steel slip-on flanges for ferrous piping. Flanges: 150 psi forged steel slip-on flanges for ferrous piping. 150 psi forged steel slip-on flanges for ferrous piping. C. Mechanical Grooved Couplings: Malleable iron housing clamps shall engage and lock: Mechanical Grooved Couplings: Malleable iron housing clamps shall engage and lock: Grooved Couplings: Malleable iron housing clamps shall engage and lock: Grooved Couplings: Malleable iron housing clamps shall engage and lock: Couplings: Malleable iron housing clamps shall engage and lock: Couplings: Malleable iron housing clamps shall engage and lock: Malleable iron housing clamps shall engage and lock: Malleable iron housing clamps shall engage and lock: Malleable iron housing clamps shall engage and lock: iron housing clamps shall engage and lock: iron housing clamps shall engage and lock: housing clamps shall engage and lock: housing clamps shall engage and lock: clamps shall engage and lock: clamps shall engage and lock: shall engage and lock: shall engage and lock: engage and lock: engage and lock: and lock: and lock: lock: lock: be designed to permit some angular deflection, contraction, and expansion: "C" designed to permit some angular deflection, contraction, and expansion: "C" designed to permit some angular deflection, contraction, and expansion: "C" to permit some angular deflection, contraction, and expansion: "C" to permit some angular deflection, contraction, and expansion: "C" permit some angular deflection, contraction, and expansion: "C" permit some angular deflection, contraction, and expansion: "C" some angular deflection, contraction, and expansion: "C" some angular deflection, contraction, and expansion: "C" angular deflection, contraction, and expansion: "C" angular deflection, contraction, and expansion: "C" deflection, contraction, and expansion: "C" deflection, contraction, and expansion: "C" contraction, and expansion: "C" contraction, and expansion: "C" and expansion: "C" and expansion: "C" expansion: "C" expansion: "C" "C" "C" "C" shaped composition sealing gasket, steel bolts, nuts and washers: galvanized composition sealing gasket, steel bolts, nuts and washers: galvanized composition sealing gasket, steel bolts, nuts and washers: galvanized sealing gasket, steel bolts, nuts and washers: galvanized sealing gasket, steel bolts, nuts and washers: galvanized gasket, steel bolts, nuts and washers: galvanized gasket, steel bolts, nuts and washers: galvanized steel bolts, nuts and washers: galvanized steel bolts, nuts and washers: galvanized bolts, nuts and washers: galvanized bolts, nuts and washers: galvanized nuts and washers: galvanized nuts and washers: galvanized and washers: galvanized and washers: galvanized washers: galvanized washers: galvanized galvanized galvanized galvanized couplings for galvanized pipe.
2.5 ACCEPTABLE MANUFACTURERS - VALVES ACCEPTABLE MANUFACTURERS - VALVES A. American Flow Controller American Flow Controller B. Kennedy Valve, Div. ITT Grinnell Kennedy Valve, Div. ITT Grinnell C. Mueller Mueller D. Approved equal Approved equal 2.6 GATE VALVES GATE VALVES A. Bronze, rising stem, (inside) screw, solid wedge. Bronze, rising stem, (inside) screw, solid wedge. B. Iron body, bronze trim, rising stem, solid wedge. Iron body, bronze trim, rising stem, solid wedge. 2.7 DRAIN VALVES DRAIN VALVES A. Bronze compression stop with nipple and cap or hose thread. Bronze compression stop with nipple and cap or hose thread. 2.8 HANGERS HANGERS A. In accord with NFPA 13. In accord with NFPA 13. PART 3 - EXECUTION EXECUTION 3.1 PREPARATION PREPARATION A. Ream pipe and tube ends to full inside diameter. Ream pipe and tube ends to full inside diameter. B. Remove burrs and bevel plain end ferrous pipe. Remove burrs and bevel plain end ferrous pipe. C. Remove scale and foreign material, inside and outside, before assembly. Remove scale and foreign material, inside and outside, before assembly. 3.2 INSTALLATION - PIPE INSTALLATION - PIPE A. Screw joint steel piping up to and including 1-1/2 inch diameter. Screw or weld 2 Screw joint steel piping up to and including 1-1/2 inch diameter. Screw or weld 2 joint steel piping up to and including 1-1/2 inch diameter. Screw or weld 2 joint steel piping up to and including 1-1/2 inch diameter. Screw or weld 2 steel piping up to and including 1-1/2 inch diameter. Screw or weld 2 steel piping up to and including 1-1/2 inch diameter. Screw or weld 2 piping up to and including 1-1/2 inch diameter. Screw or weld 2 piping up to and including 1-1/2 inch diameter. Screw or weld 2 up to and including 1-1/2 inch diameter. Screw or weld 2 up to and including 1-1/2 inch diameter. Screw or weld 2 to and including 1-1/2 inch diameter. Screw or weld 2 to and including 1-1/2 inch diameter. Screw or weld 2 and including 1-1/2 inch diameter. Screw or weld 2 and including 1-1/2 inch diameter. Screw or weld 2 including 1-1/2 inch diameter. Screw or weld 2 including 1-1/2 inch diameter. Screw or weld 2 1-1/2 inch diameter. Screw or weld 2 1-1/2 inch diameter. Screw or weld 2 inch diameter. Screw or weld 2 inch diameter. Screw or weld 2 diameter. Screw or weld 2 diameter. Screw or weld 2 Screw or weld 2 Screw or weld 2 Screw or weld 2 or weld 2 or weld 2 weld 2 weld 2 2 2 inch diameter piping. Weld piping 2-1/2 inch diameter and larger, including branch diameter piping. Weld piping 2-1/2 inch diameter and larger, including branch diameter piping. Weld piping 2-1/2 inch diameter and larger, including branch piping. Weld piping 2-1/2 inch diameter and larger, including branch piping. Weld piping 2-1/2 inch diameter and larger, including branch Weld piping 2-1/2 inch diameter and larger, including branch Weld piping 2-1/2 inch diameter and larger, including branch Weld piping 2-1/2 inch diameter and larger, including branch piping 2-1/2 inch diameter and larger, including branch piping 2-1/2 inch diameter and larger, including branch 2-1/2 inch diameter and larger, including branch 2-1/2 inch diameter and larger, including branch inch diameter and larger, including branch inch diameter and larger, including branch diameter and larger, including branch diameter and larger, including branch and larger, including branch and larger, including branch larger, including branch larger, including branch including branch including branch branch branch connections. B. Mechanical grooved joints may be used instead of threaded or welded joints. Mechanical grooved joints may be used instead of threaded or welded joints. C. Die cut screw joints with full cut standard taper pipe threads with non-toxic joint Die cut screw joints with full cut standard taper pipe threads with non-toxic joint cut screw joints with full cut standard taper pipe threads with non-toxic joint cut screw joints with full cut standard taper pipe threads with non-toxic joint screw joints with full cut standard taper pipe threads with non-toxic joint screw joints with full cut standard taper pipe threads with non-toxic joint joints with full cut standard taper pipe threads with non-toxic joint joints with full cut standard taper pipe threads with non-toxic joint with full cut standard taper pipe threads with non-toxic joint with full cut standard taper pipe threads with non-toxic joint full cut standard taper pipe threads with non-toxic joint full cut standard taper pipe threads with non-toxic joint cut standard taper pipe threads with non-toxic joint cut standard taper pipe threads with non-toxic joint standard taper pipe threads with non-toxic joint standard taper pipe threads with non-toxic joint taper pipe threads with non-toxic joint taper pipe threads with non-toxic joint pipe threads with non-toxic joint pipe threads with non-toxic joint threads with non-toxic joint threads with non-toxic joint with non-toxic joint with non-toxic joint non-toxic joint non-toxic joint joint joint compound applied to male threads only. D. Coat threaded ends with pipe lubricant compound. Coat threaded ends with pipe lubricant compound. E. In steel piping, main sized saddle branch connections or direct connection of branch In steel piping, main sized saddle branch connections or direct connection of branch steel piping, main sized saddle branch connections or direct connection of branch steel piping, main sized saddle branch connections or direct connection of branch piping, main sized saddle branch connections or direct connection of branch piping, main sized saddle branch connections or direct connection of branch main sized saddle branch connections or direct connection of branch main sized saddle branch connections or direct connection of branch sized saddle branch connections or direct connection of branch sized saddle branch connections or direct connection of branch saddle branch connections or direct connection of branch saddle branch connections or direct connection of branch branch connections or direct connection of branch branch connections or direct connection of branch connections or direct connection of branch connections or direct connection of branch or direct connection of branch or direct connection of branch direct connection of branch direct connection of branch connection of branch connection of branch of branch of branch branch branch lines to mains is permitted when main is one pipe size larger than the branch for up to mains is permitted when main is one pipe size larger than the branch for up to mains is permitted when main is one pipe size larger than the branch for up mains is permitted when main is one pipe size larger than the branch for up mains is permitted when main is one pipe size larger than the branch for up is permitted when main is one pipe size larger than the branch for up is permitted when main is one pipe size larger than the branch for up permitted when main is one pipe size larger than the branch for up permitted when main is one pipe size larger than the branch for up when main is one pipe size larger than the branch for up when main is one pipe size larger than the branch for up main is one pipe size larger than the branch for up main is one pipe size larger than the branch for up is one pipe size larger than the branch for up is one pipe size larger than the branch for up one pipe size larger than the branch for up one pipe size larger than the branch for up pipe size larger than the branch for up pipe size larger than the branch for up size larger than the branch for up size larger than the branch for up larger than the branch for up larger than the branch for up than the branch for up than the branch for up the branch for up the branch for up branch for up branch for up for up for up up up to 6 in. mains and when main is two pipe sized larger than branch for 8 in. and 6 in. mains and when main is two pipe sized larger than branch for 8 in. and 6 in. mains and when main is two pipe sized larger than branch for 8 in. and in. mains and when main is two pipe sized larger than branch for 8 in. and in. mains and when main is two pipe sized larger than branch for 8 in. and mains and when main is two pipe sized larger than branch for 8 in. and mains and when main is two pipe sized larger than branch for 8 in. and and when main is two pipe sized larger than branch for 8 in. and and when main is two pipe sized larger than branch for 8 in. and when main is two pipe sized larger than branch for 8 in. and when main is two pipe sized larger than branch for 8 in. and main is two pipe sized larger than branch for 8 in. and main is two pipe sized larger than branch for 8 in. and is two pipe sized larger than branch for 8 in. and is two pipe sized larger than branch for 8 in. and two pipe sized larger than branch for 8 in. and two pipe sized larger than branch for 8 in. and pipe sized larger than branch for 8 in. and pipe sized larger than branch for 8 in. and sized larger than branch for 8 in. and sized larger than branch for 8 in. and larger than branch for 8 in. and larger than branch for 8 in. and than branch for 8 in. and than branch for 8 in. and branch for 8 in. and branch for 8 in. and for 8 in. and for 8 in. and 8 in. and 8 in. and in. and in. and and and larger mains. Do no project branch pipes inside the main pipe. F. Install piping in accordance with NFPA 13 for sprinkler systems. Install piping in accordance with NFPA 13 for sprinkler systems. G. Reductions in pipe size shall be made only by means of reducing fittings. Bushings Reductions in pipe size shall be made only by means of reducing fittings. Bushings in pipe size shall be made only by means of reducing fittings. Bushings in pipe size shall be made only by means of reducing fittings. Bushings pipe size shall be made only by means of reducing fittings. Bushings pipe size shall be made only by means of reducing fittings. Bushings size shall be made only by means of reducing fittings. Bushings size shall be made only by means of reducing fittings. Bushings shall be made only by means of reducing fittings. Bushings shall be made only by means of reducing fittings. Bushings be made only by means of reducing fittings. Bushings be made only by means of reducing fittings. Bushings made only by means of reducing fittings. Bushings made only by means of reducing fittings. Bushings only by means of reducing fittings. Bushings only by means of reducing fittings. Bushings by means of reducing fittings. Bushings by means of reducing fittings. Bushings means of reducing fittings. Bushings means of reducing fittings. Bushings of reducing fittings. Bushings of reducing fittings. Bushings reducing fittings. Bushings reducing fittings. Bushings fittings. Bushings fittings. Bushings Bushings Bushings Bushings shall not be used. H. Connections to main shall be made only by means of a flanged fittings. Connections to main shall be made only by means of a flanged fittings. I. Unions two inches and smaller shall be screwed, malleable iron, 200 lbs. class with Unions two inches and smaller shall be screwed, malleable iron, 200 lbs. class with two inches and smaller shall be screwed, malleable iron, 200 lbs. class with two inches and smaller shall be screwed, malleable iron, 200 lbs. class with inches and smaller shall be screwed, malleable iron, 200 lbs. class with inches and smaller shall be screwed, malleable iron, 200 lbs. class with and smaller shall be screwed, malleable iron, 200 lbs. class with and smaller shall be screwed, malleable iron, 200 lbs. class with smaller shall be screwed, malleable iron, 200 lbs. class with smaller shall be screwed, malleable iron, 200 lbs. class with shall be screwed, malleable iron, 200 lbs. class with shall be screwed, malleable iron, 200 lbs. class with be screwed, malleable iron, 200 lbs. class with be screwed, malleable iron, 200 lbs. class with screwed, malleable iron, 200 lbs. class with screwed, malleable iron, 200 lbs. class with malleable iron, 200 lbs. class with malleable iron, 200 lbs. class with iron, 200 lbs. class with iron, 200 lbs. class with 200 lbs. class with 200 lbs. class with lbs. class with lbs. class with class with class with with with ground joint brass to iron seats. Unions 2 1/2 in. and larger shall be flanged. 3.3 INSTALLATION - VALVES INSTALLATION - VALVES A. Install valves with stems upright or horizontal, not inverted. Install valves with stems upright or horizontal, not inverted. B. Provide gate valves for shut-off or isolating service. Provide gate valves for shut-off or isolating service. 3.4 PREPARATION PREPARATION A. Coordinate with other work, including piping, to interface components of fire sprinkler Coordinate with other work, including piping, to interface components of fire sprinkler with other work, including piping, to interface components of fire sprinkler with other work, including piping, to interface components of fire sprinkler other work, including piping, to interface components of fire sprinkler other work, including piping, to interface components of fire sprinkler work, including piping, to interface components of fire sprinkler work, including piping, to interface components of fire sprinkler including piping, to interface components of fire sprinkler including piping, to interface components of fire sprinkler piping, to interface components of fire sprinkler piping, to interface components of fire sprinkler to interface components of fire sprinkler to interface components of fire sprinkler interface components of fire sprinkler interface components of fire sprinkler components of fire sprinkler components of fire sprinkler of fire sprinkler of fire sprinkler fire sprinkler fire sprinkler sprinkler sprinkler piping with other work. 3.5 SPRINKLER EQUIPMENT INSTALLATION SPRINKLER EQUIPMENT INSTALLATION A. On sprinkler system take-off from water supply, provide approved backflow valve On sprinkler system take-off from water supply, provide approved backflow valve sprinkler system take-off from water supply, provide approved backflow valve sprinkler system take-off from water supply, provide approved backflow valve system take-off from water supply, provide approved backflow valve system take-off from water supply, provide approved backflow valve take-off from water supply, provide approved backflow valve take-off from water supply, provide approved backflow valve from water supply, provide approved backflow valve from water supply, provide approved backflow valve water supply, provide approved backflow valve water supply, provide approved backflow valve supply, provide approved backflow valve supply, provide approved backflow valve provide approved backflow valve provide approved backflow valve approved backflow valve approved backflow valve backflow valve backflow valve valve valve assembly with gate valves on each side. 3.6 ADJUSTING AND CLEANING ADJUSTING AND CLEANING A. Sprinkler Piping Flushing: Sprinkler Piping Flushing: 1. Prior to connecting sprinkler risers for flushing, flush water feed mains, lead-in Prior to connecting sprinkler risers for flushing, flush water feed mains, lead-in to connecting sprinkler risers for flushing, flush water feed mains, lead-in to connecting sprinkler risers for flushing, flush water feed mains, lead-in connecting sprinkler risers for flushing, flush water feed mains, lead-in connecting sprinkler risers for flushing, flush water feed mains, lead-in sprinkler risers for flushing, flush water feed mains, lead-in sprinkler risers for flushing, flush water feed mains, lead-in risers for flushing, flush water feed mains, lead-in risers for flushing, flush water feed mains, lead-in for flushing, flush water feed mains, lead-in for flushing, flush water feed mains, lead-in flushing, flush water feed mains, lead-in flushing, flush water feed mains, lead-in flush water feed mains, lead-in flush water feed mains, lead-in water feed mains, lead-in water feed mains, lead-in feed mains, lead-in feed mains, lead-in mains, lead-in mains, lead-in lead-in lead-in connections and control portions of sprinkler piping. 2. After fire sprinkler piping installation is completed and before piping is placed in After fire sprinkler piping installation is completed and before piping is placed in fire sprinkler piping installation is completed and before piping is placed in fire sprinkler piping installation is completed and before piping is placed in sprinkler piping installation is completed and before piping is placed in sprinkler piping installation is completed and before piping is placed in piping installation is completed and before piping is placed in piping installation is completed and before piping is placed in installation is completed and before piping is placed in installation is completed and before piping is placed in is completed and before piping is placed in is completed and before piping is placed in completed and before piping is placed in completed and before piping is placed in and before piping is placed in and before piping is placed in before piping is placed in before piping is placed in piping is placed in piping is placed in is placed in is placed in placed in placed in in in service, flush entire sprinkler system to remove foreign substances, under flush entire sprinkler system to remove foreign substances, under flush entire sprinkler system to remove foreign substances, under entire sprinkler system to remove foreign substances, under entire sprinkler system to remove foreign substances, under sprinkler system to remove foreign substances, under sprinkler system to remove foreign substances, under system to remove foreign substances, under system to remove foreign substances, under to remove foreign substances, under to remove foreign substances, under remove foreign substances, under remove foreign substances, under foreign substances, under foreign substances, under substances, under substances, under under under pressure as specified by NFPA No. 13. 3. Continue flushing until water is clear, and verify that debris has not clogged Continue flushing until water is clear, and verify that debris has not clogged flushing until water is clear, and verify that debris has not clogged flushing until water is clear, and verify that debris has not clogged until water is clear, and verify that debris has not clogged until water is clear, and verify that debris has not clogged water is clear, and verify that debris has not clogged water is clear, and verify that debris has not clogged is clear, and verify that debris has not clogged is clear, and verify that debris has not clogged clear, and verify that debris has not clogged clear, and verify that debris has not clogged and verify that debris has not clogged and verify that debris has not clogged verify that debris has not clogged verify that debris has not clogged that debris has not clogged that debris has not clogged debris has not clogged debris has not clogged has not clogged has not clogged not clogged not clogged clogged clogged sprinklers. 3.7 FIELD QUALITY CONTROL FIELD QUALITY CONTROL A. Hydrostatic Testing: Hydrostatic Testing: 1. After flushing system, test fire sprinkler piping hydrostatically for period of 2 After flushing system, test fire sprinkler piping hydrostatically for period of 2 flushing system, test fire sprinkler piping hydrostatically for period of 2 flushing system, test fire sprinkler piping hydrostatically for period of 2 system, test fire sprinkler piping hydrostatically for period of 2 system, test fire sprinkler piping hydrostatically for period of 2 test fire sprinkler piping hydrostatically for period of 2 test fire sprinkler piping hydrostatically for period of 2 fire sprinkler piping hydrostatically for period of 2 fire sprinkler piping hydrostatically for period of 2 sprinkler piping hydrostatically for period of 2 sprinkler piping hydrostatically for period of 2 piping hydrostatically for period of 2 piping hydrostatically for period of 2 hydrostatically for period of 2 hydrostatically for period of 2 for period of 2 for period of 2 period of 2 period of 2 of 2 of 2 2 2 hours at minimum 200 psi; or at 50 psi in excess of maximum static pressure at minimum 200 psi; or at 50 psi in excess of maximum static pressure at minimum 200 psi; or at 50 psi in excess of maximum static pressure minimum 200 psi; or at 50 psi in excess of maximum static pressure minimum 200 psi; or at 50 psi in excess of maximum static pressure 200 psi; or at 50 psi in excess of maximum static pressure 200 psi; or at 50 psi in excess of maximum static pressure psi; or at 50 psi in excess of maximum static pressure psi; or at 50 psi in excess of maximum static pressure or at 50 psi in excess of maximum static pressure or at 50 psi in excess of maximum static pressure at 50 psi in excess of maximum static pressure at 50 psi in excess of maximum static pressure 50 psi in excess of maximum static pressure 50 psi in excess of maximum static pressure psi in excess of maximum static pressure psi in excess of maximum static pressure in excess of maximum static pressure in excess of maximum static pressure excess of maximum static pressure excess of maximum static pressure of maximum static pressure of maximum static pressure maximum static pressure maximum static pressure static pressure static pressure pressure pressure when maximum static pressure in excess of 150 psi. 2. Inspect system for leakage at joints. Inspect system for leakage at joints. 3. Measure hydrostatic pressure at low point of each system or zone being tested. Measure hydrostatic pressure at low point of each system or zone being tested. B. Repair or replace piping system to eliminate leakage in accordance with NFPA Repair or replace piping system to eliminate leakage in accordance with NFPA or replace piping system to eliminate leakage in accordance with NFPA or replace piping system to eliminate leakage in accordance with NFPA replace piping system to eliminate leakage in accordance with NFPA replace piping system to eliminate leakage in accordance with NFPA piping system to eliminate leakage in accordance with NFPA piping system to eliminate leakage in accordance with NFPA system to eliminate leakage in accordance with NFPA system to eliminate leakage in accordance with NFPA to eliminate leakage in accordance with NFPA to eliminate leakage in accordance with NFPA eliminate leakage in accordance with NFPA eliminate leakage in accordance with NFPA leakage in accordance with NFPA leakage in accordance with NFPA in accordance with NFPA in accordance with NFPA accordance with NFPA accordance with NFPA with NFPA with NFPA NFPA NFPA standards for "little or no leakage", and retest as specified to demonstrate for "little or no leakage", and retest as specified to demonstrate for "little or no leakage", and retest as specified to demonstrate "little or no leakage", and retest as specified to demonstrate "little or no leakage", and retest as specified to demonstrate or no leakage", and retest as specified to demonstrate or no leakage", and retest as specified to demonstrate no leakage", and retest as specified to demonstrate no leakage", and retest as specified to demonstrate leakage", and retest as specified to demonstrate leakage", and retest as specified to demonstrate and retest as specified to demonstrate and retest as specified to demonstrate retest as specified to demonstrate retest as specified to demonstrate as specified to demonstrate as specified to demonstrate specified to demonstrate specified to demonstrate to demonstrate to demonstrate demonstrate demonstrate compliance. 3.8 ADJUST AND CLEAN ADJUST AND CLEAN A. Clean equipment and completed work: Clean equipment and completed work: 1. After completion of installation thoroughly clean system to remove all paint, After completion of installation thoroughly clean system to remove all paint, completion of installation thoroughly clean system to remove all paint, completion of installation thoroughly clean system to remove all paint, of installation thoroughly clean system to remove all paint, of installation thoroughly clean system to remove all paint, installation thoroughly clean system to remove all paint, installation thoroughly clean system to remove all paint, thoroughly clean system to remove all paint, thoroughly clean system to remove all paint, clean system to remove all paint, clean system to remove all paint, system to remove all paint, system to remove all paint, to remove all paint, to remove all paint, remove all paint, remove all paint, all paint, all paint, paint, paint, grease, oil, dirt, labels and stickers. B. Clean premises.Clean premises.
P-1PARTIAL BASEMENT PLUMBING PLAN
NORTH
© Evan Lloyd Associates, Inc.
TC
S
E
CRADE
IO
N
AT
TIMOTHY
B. SMITH
L
SN
E
IC
S
TIH
F
TE
O ILIL
001-017445
Date:
Drawn By:
Revised:
Revised:
Project No.
SHEET
OF SHEETS.
Date Signed:
Expiration Date:
S ou th Six th St ree t
Sp rin gfi eld
, Il lin ois
Ph on e
7.7
.70
FI
RE
P
UM
P
SY
ST
EM
R
EP
LA
CE
ME
NT
ST
RA
TT
ON
B
UI
LD
IN
G
1 S
OU
TH
S
PR
IN
G
ST
RE
ET
SP
RI
NG
FI
EL
D, IL
LIN
OI
S
KEY PLAN
NORTHPARTIAL BASEMENT PLUMBING DEMOLITION PLAN
NORTH
PLUMBING SYMBOLS LIST
AutoCAD SHX Text
BRH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: " = 14" = 1'-0"
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text 25-081
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text
NOV. 30, 2026
AutoCAD SHX Text
INSTALL A 6" SCH. 40 PVC FUNNEL AND A 4" SCH. 40 PVC PIPE TO THE EXISTING DRAIN.
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
SCALE: " = 14" = 1'-0"
AutoCAD SHX Text
DISCONNECT THE WATER SENSING LINE TO THE FIRE PUMP CONTROLLER.
AutoCAD SHX Text INSTALL A NEW 10" RPZ ASSEMBLY, MANUFACTURED BY "WATTS. MODEL NO. WATTS. MODEL NO. 909-FAE" OR PRE-APPROVED EQUAL. OR PRE-APPROVED EQUAL. PROVIDE PIPE STANDS AS REQUIRED.
AutoCAD SHX Text
INSTALL NEW WALL PIPE SUPPORTS AS NEEDED.
AutoCAD SHX Text
INDICATES NEW CONNECTION.
AutoCAD SHX Text
NEW DOMESTIC COLD WATER PIPING.
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
EXISTING PLUMBING
AutoCAD SHX Text
DEPARTMENT
AutoCAD SHX Text
EXISTING STORAGE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
HW
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text
HW
AutoCAD SHX Text
CW
AutoCAD SHX Text
HW
AutoCAD SHX Text
HW
AutoCAD SHX Text
HW
AutoCAD SHX Text
CW
AutoCAD SHX Text
HW
AutoCAD SHX Text
HW
AutoCAD SHX Text
HW
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text INSTALL (2) NEW READ-O-MATIC WATER METERS, (1) FOR THE DOMESTIC & (1) FOR THE LAWN IRRIGATION SYSTEM. METERS SHALL BE INSTALLED PER THE REQUIREMENTS OF CWLP WATER DEPARTMENT. CONTACT CWLP WATER DEPARTMENT. CONTACT WATER DEPARTMENT. CONTACT MR. MICHAEL JOHNSON @ 217-789-2323 EXT. 1617
AutoCAD SHX Text
CAP
AutoCAD SHX Text
CAP
AutoCAD SHX Text
EXISTING BACK-FLOW PEVENTER AND LAWN IRRIGATION SHALL REMAIN.
AutoCAD SHX Text
REMOVE PORTIONS OF THE PIPING AS SHOWN.
AutoCAD SHX Text
REMOVE PORTIONS OF THE PIPING AS SHOWN.
AutoCAD SHX Text
EXISTING DOMESTIC COLD WATER PIPING.
AutoCAD SHX Text
CW
AutoCAD SHX Text
EXISTING DOMESTIC HOT WATER PIPING.
AutoCAD SHX Text
HW
AutoCAD SHX Text
EF
AutoCAD SHX Text F
AutoCAD SHX Text
EXISTING FLOOR DRAIN
AutoCAD SHX Text
EXISTING FIRE MAIN PIPING.
AutoCAD SHX Text
EF
AutoCAD SHX Text
EXISTING STORAGE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
EXISTING PLUMBING
AutoCAD SHX Text
DEPARTMENT
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
EXISTING HOT AND COLD WATER PIPING SHALL REMAIN.
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER, (SEE SHEET FP-1)
CONTRACTOR TO CONNECT 1/2" COPPER SENSING LINE TO FIRE PUMP ASSEMBLY
P-2 © Evan Lloyd Associates, Inc.
TC
S
E
CRADE
ION
AT
TIMOTHY
B. SMITH
L
SNE
IC
S
TIH
F
TE
O ILIL
001-017445
Date:
Drawn By:
Revised:
Revised:
Project No.
SHEET
OF SHEETS.
Date Signed:
Expiration Date:
S ou th Six th St ree t
Sp rin gfi eld
, Il lin ois
Ph on e
7.7
.70
FI
RE
P
UM
P
SY
ST
EM
R
EP
LA
CE
ME
NT
ST
RA
TT
ON
B
UI
LD
IN
G
1 S
OU
TH
S
PR
IN
G
ST
RE
ET
SP
RI
NG
FI
EL
D, IL
LIN
OI
S
SPECIFICATIONS
AutoCAD SHX Text
BRH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text 25-081
AutoCAD SHX Text
AutoCAD SHX Text
AUG. 5, 2026
AutoCAD SHX Text
NOV. 30, 2026
AutoCAD SHX Text DIVISION 22 - PLUMBING Section 22 05 23 - General Duty Valves for Plumbing Piping PART 1 - GENERAL GENERAL 1.1 WORK INCLUDES WORK INCLUDES A. Base Bid: Base Bid: 1. Contractor Provide: Contractor Provide: a.
This is the start of the file's text. The full file is on GovTribe.