The file contains contract drawings for a Nurse Call Replacement project for the Florida Department of Veterans' Affairs (FDVA) at the Baldomero Lopez Veterans Nursing Home located in Land O' Lakes, Florida. The project, identified with the AHCA Client Code 35/35960936-35654, involves the complete replacement of the existing Dukane nurse call system with a new Rauland system across four units (A, B, C, and D) of the nursing home. The project is scheduled for implementation in 2025 and will involve systematic demolition and installation of new nurse call devices, cabling, and infrastructure, with careful phasing to maintain continuous nurse call coverage throughout the construction process.
The project scope includes removing all existing nurse call components and cabling, installing new Rauland nurse call devices in patient rooms, corridors, and staff areas, and implementing new power connections and infrastructure. The contractor will be responsible for maintaining infection control protocols, providing negative air pressure, and ensuring minimal disruption to facility operations. The project requires comprehensive testing, certification, staff training, and will include a 5-year extended material and labor warranty. The new system will comply with multiple codes including the 2020 Florida Electrical Code, 2021 NFPA 99 Health Care Facilities Code, and 2023 Florida Building Code. The electrical infrastructure will utilize existing electrical panels with some circuit relocations and additions to support the new nurse call system.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing No:
Project Status:
Drawing Title:
BURNS PROJECT NO:
DATE:
CONTRACT DRAWINGS FOR:
AHCA CLIENT CODE / FILE NO: 35/35960936-35654 / 002
PROJECT ADDRESS:
PROJECT PHASE:
CAMPUS MAP
BURNS ENGINEERING, INC | (813) 257 7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
CA# 26183
PROJECT SCOPE:
THIS PROJECT INCLUDES THE COMPLETE REPLACEMENT
OF THE EXISTING NURSE CALL SYSTEM WITH A NEW
SYSTEM PROVIDED BY RAULAND. THE EXISTING DUKANE
SYSTEM IS NO LONGER SUPPORTED. ALL EXISTING
NURSE CALL COMPONENTS AND CABLING SHALL BE
REMOVED UNLESS NOTED OTHERWISE.
G000
COVER SHEET
AHCA STAGE III
2025-0049
FDVA BALDOMERO LOPEZ VETERANS NURSING HOME
NURSE CALL REPLACEMENT
6919 PARKWAY BOULEVARD
LAND O’ LAKES, FL 34639
06/26/2025
AHCA STAGE III
NURSE CALL SHEET INDEX
G000 COVER SHEET
NC000 NURSE CALL/RTLS LEGENDS AND GENERAL NOTES
NC001 NURSE CALL/RTLS SINGLE LINE DIAGRAMS
NC101 OVERALL NURSE CALL PLAN
NC102 CONSTRUCTION PHASING PLAN
NC201A UNIT A NURSE CALL DEMOLITION PLAN
NC201B UNIT B NURSE CALL DEMOLITION PLAN
NC201C UNIT C NURSE CALL DEMOLITION PLAN
NC201D UNIT D NURSE CALL DEMOLITION PLAN
NC301A UNIT A NURSE CALL NEW CONSTRUCTION PLAN
NC301B UNIT B NURSE CALL NEW CONSTRUCTION PLAN
NC301C UNIT C NURSE CALL NEW CONSTRUCTION PLAN
NC301D UNIT D NURSE CALL NEW CONSTRUCTION PLAN
NC401 NURSE CALL ENLARGED PLANS
NC501 NURSE CALL/RTLS DETAILS
NC601 PANELBOARD SCHEDULES
Grand total: 16
PLAN DETAIL REFERENCE
SHEET
SHEET
PLAN
ROOM
X
X
ELEVATION REFERENCE
SECTION REFERENCE
NORTH ARROW
ROOM NAME AND NUMBER
DETAIL / DIAGRAM SPECIFIC KEYED NOTE DESIGNATION
REVISION OR ADDENDUM DESIGNATION
SHEET KEYED NOTE DESIGNATION
DETAIL
SHEET
DETAIL
DETAIL
SHEET
X
MATCHLINE
TDR BOUNDARY
CONDUIT OR SLEEVE
LADDER RACK
CONDUIT CONCEALED IN
CONDUIT IN SLAB
CONDUIT SLEEVE
CONDUIT CAPPED
TURNING UP
CONDUIT OR SLEEVE
TURNING DOWN
CEILING OR WALL
OR UNDERGROUND
TAG INFORMATION
HOMERUN
CABLE TRAY
EZ-PATH
J-HOOK PATHWAY
ENCLOSED EQUIPMENT CABINET
(CLEARANCE SPACE SHOWN DASHED)
VERTICAL WIRE MANAGEMENT,TYP
OPEN FRAME EQUIPMENT RACK
WALL MOUNTED CABINET
SYMBOLOGY TAG INFORMATION
PANEL/WALL MOUNT EQUIPMENT
F R
O N
T
R E
A R
SCOPE OF WORK:
THIS PROJECT INCLUDES THE COMPLETE REPLACEMENT OF THE
EXISTING NURSE CALL SYSTEM WITH A NEW SYSTEM PROVIDED BY
RAULAND. THE EXISTING DUKANE SYSTEM IS NO LONGER SUPPORTED.
ALL EXISTING NURSE CALL COMPONENTS AND CABLING SHALL BE
REMOVED UNLESS NOTED OTHERWISE.
CODES AND STANDARDS:
GENERAL NOTES:
NC
DS
SA
PC
PA
SP
DP
FB
NCTC
DC
CL
ZL
AX AX AXAX
PS
TECHNOLOGY NURSE CALL ABBREVIATIONS
A/AMP
AC
ADA
AEC
AFF
AFG
AHJ
AL
AMP
AP
AV
AWG
BC
BFC
BMS
C
CAT
CATV
CH
CM
CMM
CMPT
CPST
CPU
CR
CU
DB
DIA
DWG
EA
EC
EIA
ELEC
ELEV
EMER
EMT
EO
EQ
EX
FA
FL
FMC
FO
FPD
GC
GRD
GRS
HDMI
HVAC
HZ
IG
IMC
IP
IP
IR
ISC
IT
ITO
JB
KVA
KW
LAN
LCD
LED
LTG
LV
M
MATV
MFR
MIC
MISC
MM
MMFO
MNS
N/A
NEC
NEMA
NFPA
NIC
NTS
OAR
OC
OFNR
OP
OTS
PA
PB
PBX
PC
PLY
PNL
POE
POSU
PP
PR
PSTN
PVC
RF
RGB
RGS
RM
RMC
RU
SCH/SCHED
SS
STB
TBD
TEC
TELE
TELECOM
TDR
TGB
TIA
TMGB
TS
TSER
TV
TYP
UL
UON
UPS
UTP
V
VAC
VC
VDC
VGA
VOIP
W/
W/IN
W/O
WAP
WIFI
WLAN
XMTR
AMPERE
ABOVE COUNTER
AMERICANS WITH DISABILITIES ACT
ACOUSTIC ECHO CANCELLATION
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTHORITY HAVING JURISDICTION
ALUMINUM
AMPLIFIER
WIRELESS ACCESS POINT
AUDIO VIDEO
AMERICAN WIRE GAUGE
BELOW CEILING
BELOW FINISHED CEILING
BUILDING MANAGEMENT SYSTEM
CONDUIT
CATEGORY
CABLE TELEVISION
CHANNEL
CENTIMETER
COMMUNICATIONS
COMPONENT
COMPOSITE
CENTRAL PROCESSING UNIT
COMMUNICATIONS ROOM
COPPER
DECIBEL
DIAMETER
DRAWING
EACH
ELECRICAL CONTRACTOR
ELECTRONICS INDUSTRY ASSOCIATION
ELECTRIC/ELECTRICAL
ELEVATOR
EMERGENCY
ELECTRICAL METALLIC TUBING
EQUAL
EQUALIZER
EXISTING
FIRE ALARM
FLOOR
FLEXIBLE METAL CONDUIT
FIBER OPTIC
FLAT PANEL DISPLAY
GENERAL CONTRACTOR
GROUND
GALVANIZED RIGID STEEL
HIGH DEFINITION MULTIMEDIA INTERFACE
HEATING VENTILATING AIR CONDITIONING
HERTZ
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INTERNET PROTOCOL
INPUT PANEL
INFRARED
INTELLIGENT SYSTEM CONTROLLER
INFORMATION TECHNOLOGY
INFORMATION TECHNOLOGY OUTLET
JUNCTION BOX
KILOVOLT AMPERE
KILOWATT
LOCAL AREA NETWORK
LIQUID CRYSTAL DISPLAY
LIGHT EMITTING DIODE
LIGHTING
LOW VOLTAGE
METER
MASTER ANTENNA TELEVISION
MANUFACTURER
MICROPHONE
MISCELLANEOUS
MILLIMETER
MULTI-MODE FIBER OPTIC
MASS NOTIFICATION SYSTEM
NOT AVAILABLE/NOT APPLICABLE
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NOT TO SCALE
OWNER AUTHROIZED REPRESENTATIVE
ON CENTER
OPTICAL FIBER NONCONDUCTIVE RISER
OUTPUT PANEL
OFF THE SHELF
PUBLIC ADDRESS
PULL BOX
PRIVATE BRANCH EXCHANGE
PERSONAL COMPUTER
PLYWOOD
PANEL
POWER OVER INTERNET
POWER SUPPLY MODULE
PATCH PANEL/POWER PANEL
PAIR
PUBLIC SWITCHED TELEPHONE NETWORK
POLYVINYL CHLORIDE
RADIO FREQUENCY
RED GREEN BLUE
RIGID GALVANIZED STEEL
ROOM
RIGID METAL CONDUIT
RACK UNIT
SCHEDULE
STAINLESS STEEL
SET TOP BOX
TO BE DETERMINED
TELECOMMUNICATIONS EQUIPMENT CENTER
TELEPHONE
TELECOMMUNICATIONS
TELECOMMUNICATIONS DISTRIBUTION ROOM
TELECOMMUNICATIONS GROUND BUSBAR
TELECOMMUNICATIONS INDUSTRY ASSOCIATION
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
TOUCH SCREEN
TELECOMMUNICATIONS SERVICE ENTRANCE ROOM
TELEVISION
TYPICAL
UNDERWRITER'S LABORATORIES
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
UNSHIELDED TWISTED PAIR
VOLT
VOLT ALTERNATING CURRENT
VOLUME CONTROL
VOLT DIRECT CURRENT
VIDEO GRAPHICS ARRAY
VOICE OVER INTERNET PROTOCOL
WITH
WITHIN
WITHOUT
WIRELESS ACCESS POINT
WIRELESS FIDELITY
WIRELESS LAN
TRANSMITTER
GENERAL NOTES
GENERAL SYMBOLS
CONDUIT AND RACEWAY
EQUIPMENT
DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT DRAWN TO
SCALE. CONTRACTOR IS RESPONSIBLE FOR COORDINATING FINAL
ROUTING OF ALL SERVICES AND DISTANCES WITH EXISTING
CONDITIONS AND WITH ALL OTHER TRADES.
ANY DISCREPANCIES BETWEEN THE PLANS AND ACTUAL FIELD
CONDITIONS MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF
THE ENGINEER OR DESIGNATED REPRESENTATIVE FOR
CLARIFICATION.
ALL WORK IS TO BE DONE IN A THOROUGH AND PROFESSIONAL
MANNER ACCORDING TO INDUSTRY AND MANUFACTURERS'
STANDARDS AND WILL BE SUBJECT TO INSPECTION AND ACCEPTANCE.
WORK THAT IS DEEMED SUB-STANDARD WILL BE SUBJECT TO
REPLACEMENT OR REPAIR AT NO ADDITIONAL COST TO THE OWNER
OR GENERAL CONTRACTOR.
PERMITS & INSPECTIONS: CONTRACTOR SHALL OBTAIN ALL REQUIRED
PERMITS AND SCHEDULE ALL INSPECTIONS WITH THE AUTHORITY
HAVING JURISDICTION (AHJ).
FACILITY OPERATIONS: WORK SHALL BE PERFORMED IN A
CONTINUOUSLY OCCUPIED HEALTHCARE FACILITY. COORDINATE ALL
ACTIVITIES, SHUTDOWNS, AND ACCESS WITH FACILITY STAFF. LIMIT
DISRUPTIONS AND MAINTAIN CONTINUITY OF CARE AT ALL TIMES.
SYSTEM COORDINATION: COORDINATE ALL DEVICE TYPES, LOCATIONS,
CABLING, AND INFRASTRUCTURE WITH THE NURSE CALL SYSTEM
VENDOR. CONTRACTOR SHALL REVIEW AND VERIFY VENDOR-
PROVIDED SHOP DRAWINGS PRIOR TO INSTALLATION.
CABLING: ALL CABLING SHALL BE REPLACED WITH NEW, VENDOR-
APPROVED CABLE TYPES. EXISTING CABLING SHALL BE REMOVED AND
DISPOSED OF PER FACILITY REQUIREMENTS. ALL CABLE RUNS SHALL
COMPLY WITH NEC AND MANUFACTURER SPECIFICATIONS.
CABLE PATHWAYS: EXISTING CONDUITS AND RACEWAYS MAY BE
REUSED WHERE ADEQUATE AND IN GOOD CONDITION. VERIFY ALL
PATHWAYS PRIOR TO INSTALLATION. DAMAGED OR UNDERSIZED
PATHWAYS SHALL BE REPLACED.
DEVICE LOCATIONS: REUSE EXISTING DEVICE LOCATIONS UNLESS
OTHERWISE NOTED OR REQUIRED BY THE VENDOR. COORDINATE ANY
ADDITIONS OR RELOCATIONS WITH FACILITY STAFF TO MEET CLINICAL
WORKFLOW NEEDS.
POWER REQUIREMENTS: PROVIDE 120V POWER CONNECTIONS TO ALL
SYSTEM COMPONENTS REQUIRING LINE VOLTAGE. COORDINATE EXACT
REQUIREMENTS WITH SYSTEM VENDOR. PROVIDE CONNECTIONS FROM
CRITICAL BRANCH
DEMOLITION: REMOVE AND TURN OVER ALL FUNCTIONING EXISTING
DEVICES TO THE FACILITY. PROPERLY DISPOSE OF ANY NON-
FUNCTIONING DEVICES, EXISTING CABLING, POWER SUPPLIES AND
HEAD-END EQUIPMENT. PATCH AND REPAIR ANY DAMAGE TO WALLS,
CEILINGS, OR FINISHES RESULTING FROM REMOVAL.
FIRESTOPPING: THE CONTRACTOR IS REQUIRED TO PROPERLY FIRE-
STOP ANY CORES UTILIZED FOR THE PLACEMENT OF
COMMUNICATIONS CABLING WITH APPROVED FIRE-STOPPING
COMPOUND AND ACCORDING TO LOCAL AND NATIONAL CODES.
ALL PENETRATED STRUCTURES ARE TO BE RETURNED TO ORIGINAL
CONDITION AND FIRE RATING.
LABELING: ALL NEW DEVICES AND CABLING SHALL BE LABELED PER
VENDOR REQUIREMENTS AND SYSTEM DIAGRAMS. INCLUDE CIRCUIT
IDENTIFICATION AND TERMINAL LABELING AS APPLICABLE.
CUTOVER PLAN: PROVIDE A DETAILED CUTOVER PLAN TO ENSURE
CONTINUOUS NURSE CALL COVERAGE DURING SYSTEM TRANSITION.
COORDINATE PHASING AND TEMPORARY SOLUTIONS WITH FACILITY
STAFF.
TEMPORARY CALL SYSTEM: IF EXISTING NURSE CALL COVERAGE MUST
BE INTERRUPTED, PROVIDE APPROVED TEMPORARY SIGNALING
METHODS (E.G., PORTABLE CALL STATIONS OR WIRELESS SYSTEMS)
FOR AFFECTED PATIENT AREAS.
TESTING & CERTIFICATION: UPON COMPLETION, THE NURSE CALL
SYSTEM SHALL BE TESTED IN THE PRESENCE OF THE FACILITY,
ENGINEER, AND VENDOR. PROVIDE A LETTER CERTIFYING THE SYSTEM
MEETS OPERATIONAL, CODE, AND MANUFACTURER REQUIREMENTS.
TRAINING: PROVIDE COMPREHENSIVE TRAINING FOR CLINICAL AND
MAINTENANCE STAFF. COORDINATE TRAINING SCHEDULE WITH THE
FACILITY PRIOR TO FINAL ACCEPTANCE.
ATTIC STOCK & WARRANTY: PROVIDE 5% ATTIC STOCK FOR NEW
NURSE CALL DEVICES INCLUDING ZONE LIGHTS, CORRIDORS LIGHTS,
PATIENT CALL STATIONS, STAFF ASSIST STATIONS, DUTY STATIONS,
AND SHOWER/BATHROOM PULL CORD STATIONS.
SYSTEM TO BE FURNISHED WITH A 5-YEAR EXTENDED MATERIAL AND
LABOR WARRANTY.
AS-BUILT DOCUMENTATION: FURNISH AS-BUILT DRAWINGS, WIRING
DIAGRAMS, O&M MANUALS, WARRANTY INFORMATION, AND
PROGRAMMING BACKUPS TO THE OWNER AT PROJECT CLOSEOUT.
ALL WORK SHALL COMPLY WITH APPLICABLE CODES AND STANDARDS
INCLUDING, BUT NOT LIMITED TO:
•2020 FLORIDA ELECTRICAL CODE (NATIONAL ELECTRICAL CODE 2020)
•2021 NFPA 99 HEALTH CARE FACILITIES CODE
•2021 NFPA 101 LIFE SAFETY CODE
•2023 FLORIDA BUILDING CODE
•2023 FLORIDA EXISTING BUILDING CODE
•2023 FLORIDA FIRE PREVENTION CODE.
•LOCAL AMENDMENTS
•2022 FACILITY GUIDELINES INSTITUTE - RESIDENTIAL
•FLORIDA ADMINISTRATIVE CODE 59A-4
TECHNOLOGY NURSE CALL SYMBOL LEGEND
NURSE CONSOLE MASTER STATION
DUTY STATION
PULL-CORD STATION (WATERPROOF)
MTG. HEIGHTDESCRIPTIONSYMBOL
45" AFF, UON
45" AFF, UON
45" AFF
45" AFF
45" AFF
18" AFF
45" AFF
45" AFF, UON
1) MANUFACTURE SPECIFIED IS FOR NEW CONSTRUCTION DEVICES ONLY. DEVICES ON DEMOLITION PLAN USE EQUIVALENT SYMBOLS FOR LAYOUT CONSISTENCY.
2) THIS IS A STANDARD SYMBOL LIST. ALL SYMBOLS MAY NOT APPEAR ON THIS PROJECT.
STAFF ASSIST STATION
PULL-CORD STATION W / AUDIO
SINGLE PATIENT STATION
DUAL PATIENT STATION
FEATURE BED RECEPTACLE
RAULAND
R5KCONSV3
RAULAND
R5KSDTY
RAULAND
R4KPB12
RAULAND
R5KPC11WP
RAULAND
R5KAUDPCV2
RAULAND
R5KPS1LCA
RAULAND
R5KPD2EA
RAULAND
NCBED
MANUFACTURE
NURSE CALL CABINET
RAULAND
NC2828
DOMELESS CONTROLLER
RAULAND
CLA246
CORRIDOR LIGHT
ZONE LIGHT
RAULAND
CLA246
RAULAND
CLA246
BACK BOXES
NOTE 1
DUAL GANG
EXISTING TO REMAIN DEMOLISHED IMPACTEDNEW
1) SURFACE MOUNTABLE; COMPATIBLE WITH SINGLE AND DUAL GANG BOXES. THE METAL HOUSING ALSO PERMITS THE R5KDC06 TO BE LOCATED ABOVE
CEILING TILES OR TO BE PLACED INTO A WALL.
SCHEDULE NOTES:
GENERAL NOTES:
PILLOW SPEAKER
RAULAND
NCPSXXX
DUAL GANG
SINGLE GANG
DUAL GANG
DUAL GANG
DUAL GANG
SINGLE GANG
3-GANG
DUAL GANG
CONSTRUCT BARRIERS TO PREVENT DUST AND DANGEROUS PATHOGENS FROM ENTERING PATIENT
CARE AND ENSURE THAT BARRIERS ARE IMPERMEABLE TO FUNGAL SPORES AND IN COMPLIANCE
WITH LOCAL FIRE CODES. INSTALL DOORS WITH SELF CLOSING DEVICES ON ICRA PARTITIONS.
THE HOSPITAL ICRA REQUIREMENTS MUST BE MET AT ALL TIMES. THE ICRA STATUS SHALL BE
REVIEWED WEEKLY WITH OWNER.
CONTRACTOR SHALL UTILIZE CRITICAL BRANCH POWER FOR ANY DUST MITIGATION EQUIPMENT (I.E.
NEGATIVE AIR MACHINE). IF CRITICAL BRANCH POWER IS NOT READILY ACCESSIBLE, CONTRACTOR SHALL RUN A TEMPORARY CRITICAL CIRCUIT BACK TO THE NEAREST CRITICAL BRANCH PANEL. AT NO TIMES SHALL THERE BE EXTENSION CORDS AND/OR TEMPORARY WIRING LAID OUT WITHIN THE EGRESS CORRIDORS AND/OR PATIENT AREAS. ANY/ALL TEMPORARY WIRING SHALL BE INSTALLED
WITHIN THE CEILING SPACE.
CONTRACTOR TO MAINTAIN ALL EXITS DURING CONSTRUCTION IN COMPLIANCE WITH: NFPA
101-4.6.10 2018 "CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS". NFPA101-7.1.10 2018 "MEANS OF EGRESS RELIABILITY" NFPA101-18.7.9 2018 "CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS" NFPA 241 2013 -"STANDARD FOR SAFEGUARDING CONSTRUCTION, AND DEMOLITION
OPERATIONS".
PROVIDE AND MAINTAIN AIR PRESSURE AND DUST CONTROL IN ALL DEMOLITION AND
CONSTRUCTION AREAS WHEN APPLICABLE.
CONTRACTOR TO REFER TO FACILITY ICRA REQUIREMENTS PRIOR TO PERFORMING ANY WORK
THAT MAY REQUIRE CUTTING OR PRODUCING DUST AND/OR DEBRIS. CONTRACTOR TO MAINTAIN
NEGATIVE AIR BALANCE WHERE REQUIRED AT ALL TIMES, AND PROVIDE DUST TIGHT PARTITIONS
AND TACKY MAT WHERE REQUIRED. REFER TO ICRA REQUIREMENTS AND FACILITY ICRA PLAN
PRIOR TO BID.
CONTRACTOR TO COORDINATE WITH THE FACILITY FOR CONTRACTOR ACCESS. ANY ITEMS,
EQUIPMENT OR MATERIAL BROUGHT INTO THE FACILITY MUST BE IN COVERED CONTAINERS.
PROVIDE COPPER #10AWG BONDING CONNECTION BETWEEN THE GROUNDING TERMINAL BUSES OF
THE CRITICAL BRANCH PANELS AND THE NORMAL BRANCH PANELS AFFECTED BY SCOPE OF WORK.
A.
B.
C.
D.
E.
F.
G.
H.
ICRA GENERAL NOTES - ELECTRICAL
CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL RISK
ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW THE
REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH THOSE
REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS OF THE
CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO THE PHASING PLAN ANY
WORK OUTSIDE THE CONSTRUCTION AREA SHALL BE COORDINATED WITH THE OWNER AND
PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER THE SUPERVISION OF THE
OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICRA COMMITTEE OFFICER.
TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, THE CONTRACTOR SHALL ENDEAVOR TO
MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN AREAS SURROUNDING AND ADJACENT TO THE CONSTRUCTION WORK ZONE AND ELSEWHERE IN THE FACILITY. IT SHOULD BE ANTICIPATED
THAT THE ICRA REPORT WILL REQUIRE MEASURES TO THIS EFFECT INCLUDING ERECTION OF
CONSTRUCTION ZONE BARRIERS AND PROVISION OF NEGATIVE AIR PRESSURE IN THE
CONSTRUCTION ZONE RELATIVE TO OTHER AREAS OF THE FACILITY.
IN ADDITION TO THE MEETING THE REQUIREMENTS OF THE ICRA REPORT, THE CONTRACTOR AT A
MINIMUM SHALL PROVIDE EQUIPMENT AND COMPONENTS NECESSARY TO CREATE A NEGATIVE
PRESSURE IN THE CONSTRUCTION WORK ZONE RELATIVE TO ADJACENT AREA. EXISTING HVAC
SYSTEMS AND COMPONENTS SHALL NOT BE USED FOR THIS FUNCTION, UNLESS SPECIFICALLY
APPROVED BY THE OWNER'S INFECTION CONTROL OFFICER. THE CONCEPT AND ALL ASPECTS OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH THE ICRA REQUIREMENTS AND AT A MINIMUM
AS FOLLOWS:
1. VERIFY ALL EXISTING DUCTWORK WHICH PASSES THROUGH THE CONSTRUCTION
ZONEAND IS TO REMAIN, IS SEALED AND PROTECTED DURING THE CONSTRUCTION DURATION.
2. AIR REMOVED FROM THE CONSTRUCTION ZONE SHALL BE FILTERED AND/ORDISCHARGED AS
DIRECTED BY THE ICRA REPORT.
3. PRESENT THE NEGATIVE AIR PRESSURE PLAN TO THE OWNER FOR APPROVAL BY THE
INFECTION CONTROL COMMITTEE.
4. PROVIDE MEANS TO MONITOR AND VERIFY NEGATIVE PRESSURE IS BEING MAINTAINED
IN ACCORDANCE WITH THE ICRA REPORT, AND PROVIDE DOCUMENTATION TO THE
OWNER AS REQUIRED
COORDINATE IN ADVANCE ANY REQUIRED EQUIPMENT SHUTDOWN WITH THE OWNER, AND VERIFY
BEFORE SHUTDOWN THAT EXISTING OR DESIRED AIR PRESSURE RELATIONSHIPS WILL NOT BE
ADVERSELY AFFECTED.
FOR MINOR WORK OUTSIDE OF THE AREA SHOWN UTILIZE PORTABLE AIRBORNE PARTICULATE
CONTAINMENT UNITS AS MANUFACTURED BY MINTIE TECHNOLOGIES, INC. OR EQUIVALENT. ALL
PROCEDURES STATED IN THE ICRA SHALL BE FOLLOWED.
A.
B.
C.
D.
E.
ICRA GENERAL NOTES - MECHANICAL
NURSE CALL SHEET INDEX
G000 COVER SHEET
NC000 NURSE CALL/RTLS LEGENDS AND GENERAL NOTES
NC001 NURSE CALL/RTLS SINGLE LINE DIAGRAMS
NC101 OVERALL NURSE CALL PLAN
NC102 CONSTRUCTION PHASING PLAN
NC201A UNIT A NURSE CALL DEMOLITION PLAN
NC201B UNIT B NURSE CALL DEMOLITION PLAN
NC201C UNIT C NURSE CALL DEMOLITION PLAN
NC201D UNIT D NURSE CALL DEMOLITION PLAN
NC301A UNIT A NURSE CALL NEW CONSTRUCTION PLAN
NC301B UNIT B NURSE CALL NEW CONSTRUCTION PLAN
NC301C UNIT C NURSE CALL NEW CONSTRUCTION PLAN
NC301D UNIT D NURSE CALL NEW CONSTRUCTION PLAN
NC401 NURSE CALL ENLARGED PLANS
NC501 NURSE CALL/RTLS DETAILS
NC601 PANELBOARD SCHEDULES
Grand total: 16
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC000
2025-0049
NURSE CALL/RTLS
LEGENDS AND
GENERAL NOTES
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
FIRE RATED WALL PARTITION LEGEND
4 HOUR FIRE RATED PARTITION
SMOKE BARRIER 1 HOUR FIRE RATED PARTITION
1 HOUR FIRE RATED PARTITION
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
1 6/19/2025 AHCA STAGE III REV 1
6/26/2025 BID SET
EC-D1 (EXIST)
208/120V 3Ø, 4W
400A (10,000 AIC)
208/120V
110A MCB
(10,000 AIC)
(5,346 SCA)
EC-A2 (EXIST)
110A
(4,491 SCA)
XFMER T-6
EC-D (EXIST)
225AF
225AT
125AF
125AT
75 KVA
480V-120/208V 3Ø, 4W
480/277V 3Ø, 4W
225A (14,000 AIC)
EXISTING
PANEL 'EC'
XFMER T-10
EC-A (EXIST)
480/277V 3Ø, 4W
225A (14,000 AIC) 225AF
225AT
50A/3P
30 KVA
480V-120/208V 3Ø, 4W
EXISTING
PANEL 'EC'
(8,656 SCA)(6,143 SCA)
400AF
250AT
SPD
20A/3P60A/3P
208/120V
60A MLO
(10,000 AIC)
EC-D2 (NEW)
20A
LRGST BRKR
4 #6AWG, 1#10, 1"C
SPD
PA
NCTC NC ZL
SP
PSPC
PA DP
PSPC
DS
CLEAN/
STORAGE 137
TYPICAL 2 BEDROOM
(30 QTY)
TYPICAL 1 BEDROOM
(2 QTY)
NC-A
TELE 139 N.S 107
DC
DS
DC
SOILED 138 CEN BATH 141 BISTRO 103
SA DS
DC
LAUND 102
DS
DC
PANTRY 104
DS
DC
NURSING PROGRAM
SPECIALIST 108
PC
ZL ZL ZL
PA
NCTC NC ZL
SP
PSPC
PA DP
PSPC
DS
PANTRY 404
TYPICAL 2 BEDROOM
( 27 QTY)
TYPICAL 1 BEDROOM
( 4 QTY)
NC-D
TELE 439 N.S 407
DC
DS
DC
SOILED 438
CLEAN
STORAGE 437 MED PREP 408
ZL
DINING 403
SA
ZL
DS
DC
DS
DC
ZL
DINING 239
SA
UNIT A
ZL ZL
ZL ZL ZL
DEVOTIONAL
ROOM 206
SA
LIBRARY 205
SA
WOMEN 202
PC
PC
PC
MEN 203
PC PC
ZL
SA
OCC.
THERAPY 332
SA
BARBER 327
SA
OCC.
THERAPY 330
SA
PHYS. THERAPY
329 & TLT 329.1
PC
VENDING 324
SA
ZL
UNIT D
UNIT C UNIT B
CL CL CL CL
CL CL CL
CLCL CL CL CLCLCL CLCL CL
PATIO
SA
CL
PATIO
SA
CL
SA
ENLCOSED
PORCH
CL
PATIO
SA
CL
QTY OF ZONE
LIGHTS PER
PLANS. (TYP)
PS
PS
1. MANUFACTURED SLEEVES ARE SHOWN FOR MAJOR
PENETRATIONS. NOT ALL PENETRATIONS ARE SHOWN.
2. MAINTAIN 40% MAX FILL RATE ON ALL SLEEVE PENETRATIONS.
3. CABLE TRAY SHALL MAINTAIN AS POSSIBLE SAME ELEVATION.
4. SUPPORT AREAS WITH HARDLID CEILINGS SHALL RUN CONDUIT TO
NEAREST ACCESSIBLE CEILING AND/OR CABLE TRAY ACCESS
PANEL.
5. TECHNOLOGY SYSTEMS SHALL BE WITHIN SEPARATE SLEEVES.
6. REFER TO OVERALL ROUTING SHEET FOR NEAREST TDR FOR
TERMINATION OF SYSTEM CABLING
NURSE CALL RISER GENERAL NOTES:
PROVIDE NEW EATON BAB 60A/3P BREAKER TO SERVE NEW
PANELBOARD.
PROVIDE NEW PANELBOARD. SEE PANELBOARD SCHEDULE ON SHEET
NC601 FOR ADDITIONAL INFORMATION.
ELECTRICAL ONE-LINE DIAGRAM KEYNOTES
ONE-LINE DIAGRAM LEGEND
EXISTING TO REMAIN
NEW
EXISTING AFFECTED BY THIS PROJECT
NOT TO SCALENC001
1 NURSE CALL RISER DIAGRAM
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC001
2025-0049
NURSE CALL/RTLS
SINGLE LINE
DIAGRAMS
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
12" = 1'-0"NC001
2 PARTIAL ELECTRICAL ONE-LINE DIAGRAM
NOT TO SCALENC001
3 SELECTIVE COORDINATION STUDY
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
PATIO
DISPLAY
2 BR
TLT
131.1
ALCOVE
1C4.2
2 BR
2 BR
TLT
133.1
2 BR
2 BR
TLT
135.1
2 BR
STOR
1C4.3
STOR
1C4.4
CLEAN/STORAGE
TLT
143.1
2 BR
SOILED
TELE
CEN BATH
JAN
CORR
1C5
ALCOVE
1C5.1
2 BR
2 BR
TLT
144.1
2 BR
2 BR
TLT
146.1 DIS
PL
AY
DIS
PL
AY
DISPLAY
ALCOVE
1C5.2
TLT
148.1
2 BR
2 BR
2 BR
2 BR
TLT
150.1
TYP
2 BR
2 BR
TYP
TLT
152.1
STOR
1C5.4
STOR
1C5.3
CORR
1C1
PANTRY
CHARTING ROOM
BISTRO
LAUND
CORR
1C1.1
N.S.
MED
PREP
REF
MED.
CARTS
R.N.
TYP TLT
1 BR
NURSING PROG.
SPECIALIST
WC/ALCOVE
2 BR
TLT
111.1ALCOVE
1C3.1
2 BR
2 BR
2 BR
TLT
113.1ALCOVE
1C3.2
TLT
115.1
2 BR
2 BR
DIS
PL
AY
2 BR
2 BR
TLT
117.1
DIS
PL
AY
TYP
1 BR
ALCOVE
1C3.3
TLT
119.1
HC TLT
MECH
CORR
1C2
TLT
122GAS CYL
123ELEC
TLT
125.1
2 BR
JAN
2 BR
TLT
127.1
ALCOVE
1C4.1
ENCLOSED PORCH
REC. THERAPY
OCC. THERAPY
330 PHYS. THERAPY
OFFICE
STOR
STOR
CORR
3C6
OFFICE
STOR
STOR
TLT
329.1
CORR
3C5
BARBER
VENDING
DRUGS
325.1
CHEMO
PREP
PHARMACY
MEN
203WOMEN
ENTRY
201.1
STOR
LIBRARY
DRYER
EQUIP.
207.1
DRYER
WASHER
STORAGE
STOR KEEP
CORR
2C5
STORAGE
REPAIRS
LKR
TLT
211.1TLT
210.1
LKR
VEST
2C2.1
PRE-RINSE
DEVOTIONAL
ROOM
CORR
2C1
LOBBY
OFFICE
OFFICE
OXY
TLT
COMM
COMP
SWITCHGEAR
ELEC
MECH
MECH
MECH
STOR
225 STORAGE
OFFICE
MECH
OFFICE
JAN
DRY STOR
OFFICE
JAN
OFFICE
TLT
236.1
TLT
236.2
KITCHEN
237.2
KITCHEN
SERVING
DINING
DIR. OF
NURSING
OFFICE
TLT
TLT
ADMIT.
RECPT.
WAITING
ADMIN.
OFFICE
CONFERENCE
ADMIN
OFFICE
STAFF
LOUNGE
LKR
TLT
322.1
CORR
3C4
TLT
323.1
LKR
MECH
JAN
OFFICE
OFFICE
317CORR
3C2
CORR
3C3
ALCOVE
3C3.1
VOL
OFFICE
OFFICE
CLERICAL
OFFICE
DINING
QUIET RM
PANTRY
CORR
4C1
CORR
4C1.1
CHARTING ROOM
TYP TLT
410.1
1 BR
MED.
CARTS
REF
MED
PREP
MED PREP
WC/ALCOVE
2 BR
TLT
411.1
2 BR
ALCOVE
4C3.1
DIS
PL
AY
DIS
PL
AY
2 BR
TLT
413.1
2 BR
ALCOVE
4C3.2 TLT
415.1
2 BR
2 BR
2 BR
2 BR
TLT
417.1
ALCOVE
4C3.3
MECH
HC TLT
TYP
1 BR
TLT
419.1
TLT
425.1
1 BR
ELEC
GAS CYL
TLT
CORR
4C2
STOR
4C4.3
STOR
4C4.4
JAN
2 BR
2 BR
TLT
427.1
ALCOVE
4C4.1
DISPLAY
2 BR
TLT
429.1
DISPLAY
2 BR
ALCOVE
4C4.2
2 BR
TLT
431.1
2 BR
2 BR
TLT
433.1
2 BR
2 BR
TLT
435.1
2 BR
CLEAN/STORAGE
TLT
443.1
1 BR
SOILED
TELE
BARBER SHOP
JAN
2 BR
TLT
444.1
ALCOVE
4C5.1
CORR
4C5
DIS
PL
AY
2 BR
2 BR
2 BR
TLT
446.1DIS
PL
AY
AWNING
ALCOVE
4C5.2
TLT
448.1
2 BR
2 BR
2 BR
TLT
450.1
2 BR
2 BR
TYP
TLT
452.1
STOR
4C5.3
STOR
4C5.4
2 BR
2 BR
TLT
129.1
2 BR
PATIO
TV LOUNGE
DELTA 200 HALL
DELTA 300 HALL
DELTA 100 HALL
ALPHA 100 HALL
ALPHA 300 HALL
ALPHA 200 HALL
PATIO
TYP
TLT
452.1
UNIT "A" UNIT "D"
UNIT "C"
UNIT B"
C L
C L
C L
C L C L
C L
C L
C L
CL
CLCLCLCL
CL CL CL CL CL CL
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C
L CL
C L
C L
CL CL CL CL CL
CLCLCLCLCLCL
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
CL
N C
C L
C L
C L
C L
N C
C L
C L
CL CL CL
C L
C L
ZL
ZL ZL
ZL
ZL
ZL ZL
ZL
ZL
ZL ZL
Z L
ZL
Z L
ZL
C L
C L
C L
C L
C L
C L
C L
CL
CL CL
C L
MATCHLINE UNIT C MATCHLINE UNIT C
MATCHLINE UNIT B MATCHLINE UNIT B
M A
T C
H
LI
N E
U N
IT
C
M A
T C
H
LI
N E
U N
IT
C
M A
T C
H
LI
N E
U N
IT
C
M A
T C
H
LI
N E
U N
IT
C
M A
T C
H
LI
N E
U N
IT
D
M A
T C
H
LI
N E
U N
IT
D
M A
T C
H
LI
N E
U N
IT
A
M A
T C
H
LI
N E
U N
IT
A
NC401
NC401
NC401
NC401
NC401
NC401
NC401
NC401
PORCH:
NO RESIDENT
ACCESS
PORCH:
NO RESIDENT ACCESS AWNING:
NO RESIDENT ACCESS
PORCH:
NO RESIDENT
ACCESS
EC-D2
OVERALL PLAN INDICATES
CORRIDOR AND ZONE
LIGHTING ONLY.
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
A
C B
D
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
1/16" = 1'-0"
NC101
2025-0049
OVERALL NURSE CALL
PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
N
1/16" = 1'-0"NC101
1 OVERALL FLOOR PLAN
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
DISPLAY
2 BR
TLT
131.1
ALCOVE
1C4.2
2 BR
2 BR
TLT
133.1
2 BR
2 BR
TLT
135.1
2 BR
STOR
1C4.3
STOR
1C4.4
CLEAN/STORAGE
TLT
143.1
2 BR
SOILED
TELE
CEN BATH
JAN
CORR
1C5
ALCOVE
1C5.1
2 BR
2 BR
TLT
144.1
2 BR
2 BR
TLT
146.1 DIS
PL
AY
DIS
PL
AY
DISPLAY
ALCOVE
1C5.2
TLT
148.1
2 BR
2 BR
2 BR
2 BR
TLT
150.1
TYP
2 BR
2 BR
TYP
TLT
152.1
STOR
1C5.4
STOR
1C5.3
CORR
1C1
PANTRY
CHARTING ROOM
BISTRO
LAUND
CORR
1C1.1
N.S.
MED
PREP
REF
MED.
CARTS
R.N.
TYP TLT
1 BR
NURSING PROG.
SPECIALIST
WC/ALCOVE
2 BR
TLT
111.1ALCOVE
1C3.1
2 BR
2 BR
2 BR
TLT
113.1ALCOVE
1C3.2
TLT
115.1
2 BR
2 BR
DIS
PL
AY
2 BR
2 BR
TLT
117.1
DIS
PL
AY
TYP
1 BR
ALCOVE
1C3.3
TLT
119.1
HC TLT
MECH
CORR
1C2
TLT
122GAS CYL
123ELEC
TLT
125.1
2 BR
JAN
2 BR
TLT
127.1
ALCOVE
1C4.1
ENCLOSED PORCH
REC. THERAPY
OCC. THERAPY
330 PHYS. THERAPY
OFFICE
STOR
STOR
CORR
3C6
OFFICE
STOR
STOR
TLT
329.1
CORR
3C5
BARBER
VENDING
DRUGS
325.1
CHEMO
PREP
PHARMACY
MEN
203WOMEN
ENTRY
201.1
STOR
LIBRARY
DRYER
EQUIP.
207.1
DRYER
WASHER
STORAGE
STOR KEEP
CORR
2C5
STORAGE
REPAIRS
LKR
TLT
211.1TLT
210.1
LKR
VEST
2C2.1
PRE-RINSE
DEVOTIONAL
ROOM
CORR
2C1
LOBBY
OFFICE
OFFICE
OXY
TLT
COMM
COMP
SWITCHGEAR
ELEC
MECH
MECH
MECH
STOR
225 STORAGE
OFFICE
MECH
OFFICE
JAN
DRY STOR
OFFICE
JAN
OFFICE
TLT
236.1
TLT
236.2
KITCHEN
237.2
KITCHEN
SERVING
DINING
DIR. OF
NURSING
OFFICE
TLT
TLT
ADMIT.
RECPT.
WAITING
ADMIN.
OFFICE
CONFERENCE
ADMIN
OFFICE
STAFF
LOUNGE
LKR
TLT
322.1
CORR
3C4
TLT
323.1
LKR
MECH
JAN
OFFICE
OFFICE
317CORR
3C2
CORR
3C3
ALCOVE
3C3.1
VOL
OFFICE
OFFICE
CLERICAL
OFFICE
DINING
QUIET RM
PANTRY
CORR
4C1
CORR
4C1.1
CHARTING ROOM
TYP TLT
410.1
1 BR
MED.
CARTS
REF
MED
PREP
MED PREP
WC/ALCOVE
2 BR
TLT
411.1
2 BR
ALCOVE
4C3.1
DIS
PL
AY
DIS
PL
AY
2 BR
TLT
413.1
2 BR
ALCOVE
4C3.2 TLT
415.1
2 BR
2 BR
2 BR
2 BR
TLT
417.1
ALCOVE
4C3.3
MECH
HC TLT
TYP
1 BR
TLT
419.1
TLT
425.1
1 BR
ELEC
GAS CYL
TLT
CORR
4C2
STOR
4C4.3
STOR
4C4.4
JAN
2 BR
2 BR
TLT
427.1
ALCOVE
4C4.1
DISPLAY
2 BR
TLT
429.1
DISPLAY
2 BR
ALCOVE
4C4.2
2 BR
TLT
431.1
2 BR
2 BR
TLT
433.1
2 BR
2 BR
TLT
435.1
2 BR
CLEAN/STORAGE
TLT
443.1
1 BR
SOILED
TELE
BARBER SHOP
JAN
2 BR
TLT
444.1
ALCOVE
4C5.1
CORR
4C5
DIS
PL
AY
2 BR
2 BR
2 BR
TLT
446.1DIS
PL
AY
AWNING
ALCOVE
4C5.2
TLT
448.1
2 BR
2 BR
2 BR
TLT
450.1
2 BR
2 BR
TYP
TLT
452.1
STOR
4C5.3
STOR
4C5.4
2 BR
2 BR
TLT
129.1
2 BR
PATIO
TV LOUNGE
DELTA 200 HALL
DELTA 300 HALL
DELTA 100 HALL
ALPHA 100 HALL
ALPHA 300 HALL
ALPHA 200 HALL
PATIO
TYP
TLT
452.1
UNIT "A" UNIT "D"
UNIT "C"
UNIT B"
1&5
2 2
3a
3a
3b
3b
3c
3c
4 4
4 4
4 4
3g
3h
3j
3g
3h
3i
3q
3r
3s
3q
3r
3s
3p 3o 3n
3p 3o 3n
3f
3e
3d
3f
3e
3d
3m
3l
3k
3m
3l
3k
1&5
1&5
1&5
THE NARRATIVE BELOW DEPICTS A PROPOSED CONSTRUCTION SEQUENCING PLAN FOR THE
REPLACEMENT OF THE EXISTING NURSE CALL SYSTEM. THE CONTRACTOR SHALL CREATE A DETAILED PHASING AND CUTOVER PLAN AS DESCRIBED IN THE SPECIFICATIONS (SECTION 260010 1.5) WHICH IS TO BE COORDINATED WITH THE FACILITY AND SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL.
THE INTENT IS THAT THE EXISTING NURSE CALL SYSTEM BE TRANISITIONED TO THE NEW SYSTEM, AREA-BY-AREA IN SUCH A WAY THAT AN ACTIVE NURSE CALL SYSTEM SERVICES ARE MAINTAINED
THROUGHOUT THE DURATION OF CONSTRUCTION.
PHASE 1: INSTALL THE NEW NURSE CALL SYSTEM HEADEND EQUIPMENT AND POWER CONNECTIONS.
THE EXISTING NURSE CALL HEAD END SYSTEM AND ALL EXISTING DEVICES ARE TO REMAIN FUNCTIONAL
DURING THIS PHASE.
PHASE 2:
• INSTALL NEW RACEWAY (CABLE TRAY OR J-HOOKS) FOR THE NURSE CALL SYSTEM THROUGHOUT
THE CORRIDORS AS REQUIRED FOR A FULL AND COMPLETE SYSTEM.
• INSTALL CABLE IN RACEWAY AS REQUIRED FROM HEADEND TO NEW DEVICE LOCATIONS. PROVIDE SLACK CABLE AS NEEDED COILED IN CEILING FOR FINAL INSTALLATION TO NEW DEVICES IN LATER
PHASES.
• INSTALL NEW NURSE CALL MASTER STATIONS AT EACH NURSE STATION AS SHOWN ON THE NEW
CONSTRUCTION PLANS.
• INSTALL NEW ZONE LIGHTS AS SHOWN ON NEW CONSTRUCTION PLANS.
• THE EXISTING NURSE CALL HEADEND SYSTEM AND ALL EXISTING DEVICES (INCLUDING ZONE
LIGHTS AND MASTER STATIONS) ARE TO REMAIN FUNCTIONAL DURING THIS PHASE.
PHASE 3:
• PATIENT ROOM DEVICE TURNOVER IS TO COMPLETED IN GROUPS OF ROOMS AT A TIME.
COORDINATE WITH THE FACILITY FOR QUANTITY OF ROOMS THAT CAN BE TURNED OVER DURING
EACH PARTIAL SEQUENCE IN PHASE 3.
• PROVIDE ICRA BARRIERS AND NEGATIVE AIR MACHINES AS REQUIRED TO MAINTAIN FACILITY ICRA
PLAN.
• REMOVE AND DECOMISSION NURSE CALL DEVICES WITHIN EACH GROUP OF PATIENT ROOMS AND
BATHROOMS ALONG WITH THE CORESPONDING CORRIDOR LIGHT OUTSIDE OF THE ROOMS.
• INSTALL NEW CABLING AND NURSE CALL DEVICES FROM CORRIDOR TO DEVICE BOX LOCATIONS IN
ACCORDANCE WITH THE NEW CONSTRUCTION PLANS.
• INSTALL NEW NURSE CALL DEVICES WITHIN THE GROUP OF PATIENT ROOMS AND BATHROOMS AS
SHOWN ON NEW CONSTRUCTION PLANS.
• INSTALL NEW CORRIDOR LIGHT AS FOR EACH ROOM IN THE GROUP AS SHOWN ON NEW
CONSTRUCTION PLAN.
• BEFORE MOVING TO THE NEXT GROUP OF PATIENT ROOMS, CONTRACTOR IS TO CONFIRM NEW
NURSE CALL DEVICES INSTALLED FOR THIS SEQUENCE ARE FULLY FUNCTIONAL. COORDINATE WITH
AHCA FOR INSPECTION AND SIGN OFF OF NEW SYSTEM BEFORE ALLOWING PATIENTS TO
REOCCUPY THE ROOM.
• REPEAT PHASE 3 FOR EACH GROUP OF PATIENT ROOMS.
PHASE 4:
• REMOVE AND DECOMMISSION NURSE CALL DEVICES IN STAFF ROOMS AND PATIENT COMMON
AREAS. COORDINATE WITH FACILITY FOR GROUPING AND SCHEDULE OF SPACES IN THE PHASE.
• INSTALL NEW NURSE CALL DEVICES FOR STAFF ROOMS AND COMMON AREAS AS SHOWN ON THE
NEW CONSTRUCTION PLAN.
PHASE 5: ONCE THE NEW NURSE CALL SYSTEM IS FULLY FUNCTIONAL AND FINAL APPROVAL OF IT'S USE HAS BEEN OBTAINED, PROCEED WITH DEMOLITION OF ANY REMAINING COMPONENTS OF THE EXISTING
NURSE CALL SYSTEM INCLUDING THE HEADEND EQUIPMENT.
PROPOSED PHASING PLAN
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
A
C B
D
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC102
2025-0049
CONSTRUCTION
PHASING PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
1/16" = 1'-0"NC102
1 PROPOSED CONSTRUCTION PHASING PLAN
Rev. No. Rev. Date Rev. Description
N.S.
2 BR
TLT
129.1
2 BR
2 BR
TLT
127.1
2 BR
2 BR
TLT
125.1
JAN
ELEC
GAS CYL
TLT
MECH
HC TLT
TLT
119.1
TYP
1 BR
ALCOVE
1C3.3
2 BR
TLT
117.1
2 BR
2 BR
TLT
115.1
2 BR
DISPLAY
ALCOVE
1C3.2
2 BR
TLT
113.1
2 BR
2 BR
TLT
111.1
DISPLAY
ALCOVE
1C3.1
2 BR
1 BR
TYP TLT
WC/ALCOVE
109 NURSING
PROG.
SPECIALIST108
REF
M E
D
C A
R T
S
MED
PREP
R.N.
CORR
1C2
CORR
1C1.1
CHARTING ROOM
PANTRY
BISTRO
LAUND
CORR
1C1
TYP
2 BR
TYP
TLT
152.1
2 BR
2 BR
TLT
150.1
2 BR
2 BR
TLT
148.1
2 BR
2 BR
TLT
146.1
DISPLAY
2 BR
3092 BR
TLT
144.1
2 BR
CORR
1C5
DISPLAY
ALCOVE
1C5.2
ALCOVE
1C5.1
2 BR
JAN
TLT
143.1
CEN BATH
CLEAN/STORAGE
SOILED
138 TELE
STOR
1C5.4
STOR
1C5.3
2 BR
2 BR
TLT
135.1
2 BR
2 BR
TLT
133.1
2 BR
TLT
131.1
2 BR
DISPLAY
ALCOVE
1C4.2
ALCOVE
1C4.1
STOR
1C4.3
STOR
1C4.4
DISPLAY
PATIO
ALPHA 100 HALL
ALPHA 300 HALL
ALPHA 200 HALL
DS
DS
DS
DS
DS
SA C
L
NC
PC
CL CL CL CL
CLCLCLCL
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
CL CL CL CL CL
CLCLCLCLCLCL
CL
CL
C L
N C
T C
ZL
ZL
ZL
/1 NC201C /1 NC201C
NC401
NC401
NC401
/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401
/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401 /SEE 6 NC401
/SEE 6 NC401
/SEE 6 NC401
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND
FOR DEVICE DESCRIPTION.
EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL
DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE
VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.
THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN
THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A
GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT
AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL
BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS
RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE
PLANS OR NOT.
ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE
PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO
CAUSE ANY DISRUPTION TO THESE OTHER SPACES.
REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.
PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER
SUPPLIES, AND HEAD-END EQUIPMENT.
PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR
SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE
THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY
LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS
EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A
NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO
ENSURE OPERATION UPON COMPLETION OF THE PROJECT.
DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON
WIRING AND CONDUIT BACK TO SOURCE.
ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE
TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED
MEANS AND MATERIALS.
A.
B.
C.
D.
E.
F.
G.
H.
DEMOLITION SHEET NOTESDEMOLITION KEYNOTES
1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX
FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.
REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION
PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION
PHASING PLAN.
DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE
CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING
NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET
SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO
SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
A
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC201A
2025-0049
UNIT A NURSE CALL
DEMOLITION PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
1/8" = 1'-0"NC201A
1 UNIT A NURSE CALL DEMOLITION PLAN
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
COMM
SWITCHGEAR
COMP
TLT
OXY
OFFICE
OFFICE
STORAGE
CORR
2C5
REPAIRS
STOR KEEP
STORAGE
LKR
LKR
TLT
210.1
TLT
211.1
VEST
2C2.1
PRE-RINSE
WASHER
DRYER
DRYER
EQUIP.
207.1
DEVOTIONAL
ROOM
LIBRARY
STOR
CORR
2C1
ENTRY
201.1
WOMEN
MEN
LOBBY
DINING
SERVING
237.2
KITCHEN
OFFICE
OFFICE
TLT
236.2
TLT
236.1
MECH
DRY STOR
JAN
ELEC
MECH
STOR
STORAGE
OFFICE
MECH
OFFICE
228 JAN
MECH
KITCHEN
SA
SA
SA
PC
PC
PC
PC
PC
CL
CL CL
CL
C L
C L
N C C
N C C
N C C
(TYP)
(TYP)
(TYP)
ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND
FOR DEVICE DESCRIPTION.
EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL
DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE
VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.
THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN
THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A
GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT
AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL
BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS
RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE
PLANS OR NOT.
ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE
PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO
CAUSE ANY DISRUPTION TO THESE OTHER SPACES.
REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.
PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER
SUPPLIES, AND HEAD-END EQUIPMENT.
PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR
SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE
THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY
LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS
EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A
NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO
ENSURE OPERATION UPON COMPLETION OF THE PROJECT.
DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON
WIRING AND CONDUIT BACK TO SOURCE.
ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE
TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED
MEANS AND MATERIALS.
A.
B.
C.
D.
E.
F.
G.
H.
DEMOLITION SHEET NOTESDEMOLITION KEYNOTES
1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX
FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.
REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION
PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION
PHASING PLAN.
DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE
CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING
NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET
SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO
SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
B
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC201B
2025-0049
UNIT B NURSE CALL
DEMOLITION PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
1/8" = 1'-0"NC201B
1 UNIT B NURSE CALL DEMOLITION PLAN
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
WAITING
RECPT.
ADMIN.
OFFICE
CONFERENCE
ADMIN
CLERICAL
OFFICE
OFFICE
OFFICE
OFFICE
VOL
MECH
STAFF
LOUNGE
OFFICE
OFFICE
JAN
TLT
323.1
TLT
322.1
LKR
LKR
CORR
3C2
DIR. OF
NURSING
OFFICE
CORR
3C3
ALCOVE
3C3.1
TLT
TLT
ADMIT.
ENCLOSED PORCH
CORR
3C6
OFFICE
STOR STOR
REC. THERAPY
OCC. THERAPY
PHYS. THERAPY
OFFICE
STORSTOR
TLT
329.1
CORR
3C5
BARBER
VENDING
DRUGS
325.1
CHEMO
PREP
325PHARMACY
SA
SA
PC
SA
SA
SA
C L
C L
C L
CL
C L
N C B
N C B
N C B
/1 NC201A
/1 NC201D
/1 NC201A
/1 NC201D
(TYP)
(TYP)
(TYP)
ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND
FOR DEVICE DESCRIPTION.
EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL
DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE
VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.
THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN
THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A
GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT
AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL
BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS
RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE
PLANS OR NOT.
ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE
PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO
CAUSE ANY DISRUPTION TO THESE OTHER SPACES.
REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.
PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER
SUPPLIES, AND HEAD-END EQUIPMENT.
PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR
SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE
THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY
LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS
EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A
NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO
ENSURE OPERATION UPON COMPLETION OF THE PROJECT.
DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON
WIRING AND CONDUIT BACK TO SOURCE.
ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE
TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED
MEANS AND MATERIALS.
A.
B.
C.
D.
E.
F.
G.
H.
DEMOLITION SHEET NOTESDEMOLITION KEYNOTES
1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX
FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.
REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION
PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION
PHASING PLAN.
DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE
CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING
NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET
SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO
SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
C
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC201C
2025-0049
UNIT C NURSE CALL
DEMOLITION PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
1/8" = 1'-0"NC201C
1 UNIT C NURSE CALL DEMOLITION PLAN
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
2 BR
TLT
429.1
2 BR
2 BR
TLT
427.1
2 BR
1 BR
TLT
425.1
JAN
ELEC
GAS CYL
TLT
422MECH
HC TLT
TLT
419.1TYP
1 BR
ALCOVE
4C3.3
2 BR
TLT
417.1
2 BR
2 BR
TLT
415.1
2 BR
DISPLAY
ALCOVE
4C3.2
2 BR
TLT
413.1
2 BR
2 BR
TLT
411.1
DISPLAY
ALCOVE
4C3.1
2 BR
104 1 BR
102 TYP TLT
410.1
WC/ALCOVE
MED PREP
REF
MED.
CARTS
MED
PREP
CHARTING ROOM
CORR
4C2
CORR
4C1.1
QUIET RM
401 PANTRY
DINING
CORR
4C1
TYP
TLT
452.1
2 BR
2 BR
TLT
450.1
2 BR
2 BR
TLT
448.1
2 BR
AWNING
2 BR
TLT
446.1
DISPLAY
2 BR
2 BR
TLT
444.1
2 BR
CORR
4C5
DISPLAY ALCOVE
4C5.2
ALCOVE
4C5.1
1 BR
JAN
TLT
443.1
BARBER SHOP
CLEAN/STORAGE
SOILED
TELE
STOR
4C5.4
STOR
4C5.3
2 BR
2 BR
TLT
435.1
2 BR
2 BR
TLT
433.1
2 BR
TLT
431.1
2 BR
DISPLAY
ALCOVE
4C4.2
DISPLAY
ALCOVE
4C4.1
STOR
4C4.4
STOR
4C4.3
TV LOUNGE
DELTA 200 HALL
DELTA 300 HALL
DELTA 100 HALL
PATIO
TYP
TLT
452.1
SA
DS
DS
DS
DS
CL CL CL CL CL
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
CL CL CL CL CL
CLCLCLCLCL
CL
NC
N C
T C
CL CL CL CL
ZL
ZL
ZL
S A
NC401
/1 NC201C/1 NC201C
/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401
/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 5 NC401
/SEE 6 NC401
/SEE 5 NC401
/SEE 6 NC401
/SEE 6 NC401
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND
FOR DEVICE DESCRIPTION.
EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL
DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE
VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.
THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN
THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A
GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT
AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL
BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS
RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE
PLANS OR NOT.
ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE
PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO
CAUSE ANY DISRUPTION TO THESE OTHER SPACES.
REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.
PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER
SUPPLIES, AND HEAD-END EQUIPMENT.
PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR
SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE
THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY
LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS
EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A
NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO
ENSURE OPERATION UPON COMPLETION OF THE PROJECT.
DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON
WIRING AND CONDUIT BACK TO SOURCE.
ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE
TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED
MEANS AND MATERIALS.
A.
B.
C.
D.
E.
F.
G.
H.
DEMOLITION SHEET NOTESDEMOLITION KEYNOTES
1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX
FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.
REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION
PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION
PHASING PLAN.
DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE
CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING
NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET
SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO
SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
D
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC201D
2025-0049
UNIT D NURSE CALL
DEMOLITION PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
N
1/8" = 1'-0"NC201D
1 UNIT D NURSE CALL DEMOLITION PLAN
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
2 BR
TLT
129.1
2 BR
2 BR
TLT
127.1
2 BR
2 BR
TLT
125.1
JAN
ELEC
GAS CYL
TLT
MECH
HC TLT
TLT
119.1
TYP
1 BR
ALCOVE
1C3.3
2 BR
TLT
117.1
2 BR
2 BR
TLT
115.1
2 BR
DISPLAY
ALCOVE
1C3.2
2 BR
TLT
113.1
2 BR
2 BR
TLT
111.1
DISPLAY
ALCOVE
1C3.1
2 BR
1 BR
TYP TLT
WC/ALCOVE
109 NURSING
PROG.
SPECIALIST108
REF
M E
D
C A
R T
S
MED
PREP
R.N.
CORR
1C2
CORR
1C1.1
CHARTING ROOM
PANTRY
BISTRO
LAUND
CORR
1C1
TYP
2 BR
TYP
TLT
152.1
2 BR
2 BR
TLT
150.1
2 BR
2 BR
TLT
148.1
2 BR
2 BR
TLT
146.1
DISPLAY
2 BR
3092 BR
TLT
144.1
2 BR
CORR
1C5
DISPLAY
ALCOVE
1C5.2
ALCOVE
1C5.1
2 BR
JAN
TLT
143.1
CEN BATH
CLEAN/STORAGE
SOILED
138 TELE
STOR
1C5.4
STOR
1C5.3
2 BR
2 BR
TLT
135.1
2 BR
2 BR
TLT
133.1
2 BR
TLT
131.1
2 BR
DISPLAY
ALCOVE
1C4.2
ALCOVE
1C4.1
STOR
1C4.3
STOR
1C4.4
DISPLAY
PATIO
ALPHA 100 HALL
ALPHA 300 HALL
ALPHA 200 HALL
CL CL CL CL
CLCLCLCL
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
C L
CL CL CL CL CL
CLCLCLCLCLCL
CL
CL
DS
DS
DS
DS
DS
SA C
L
NC
PC
N C
T C
Z L
Z L
Z L
Z L
Z L
Z L
DC
DC
DC
DC
DC
CL
C L
S A
NC401
/1 NC301C /1 NC301C
NC401
NC401
NC401
NC-A
/SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401
/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401
/SEE 7 NC401
/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401 /SEE 1 NC401
/SEE 1 NC401
/SEE 1 NC401
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES WITH
CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS.
VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL
EQUIPMENT WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO
INSTALLATION OF EQUIPMENT.
REFER TO THE ONE-LINE DIAGRAM FOR BRANCH CIRCUIT AND CONDUIT SIZES.
ALL WALL/COLUMN MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED CFCI
UNI-STRUT SUPPORTS.
A.
B.
C.
D.
NEW WORK SHEET NOTESNEW WORK KEYNOTES
1 PROVIDE NEW DEVICE AS INDICATED. INSTALL IN EXISTING BACKBOX MADE
AVAILABLE PER DEMOLITION WHERE APPLICABLE. DEVICES SHALL BE INSTALLED
IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO SHEET
NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.
NEW ZONE LIGHT SHALL BE INSTALLED NEXT TO EXISTING ZONE LIGHT (WHERE
APPLICABLE). ZONE LIGHT TO OPERATE IN PARALLEL WITH EXISTING SYSTEM
UNTIL NEW SYSTEM IS FULLY OPERATIONAL AS OUTLINED IN THE PROPOSED
CONSTRUCTION PHASING PLAN ON SHEET NC102.
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
A
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC301A
2025-0049
UNIT A NURSE CALL
NEW CONSTRUCTION
PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
1/8" = 1'-0"NC301A
1 UNIT A NURSE CALL NEW CONSTRUCTION PLAN N
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
COMM
SWITCHGEAR
COMP
TLT
OXY
OFFICE
OFFICE
STORAGE
CORR
2C5
REPAIRS
STOR KEEP
STORAGE
LKR
LKR
TLT
210.1
TLT
211.1
VEST
2C2.1
PRE-RINSE
WASHER
DRYER
DRYER
EQUIP.
207.1
DEVOTIONAL
ROOM
LIBRARY
STOR
CORR
2C1
ENTRY
201.1
WOMEN
MEN
LOBBY
DINING
SERVING
237.2
KITCHEN
OFFICE
OFFICE
TLT
236.2
TLT
236.1
MECH
DRY STOR
JAN
ELEC
MECH
STOR
STORAGE
OFFICE
MECH
OFFICE
228 JAN
MECH
KITCHEN
SA
SA
SA
PC
PC
PC
PC
PC
CL
CL CL
CL
C L
C L
Z L
SA
CL
N C C
N C C
N C C
(TYP)
(TYP)
(TYP)
(TYP)
COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES WITH
CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS.
VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL
EQUIPMENT WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO
INSTALLATION OF EQUIPMENT.
REFER TO THE ONE-LINE DIAGRAM FOR BRANCH CIRCUIT AND CONDUIT SIZES.
ALL WALL/COLUMN MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED CFCI
UNI-STRUT SUPPORTS.
A.
B.
C.
D.
NEW WORK SHEET NOTESNEW WORK KEYNOTES
1 PROVIDE NEW DEVICE AS INDICATED. INSTALL IN EXISTING BACKBOX MADE
AVAILABLE PER DEMOLITION WHERE APPLICABLE. DEVICES SHALL BE INSTALLED
IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO SHEET
NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.
NEW ZONE LIGHT SHALL BE INSTALLED NEXT TO EXISTING ZONE LIGHT (WHERE
APPLICABLE). ZONE LIGHT TO OPERATE IN PARALLEL WITH EXISTING SYSTEM
UNTIL NEW SYSTEM IS FULLY OPERATIONAL AS OUTLINED IN THE PROPOSED
CONSTRUCTION PHASING PLAN ON SHEET NC102.
N
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED
SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE
MUST BE VERIFIED ON ANY ELECTRONIC COPIES
BURNS ENGINEERING, INC. I (813) 257-7442
400 N TAMPA ST, SUITE 925
TAMPA, FL 33602
Drawing No:
Job No:
Checked:
Drawn:
Scale:
Date:
Drawing Title:
Project Title:
KEY PLAN
B
Project Address:
6919 Parkway Boulevard Land O' Lakes, FL 34639
Project Facility Name:
Baldomero Lopez Memorial Veterans Nursing Home Project Name:
Nurse Call Replacement OPC Project #:
35/35960936-35654
06/26/2025
KW
JB
As indicated
NC301B
2025-0049
UNIT B NURSE CALL
NEW CONSTRUCTION
PLAN
FDVA BALDOMERO
LOPEZ VETERANS
NURSING HOME
NURSE CALL
REPLACEMENT
1/8" = 1'-0"NC301B
1 UNIT B NURSE CALL NEW CONSTRUCTION PLAN
Rev. No. Rev. Date Rev. Description
6/18/2025 AHCA STAGE III
WAITING
RECPT.
ADMIN.
OFFICE
CONFERENCE
ADMIN
CLERICAL
OFFICE
OFFICE
OFFICE
OFFICE
VOL
MECH
STAFF
LOUNGE
OFFICE
OFFICE
JAN
TLT
323.1
TLT
322.1
LKR
LKR
CORR
3C2
DIR. OF
NURSING
OFFICE
CORR
3C3
ALCOVE
3C3.1
TLT
TLT
ADMIT.
ENCLOSED PORCH
CORR
3C6
OFFICE
STOR STOR
REC. THERAPY
OCC. THERAPY
PHYS. THERAPY
OFFICE
STORSTOR
TLT
329.1
CORR
3C5
BARBER
VENDING
DRUGS
325.1
CHEMO
PREP
325PHARMACY
SA
SA
PC
SA
SA
SA
C L
C L
C L
CL
C L
Z L
Z L
C L
S A
N C B
N C B
N C B
/1 NC301A
/1 NC301D
/1 NC301A
/1 NC301D
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES WITH
CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS.
VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL
EQUIPMENT WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO
INSTALLATION OF EQUIPMENT.
REFER TO THE ONE-LINE DIAGRAM FOR BRANCH CIRCUIT AND CONDUIT SIZES.
ALL WALL/COLUMN MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED CFCI
UNI-STRUT SUPPORTS.
A.
B.
C.
D.
NEW WORK SHEET NOTESNEW WORK…