These documents are contract drawings for a Nurse Call System Replacement project for the Florida Department of Veterans' Affairs (FDVA) at the Baldomero Lopez Veterans Nursing Home located in Land O' Lakes, Florida. The project involves a complete replacement of the existing Dukane nurse call system with a new Rauland system, including removing all existing nurse call components and cabling unless specifically noted otherwise. The project is scheduled for completion by 06/26/2025 and is currently in the AHCA Stage III phase. The facility is a comprehensive veterans nursing home with multiple units (A, B, C, and D) containing various room types including single and double bedrooms, bathrooms, staff areas, and common spaces.

The project scope includes installing new nurse call devices, master stations, zone lights, and associated infrastructure across all units, with a detailed phasing plan to ensure continuous nurse call coverage during the transition. The contractor will be responsible for providing new cabling, raceways, power connections, and coordinating with facility staff to minimize disruptions. Additional requirements include providing 5% attic stock for new devices, a 5-year extended material and labor warranty, comprehensive staff training, and as-built documentation. The project will adhere to multiple codes and standards, including the 2020 Florida Electrical Code, 2021 NFPA 99 Health Care Facilities Code, and 2023 Florida Building Code. The electrical infrastructure will involve modifications to existing electrical panels, with new panels (EC-D2) being installed to support the nurse call system.

View the file

Other files

File Type Posted
FDVA Baldomero Lopez - BID SET - Electrical.pdf PDF
FDVA- Lopez - Division 26,27 Specifications.pdf PDF
ITB-26-001B- Lopez-Nurse Call System.pdf PDF
ITB-26-001B PreBid Attendance Sheet.pdf PDF
ITB-26-001B- Lopez-Nurse Call System.pdf PDF
ITB-26-001B- Bid Opening Attendance Sheet.pdf PDF
FDVA-ITB-26-001B-ADDENDUM NO.1.pdf PDF
ITB-26-001B- Bid Opening Attendance Sheet.pdf PDF
ITB-26-001B PreBid Attendance Sheet.pdf PDF
ITB-26-001B- Lopez-Nurse Call System.pdf PDF
FDVA- Lopez - Division 26,27 Specifications.pdf PDF
Public Notice of Cancellation.pdf PDF
FDVA Baldomero Lopez - BID SET - Electrical.pdf PDF
FDVA-ITB-26-001B-ADDENDUM NO.1.pdf PDF
ITB-26-001B- Lopez-Nurse Call System.pdf PDF
FDVA- Lopez - Division 26,27 Specifications.pdf PDF
FDVA-ITB-26-001B-ADDENDUM NO.1.pdf PDF
ITB-26-001B Notice of Intent to Award.pdf PDF
ITB-26-001B- Bid Opening Tabulation Sheet.pdf PDF
FDVA- Lopez - Division 26,27 Specifications.pdf PDF
FDVA- Lopez - Division 26,27 Specifications.pdf PDF
ITB-26-001B PreBid Attendance Sheet.pdf PDF
FDVA Baldomero Lopez - BID SET - Electrical.pdf PDF
FDVA Baldomero Lopez - BID SET - Electrical.pdf PDF
ITB-26-001B Notice of Intent to Award.pdf PDF
ITB-26-001B PreBid Attendance Sheet.pdf PDF
ITB-26-001B- Lopez-Nurse Call System.pdf PDF
ITB-26-001B- Bid Opening Tabulation Sheet.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Drawing No:

Project Status:

Drawing Title:

BURNS PROJECT NO:

DATE:

CONTRACT DRAWINGS FOR:

AHCA CLIENT CODE / FILE NO: 35/35960936-35654 / 002

PROJECT ADDRESS:

PROJECT PHASE:

CAMPUS MAP

BURNS ENGINEERING, INC | (813) 257 7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

CA# 26183

PROJECT SCOPE:

THIS PROJECT INCLUDES THE COMPLETE REPLACEMENT

OF THE EXISTING NURSE CALL SYSTEM WITH A NEW

SYSTEM PROVIDED BY RAULAND. THE EXISTING DUKANE

SYSTEM IS NO LONGER SUPPORTED. ALL EXISTING

NURSE CALL COMPONENTS AND CABLING SHALL BE

REMOVED UNLESS NOTED OTHERWISE.

G000

COVER SHEET

AHCA STAGE III

2025-0049

FDVA BALDOMERO LOPEZ VETERANS NURSING HOME

NURSE CALL REPLACEMENT

6919 PARKWAY BOULEVARD

LAND O’ LAKES, FL 34639

06/26/2025

AHCA STAGE III

NURSE CALL SHEET INDEX

G000 COVER SHEET

NC000 NURSE CALL/RTLS LEGENDS AND GENERAL NOTES

NC001 NURSE CALL/RTLS SINGLE LINE DIAGRAMS

NC101 OVERALL NURSE CALL PLAN

NC102 CONSTRUCTION PHASING PLAN

NC201A UNIT A NURSE CALL DEMOLITION PLAN

NC201B UNIT B NURSE CALL DEMOLITION PLAN

NC201C UNIT C NURSE CALL DEMOLITION PLAN

NC201D UNIT D NURSE CALL DEMOLITION PLAN

NC301A UNIT A NURSE CALL NEW CONSTRUCTION PLAN

NC301B UNIT B NURSE CALL NEW CONSTRUCTION PLAN

NC301C UNIT C NURSE CALL NEW CONSTRUCTION PLAN

NC301D UNIT D NURSE CALL NEW CONSTRUCTION PLAN

NC401 NURSE CALL ENLARGED PLANS

NC501 NURSE CALL/RTLS DETAILS

NC601 PANELBOARD SCHEDULES

Grand total: 16

PLAN DETAIL REFERENCE

SHEET

SHEET

PLAN

ROOM

X

X

ELEVATION REFERENCE

SECTION REFERENCE

NORTH ARROW

ROOM NAME AND NUMBER

DETAIL / DIAGRAM SPECIFIC KEYED NOTE DESIGNATION

REVISION OR ADDENDUM DESIGNATION

SHEET KEYED NOTE DESIGNATION

DETAIL

SHEET

DETAIL

DETAIL

SHEET

X

MATCHLINE

TDR BOUNDARY

CONDUIT OR SLEEVE

LADDER RACK

CONDUIT CONCEALED IN

CONDUIT IN SLAB

CONDUIT SLEEVE

CONDUIT CAPPED

TURNING UP

CONDUIT OR SLEEVE

TURNING DOWN

CEILING OR WALL

OR UNDERGROUND

TAG INFORMATION

HOMERUN

CABLE TRAY

EZ-PATH

J-HOOK PATHWAY

ENCLOSED EQUIPMENT CABINET

(CLEARANCE SPACE SHOWN DASHED)

VERTICAL WIRE MANAGEMENT,TYP

OPEN FRAME EQUIPMENT RACK

WALL MOUNTED CABINET

SYMBOLOGY TAG INFORMATION

PANEL/WALL MOUNT EQUIPMENT

F R

O N

T

R E

A R

SCOPE OF WORK:

THIS PROJECT INCLUDES THE COMPLETE REPLACEMENT OF THE

EXISTING NURSE CALL SYSTEM WITH A NEW SYSTEM PROVIDED BY

RAULAND. THE EXISTING DUKANE SYSTEM IS NO LONGER SUPPORTED.

ALL EXISTING NURSE CALL COMPONENTS AND CABLING SHALL BE

REMOVED UNLESS NOTED OTHERWISE.

CODES AND STANDARDS:

GENERAL NOTES:

NC

DS

SA

PC

PA

SP

DP

FB

NCTC

DC

CL

ZL

AX AX AXAX

PS

TECHNOLOGY NURSE CALL ABBREVIATIONS

A/AMP

AC

ADA

AEC

AFF

AFG

AHJ

AL

AMP

AP

AV

AWG

BC

BFC

BMS

C

CAT

CATV

CH

CM

CMM

CMPT

CPST

CPU

CR

CU

DB

DIA

DWG

EA

EC

EIA

ELEC

ELEV

EMER

EMT

EO

EQ

EX

FA

FL

FMC

FO

FPD

GC

GRD

GRS

HDMI

HVAC

HZ

IG

IMC

IP

IP

IR

ISC

IT

ITO

JB

KVA

KW

LAN

LCD

LED

LTG

LV

M

MATV

MFR

MIC

MISC

MM

MMFO

MNS

N/A

NEC

NEMA

NFPA

NIC

NTS

OAR

OC

OFNR

OP

OTS

PA

PB

PBX

PC

PLY

PNL

POE

POSU

PP

PR

PSTN

PVC

RF

RGB

RGS

RM

RMC

RU

SCH/SCHED

SS

STB

TBD

TEC

TELE

TELECOM

TDR

TGB

TIA

TMGB

TS

TSER

TV

TYP

UL

UON

UPS

UTP

V

VAC

VC

VDC

VGA

VOIP

W/

W/IN

W/O

WAP

WIFI

WLAN

XMTR

AMPERE

ABOVE COUNTER

AMERICANS WITH DISABILITIES ACT

ACOUSTIC ECHO CANCELLATION

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTHORITY HAVING JURISDICTION

ALUMINUM

AMPLIFIER

WIRELESS ACCESS POINT

AUDIO VIDEO

AMERICAN WIRE GAUGE

BELOW CEILING

BELOW FINISHED CEILING

BUILDING MANAGEMENT SYSTEM

CONDUIT

CATEGORY

CABLE TELEVISION

CHANNEL

CENTIMETER

COMMUNICATIONS

COMPONENT

COMPOSITE

CENTRAL PROCESSING UNIT

COMMUNICATIONS ROOM

COPPER

DECIBEL

DIAMETER

DRAWING

EACH

ELECRICAL CONTRACTOR

ELECTRONICS INDUSTRY ASSOCIATION

ELECTRIC/ELECTRICAL

ELEVATOR

EMERGENCY

ELECTRICAL METALLIC TUBING

EQUAL

EQUALIZER

EXISTING

FIRE ALARM

FLOOR

FLEXIBLE METAL CONDUIT

FIBER OPTIC

FLAT PANEL DISPLAY

GENERAL CONTRACTOR

GROUND

GALVANIZED RIGID STEEL

HIGH DEFINITION MULTIMEDIA INTERFACE

HEATING VENTILATING AIR CONDITIONING

HERTZ

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

INTERNET PROTOCOL

INPUT PANEL

INFRARED

INTELLIGENT SYSTEM CONTROLLER

INFORMATION TECHNOLOGY

INFORMATION TECHNOLOGY OUTLET

JUNCTION BOX

KILOVOLT AMPERE

KILOWATT

LOCAL AREA NETWORK

LIQUID CRYSTAL DISPLAY

LIGHT EMITTING DIODE

LIGHTING

LOW VOLTAGE

METER

MASTER ANTENNA TELEVISION

MANUFACTURER

MICROPHONE

MISCELLANEOUS

MILLIMETER

MULTI-MODE FIBER OPTIC

MASS NOTIFICATION SYSTEM

NOT AVAILABLE/NOT APPLICABLE

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NOT IN CONTRACT

NOT TO SCALE

OWNER AUTHROIZED REPRESENTATIVE

ON CENTER

OPTICAL FIBER NONCONDUCTIVE RISER

OUTPUT PANEL

OFF THE SHELF

PUBLIC ADDRESS

PULL BOX

PRIVATE BRANCH EXCHANGE

PERSONAL COMPUTER

PLYWOOD

PANEL

POWER OVER INTERNET

POWER SUPPLY MODULE

PATCH PANEL/POWER PANEL

PAIR

PUBLIC SWITCHED TELEPHONE NETWORK

POLYVINYL CHLORIDE

RADIO FREQUENCY

RED GREEN BLUE

RIGID GALVANIZED STEEL

ROOM

RIGID METAL CONDUIT

RACK UNIT

SCHEDULE

STAINLESS STEEL

SET TOP BOX

TO BE DETERMINED

TELECOMMUNICATIONS EQUIPMENT CENTER

TELEPHONE

TELECOMMUNICATIONS

TELECOMMUNICATIONS DISTRIBUTION ROOM

TELECOMMUNICATIONS GROUND BUSBAR

TELECOMMUNICATIONS INDUSTRY ASSOCIATION

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TOUCH SCREEN

TELECOMMUNICATIONS SERVICE ENTRANCE ROOM

TELEVISION

TYPICAL

UNDERWRITER'S LABORATORIES

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNSHIELDED TWISTED PAIR

VOLT

VOLT ALTERNATING CURRENT

VOLUME CONTROL

VOLT DIRECT CURRENT

VIDEO GRAPHICS ARRAY

VOICE OVER INTERNET PROTOCOL

WITH

WITHIN

WITHOUT

WIRELESS ACCESS POINT

WIRELESS FIDELITY

WIRELESS LAN

TRANSMITTER

GENERAL NOTES

GENERAL SYMBOLS

CONDUIT AND RACEWAY

EQUIPMENT

DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT DRAWN TO

SCALE. CONTRACTOR IS RESPONSIBLE FOR COORDINATING FINAL

ROUTING OF ALL SERVICES AND DISTANCES WITH EXISTING

CONDITIONS AND WITH ALL OTHER TRADES.

ANY DISCREPANCIES BETWEEN THE PLANS AND ACTUAL FIELD

CONDITIONS MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ENGINEER OR DESIGNATED REPRESENTATIVE FOR

CLARIFICATION.

ALL WORK IS TO BE DONE IN A THOROUGH AND PROFESSIONAL

MANNER ACCORDING TO INDUSTRY AND MANUFACTURERS'

STANDARDS AND WILL BE SUBJECT TO INSPECTION AND ACCEPTANCE.

WORK THAT IS DEEMED SUB-STANDARD WILL BE SUBJECT TO

REPLACEMENT OR REPAIR AT NO ADDITIONAL COST TO THE OWNER

OR GENERAL CONTRACTOR.

PERMITS & INSPECTIONS: CONTRACTOR SHALL OBTAIN ALL REQUIRED

PERMITS AND SCHEDULE ALL INSPECTIONS WITH THE AUTHORITY

HAVING JURISDICTION (AHJ).

FACILITY OPERATIONS: WORK SHALL BE PERFORMED IN A

CONTINUOUSLY OCCUPIED HEALTHCARE FACILITY. COORDINATE ALL

ACTIVITIES, SHUTDOWNS, AND ACCESS WITH FACILITY STAFF. LIMIT

DISRUPTIONS AND MAINTAIN CONTINUITY OF CARE AT ALL TIMES.

SYSTEM COORDINATION: COORDINATE ALL DEVICE TYPES, LOCATIONS,

CABLING, AND INFRASTRUCTURE WITH THE NURSE CALL SYSTEM

VENDOR. CONTRACTOR SHALL REVIEW AND VERIFY VENDOR-

PROVIDED SHOP DRAWINGS PRIOR TO INSTALLATION.

CABLING: ALL CABLING SHALL BE REPLACED WITH NEW, VENDOR-

APPROVED CABLE TYPES. EXISTING CABLING SHALL BE REMOVED AND

DISPOSED OF PER FACILITY REQUIREMENTS. ALL CABLE RUNS SHALL

COMPLY WITH NEC AND MANUFACTURER SPECIFICATIONS.

CABLE PATHWAYS: EXISTING CONDUITS AND RACEWAYS MAY BE

REUSED WHERE ADEQUATE AND IN GOOD CONDITION. VERIFY ALL

PATHWAYS PRIOR TO INSTALLATION. DAMAGED OR UNDERSIZED

PATHWAYS SHALL BE REPLACED.

DEVICE LOCATIONS: REUSE EXISTING DEVICE LOCATIONS UNLESS

OTHERWISE NOTED OR REQUIRED BY THE VENDOR. COORDINATE ANY

ADDITIONS OR RELOCATIONS WITH FACILITY STAFF TO MEET CLINICAL

WORKFLOW NEEDS.

POWER REQUIREMENTS: PROVIDE 120V POWER CONNECTIONS TO ALL

SYSTEM COMPONENTS REQUIRING LINE VOLTAGE. COORDINATE EXACT

REQUIREMENTS WITH SYSTEM VENDOR. PROVIDE CONNECTIONS FROM

CRITICAL BRANCH

DEMOLITION: REMOVE AND TURN OVER ALL FUNCTIONING EXISTING

DEVICES TO THE FACILITY. PROPERLY DISPOSE OF ANY NON-

FUNCTIONING DEVICES, EXISTING CABLING, POWER SUPPLIES AND

HEAD-END EQUIPMENT. PATCH AND REPAIR ANY DAMAGE TO WALLS,

CEILINGS, OR FINISHES RESULTING FROM REMOVAL.

FIRESTOPPING: THE CONTRACTOR IS REQUIRED TO PROPERLY FIRE-

STOP ANY CORES UTILIZED FOR THE PLACEMENT OF

COMMUNICATIONS CABLING WITH APPROVED FIRE-STOPPING

COMPOUND AND ACCORDING TO LOCAL AND NATIONAL CODES.

ALL PENETRATED STRUCTURES ARE TO BE RETURNED TO ORIGINAL

CONDITION AND FIRE RATING.

LABELING: ALL NEW DEVICES AND CABLING SHALL BE LABELED PER

VENDOR REQUIREMENTS AND SYSTEM DIAGRAMS. INCLUDE CIRCUIT

IDENTIFICATION AND TERMINAL LABELING AS APPLICABLE.

CUTOVER PLAN: PROVIDE A DETAILED CUTOVER PLAN TO ENSURE

CONTINUOUS NURSE CALL COVERAGE DURING SYSTEM TRANSITION.

COORDINATE PHASING AND TEMPORARY SOLUTIONS WITH FACILITY

STAFF.

TEMPORARY CALL SYSTEM: IF EXISTING NURSE CALL COVERAGE MUST

BE INTERRUPTED, PROVIDE APPROVED TEMPORARY SIGNALING

METHODS (E.G., PORTABLE CALL STATIONS OR WIRELESS SYSTEMS)

FOR AFFECTED PATIENT AREAS.

TESTING & CERTIFICATION: UPON COMPLETION, THE NURSE CALL

SYSTEM SHALL BE TESTED IN THE PRESENCE OF THE FACILITY,

ENGINEER, AND VENDOR. PROVIDE A LETTER CERTIFYING THE SYSTEM

MEETS OPERATIONAL, CODE, AND MANUFACTURER REQUIREMENTS.

TRAINING: PROVIDE COMPREHENSIVE TRAINING FOR CLINICAL AND

MAINTENANCE STAFF. COORDINATE TRAINING SCHEDULE WITH THE

FACILITY PRIOR TO FINAL ACCEPTANCE.

ATTIC STOCK & WARRANTY: PROVIDE 5% ATTIC STOCK FOR NEW

NURSE CALL DEVICES INCLUDING ZONE LIGHTS, CORRIDORS LIGHTS,

PATIENT CALL STATIONS, STAFF ASSIST STATIONS, DUTY STATIONS,

AND SHOWER/BATHROOM PULL CORD STATIONS.

SYSTEM TO BE FURNISHED WITH A 5-YEAR EXTENDED MATERIAL AND

LABOR WARRANTY.

AS-BUILT DOCUMENTATION: FURNISH AS-BUILT DRAWINGS, WIRING

DIAGRAMS, O&M MANUALS, WARRANTY INFORMATION, AND

PROGRAMMING BACKUPS TO THE OWNER AT PROJECT CLOSEOUT.

ALL WORK SHALL COMPLY WITH APPLICABLE CODES AND STANDARDS

INCLUDING, BUT NOT LIMITED TO:

•2020 FLORIDA ELECTRICAL CODE (NATIONAL ELECTRICAL CODE 2020)

•2021 NFPA 99 HEALTH CARE FACILITIES CODE

•2021 NFPA 101 LIFE SAFETY CODE

•2023 FLORIDA BUILDING CODE

•2023 FLORIDA EXISTING BUILDING CODE

•2023 FLORIDA FIRE PREVENTION CODE.

•LOCAL AMENDMENTS

•2022 FACILITY GUIDELINES INSTITUTE - RESIDENTIAL

•FLORIDA ADMINISTRATIVE CODE 59A-4

TECHNOLOGY NURSE CALL SYMBOL LEGEND

NURSE CONSOLE MASTER STATION

DUTY STATION

PULL-CORD STATION (WATERPROOF)

MTG. HEIGHTDESCRIPTIONSYMBOL

45" AFF, UON

45" AFF, UON

45" AFF

45" AFF

45" AFF

18" AFF

45" AFF

45" AFF, UON

1) MANUFACTURE SPECIFIED IS FOR NEW CONSTRUCTION DEVICES ONLY. DEVICES ON DEMOLITION PLAN USE EQUIVALENT SYMBOLS FOR LAYOUT CONSISTENCY.

2) THIS IS A STANDARD SYMBOL LIST. ALL SYMBOLS MAY NOT APPEAR ON THIS PROJECT.

STAFF ASSIST STATION

PULL-CORD STATION W / AUDIO

SINGLE PATIENT STATION

DUAL PATIENT STATION

FEATURE BED RECEPTACLE

RAULAND

R5KCONSV3

RAULAND

R5KSDTY

RAULAND

R4KPB12

RAULAND

R5KPC11WP

RAULAND

R5KAUDPCV2

RAULAND

R5KPS1LCA

RAULAND

R5KPD2EA

RAULAND

NCBED

MANUFACTURE

NURSE CALL CABINET

RAULAND

NC2828

DOMELESS CONTROLLER

RAULAND

CLA246

CORRIDOR LIGHT

ZONE LIGHT

RAULAND

CLA246

RAULAND

CLA246

BACK BOXES

NOTE 1

DUAL GANG

EXISTING TO REMAIN DEMOLISHED IMPACTEDNEW

1) SURFACE MOUNTABLE; COMPATIBLE WITH SINGLE AND DUAL GANG BOXES. THE METAL HOUSING ALSO PERMITS THE R5KDC06 TO BE LOCATED ABOVE

CEILING TILES OR TO BE PLACED INTO A WALL.

SCHEDULE NOTES:

GENERAL NOTES:

PILLOW SPEAKER

RAULAND

NCPSXXX

DUAL GANG

SINGLE GANG

DUAL GANG

DUAL GANG

DUAL GANG

SINGLE GANG

3-GANG

DUAL GANG

CONSTRUCT BARRIERS TO PREVENT DUST AND DANGEROUS PATHOGENS FROM ENTERING PATIENT

CARE AND ENSURE THAT BARRIERS ARE IMPERMEABLE TO FUNGAL SPORES AND IN COMPLIANCE

WITH LOCAL FIRE CODES. INSTALL DOORS WITH SELF CLOSING DEVICES ON ICRA PARTITIONS.

THE HOSPITAL ICRA REQUIREMENTS MUST BE MET AT ALL TIMES. THE ICRA STATUS SHALL BE

REVIEWED WEEKLY WITH OWNER.

CONTRACTOR SHALL UTILIZE CRITICAL BRANCH POWER FOR ANY DUST MITIGATION EQUIPMENT (I.E.

NEGATIVE AIR MACHINE). IF CRITICAL BRANCH POWER IS NOT READILY ACCESSIBLE, CONTRACTOR SHALL RUN A TEMPORARY CRITICAL CIRCUIT BACK TO THE NEAREST CRITICAL BRANCH PANEL. AT NO TIMES SHALL THERE BE EXTENSION CORDS AND/OR TEMPORARY WIRING LAID OUT WITHIN THE EGRESS CORRIDORS AND/OR PATIENT AREAS. ANY/ALL TEMPORARY WIRING SHALL BE INSTALLED

WITHIN THE CEILING SPACE.

CONTRACTOR TO MAINTAIN ALL EXITS DURING CONSTRUCTION IN COMPLIANCE WITH: NFPA

101-4.6.10 2018 "CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS". NFPA101-7.1.10 2018 "MEANS OF EGRESS RELIABILITY" NFPA101-18.7.9 2018 "CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS" NFPA 241 2013 -"STANDARD FOR SAFEGUARDING CONSTRUCTION, AND DEMOLITION

OPERATIONS".

PROVIDE AND MAINTAIN AIR PRESSURE AND DUST CONTROL IN ALL DEMOLITION AND

CONSTRUCTION AREAS WHEN APPLICABLE.

CONTRACTOR TO REFER TO FACILITY ICRA REQUIREMENTS PRIOR TO PERFORMING ANY WORK

THAT MAY REQUIRE CUTTING OR PRODUCING DUST AND/OR DEBRIS. CONTRACTOR TO MAINTAIN

NEGATIVE AIR BALANCE WHERE REQUIRED AT ALL TIMES, AND PROVIDE DUST TIGHT PARTITIONS

AND TACKY MAT WHERE REQUIRED. REFER TO ICRA REQUIREMENTS AND FACILITY ICRA PLAN

PRIOR TO BID.

CONTRACTOR TO COORDINATE WITH THE FACILITY FOR CONTRACTOR ACCESS. ANY ITEMS,

EQUIPMENT OR MATERIAL BROUGHT INTO THE FACILITY MUST BE IN COVERED CONTAINERS.

PROVIDE COPPER #10AWG BONDING CONNECTION BETWEEN THE GROUNDING TERMINAL BUSES OF

THE CRITICAL BRANCH PANELS AND THE NORMAL BRANCH PANELS AFFECTED BY SCOPE OF WORK.

A.

B.

C.

D.

E.

F.

G.

H.

ICRA GENERAL NOTES - ELECTRICAL

CONTRACTOR SHALL OBTAIN FROM THE OWNER A COPY OF THE INFECTION CONTROL RISK

ASSESSMENT (ICRA) PREPARED FOR THIS PROJECT. CONTRACTOR SHALL REVIEW THE

REQUIREMENTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH THOSE

REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS OF THE

CONSTRUCTION AREA, AND WHERE PHASING APPLIES SHALL ADHERE TO THE PHASING PLAN ANY

WORK OUTSIDE THE CONSTRUCTION AREA SHALL BE COORDINATED WITH THE OWNER AND

PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER THE SUPERVISION OF THE

OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICRA COMMITTEE OFFICER.

TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, THE CONTRACTOR SHALL ENDEAVOR TO

MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN AREAS SURROUNDING AND ADJACENT TO THE CONSTRUCTION WORK ZONE AND ELSEWHERE IN THE FACILITY. IT SHOULD BE ANTICIPATED

THAT THE ICRA REPORT WILL REQUIRE MEASURES TO THIS EFFECT INCLUDING ERECTION OF

CONSTRUCTION ZONE BARRIERS AND PROVISION OF NEGATIVE AIR PRESSURE IN THE

CONSTRUCTION ZONE RELATIVE TO OTHER AREAS OF THE FACILITY.

IN ADDITION TO THE MEETING THE REQUIREMENTS OF THE ICRA REPORT, THE CONTRACTOR AT A

MINIMUM SHALL PROVIDE EQUIPMENT AND COMPONENTS NECESSARY TO CREATE A NEGATIVE

PRESSURE IN THE CONSTRUCTION WORK ZONE RELATIVE TO ADJACENT AREA. EXISTING HVAC

SYSTEMS AND COMPONENTS SHALL NOT BE USED FOR THIS FUNCTION, UNLESS SPECIFICALLY

APPROVED BY THE OWNER'S INFECTION CONTROL OFFICER. THE CONCEPT AND ALL ASPECTS OF THIS WORK SHALL BE DONE IN ACCORDANCE WITH THE ICRA REQUIREMENTS AND AT A MINIMUM

AS FOLLOWS:

1. VERIFY ALL EXISTING DUCTWORK WHICH PASSES THROUGH THE CONSTRUCTION

ZONEAND IS TO REMAIN, IS SEALED AND PROTECTED DURING THE CONSTRUCTION DURATION.

2. AIR REMOVED FROM THE CONSTRUCTION ZONE SHALL BE FILTERED AND/ORDISCHARGED AS

DIRECTED BY THE ICRA REPORT.

3. PRESENT THE NEGATIVE AIR PRESSURE PLAN TO THE OWNER FOR APPROVAL BY THE

INFECTION CONTROL COMMITTEE.

4. PROVIDE MEANS TO MONITOR AND VERIFY NEGATIVE PRESSURE IS BEING MAINTAINED

IN ACCORDANCE WITH THE ICRA REPORT, AND PROVIDE DOCUMENTATION TO THE

OWNER AS REQUIRED

COORDINATE IN ADVANCE ANY REQUIRED EQUIPMENT SHUTDOWN WITH THE OWNER, AND VERIFY

BEFORE SHUTDOWN THAT EXISTING OR DESIRED AIR PRESSURE RELATIONSHIPS WILL NOT BE

ADVERSELY AFFECTED.

FOR MINOR WORK OUTSIDE OF THE AREA SHOWN UTILIZE PORTABLE AIRBORNE PARTICULATE

CONTAINMENT UNITS AS MANUFACTURED BY MINTIE TECHNOLOGIES, INC. OR EQUIVALENT. ALL

PROCEDURES STATED IN THE ICRA SHALL BE FOLLOWED.

A.

B.

C.

D.

E.

ICRA GENERAL NOTES - MECHANICAL

NURSE CALL SHEET INDEX

G000 COVER SHEET

NC000 NURSE CALL/RTLS LEGENDS AND GENERAL NOTES

NC001 NURSE CALL/RTLS SINGLE LINE DIAGRAMS

NC101 OVERALL NURSE CALL PLAN

NC102 CONSTRUCTION PHASING PLAN

NC201A UNIT A NURSE CALL DEMOLITION PLAN

NC201B UNIT B NURSE CALL DEMOLITION PLAN

NC201C UNIT C NURSE CALL DEMOLITION PLAN

NC201D UNIT D NURSE CALL DEMOLITION PLAN

NC301A UNIT A NURSE CALL NEW CONSTRUCTION PLAN

NC301B UNIT B NURSE CALL NEW CONSTRUCTION PLAN

NC301C UNIT C NURSE CALL NEW CONSTRUCTION PLAN

NC301D UNIT D NURSE CALL NEW CONSTRUCTION PLAN

NC401 NURSE CALL ENLARGED PLANS

NC501 NURSE CALL/RTLS DETAILS

NC601 PANELBOARD SCHEDULES

Grand total: 16

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC000

2025-0049

NURSE CALL/RTLS

LEGENDS AND

GENERAL NOTES

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

FIRE RATED WALL PARTITION LEGEND

4 HOUR FIRE RATED PARTITION

SMOKE BARRIER 1 HOUR FIRE RATED PARTITION

1 HOUR FIRE RATED PARTITION

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

1 6/19/2025 AHCA STAGE III REV 1

6/26/2025 BID SET

EC-D1 (EXIST)

208/120V 3Ø, 4W

400A (10,000 AIC)

208/120V

110A MCB

(10,000 AIC)

(5,346 SCA)

EC-A2 (EXIST)

110A

(4,491 SCA)

XFMER T-6

EC-D (EXIST)

225AF

225AT

125AF

125AT

75 KVA

480V-120/208V 3Ø, 4W

480/277V 3Ø, 4W

225A (14,000 AIC)

EXISTING

PANEL 'EC'

XFMER T-10

EC-A (EXIST)

480/277V 3Ø, 4W

225A (14,000 AIC) 225AF

225AT

50A/3P

30 KVA

480V-120/208V 3Ø, 4W

EXISTING

PANEL 'EC'

(8,656 SCA)(6,143 SCA)

400AF

250AT

SPD

20A/3P60A/3P

208/120V

60A MLO

(10,000 AIC)

EC-D2 (NEW)

20A

LRGST BRKR

4 #6AWG, 1#10, 1"C

SPD

PA

NCTC NC ZL

SP

PSPC

PA DP

PSPC

DS

CLEAN/

STORAGE 137

TYPICAL 2 BEDROOM

(30 QTY)

TYPICAL 1 BEDROOM

(2 QTY)

NC-A

TELE 139 N.S 107

DC

DS

DC

SOILED 138 CEN BATH 141 BISTRO 103

SA DS

DC

LAUND 102

DS

DC

PANTRY 104

DS

DC

NURSING PROGRAM

SPECIALIST 108

PC

ZL ZL ZL

PA

NCTC NC ZL

SP

PSPC

PA DP

PSPC

DS

PANTRY 404

TYPICAL 2 BEDROOM

( 27 QTY)

TYPICAL 1 BEDROOM

( 4 QTY)

NC-D

TELE 439 N.S 407

DC

DS

DC

SOILED 438

CLEAN

STORAGE 437 MED PREP 408

ZL

DINING 403

SA

ZL

DS

DC

DS

DC

ZL

DINING 239

SA

UNIT A

ZL ZL

ZL ZL ZL

DEVOTIONAL

ROOM 206

SA

LIBRARY 205

SA

WOMEN 202

PC

PC

PC

MEN 203

PC PC

ZL

SA

OCC.

THERAPY 332

SA

BARBER 327

SA

OCC.

THERAPY 330

SA

PHYS. THERAPY

329 & TLT 329.1

PC

VENDING 324

SA

ZL

UNIT D

UNIT C UNIT B

CL CL CL CL

CL CL CL

CLCL CL CL CLCLCL CLCL CL

PATIO

SA

CL

PATIO

SA

CL

SA

ENLCOSED

PORCH

CL

PATIO

SA

CL

QTY OF ZONE

LIGHTS PER

PLANS. (TYP)

PS

PS

1. MANUFACTURED SLEEVES ARE SHOWN FOR MAJOR

PENETRATIONS. NOT ALL PENETRATIONS ARE SHOWN.

2. MAINTAIN 40% MAX FILL RATE ON ALL SLEEVE PENETRATIONS.

3. CABLE TRAY SHALL MAINTAIN AS POSSIBLE SAME ELEVATION.

4. SUPPORT AREAS WITH HARDLID CEILINGS SHALL RUN CONDUIT TO

NEAREST ACCESSIBLE CEILING AND/OR CABLE TRAY ACCESS

PANEL.

5. TECHNOLOGY SYSTEMS SHALL BE WITHIN SEPARATE SLEEVES.

6. REFER TO OVERALL ROUTING SHEET FOR NEAREST TDR FOR

TERMINATION OF SYSTEM CABLING

NURSE CALL RISER GENERAL NOTES:

PROVIDE NEW EATON BAB 60A/3P BREAKER TO SERVE NEW

PANELBOARD.

PROVIDE NEW PANELBOARD. SEE PANELBOARD SCHEDULE ON SHEET

NC601 FOR ADDITIONAL INFORMATION.

ELECTRICAL ONE-LINE DIAGRAM KEYNOTES

ONE-LINE DIAGRAM LEGEND

EXISTING TO REMAIN

NEW

EXISTING AFFECTED BY THIS PROJECT

NOT TO SCALENC001

1 NURSE CALL RISER DIAGRAM

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC001

2025-0049

NURSE CALL/RTLS

SINGLE LINE

DIAGRAMS

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

12" = 1'-0"NC001

2 PARTIAL ELECTRICAL ONE-LINE DIAGRAM

NOT TO SCALENC001

3 SELECTIVE COORDINATION STUDY

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

PATIO

DISPLAY

2 BR

TLT

131.1

ALCOVE

1C4.2

2 BR

2 BR

TLT

133.1

2 BR

2 BR

TLT

135.1

2 BR

STOR

1C4.3

STOR

1C4.4

CLEAN/STORAGE

TLT

143.1

2 BR

SOILED

TELE

CEN BATH

JAN

CORR

1C5

ALCOVE

1C5.1

2 BR

2 BR

TLT

144.1

2 BR

2 BR

TLT

146.1 DIS

PL

AY

DIS

PL

AY

DISPLAY

ALCOVE

1C5.2

TLT

148.1

2 BR

2 BR

2 BR

2 BR

TLT

150.1

TYP

2 BR

2 BR

TYP

TLT

152.1

STOR

1C5.4

STOR

1C5.3

CORR

1C1

PANTRY

CHARTING ROOM

BISTRO

LAUND

CORR

1C1.1

N.S.

MED

PREP

REF

MED.

CARTS

R.N.

TYP TLT

1 BR

NURSING PROG.

SPECIALIST

WC/ALCOVE

2 BR

TLT

111.1ALCOVE

1C3.1

2 BR

2 BR

2 BR

TLT

113.1ALCOVE

1C3.2

TLT

115.1

2 BR

2 BR

DIS

PL

AY

2 BR

2 BR

TLT

117.1

DIS

PL

AY

TYP

1 BR

ALCOVE

1C3.3

TLT

119.1

HC TLT

MECH

CORR

1C2

TLT

122GAS CYL

123ELEC

TLT

125.1

2 BR

JAN

2 BR

TLT

127.1

ALCOVE

1C4.1

ENCLOSED PORCH

REC. THERAPY

OCC. THERAPY

330 PHYS. THERAPY

OFFICE

STOR

STOR

CORR

3C6

OFFICE

STOR

STOR

TLT

329.1

CORR

3C5

BARBER

VENDING

DRUGS

325.1

CHEMO

PREP

PHARMACY

MEN

203WOMEN

ENTRY

201.1

STOR

LIBRARY

DRYER

EQUIP.

207.1

DRYER

WASHER

STORAGE

STOR KEEP

CORR

2C5

STORAGE

REPAIRS

LKR

TLT

211.1TLT

210.1

LKR

VEST

2C2.1

PRE-RINSE

DEVOTIONAL

ROOM

CORR

2C1

LOBBY

OFFICE

OFFICE

OXY

TLT

COMM

COMP

SWITCHGEAR

ELEC

MECH

MECH

MECH

STOR

225 STORAGE

OFFICE

MECH

OFFICE

JAN

DRY STOR

OFFICE

JAN

OFFICE

TLT

236.1

TLT

236.2

KITCHEN

237.2

KITCHEN

SERVING

DINING

DIR. OF

NURSING

OFFICE

TLT

TLT

ADMIT.

RECPT.

WAITING

ADMIN.

OFFICE

CONFERENCE

ADMIN

OFFICE

STAFF

LOUNGE

LKR

TLT

322.1

CORR

3C4

TLT

323.1

LKR

MECH

JAN

OFFICE

OFFICE

317CORR

3C2

CORR

3C3

ALCOVE

3C3.1

VOL

OFFICE

OFFICE

CLERICAL

OFFICE

DINING

QUIET RM

PANTRY

CORR

4C1

CORR

4C1.1

CHARTING ROOM

TYP TLT

410.1

1 BR

MED.

CARTS

REF

MED

PREP

MED PREP

WC/ALCOVE

2 BR

TLT

411.1

2 BR

ALCOVE

4C3.1

DIS

PL

AY

DIS

PL

AY

2 BR

TLT

413.1

2 BR

ALCOVE

4C3.2 TLT

415.1

2 BR

2 BR

2 BR

2 BR

TLT

417.1

ALCOVE

4C3.3

MECH

HC TLT

TYP

1 BR

TLT

419.1

TLT

425.1

1 BR

ELEC

GAS CYL

TLT

CORR

4C2

STOR

4C4.3

STOR

4C4.4

JAN

2 BR

2 BR

TLT

427.1

ALCOVE

4C4.1

DISPLAY

2 BR

TLT

429.1

DISPLAY

2 BR

ALCOVE

4C4.2

2 BR

TLT

431.1

2 BR

2 BR

TLT

433.1

2 BR

2 BR

TLT

435.1

2 BR

CLEAN/STORAGE

TLT

443.1

1 BR

SOILED

TELE

BARBER SHOP

JAN

2 BR

TLT

444.1

ALCOVE

4C5.1

CORR

4C5

DIS

PL

AY

2 BR

2 BR

2 BR

TLT

446.1DIS

PL

AY

AWNING

ALCOVE

4C5.2

TLT

448.1

2 BR

2 BR

2 BR

TLT

450.1

2 BR

2 BR

TYP

TLT

452.1

STOR

4C5.3

STOR

4C5.4

2 BR

2 BR

TLT

129.1

2 BR

PATIO

TV LOUNGE

DELTA 200 HALL

DELTA 300 HALL

DELTA 100 HALL

ALPHA 100 HALL

ALPHA 300 HALL

ALPHA 200 HALL

PATIO

TYP

TLT

452.1

UNIT "A" UNIT "D"

UNIT "C"

UNIT B"

C L

C L

C L

C L C L

C L

C L

C L

CL

CLCLCLCL

CL CL CL CL CL CL

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C

L CL

C L

C L

CL CL CL CL CL

CLCLCLCLCLCL

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

CL

N C

C L

C L

C L

C L

N C

C L

C L

CL CL CL

C L

C L

ZL

ZL ZL

ZL

ZL

ZL ZL

ZL

ZL

ZL ZL

Z L

ZL

Z L

ZL

C L

C L

C L

C L

C L

C L

C L

CL

CL CL

C L

MATCHLINE UNIT C MATCHLINE UNIT C

MATCHLINE UNIT B MATCHLINE UNIT B

M A

T C

H

LI

N E

U N

IT

C

M A

T C

H

LI

N E

U N

IT

C

M A

T C

H

LI

N E

U N

IT

C

M A

T C

H

LI

N E

U N

IT

C

M A

T C

H

LI

N E

U N

IT

D

M A

T C

H

LI

N E

U N

IT

D

M A

T C

H

LI

N E

U N

IT

A

M A

T C

H

LI

N E

U N

IT

A

NC401

NC401

NC401

NC401

NC401

NC401

NC401

NC401

PORCH:

NO RESIDENT

ACCESS

PORCH:

NO RESIDENT ACCESS AWNING:

NO RESIDENT ACCESS

PORCH:

NO RESIDENT

ACCESS

EC-D2

OVERALL PLAN INDICATES

CORRIDOR AND ZONE

LIGHTING ONLY.

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

A

C B

D

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

1/16" = 1'-0"

NC101

2025-0049

OVERALL NURSE CALL

PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

N

1/16" = 1'-0"NC101

1 OVERALL FLOOR PLAN

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

DISPLAY

2 BR

TLT

131.1

ALCOVE

1C4.2

2 BR

2 BR

TLT

133.1

2 BR

2 BR

TLT

135.1

2 BR

STOR

1C4.3

STOR

1C4.4

CLEAN/STORAGE

TLT

143.1

2 BR

SOILED

TELE

CEN BATH

JAN

CORR

1C5

ALCOVE

1C5.1

2 BR

2 BR

TLT

144.1

2 BR

2 BR

TLT

146.1 DIS

PL

AY

DIS

PL

AY

DISPLAY

ALCOVE

1C5.2

TLT

148.1

2 BR

2 BR

2 BR

2 BR

TLT

150.1

TYP

2 BR

2 BR

TYP

TLT

152.1

STOR

1C5.4

STOR

1C5.3

CORR

1C1

PANTRY

CHARTING ROOM

BISTRO

LAUND

CORR

1C1.1

N.S.

MED

PREP

REF

MED.

CARTS

R.N.

TYP TLT

1 BR

NURSING PROG.

SPECIALIST

WC/ALCOVE

2 BR

TLT

111.1ALCOVE

1C3.1

2 BR

2 BR

2 BR

TLT

113.1ALCOVE

1C3.2

TLT

115.1

2 BR

2 BR

DIS

PL

AY

2 BR

2 BR

TLT

117.1

DIS

PL

AY

TYP

1 BR

ALCOVE

1C3.3

TLT

119.1

HC TLT

MECH

CORR

1C2

TLT

122GAS CYL

123ELEC

TLT

125.1

2 BR

JAN

2 BR

TLT

127.1

ALCOVE

1C4.1

ENCLOSED PORCH

REC. THERAPY

OCC. THERAPY

330 PHYS. THERAPY

OFFICE

STOR

STOR

CORR

3C6

OFFICE

STOR

STOR

TLT

329.1

CORR

3C5

BARBER

VENDING

DRUGS

325.1

CHEMO

PREP

PHARMACY

MEN

203WOMEN

ENTRY

201.1

STOR

LIBRARY

DRYER

EQUIP.

207.1

DRYER

WASHER

STORAGE

STOR KEEP

CORR

2C5

STORAGE

REPAIRS

LKR

TLT

211.1TLT

210.1

LKR

VEST

2C2.1

PRE-RINSE

DEVOTIONAL

ROOM

CORR

2C1

LOBBY

OFFICE

OFFICE

OXY

TLT

COMM

COMP

SWITCHGEAR

ELEC

MECH

MECH

MECH

STOR

225 STORAGE

OFFICE

MECH

OFFICE

JAN

DRY STOR

OFFICE

JAN

OFFICE

TLT

236.1

TLT

236.2

KITCHEN

237.2

KITCHEN

SERVING

DINING

DIR. OF

NURSING

OFFICE

TLT

TLT

ADMIT.

RECPT.

WAITING

ADMIN.

OFFICE

CONFERENCE

ADMIN

OFFICE

STAFF

LOUNGE

LKR

TLT

322.1

CORR

3C4

TLT

323.1

LKR

MECH

JAN

OFFICE

OFFICE

317CORR

3C2

CORR

3C3

ALCOVE

3C3.1

VOL

OFFICE

OFFICE

CLERICAL

OFFICE

DINING

QUIET RM

PANTRY

CORR

4C1

CORR

4C1.1

CHARTING ROOM

TYP TLT

410.1

1 BR

MED.

CARTS

REF

MED

PREP

MED PREP

WC/ALCOVE

2 BR

TLT

411.1

2 BR

ALCOVE

4C3.1

DIS

PL

AY

DIS

PL

AY

2 BR

TLT

413.1

2 BR

ALCOVE

4C3.2 TLT

415.1

2 BR

2 BR

2 BR

2 BR

TLT

417.1

ALCOVE

4C3.3

MECH

HC TLT

TYP

1 BR

TLT

419.1

TLT

425.1

1 BR

ELEC

GAS CYL

TLT

CORR

4C2

STOR

4C4.3

STOR

4C4.4

JAN

2 BR

2 BR

TLT

427.1

ALCOVE

4C4.1

DISPLAY

2 BR

TLT

429.1

DISPLAY

2 BR

ALCOVE

4C4.2

2 BR

TLT

431.1

2 BR

2 BR

TLT

433.1

2 BR

2 BR

TLT

435.1

2 BR

CLEAN/STORAGE

TLT

443.1

1 BR

SOILED

TELE

BARBER SHOP

JAN

2 BR

TLT

444.1

ALCOVE

4C5.1

CORR

4C5

DIS

PL

AY

2 BR

2 BR

2 BR

TLT

446.1DIS

PL

AY

AWNING

ALCOVE

4C5.2

TLT

448.1

2 BR

2 BR

2 BR

TLT

450.1

2 BR

2 BR

TYP

TLT

452.1

STOR

4C5.3

STOR

4C5.4

2 BR

2 BR

TLT

129.1

2 BR

PATIO

TV LOUNGE

DELTA 200 HALL

DELTA 300 HALL

DELTA 100 HALL

ALPHA 100 HALL

ALPHA 300 HALL

ALPHA 200 HALL

PATIO

TYP

TLT

452.1

UNIT "A" UNIT "D"

UNIT "C"

UNIT B"

1&5

2 2

3a

3a

3b

3b

3c

3c

4 4

4 4

4 4

3g

3h

3j

3g

3h

3i

3q

3r

3s

3q

3r

3s

3p 3o 3n

3p 3o 3n

3f

3e

3d

3f

3e

3d

3m

3l

3k

3m

3l

3k

1&5

1&5

1&5

THE NARRATIVE BELOW DEPICTS A PROPOSED CONSTRUCTION SEQUENCING PLAN FOR THE

REPLACEMENT OF THE EXISTING NURSE CALL SYSTEM. THE CONTRACTOR SHALL CREATE A DETAILED PHASING AND CUTOVER PLAN AS DESCRIBED IN THE SPECIFICATIONS (SECTION 260010 1.5) WHICH IS TO BE COORDINATED WITH THE FACILITY AND SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL.

THE INTENT IS THAT THE EXISTING NURSE CALL SYSTEM BE TRANISITIONED TO THE NEW SYSTEM, AREA-BY-AREA IN SUCH A WAY THAT AN ACTIVE NURSE CALL SYSTEM SERVICES ARE MAINTAINED

THROUGHOUT THE DURATION OF CONSTRUCTION.

PHASE 1: INSTALL THE NEW NURSE CALL SYSTEM HEADEND EQUIPMENT AND POWER CONNECTIONS.

THE EXISTING NURSE CALL HEAD END SYSTEM AND ALL EXISTING DEVICES ARE TO REMAIN FUNCTIONAL

DURING THIS PHASE.

PHASE 2:

• INSTALL NEW RACEWAY (CABLE TRAY OR J-HOOKS) FOR THE NURSE CALL SYSTEM THROUGHOUT

THE CORRIDORS AS REQUIRED FOR A FULL AND COMPLETE SYSTEM.

• INSTALL CABLE IN RACEWAY AS REQUIRED FROM HEADEND TO NEW DEVICE LOCATIONS. PROVIDE SLACK CABLE AS NEEDED COILED IN CEILING FOR FINAL INSTALLATION TO NEW DEVICES IN LATER

PHASES.

• INSTALL NEW NURSE CALL MASTER STATIONS AT EACH NURSE STATION AS SHOWN ON THE NEW

CONSTRUCTION PLANS.

• INSTALL NEW ZONE LIGHTS AS SHOWN ON NEW CONSTRUCTION PLANS.

• THE EXISTING NURSE CALL HEADEND SYSTEM AND ALL EXISTING DEVICES (INCLUDING ZONE

LIGHTS AND MASTER STATIONS) ARE TO REMAIN FUNCTIONAL DURING THIS PHASE.

PHASE 3:

• PATIENT ROOM DEVICE TURNOVER IS TO COMPLETED IN GROUPS OF ROOMS AT A TIME.

COORDINATE WITH THE FACILITY FOR QUANTITY OF ROOMS THAT CAN BE TURNED OVER DURING

EACH PARTIAL SEQUENCE IN PHASE 3.

• PROVIDE ICRA BARRIERS AND NEGATIVE AIR MACHINES AS REQUIRED TO MAINTAIN FACILITY ICRA

PLAN.

• REMOVE AND DECOMISSION NURSE CALL DEVICES WITHIN EACH GROUP OF PATIENT ROOMS AND

BATHROOMS ALONG WITH THE CORESPONDING CORRIDOR LIGHT OUTSIDE OF THE ROOMS.

• INSTALL NEW CABLING AND NURSE CALL DEVICES FROM CORRIDOR TO DEVICE BOX LOCATIONS IN

ACCORDANCE WITH THE NEW CONSTRUCTION PLANS.

• INSTALL NEW NURSE CALL DEVICES WITHIN THE GROUP OF PATIENT ROOMS AND BATHROOMS AS

SHOWN ON NEW CONSTRUCTION PLANS.

• INSTALL NEW CORRIDOR LIGHT AS FOR EACH ROOM IN THE GROUP AS SHOWN ON NEW

CONSTRUCTION PLAN.

• BEFORE MOVING TO THE NEXT GROUP OF PATIENT ROOMS, CONTRACTOR IS TO CONFIRM NEW

NURSE CALL DEVICES INSTALLED FOR THIS SEQUENCE ARE FULLY FUNCTIONAL. COORDINATE WITH

AHCA FOR INSPECTION AND SIGN OFF OF NEW SYSTEM BEFORE ALLOWING PATIENTS TO

REOCCUPY THE ROOM.

• REPEAT PHASE 3 FOR EACH GROUP OF PATIENT ROOMS.

PHASE 4:

• REMOVE AND DECOMMISSION NURSE CALL DEVICES IN STAFF ROOMS AND PATIENT COMMON

AREAS. COORDINATE WITH FACILITY FOR GROUPING AND SCHEDULE OF SPACES IN THE PHASE.

• INSTALL NEW NURSE CALL DEVICES FOR STAFF ROOMS AND COMMON AREAS AS SHOWN ON THE

NEW CONSTRUCTION PLAN.

PHASE 5: ONCE THE NEW NURSE CALL SYSTEM IS FULLY FUNCTIONAL AND FINAL APPROVAL OF IT'S USE HAS BEEN OBTAINED, PROCEED WITH DEMOLITION OF ANY REMAINING COMPONENTS OF THE EXISTING

NURSE CALL SYSTEM INCLUDING THE HEADEND EQUIPMENT.

PROPOSED PHASING PLAN

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

A

C B

D

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC102

2025-0049

CONSTRUCTION

PHASING PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

1/16" = 1'-0"NC102

1 PROPOSED CONSTRUCTION PHASING PLAN

Rev. No. Rev. Date Rev. Description

N.S.

2 BR

TLT

129.1

2 BR

2 BR

TLT

127.1

2 BR

2 BR

TLT

125.1

JAN

ELEC

GAS CYL

TLT

MECH

HC TLT

TLT

119.1

TYP

1 BR

ALCOVE

1C3.3

2 BR

TLT

117.1

2 BR

2 BR

TLT

115.1

2 BR

DISPLAY

ALCOVE

1C3.2

2 BR

TLT

113.1

2 BR

2 BR

TLT

111.1

DISPLAY

ALCOVE

1C3.1

2 BR

1 BR

TYP TLT

WC/ALCOVE

109 NURSING

PROG.

SPECIALIST108

REF

M E

D

C A

R T

S

MED

PREP

R.N.

CORR

1C2

CORR

1C1.1

CHARTING ROOM

PANTRY

BISTRO

LAUND

CORR

1C1

TYP

2 BR

TYP

TLT

152.1

2 BR

2 BR

TLT

150.1

2 BR

2 BR

TLT

148.1

2 BR

2 BR

TLT

146.1

DISPLAY

2 BR

3092 BR

TLT

144.1

2 BR

CORR

1C5

DISPLAY

ALCOVE

1C5.2

ALCOVE

1C5.1

2 BR

JAN

TLT

143.1

CEN BATH

CLEAN/STORAGE

SOILED

138 TELE

STOR

1C5.4

STOR

1C5.3

2 BR

2 BR

TLT

135.1

2 BR

2 BR

TLT

133.1

2 BR

TLT

131.1

2 BR

DISPLAY

ALCOVE

1C4.2

ALCOVE

1C4.1

STOR

1C4.3

STOR

1C4.4

DISPLAY

PATIO

ALPHA 100 HALL

ALPHA 300 HALL

ALPHA 200 HALL

DS

DS

DS

DS

DS

SA C

L

NC

PC

CL CL CL CL

CLCLCLCL

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

CL CL CL CL CL

CLCLCLCLCLCL

CL

CL

C L

N C

T C

ZL

ZL

ZL

/1 NC201C /1 NC201C

NC401

NC401

NC401

/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401

/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401/SEE 5 NC401 /SEE 6 NC401

/SEE 6 NC401

/SEE 6 NC401

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND

FOR DEVICE DESCRIPTION.

EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL

DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE

VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.

THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN

THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A

GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT

AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL

BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS

RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE

PLANS OR NOT.

ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE

PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO

CAUSE ANY DISRUPTION TO THESE OTHER SPACES.

REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.

PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER

SUPPLIES, AND HEAD-END EQUIPMENT.

PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR

SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE

THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY

LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS

EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A

NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO

ENSURE OPERATION UPON COMPLETION OF THE PROJECT.

DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON

WIRING AND CONDUIT BACK TO SOURCE.

ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE

TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED

MEANS AND MATERIALS.

A.

B.

C.

D.

E.

F.

G.

H.

DEMOLITION SHEET NOTESDEMOLITION KEYNOTES

1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX

FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.

REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION

PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION

PHASING PLAN.

DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE

CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING

NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET

SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO

SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

A

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC201A

2025-0049

UNIT A NURSE CALL

DEMOLITION PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

1/8" = 1'-0"NC201A

1 UNIT A NURSE CALL DEMOLITION PLAN

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

COMM

SWITCHGEAR

COMP

TLT

OXY

OFFICE

OFFICE

STORAGE

CORR

2C5

REPAIRS

STOR KEEP

STORAGE

LKR

LKR

TLT

210.1

TLT

211.1

VEST

2C2.1

PRE-RINSE

WASHER

DRYER

DRYER

EQUIP.

207.1

DEVOTIONAL

ROOM

LIBRARY

STOR

CORR

2C1

ENTRY

201.1

WOMEN

MEN

LOBBY

DINING

SERVING

237.2

KITCHEN

OFFICE

OFFICE

TLT

236.2

TLT

236.1

MECH

DRY STOR

JAN

ELEC

MECH

STOR

STORAGE

OFFICE

MECH

OFFICE

228 JAN

MECH

KITCHEN

SA

SA

SA

PC

PC

PC

PC

PC

CL

CL CL

CL

C L

C L

N C C

N C C

N C C

(TYP)

(TYP)

(TYP)

ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND

FOR DEVICE DESCRIPTION.

EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL

DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE

VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.

THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN

THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A

GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT

AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL

BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS

RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE

PLANS OR NOT.

ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE

PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO

CAUSE ANY DISRUPTION TO THESE OTHER SPACES.

REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.

PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER

SUPPLIES, AND HEAD-END EQUIPMENT.

PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR

SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE

THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY

LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS

EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A

NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO

ENSURE OPERATION UPON COMPLETION OF THE PROJECT.

DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON

WIRING AND CONDUIT BACK TO SOURCE.

ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE

TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED

MEANS AND MATERIALS.

A.

B.

C.

D.

E.

F.

G.

H.

DEMOLITION SHEET NOTESDEMOLITION KEYNOTES

1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX

FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.

REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION

PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION

PHASING PLAN.

DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE

CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING

NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET

SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO

SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

B

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC201B

2025-0049

UNIT B NURSE CALL

DEMOLITION PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

1/8" = 1'-0"NC201B

1 UNIT B NURSE CALL DEMOLITION PLAN

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

WAITING

RECPT.

ADMIN.

OFFICE

CONFERENCE

ADMIN

CLERICAL

OFFICE

OFFICE

OFFICE

OFFICE

VOL

MECH

STAFF

LOUNGE

OFFICE

OFFICE

JAN

TLT

323.1

TLT

322.1

LKR

LKR

CORR

3C2

DIR. OF

NURSING

OFFICE

CORR

3C3

ALCOVE

3C3.1

TLT

TLT

ADMIT.

ENCLOSED PORCH

CORR

3C6

OFFICE

STOR STOR

REC. THERAPY

OCC. THERAPY

PHYS. THERAPY

OFFICE

STORSTOR

TLT

329.1

CORR

3C5

BARBER

VENDING

DRUGS

325.1

CHEMO

PREP

325PHARMACY

SA

SA

PC

SA

SA

SA

C L

C L

C L

CL

C L

N C B

N C B

N C B

/1 NC201A

/1 NC201D

/1 NC201A

/1 NC201D

(TYP)

(TYP)

(TYP)

ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND

FOR DEVICE DESCRIPTION.

EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL

DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE

VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.

THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN

THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A

GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT

AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL

BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS

RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE

PLANS OR NOT.

ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE

PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO

CAUSE ANY DISRUPTION TO THESE OTHER SPACES.

REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.

PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER

SUPPLIES, AND HEAD-END EQUIPMENT.

PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR

SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE

THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY

LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS

EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A

NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO

ENSURE OPERATION UPON COMPLETION OF THE PROJECT.

DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON

WIRING AND CONDUIT BACK TO SOURCE.

ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE

TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED

MEANS AND MATERIALS.

A.

B.

C.

D.

E.

F.

G.

H.

DEMOLITION SHEET NOTESDEMOLITION KEYNOTES

1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX

FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.

REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION

PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION

PHASING PLAN.

DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE

CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING

NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET

SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO

SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

C

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC201C

2025-0049

UNIT C NURSE CALL

DEMOLITION PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

1/8" = 1'-0"NC201C

1 UNIT C NURSE CALL DEMOLITION PLAN

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

2 BR

TLT

429.1

2 BR

2 BR

TLT

427.1

2 BR

1 BR

TLT

425.1

JAN

ELEC

GAS CYL

TLT

422MECH

HC TLT

TLT

419.1TYP

1 BR

ALCOVE

4C3.3

2 BR

TLT

417.1

2 BR

2 BR

TLT

415.1

2 BR

DISPLAY

ALCOVE

4C3.2

2 BR

TLT

413.1

2 BR

2 BR

TLT

411.1

DISPLAY

ALCOVE

4C3.1

2 BR

104 1 BR

102 TYP TLT

410.1

WC/ALCOVE

MED PREP

REF

MED.

CARTS

MED

PREP

CHARTING ROOM

CORR

4C2

CORR

4C1.1

QUIET RM

401 PANTRY

DINING

CORR

4C1

TYP

TLT

452.1

2 BR

2 BR

TLT

450.1

2 BR

2 BR

TLT

448.1

2 BR

AWNING

2 BR

TLT

446.1

DISPLAY

2 BR

2 BR

TLT

444.1

2 BR

CORR

4C5

DISPLAY ALCOVE

4C5.2

ALCOVE

4C5.1

1 BR

JAN

TLT

443.1

BARBER SHOP

CLEAN/STORAGE

SOILED

TELE

STOR

4C5.4

STOR

4C5.3

2 BR

2 BR

TLT

435.1

2 BR

2 BR

TLT

433.1

2 BR

TLT

431.1

2 BR

DISPLAY

ALCOVE

4C4.2

DISPLAY

ALCOVE

4C4.1

STOR

4C4.4

STOR

4C4.3

TV LOUNGE

DELTA 200 HALL

DELTA 300 HALL

DELTA 100 HALL

PATIO

TYP

TLT

452.1

SA

DS

DS

DS

DS

CL CL CL CL CL

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

CL CL CL CL CL

CLCLCLCLCL

CL

NC

N C

T C

CL CL CL CL

ZL

ZL

ZL

S A

NC401

/1 NC201C/1 NC201C

/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401

/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401 /SEE 5 NC401 /SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 5 NC401

/SEE 6 NC401

/SEE 5 NC401

/SEE 6 NC401

/SEE 6 NC401

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

ALL DEVICES SHOWN ON THIS PLAN ARE EXISTING. REFER TO SYMBOL LEGEND

FOR DEVICE DESCRIPTION.

EXISTING CONDITIONS SHOWN ON THIS DRAWING ARE TAKEN FROM ORIGINAL

DRAWINGS AND FIELD INVESTIGATION. ALL EXISTING CONDITIONS MUST BE

VERIFIED PRIOR TO BID. FIELD CONDITIONS SHALL GOVERN.

THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES WITHIN

THE PROJECT AREA. IT IS INTENDED TO PROVIDE THE CONTRACTOR WITH A

GENERAL KNOWLEDGE OF THE EXISTING CONDITIONS WITHIN THE PROJECT

AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THIS PLAN SHALL

BE BROUGHT TO THE ATTENTION OF THE ENGINEER. THE CONTRACTOR IS

RESPONSIBLE FOR ALL REQUIRED DEMOLITION WHETHER SHOWN ON THE

PLANS OR NOT.

ALL CONDUITS SERVING OTHER SPACES OR FLOORS, THAT RUN THROUGH THE

PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION, SO AS NOT TO

CAUSE ANY DISRUPTION TO THESE OTHER SPACES.

REMOVE AND TURN OVER ALL FUNCTIONING EXISTING DEVICES TO THE FACILITY.

PROPERLY DISPOSE OF ANY NON- FUNCTIONAL DEVICES, CABLINGM POWER

SUPPLIES, AND HEAD-END EQUIPMENT.

PRIOR TO THE DEMOLITION OF ANY/ALL CIRCUITS AND RACEWAYS, CONTRACTOR

SHALL FULLY INVESTIGATE (TRACE BACK) THE CIRCUIT AND CONDUIT TO ENSURE

THAT THE DEMOLITION OF THE PROPOSED SYSTEM WILL NOT AFFECT ANY

LOADS/EQUIPMENT PROPOSED TO REMAIN. IF THE DEMOLITION AFFECTS

EQUIPMENT TR THE CONTRACTOR SHALL RE-FEED THE SYSTEM BY PROVIDING A

NEW OMERUN" TO THE NEW ELECTRICAL SYSTEM, SIZED AS REQUIRED TO

ENSURE OPERATION UPON COMPLETION OF THE PROJECT.

DEVICES MARKED FOR DEMOLITION SHALL INCLUDE REMOVAL OF ALL ABANDON

WIRING AND CONDUIT BACK TO SOURCE.

ANY/ALL RATED WALLS AND/OR CEILING/FLOOR PENETRATIONS LEFT OPEN DUE

TO REMOVAL OF RACEWAY SHALL BE PROPERLY SEALED VIA USE OF UL LISTED

MEANS AND MATERIALS.

A.

B.

C.

D.

E.

F.

G.

H.

DEMOLITION SHEET NOTESDEMOLITION KEYNOTES

1 DEMOLISH AND REMOVE EXISTING DEVICE. RE-PURPOSE EXISTING BACKBOX

FOR DEVICES SHOWN ON NEW CONSTRUCTION PLANS WHERE APPLICABLE.

REMOVAL OF DEVICE SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION

PHASING PLAN. REFER TO SHEET NC102 FOR PROPOSED CONSTRUCTION

PHASING PLAN.

DEMOLISH AND REMOVE EXISTING NURSE CALL CABINET. ONCE NEW NURSE

CALL SYSTEM IS FULLY OPERATIONAL, DISCONNECT POWER FROM EXISTING

NURSE CALL CABINET AND FULLY DEMOLISH CIRCUIT. REMOVAL OF CABINET

SHALL BE IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO

SHEET NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

D

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC201D

2025-0049

UNIT D NURSE CALL

DEMOLITION PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

N

1/8" = 1'-0"NC201D

1 UNIT D NURSE CALL DEMOLITION PLAN

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

2 BR

TLT

129.1

2 BR

2 BR

TLT

127.1

2 BR

2 BR

TLT

125.1

JAN

ELEC

GAS CYL

TLT

MECH

HC TLT

TLT

119.1

TYP

1 BR

ALCOVE

1C3.3

2 BR

TLT

117.1

2 BR

2 BR

TLT

115.1

2 BR

DISPLAY

ALCOVE

1C3.2

2 BR

TLT

113.1

2 BR

2 BR

TLT

111.1

DISPLAY

ALCOVE

1C3.1

2 BR

1 BR

TYP TLT

WC/ALCOVE

109 NURSING

PROG.

SPECIALIST108

REF

M E

D

C A

R T

S

MED

PREP

R.N.

CORR

1C2

CORR

1C1.1

CHARTING ROOM

PANTRY

BISTRO

LAUND

CORR

1C1

TYP

2 BR

TYP

TLT

152.1

2 BR

2 BR

TLT

150.1

2 BR

2 BR

TLT

148.1

2 BR

2 BR

TLT

146.1

DISPLAY

2 BR

3092 BR

TLT

144.1

2 BR

CORR

1C5

DISPLAY

ALCOVE

1C5.2

ALCOVE

1C5.1

2 BR

JAN

TLT

143.1

CEN BATH

CLEAN/STORAGE

SOILED

138 TELE

STOR

1C5.4

STOR

1C5.3

2 BR

2 BR

TLT

135.1

2 BR

2 BR

TLT

133.1

2 BR

TLT

131.1

2 BR

DISPLAY

ALCOVE

1C4.2

ALCOVE

1C4.1

STOR

1C4.3

STOR

1C4.4

DISPLAY

PATIO

ALPHA 100 HALL

ALPHA 300 HALL

ALPHA 200 HALL

CL CL CL CL

CLCLCLCL

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

C L

CL CL CL CL CL

CLCLCLCLCLCL

CL

CL

DS

DS

DS

DS

DS

SA C

L

NC

PC

N C

T C

Z L

Z L

Z L

Z L

Z L

Z L

DC

DC

DC

DC

DC

CL

C L

S A

NC401

/1 NC301C /1 NC301C

NC401

NC401

NC401

NC-A

/SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401 /SEE 7 NC401

/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401

/SEE 7 NC401

/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401/SEE 7 NC401 /SEE 1 NC401

/SEE 1 NC401

/SEE 1 NC401

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES WITH

CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS.

VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL

EQUIPMENT WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO

INSTALLATION OF EQUIPMENT.

REFER TO THE ONE-LINE DIAGRAM FOR BRANCH CIRCUIT AND CONDUIT SIZES.

ALL WALL/COLUMN MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED CFCI

UNI-STRUT SUPPORTS.

A.

B.

C.

D.

NEW WORK SHEET NOTESNEW WORK KEYNOTES

1 PROVIDE NEW DEVICE AS INDICATED. INSTALL IN EXISTING BACKBOX MADE

AVAILABLE PER DEMOLITION WHERE APPLICABLE. DEVICES SHALL BE INSTALLED

IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO SHEET

NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.

NEW ZONE LIGHT SHALL BE INSTALLED NEXT TO EXISTING ZONE LIGHT (WHERE

APPLICABLE). ZONE LIGHT TO OPERATE IN PARALLEL WITH EXISTING SYSTEM

UNTIL NEW SYSTEM IS FULLY OPERATIONAL AS OUTLINED IN THE PROPOSED

CONSTRUCTION PHASING PLAN ON SHEET NC102.

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

A

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC301A

2025-0049

UNIT A NURSE CALL

NEW CONSTRUCTION

PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

1/8" = 1'-0"NC301A

1 UNIT A NURSE CALL NEW CONSTRUCTION PLAN N

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

COMM

SWITCHGEAR

COMP

TLT

OXY

OFFICE

OFFICE

STORAGE

CORR

2C5

REPAIRS

STOR KEEP

STORAGE

LKR

LKR

TLT

210.1

TLT

211.1

VEST

2C2.1

PRE-RINSE

WASHER

DRYER

DRYER

EQUIP.

207.1

DEVOTIONAL

ROOM

LIBRARY

STOR

CORR

2C1

ENTRY

201.1

WOMEN

MEN

LOBBY

DINING

SERVING

237.2

KITCHEN

OFFICE

OFFICE

TLT

236.2

TLT

236.1

MECH

DRY STOR

JAN

ELEC

MECH

STOR

STORAGE

OFFICE

MECH

OFFICE

228 JAN

MECH

KITCHEN

SA

SA

SA

PC

PC

PC

PC

PC

CL

CL CL

CL

C L

C L

Z L

SA

CL

N C C

N C C

N C C

(TYP)

(TYP)

(TYP)

(TYP)

COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES WITH

CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS.

VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL

EQUIPMENT WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO

INSTALLATION OF EQUIPMENT.

REFER TO THE ONE-LINE DIAGRAM FOR BRANCH CIRCUIT AND CONDUIT SIZES.

ALL WALL/COLUMN MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED CFCI

UNI-STRUT SUPPORTS.

A.

B.

C.

D.

NEW WORK SHEET NOTESNEW WORK KEYNOTES

1 PROVIDE NEW DEVICE AS INDICATED. INSTALL IN EXISTING BACKBOX MADE

AVAILABLE PER DEMOLITION WHERE APPLICABLE. DEVICES SHALL BE INSTALLED

IN ACCORDANCE WITH THE CONSTRUCTION PHASING PLAN. REFER TO SHEET

NC102 FOR PROPOSED CONSTRUCTION PHASING PLAN.

NEW ZONE LIGHT SHALL BE INSTALLED NEXT TO EXISTING ZONE LIGHT (WHERE

APPLICABLE). ZONE LIGHT TO OPERATE IN PARALLEL WITH EXISTING SYSTEM

UNTIL NEW SYSTEM IS FULLY OPERATIONAL AS OUTLINED IN THE PROPOSED

CONSTRUCTION PHASING PLAN ON SHEET NC102.

N

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED

SIGNED AND SEALED AND THE SHA AUTHENTICATION CODE

MUST BE VERIFIED ON ANY ELECTRONIC COPIES

BURNS ENGINEERING, INC. I (813) 257-7442

400 N TAMPA ST, SUITE 925

TAMPA, FL 33602

Drawing No:

Job No:

Checked:

Drawn:

Scale:

Date:

Drawing Title:

Project Title:

KEY PLAN

B

Project Address:

6919 Parkway Boulevard Land O' Lakes, FL 34639

Project Facility Name:

Baldomero Lopez Memorial Veterans Nursing Home Project Name:

Nurse Call Replacement OPC Project #:

35/35960936-35654

06/26/2025

KW

JB

As indicated

NC301B

2025-0049

UNIT B NURSE CALL

NEW CONSTRUCTION

PLAN

FDVA BALDOMERO

LOPEZ VETERANS

NURSING HOME

NURSE CALL

REPLACEMENT

1/8" = 1'-0"NC301B

1 UNIT B NURSE CALL NEW CONSTRUCTION PLAN

Rev. No. Rev. Date Rev. Description

6/18/2025 AHCA STAGE III

WAITING

RECPT.

ADMIN.

OFFICE

CONFERENCE

ADMIN

CLERICAL

OFFICE

OFFICE

OFFICE

OFFICE

VOL

MECH

STAFF

LOUNGE

OFFICE

OFFICE

JAN

TLT

323.1

TLT

322.1

LKR

LKR

CORR

3C2

DIR. OF

NURSING

OFFICE

CORR

3C3

ALCOVE

3C3.1

TLT

TLT

ADMIT.

ENCLOSED PORCH

CORR

3C6

OFFICE

STOR STOR

REC. THERAPY

OCC. THERAPY

PHYS. THERAPY

OFFICE

STORSTOR

TLT

329.1

CORR

3C5

BARBER

VENDING

DRUGS

325.1

CHEMO

PREP

325PHARMACY

SA

SA

PC

SA

SA

SA

C L

C L

C L

CL

C L

Z L

Z L

C L

S A

N C B

N C B

N C B

/1 NC301A

/1 NC301D

/1 NC301A

/1 NC301D

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES WITH

CONSTRUCTION DOCUMENTS AND EXISTING CONDITIONS.

VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL

EQUIPMENT WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO

INSTALLATION OF EQUIPMENT.

REFER TO THE ONE-LINE DIAGRAM FOR BRANCH CIRCUIT AND CONDUIT SIZES.

ALL WALL/COLUMN MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED CFCI

UNI-STRUT SUPPORTS.

A.

B.

C.

D.

NEW WORK SHEET NOTESNEW WORK…