Napa Fire Station #2 Electrical Service Upgrade
Solicitation number
FC24FD02
Issued by
Napa County, California

About this file

The provided documents are bid set plans and specifications for the Napa Fire Station #2 Electrical Service Upgrade project, prepared by Colebreit Engineering (Axiom Engineers) for the City of Napa, California. The project involves a comprehensive electrical service upgrade at 1501 Park Avenue, with bid documents dated 5/27/2024 and a projected implementation date of 6/21/2024. The electrical upgrade includes installing a new main switchboard, removing existing overhead service conductors, installing new panelboards, and upgrading electrical infrastructure with specific conduit and conductor specifications.

The project appears to be funded through municipal infrastructure improvements, with detailed electrical design focusing on modernizing the fire station's electrical systems. The bid set includes comprehensive technical specifications covering electrical symbols, single line diagrams, site plans, and installation details, with specific attention to grounding systems, conduit installations, and compliance with 2022 California electrical codes. The documents indicate coordination will be required with PG&E for utility connections, and the project includes provisions for future expansion, such as spare conduit stubouts and precise installation requirements for electrical equipment.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NUM

BER

REVISION SCHEDULE

JOB NUM

BER:

THE USE OF THESE PLANS AND SPECIFICATIONS SHALL BE RESTRICTED TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO SUCH USE. RE-USE, REPRODUCTION, OR PUBLICATION BY ANY METHOD, IN WHOLE OR IN PART, IS PROHIBITED. TITLE TO THE PLANS AND SPECIFICATIONS REMAINS WITH THE ENGINEER WITHOUT PREJUDICE. VISUAL CONTACT WITH THESE PLANS AND SPECIFICATIONS SHALL CONSTITUTE PRIMA FACIE EVIDENCE OF THE ACCEPTANCE OF THESE RESTRICTIONS. COLEBREIT ENGINEERING, LLC DBA AXIOM ENGINEERS

NAPA FIRE STATION #2

ELECTRICAL SERVICE UPGRADE

DATE:

6/21/2024

2024083

1501 PARK AVENUE

NAPA, CA 94558

BID SET

5/27/2024

BEND | EUGENE | M

EDFORD

M

ONTEREY | NAPA | SANTA CRUZ

E N G

I N E E R I N

G

ELECTRICAL SYM

BOLS

LEGEND

E0.1

ABBREVIATIONS

ABBRV.

POW

ER SYM

BOLS

SYM

BOL

IDENTIFICATION

IDENTIFICATION

AC

ALTERNATING CURRENT

AFF

ABOVE FINISH FLOOR

AT

TRIP RATING IN AM

PERES

FRAM

E RATING IN AM

PERES

AS

SW

ITCH RATING IN AM

PERES

ATS

AUTOM

ATIC TRANSFER SW

ITCH

AV

AUDIO VISUAL

C

CONDUIT

CL

CENTERLINE

DC

DIRECT CURRENT

(E)

EXISTING TO REM

AIN

ELEV

ELEVATOR

EM

T

ELECTRO M

ETALLIC TUBING

G

GROUND

GFCI

GROUND FAULT CIRCUIT INTERRUPTER

HID

HIGH INTENSITY DISCHARGE

IG

ISOLATED GROUND

LCP

LIGHTING CONTROL PANEL

NC

NORM

ALLY CLOSED

NEM

A

NATIONAL ELECTRICAL M

ANUFACTURER'S

ASSOCIATION

NO

NORM

ALLY OPEN

NTS

NOT TO SCALE

PVC

POLYVINYL CHLORIDE CONDUIT

RSC

RIGID STEEL CONDUIT

TTB

TERM

INAL BACKBOARD

TC

TERM

INAL CABINET

TEL

TELEPHONE

UON

UNLESS OTHERW

ISE NOTED

VFD

VARIABLE FREQUENCY DRIVE

W W

EATHERPROOF

W

AP

W

IRELESS ACCESS POINT

W

W

ITH

XFM

R

TRANSFORM

ER

XP

EXPLOSION PROOF

NEC

NATIONAL ELECTRIC CODE

(X)

REM

OVE EXISTING

(R)

RELOCATE EXISTING

20A, 125V, DUPLEX RECEPTACLE OUTLET +18" AFF TO CENTERLINE

OF BOX UNLESS OTHERW

ISE NOTED

20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET +18" AFF TO

CENTERLINE OF BOX UNLESS OTHERW

ISE NOTED

CONN

CONNECTED

SPECIAL PURPOSE RECEPTACLE OUTLET; NEM

A

CONFIGURATIONS AS SHOW

N ON DRAW

INGS; 18" AFF TO

CENTERLINE OF BOX UNLESS OTHERW

ISE NOTED

20A, 125V, SINGLE RECEPTACLE OUTLET; +18" AFF TO

CENTERLINE OF BOX UNLESS OTHERW

ISE NOTED

A = ABOVE COUNTER

C = CEILING M

OUNTED

G = GFCI

S = SW

ITCHED RECEPTACLE

U = W

ITH (2) USB PORTS

W = W

EATHERPROOF COVER AND GFCI

X

20A, 125V, DUPLEX RECEPTACLE OUTLET;

FLOOR RECESSED

20A, 125V, DOUBLE DUPLEX RECEPTACLE OUTLET;

FLOOR RECESSED

2-COM

PARTM

ENT FLOOR BOX W

/ (2) GANG POW

ER / (2)

GANG DATA; PROVIDE 1"C. FROM

EACH DATA OUTLET TO

ACCESSIBLE CEILING SPACE.

SINGLE POLE SW

ITCH

3 = THREE W

AY SW

ITCH

4 = FOUR-W

AY SW

ITCH

D = DIM

M

ER SW

ITCH

K = KEY OPERATED SW

ITCH

M = M

OTOR RATED SW

ITCH

T = INTERVAL TIM

ER

V = VACANCY SENSOR SW

ITCH

W = W

EATHERPROOF SW

ITCH

X

PUSH BUTTON

OCCUPANCY LIGHT CONTROL SW

ITCH; CEILING M

OUNTED

OCCUPANCY LIGHT CONTROL SW

ITCH; W

ALL M

OUNTED

PHOTOSENSOR; CEILING M

OUNTED

C = CORRIDOR PATTERN

X

DIM

M

ING PHOTOSENSOR

D

ELECTRIC VEHICLE CHARGING STATION

LUM

INAIRE; CEILING OR SURFACE M

OUNTED

LUM

INAIRE; W

ALL M

OUNTED

AREA POLE W

ITH M

OUNTED LUM

INAIRE

LUM

INAIRE ON EM

ERGENCY POW

ER

EXIT SIGN; CEILING M

OUNTED; ARROW

S AND FACES AS

SHOW

N ON PLANS

EXIT SIGN; W

ALL M

OUNTED; ARROW

S AND FACES AS

SHOW

N ON PLANS

SPD

SURGE PROTECTION DEVICE

PH

PHASE

GND

GROUND

CONTRACTOR FURNISHED,

CONTRACTOR INSTALLED

CFCI

CONTRACTOR FURNISHED, OW

NER

INSTALLED

CFOI

OFCI

OW

NER FURNISHED, CONTRACTOR

INSTALLED

M

OTOR CONNECTION

FUSED DISCONNECT

SW

ITCH XX/XX/XX = AM

P SW

ITCH/POLES/AM

P FUSE

NON-FUSED DISCONNECT

SW

ITCH XX/XX = AM

P SW

ITCH/POLES

JUNCTION BOX

JUNCTION BOX; CEILING M

OUNTED

C

JUNCTION BOX W

ITH W

HIP-STYLE CONNECTION TO

POW

ERED FURNITURE; POW

ER AND/OR DATA

JUNCTION BOX; W

ALL M

OUNTED

GENERATOR CONNECTION

TRANSFORM

ER; BOTTOM

OF T DESIGNATES FRONT SIDE

PANELBOARD OR TERM

INAL CABINET; SURFACE M

OUNTED

PANELBOARD OR TERM

INAL CABINET; FLUSH M

OUNTED

AUTOM

ATIC TRANSFER SW

ITCH

DRAW

OUT CIRCUIT BREAKER; RATING AS SHOW

N ON PLANS

STATIONARY - CIRCUIT BREAKER; RATING AS SHOW

N ON PLANS

FUSED DISCONNECT; RATING AS SHOW

N ON PLANS

NON-FUSED DISCONNECT; RATING AS SHOW

N ON PLANS

TRANSFORM

ER

INVERTER

GROUNDING POINT

UTILITY M

ETER

GROUND BUS BAR

MGFJJJ

$$O

SOS

O

SPS

S = OCCUPANCY SENSOR SW

ITCH

T = TAM

PER PROOF

+#" = INCHES ABOVE FINISH FLOOR TO CENTERLINE OF BOX

COM

M

ERCIAL CORD REEL RECEPTACLE; CEILING M

OUNTED

H = HIGH BAY SENSOR

V = VACANCY SENSOR M

ODE

EV

J

EM

ERGENCY FIXTURE; DUAL LAM

P HEAD

J C

M

PB

LIGHTING SYM

BOLS

SYM

BOL

IDENTIFICATION

W

IRING DEVICE SYM

BOLS

SYM

BOL

IDENTIFICATION

CONDUIT INSTALLED BELOW

FINISHED FLOOR OR BELOW

GRADE

CONDUIT INSTALLED ABOVE FINISHED FLOOR OR GRADE

INDICATES CONDUIT TURNING UP

CONDUIT HOM

ERUN; ROUTE TO PANELBOARD, CABINET, OR

TERM

INAL BOARD INDICATED, AND TERM

INATE CONDUCTORS TO

CIRCUIT OVER CURRENT PROTECTIVE DEVICE

CONDUIT SYM

BOLS

SYM

BOL

IDENTIFICATION

TELEPHONE/DATA OUTLET; PROVIDE 1"C. W

/ PULL-

STRING TO ACCESSIBLE CEILING SPACE UNLESS

OTHERW

ISE NOTED

X

C = CEILING M

OUNTED; BACK BOX ONLY FOR FUTURE

W

AP UNLESS OTHERW

ISE NOTED

TELECOM

SYM

BOLS

SYM

BOL

IDENTIFICATION

FEEDER DESIGNATION TAG

SHEET KEYNOTE TAG

M

ECHANICAL EQUIPM

ENT TAG

CONTRACTOR EQUIPM

ENT TAG

LETTER IN

DICATES FIXTU

RES CO

N

TRO

L (W

HERE SHO

W

N

N U

M

BER IN

DICATES CIRCU

IT N

U M

BER (W

HERE SHO

W N

REVISION DELTA W

ITH REVISION NUM

BER

#. a.

XX-#

XX-# # DESIGNATION SYM

BOLS

SYM

BOL

IDENTIFICATION

M

ANUAL TRANSFER SW

ITCH

CUSTOM

ER M

ETER

CM

T

INDICATES CONDUIT TURNING DOW

N

CONDUIT STUBBED AND CAPPED

CONDUIT AND W

IRE. HATCH LINES INDICATE QUANTITY OF

UNGROUNDED #12 CONDUCTORS, OR CONDUCTOR SIZE AS NOTED

ADJACENT TO HATCH LINES. GROUND CONDUCTOR TO BE PROVIDED

SIZED IN ACCORDANCE W

ITH NEC TABLE 250-122. IF NO HATCH LINES

ARE SHOW

N, 2#12 & 1#12G CONDUCTORS ARE ASSUM

ED.

TERM

INAL CABINET OR CONTROL PANEL; FLUSH M

OUNTED

TERM

INAL CABINET OR CONTROL PANEL; FLUSH M

OUNTED

EXIT SIGN W

ITH DUAL LAM

P HEAD

STRIP LIGHT

SECURITY CAM

ERA

EPO PUSH BUTTON

O

SPS

COM

BINATION OCCUPANCY SENSOR/PHOTOSENSOR

PS

AIC

AM

PS INTERRUPTING CURRENT

A

AM

PERES

AW

G

AM

ERICAN W

IRE GAUGE

AFCI

ARC FAULT CIRCUIT INTERRUPTER

AFG

ABOVE FINISHED GRADE

CATV

CABLE TELEVISION

CB

CIRCUIT BREAKER

CCTV

CLOSED CIRCUIT TELEVISION

CU

COPPER

EM

EM

ERGENCY / STANDBY POW

ER

FA

FIRE ALARM

FACP

FIRE ALARM

CONTROL PANEL

HP

HORSEPOW

ER

HZ

HERTZ

IDF

INTERM

EDIATE DISTRIBUTION FRAM

E

KV

KILOVOLT

KVA

KILOVOLT AM

PERE

KW

KILOW

ATT

LED

LIGHT EM

ITTING DIODE

M

CB

M

AIN CIRCUIT BREAKER

M

CC

M

OTOR CONTROL CENTER

M

DF

M

AIN DISTRIBUTION FRAM

E

M

TS

M

ANUAL TRANSFER SW

ITCH

NIC

NOT INCLUDED IN CONTRACT

PV

PHOTOVOLTAIC

TYP

TYPICAL

(RR)

REM

OVE AND REPLACE W

ITH NEW

EV

ELECTRICAL VEHICLE

M

LO

M

AIN LUGS ONLY

CONDUIT ONLY

CO

CURRENT TRANSFORM

ER

CT

UL

UNDERW

RITER LABORATORIES

V

VOLTAGE

W /O

W

ITHOUT

AF

LEGEND NOTES

A.B.C.D.

ALL SYM

BOLS M

AY NOT BE USED IN THIS PROJECT

SYM

BOLS DO NOT ALW

AYS REPRESENT REAL LIFE DIM

ENSIONS

SEE SPECIFICATIONS FOR ADDITIONAL INFORM

ATION

M

OUNTING HEIGHTS OF DEVICES SHALL BE AS NOTED IN THE LEGEND FOR THE RESPECTIVE

SYM

BOL, UON ON FLOOR PLANS OR AS REQUIRED PER ADA REQUIREM

ENTS.

ABBRV.

IDENTIFICATION

CDM

F

CDCD

S W H

F

W CD

VISIBLE ONLY (STROBE)

W

ALL M

OUNTED

VISIBLE ONLY (STROBE)

CEILING M

OUNTED

SPEAKER ONLY

W

ALL M

OUNTED

HORN/STROBE VISUAL & AUDIBLE APPLIANCE

SOUNDER TO USE TEM

PORAL 3 PATTERN.

W

ALL M

OUNTED

HORN ONLY AUDIBLE APPLIANCE

SOUNDER TO USE TEM

PORAL 3 PATTERN

W

ALL M

OUNTED

M

INI-HORN AUDIBLE APPLIANCE

SOUNDER TO USE LOW

FREQUENCY OF 520HZ

W

ALL M

OUNTED

SPEAKER/STROBE VISUAL & AUDIBLE APPLIANCE

W

ALL M

OUNTED

NOTIFICATION APPLIANCES

PRI

PRIM

ARY

SEC

SECONDARY

P

POLE

(RR)

RECEPTACLE

LGT

LIGHTING

1.

DISCONNECT SW

ITCHES TO BE SIZED AT M

INIM

UM

TO M

ATCH THE BREAKER SIZE OF THE

RESPECTIVE BRANCH CIRCUIT BEING FED.

2.

RACEW

AY SYSTEM

S AND CONDUIT ROUTING SHOW

N ON ELECTRICAL DRAW

INGS IS

DIAGRAM

M

ATIC IN NATURE AND TO SHOW

THE DESIGN INTENT OF CONDUIT

INFRASTRUCTURE REQUIREM

ENTS. ACTUAL LOCATION AND ROUTING OF ALL CONDUIT

RACEW

AYS SHALL BE DETERM

INED BY CONTRACTOR TO SUIT FIELD CONDITIONS.

3.

CONTRACTOR TO PROVIDE PULL STRINGS IN ALL LOW

VOLTAGE SYSTEM

CONDUITS AND ALL

SPARE CONDUITS.

4.

PROVIDE DEDICATED NEUTRAL FOR EACH NEW

CIRCUIT. HOM

E RUN CONDUCTORS M

AY BE

COM

BINED INTO ONE CONDUIT. NO RACEW

AY OR CABLE SHALL CONTAIN M

ORE THAN NINE

(9) CURRENT CARRYING CONDUCTORS.

5.

BRANCH CIRCUITS TO BE SIZED FOR M

AXIM

UM

3%

VOLTAGE DROP. PROVIDE #10 AW

G

CONDUCTORS FOR 20 AM

PERE, 120V BRANCH CIRCUITS LONGER THAN 75' AND #8 AW

G

CONDUCTORS FOR 20 AM

PERE, 120V BRANCH CIRCUITS LONGER THAN 120'. PROVIDE #10

AW

G CONDUCTORS FOR 20 AM

PERE, 277V BRANCH CIRCUITS LONGER THAN 200'.

6.

PROVIDE DEDICATED NEUTRAL TO EACH BRANCH CIRCUIT PER NEC 210.4.

THIS W

ORK SHALL CONFORM

TO ALL CURRENT AND ADOPTED LOCAL CODES

2022 CALIFORNIA ADM

INISTRATIVE CODE (CAC)

2022 CALIFORNIA BUILDING CODE (CBC) - BASED ON THE 2021 INTERNATIONAL BUILDING CODE 2022 CALIFORNIA ELECTRICAL CODE (CEC) - BASED ON THE 2020 NATIONAL ELECTRICAL CODE

2022 CALIFORNIA M

ECHANICAL CODE (CM

C) - BASED ON THE 2021 UNIFORM

M

ECHANICAL CODE

2022 CALIFORNIA PLUM

BING CODE (CPC) - BASED ON THE 2021 UNIFORM

PLUM

BING CODE

2022 CALIFORNIA ENERGY CODE - TITLE 24, PART 6

2022 CALIFORNIA FIRE CODE (CFC) - BASED ON THE 2021 INTERNATIONAL FIRE CODE

2022 CALIFORNIA GREEN BUILDING STANDARDS (CGBSC) - CALGreen Code

(CA) LIST O

F GO

VERN

IN

G CO

DES

GENERAL ELECTRICAL NOTES:

SHEET INDEX

E0.1

ELECTRICAL SYM

BOLS AND LEGEND

E0.2

ELECTRICAL SPECIFICATIONS

E1.1

ELECTRICAL SITE PLAN

E2.1

ELECTRICAL SINGLE LINE DIAGRAM

E3.1

ELECTRICAL DETAILS

jkrum Snapshot

REVISION SCHEDULE

JOB NUM

BER:

THE USE OF THESE PLANS AND SPECIFICATIONS SHALL BE RESTRICTED TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO SUCH USE. RE-USE, REPRODUCTION, OR PUBLICATION BY ANY METHOD, IN WHOLE OR IN PART, IS PROHIBITED. TITLE TO THE PLANS AND SPECIFICATIONS REMAINS WITH THE ENGINEER WITHOUT PREJUDICE. VISUAL CONTACT WITH THESE PLANS AND SPECIFICATIONS SHALL CONSTITUTE PRIMA FACIE EVIDENCE OF THE ACCEPTANCE OF THESE RESTRICTIONS. COLEBREIT ENGINEERING, LLC DBA AXIOM ENGINEERS

NAPA FIRE STATION #2

ELECTRICAL SERVICE UPGRADE

DATE:

6/21/2024

2024083

1501 PARK AVENUE

NAPA, CA 94558

BID SET

5/27/2024

BEND | EUGENE | M

EDFORD

M

ONTEREY | NAPA | SANTA CRUZ

E N G

I N E E R I N

G

ELECTRICAL SPECIFICATIONS

E0.2

REVISION SCHEDULE

JOB NUM

BER:

THE USE OF THESE PLANS AND SPECIFICATIONS SHALL BE RESTRICTED TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO SUCH USE. RE-USE, REPRODUCTION, OR PUBLICATION BY ANY METHOD, IN WHOLE OR IN PART, IS PROHIBITED. TITLE TO THE PLANS AND SPECIFICATIONS REMAINS WITH THE ENGINEER WITHOUT PREJUDICE. VISUAL CONTACT WITH THESE PLANS AND SPECIFICATIONS SHALL CONSTITUTE PRIMA FACIE EVIDENCE OF THE ACCEPTANCE OF THESE RESTRICTIONS. COLEBREIT ENGINEERING, LLC DBA AXIOM ENGINEERS

NAPA FIRE STATION #2

ELECTRICAL SERVICE UPGRADE

DATE:

6/21/2024

2024083

1501 PARK AVENUE

NAPA, CA 94558

BID SET

5/27/2024

BEND | EUGENE | M

EDFORD

M

ONTEREY | NAPA | SANTA CRUZ

E N G

I N E E R I N

G

ELECTRICAL SITE PLAN

E1.1

SCALE:

ELECTRICA

L SITE PLA

N

1/8 = 1'-0"

(N

) PAN

EL '3'

(E)M

ETER/M

AIN

(N

) PAN

EL '2'

(E) PG&

E PO

LE

M

AIN

SW

ITCHBO

ARD

'M

SB'

(E)CO

M

BO

X

FU

TU

RE FIBER IN

TERN

ET

CO

N

DU

IT STU

B U

P AN

D CAP

3"CO

(LV)

4"CO

PG&

E SECO

N

DARY

2"C

4" PG&

E CO

N

DU

IT RISER

(N

) PG&

E TRAN

SFO

RM

ER

T

(2) 2"CO

(PO

W

ER)

(2) 3"CO

(LV)

2"C

SHEET KEYNOTES

1.

INSTALL NEW

SW

ITCHBOARD ON 2" CONCRETE EQUIPM

ENT PAD. PAD TO EXTEND

OUT LESS THAN 2" FROM

FRONT OF SW

ITCHBOARD ENCLOSURE, PER PG&E

REQUIREM

ENTS.

2.

COORDINATE REM

OVAL OF EXISTING SERVICE CONDUCTORS W

ITH PG&E.

REM

OVE EXISTING OVERHEAD SERVICE CONDUIT AND CONDUIT RISER BACK TO

BELOW

GRADE. EXISTING BELOW

GRADE SERVICE CONDUIT TO BE ABANDONED IN

PLACE.

3.

INSTALL 2" EM

T CONDUIT SURFACE M

OUNTED ON INTERIOR W

ALL/CEILING OF

FIRE STATION TO SERVE NEW

PANEL '3'. FIELD COORDINATE EXACT ROUTING.

CORE THROUGH EXISTING EXTERIOR W

ALL ON BOTH SIDES OF FIRE STATION AND

PROVIDE LB OR J-BOX LOCATED AT TOP OF EXTERIOR W

ALL.

4.

INSTALL NEW

PANELBOARD ON EXTERIOR W

ALL BELOW

W

INDOW

. FIELD

COORDINATE EXACT LOCATION.

5.

STUB UP AND CAP SPARE CONDUIT AT EDGE OF BUILDING.

GENERAL NOTES

1.

PATCH AND REPAIR ALL SURFACES IM

PACTED BY TRENCHING TO M

ATCH EXISTING.

2.

PAINT ALL EXTERIOR BUILDING M

OUNTED CONDUIT, ELBOW

S, AND JUNCTION BOXES TO M

ATCH

EXTERIOR OF BUILDING.

3.

ALL EXTERIOR ABOVE GRADE CONDUIT TO BE GALVANIZED RIGID STEEL CONDUIT.

(X) PG&

E SECO

N

DARY

(X) PG&

E SECO

N

DARY

M

AutoCAD SHX Text

AutoCAD SHX Text E3.1

AutoCAD SHX Text

AutoCAD SHX Text E3.1

REVISION SCHEDULE

JOB NUM

BER:

THE USE OF THESE PLANS AND SPECIFICATIONS SHALL BE RESTRICTED TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO SUCH USE. RE-USE, REPRODUCTION, OR PUBLICATION BY ANY METHOD, IN WHOLE OR IN PART, IS PROHIBITED. TITLE TO THE PLANS AND SPECIFICATIONS REMAINS WITH THE ENGINEER WITHOUT PREJUDICE. VISUAL CONTACT WITH THESE PLANS AND SPECIFICATIONS SHALL CONSTITUTE PRIMA FACIE EVIDENCE OF THE ACCEPTANCE OF THESE RESTRICTIONS. COLEBREIT ENGINEERING, LLC DBA AXIOM ENGINEERS

NAPA FIRE STATION #2

ELECTRICAL SERVICE UPGRADE

DATE:

6/21/2024

2024083

1501 PARK AVENUE

NAPA, CA 94558

BID SET

5/27/2024

BEND | EUGENE | M

EDFORD

M

ONTEREY | NAPA | SANTA CRUZ

E N G

I N E E R I N

G

ELECTRICAL SINGLE LINE

DIAGRAM

E2.1

SCALE:

ELECTRICA

L SIN

G

LE LIN

E D

IA

G

RA

M N.T.S.

2P

MCB

PG&E POLE

M

OUNTED

TRANSFORM

ER

M

AIN SW

ITCHBOARD 'M

SB'

400A, 240/120V, 1Ø, 3W

65 KAIC RATED, NEM

A 3R

GND

NEU 400A

1.

LABEL M

AIN

CIRCU

IT BREAKER AS "M

AIN

EV SERVICE DISCO

N

N

ECT"

2.

PRO

VIDE AN

U

N

SPLICED GRO

U N

DIN

G ELECTRO

DE CO

N

DU

CTO

R TO

THE

GRO

U

N

DIN

G ELECTRO

DE SYSTEM

3.

N

O T U

SED

4.

N

O T U

SED

5.

PRO

VIDE PHYSICAL PRO

TECTIO

N

FO

R GRO

U

N

DIN

G ELECTRO

DE AN

D BO

N

DIN

G

CO

N

DU

CTO

RS IN

ACCO

RDAN

CE W

ITH N

EC 250-64. GRO

U N

DIN

G CO

N

DU

CTO

RS

IN

STALLED IN

ELECTRICAL/TELECO

M

RO

O

M S M

AY BE RU

N

LO

O

SE AS PERM

ITTED

BY N

EC 250-64(b); GRO

U N

DIN

G CO

N

DU

CTO

RS IN

ALL O

THER LO

CATIO

N

S SHALL

BE IN

CO

N

DU

IT IN

STALLED IN

ACCO

RDAN

CE W

ITH N

EC 250-64(e) AN

D

IDEN

TIFIED.

6.

PRO

VIDE GRO

U

N

D RO

D AN

D CO

N

CRETE W

ELL W

ITH STEEL LID LABELED

"GRO

U

N

D". RESISTAN

CE O

F GRO

U N

D RO

D SHALL N

O

T EXCEED 0-25 O

HM

S. IF A

SIN

GLE RO

D EXCEEDS 25 O

HM

S, PRO

VIDE ADDITIO

N

AL GRO

U N

D RO

D(S) SPACED

A M

IN

IM

U

M O

F 6-FEET APART IN

ACCO

RDAN

CE W

ITH N

EC 250-56.

7.

W

HERE THE TRAN

SFO

RM

ER SU

PPLYIN

G THE SERVICE IS LO

CATED O

U

TSIDE THE

BU

ILDIN

G, AT LEAST O

N

E ADDITIO

N

AL GRO

U N

DIN

G CO

N N

ECTIO

N

SHALL BE

M

ADE FRO

M

THE GRO

U

N

DED SERVICE CO

N

DU

CTO

R TO

A GRO

U

N

DED

ELECTRO

DE AT THE TRAN

SFO

RM

ER PER U

TILITY RU

LES, REGU

LATIO

N

S AN

D

STAN

DARDS.

8.

GRO

U N

D BU

SS SHALL BE CO

N

TIN

U O

U

S AN

D 100%

RATED THRO

U

GHO

U T .

9.

THE CO

N

TRACTO

R SHALL SU

BM

IT THE M

AIN

SW

ITCHBO

ARD SHO

P DRAW

IN

GS

TO

PG&

E FO

R FIN

AL APPRO

VAL AN

D AIC VERIFICATIO

N

PRIO

R TO

RELEASE FO

R

M

AN

U

FACTU

RIN

G. N

O

EXTRA CHARGES SHALL BE APPRO

VED FO

R FAILU

RE TO

DO

SO

. THE SW

ITCHBO

ARD SHALL M

EET ALL REQ

U

IREM

EN

TS O

F PG&

E FO

R A

CO

M

PLETE AN

D PERM

AN

EN

T IN

STALLATIO

N

10.

THE CO

N

TRACTO

R SHALL PERFO

RM

ELECTRICAL DISTRIBU

TIO

N

SYSTEM

TESTIN

G

PRIO

R TO

EN

ERGIZIN

G AN

Y FEEDERS

11.

REM

O

VE N

EU

TRAL TO

GRO

U

N

D BO

N D W

HEN

N

EW

SERVICE IS CO

N N

ECTED.

12.

SECO

N

DARY U

TILITY CO

N

DU

ITS PRO

VIDED BY THE CO

N

TRACTO

R PER THE U

TILITY

CO

M

PAN

Y REQ

U

IREM

EN

TS. CABLIN

G PRO

VIDED BY U

TILITY CO

M

PAN

Y.

13.

CO

O

RDIN

ATE W

ITH PG&

E FO

R REM

O

VAL O

F EXISTIN

G M

ETER AN

D PRO

VIDE

M

ETER SO

CKET.

14.

IN

STALL SW

ITCHBO

ARD O

N

6" HO

U

SEKEEPIN

G PAD. VERIFY HEIGHT O

F M

ETER IS

ACCEPTABLE TO

PG&

E. #4 REBAR O

N

12" CEN

TERS.

15.

M

AIN

TAIN

FEEDERS AN

D CO

N N

ECTIO

N

TO

ALL EXISTIN

G DO

W

N

STREAM

EQ

U

IPM

EN

T.

DETAIL NOTES

M

U

TIL-S

(E)

#1/O CU

2P 200A 2P 200A

SHEET KEYNOTES

A.

THE CO

N

TRACTO

R SHALL CO

O

RDIN

ATE ALL SERVICE REQ

U

IREM

EN

TS W

ITH PG&

E

PRIO

R TO

CO

N

STRU

CTIO

N

B.

ALL ELECTRICAL EQUIPMENT SUCH AS SW

ITCHBOARDS, PANELBOARDS, METER SOCKETS

AND MOTOR CONTROL CENTERS SHALL BE PROVIDED W

ITH A PERMANENTLY AFFIXED ARC

FLASH W

ARNING LABELS PER CEC 110.16 AND 110.21 REQUIREMENTS. LABEL SHALL AT

MINIMUM STATE "W

ARNING: ARC FLASH AND SHOCK HAZARD APPROPRIATE PPE

REQUIRED"

PAN

EL

'3' (N

EW

PAN

EL

'2' (N

EW

SCALE:

M

SB SPECIFICA

TIO

N

SH

EETS

N.T.S.

(E) M

ETER

M

AIN

240V,1Ø

, 3W

FEEDER SCHEDU

LE (CO

PPER)

FEEDER

DESIG

N

ATIO

N

CO

N

DU

CTO

R Q U

AN

TITY, SIZE (AW

G

/KCM

IL), &

CO

N

DU

IT (IN

CHES)

U

TIL-S

(1) 4"C - CO

N

DU

CTO

RS BY PG&

E

3 #3/0 CU

THW

N

-2, 1 #4 CU

GN

D., IN

2"C.

.80 VD

0.33%

VD

2.40 VD

1.00%

VD

TO

TRAIN

IN

G TO

W

ER

NG

(E)

M

(X) PG&E METER

2P 200A

XXXXX

(E) SERVICE TO BE

REM

OVED

(2) 2" CO

PG&E METER

6" M

IN

6" M

IN

REVISION SCHEDULE

JOB NUM

BER:

THE USE OF THESE PLANS AND SPECIFICATIONS SHALL BE RESTRICTED TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO SUCH USE. RE-USE, REPRODUCTION, OR PUBLICATION BY ANY METHOD, IN WHOLE OR IN PART, IS PROHIBITED. TITLE TO THE PLANS AND SPECIFICATIONS REMAINS WITH THE ENGINEER WITHOUT PREJUDICE. VISUAL CONTACT WITH THESE PLANS AND SPECIFICATIONS SHALL CONSTITUTE PRIMA FACIE EVIDENCE OF THE ACCEPTANCE OF THESE RESTRICTIONS. COLEBREIT ENGINEERING, LLC DBA AXIOM ENGINEERS

NAPA FIRE STATION #2

ELECTRICAL SERVICE UPGRADE

DATE:

6/21/2024

2024083

1501 PARK AVENUE

NAPA, CA 94558

BID SET

5/27/2024

BEND | EUGENE | M

EDFORD

M

ONTEREY | NAPA | SANTA CRUZ

E N G

I N E E R I N

G

ELECTRICAL DETAILS

E3.1

48"

N O

TE:

FIN

ISH

G R

AD

E

PATC

H

& M

ATC

H

EXISTIN

G

SU

R

FAC

E

34 " AB C

LASS 2 C

O M

PAC

TED

BASE FILL & FIN

ISH

AS

N

EED

ED

(95% C

O M

PAC

TIO

N M

IN

SAN

D

BAC

KFILL

SAN

D

BAC

KFILL

12" M

IN

. C

LEAR

AN

C

E

SAN

D

BAC

KFILL

C O

O R

D

IN

ATE W

/LO

C

AL U

TILITY

C

O M

PAN

YS, C

ITY & C

O

U N

TY

R

EQ

U

IR

EM

EN

TS FO

R M

IN

IM

U M

R

EQ

U

IR

ED

TR

EN

C

H

IN

G D

EPTH

'S.

12 3/8"

9"

FINISH GRADE

1 3/4"

CAST IRON LID

GROUND ROD BOX. CHRISTY

#F8 OR EQUAL.

GROUND CONNECTOR

AGGREGATED BASE

GROUND ROD ELECTRODE (3/4"x10' LONG, COUPLING TYPE, COPPER OR COPPER

CLAD STEEL

GROUND CONDUCTOR #4 AW

G MIN., BARE,

STRANDED, COPPER W

IRE, U.N.O.

SCALE:

E401

G

RO

U N

D

RO

D D

ETA

IL

N.T.S

SCALE:

2E3.1

TREN

CH

D

ETA

IL

N.T.S

18"

4" 3"

2" M

IN

PER CITY STANDARD

34 " AB C

LASS 2 PER

C

ITY

STAN

D

AR

D

SCALE:

3E3.1

TREN

CH

D

ETA

IL

N.T.S

18"

3" 3"

2" 2"

24" M

IN

IN

TH

E C

LEAR

T-C U

T PER

C

ITY STAN

D

AR

D

12"

5" OR

M

ATCH

EXISTING,

W

HICHEVER

ISGREATER

12" SAN

D

BAC

KFILL

Sheets and Views