FAALC EQUIPMENT SHELTER SPECIFICATION
Revision: 1.0 (10 Year) Revision Date: 03/13/2023
1.0 Intent – The intent of this specification is to provide a means of procuring fiberglass equipment shelters for the housing and installation of electronic equipment including but not limited to Navigation, Landing, Lighting and related equipment, communication equipment, weather equipment, engine generators and other equipment for the Federal Aviation Administration (FAA) and other Government sites. Certain items listed within this specification may have further terms and conditions enumerated within the contract documents. They include:
1.1. Submittal process and timeframes.
1.2. Fabrication timeframes and expedited assembly compensation.
1.3. Transportation/delivery responsibilities.
2.0 Scope – This specification covers the responsibilities of the fiberglass equipment shelter manufacturer (hereinafter simply referred to as “shelter manufacturer”) to fabricate and assemble transportable prefabricated insulated fiberglass equipment shelters complete including: interior finish materials, exterior door and frame, hardware, door hood, HVAC, electrical equipment, and fixtures. The shelters must be pre-assembled and fiber-glassed with Gelcoat finish, completely dust-proof and watertight, and must be completely shop-fabricated with the required appurtenances. The shelters must be designed for the explicit use of housing and maintaining electronic equipment and related components within an environmentally controlled atmosphere by maintaining the proper operating conditions for the equipment.
3.0 General – Except for any items specifically identified herein as being Government Furnished Material (GFM), all labor, equipment, materials, parts, and supplies necessary for completing the work as shown on drawings or herein described must be furnished by the shelter manufacturer. All equipment, materials and parts furnished by the shelter manufacturer must be new, suitable for the intended use, and of proven design to adequately withstand the loads and conditions specified without damage, leaking, corrosion, warping, twisting, or any other deleterious effects. All exterior surfaces must be either painted, hot-dipped galvanized (for metal components), or stainless steel. All exterior hardware must be stainless steel.
4.0 Applicable Documents – The current issues of the following documents in effect on the date of the invitation for bid form a part of this specification and are applicable to the extent specified herein:
4.1. FAA-C-1217g: Electrical Work, Interior.
4.2. FAA-STD-019f; Lightning Protection, Grounding, Bonding and Shielding Requirements for Facilities.
4.3. IEEE-1100; Recommended Practices for Powering and Grounding Sensitive Electronic Equipment.
4.4. National Electric Code (2017 or current applicable year addition).
4.5. National Fire Protection Code NFPA-70.
4.6. AC 70/7460 Paint Advisory Circular.
5.0 Shelter Drawings: The shelter manufacturer must originate and provide the design drawings based upon the generic drawings provided by the FAA Logistics Center (FAALC). (Drawings must be included in contract pricing.) These drawings must demonstrate detailed specifications of the different interior and exterior exposures. In addition, the drawings must include electrical layouts and all options for the shelters. The shelter manufacturer must include in the documentation a foundation plan for each size shelter built for the FAALC for proper construction at FAA facilities. Generic designs for grade beam, slab, and pier construction are required to be provided.
5.1. Standard Size Requirements
6 x 8 feet 8 x 16 feet 10 x 16 feet 12 x 26 feet 8 x 12 feet 10 x 12 feet 10 x 20 feet
5.1.1. Shelter designations are “Left” or “Right” along with the shelter size. “Left” or “Right” is identified, as upon entrance to a shelter, the power panels would be located to the left or right of the entrance.
For reference, Attachment 13 this package is a “Left” designation shelter. A “Right” designation would be the mirror image of that drawing.
5.2. The shelter manufacturer will be required to produce shelters of an opposite or “mirror image” of the shelters designated below. Drawings for these shelters are required where applicable.
5.3. Upon delivery, the Shelter Manufacturer must provide two (2) paper copies of final drawings and one (1) electronic copy in a format approved by the FAALC.
5.3.1. (Manufacturer Drawing No.): 12-foot by 26-foot Fiberglass Equipment Shelter Manufacturer
Requirements Floor Plan and Elevations.
5.3.2. (Manufacturer Drawing No.): 10-foot by 20-foot Fiberglass Equipment Shelter Manufacturer
Requirements Floor Plan and Elevations.
5.3.3. (Manufacturer Drawing No.): 10-foot by 16-foot Fiberglass Equipment Shelter Manufacturer
Requirements Floor Plan and Elevations.
5.3.4. (Manufacturer Drawing No.): 10-foot by 12-foot Fiberglass Equipment Shelter Manufacturer
Requirements Floor Plan and Elevations.
5.3.5. (Manufacturer Drawing No.): 8-foot by 16-foot Fiberglass Equipment Shelter Manufacturer
Requirements Floor Plan and Elevations.
5.3.6. (Manufacturer Drawing No.): 8-foot by 12-foot Fiberglass Equipment Shelter Manufacturer
Requirements Floor Plan and Elevations.
5.3.7. (Manufacturer Drawing No.): 6-foot by 8-foot Fiberglass Equipment Shelter Manufacturer
Requirements Floor Plan and Elevations.
5.3.8. (Manufacturer Drawing No.): Shelter Foundation Details
5.3.9. (Manufacturer Drawing No.): 3-0 foot by 4-2 feet Shelter Galvanized Step Details in one, two, and three step configurations.
5.3.10. (Manufacturer Drawing No.) Basic shelter lightning protection components and installation layout
(reference FAA-STD 19f).
5.4. Individual site and function specific drawings must be created for each shelter ordered under this contract.
Said drawings will be created in the latest available AutoCAD format and delivered to the FAALC for design approval within two (2) weeks of delivery order receipt. Unless specifically authorized, no manufacturing must occur before drawing approval.
5.5. The release of drawings or any other information or material related to shelters or products produced under this contract must be coordinated through the Contracting Officer (CO) or Contracting Officer’s Representative (COR).
5.6. The drawings produced by the Manufacturer for the generic design, including revisions, or any buildings purchased under this contract become the property of the Government. The Government reserves the right to further use these drawings without limits, for site development and design, customization, etc.
5.7. Any changes and/or modifications to contract documents however minute, e.g., stock-list component substitutions or replacements must not be made without COR approval.
6.0 Shelter Manufacturer’s Qualifications – The shelter manufacturer must be regularly engaged in the fabrication of pre-assembled fiberglass equipment shelters with existing plant facilities equipped for year-round shelter manufacturing with a minimum of 10 years’ experience. Plant must be capable of producing multiple shelters simultaneously and multiple quantities (minimum 12) per month for this contract. Shelter manufacturer must be ISO 9001:2015 certified.
7.0 Shelter Type: The shelter must be a prefabricated, pre-assembled fiberglass portable buildings using standard manufactured sizes. The use of concrete or metal for the structure or metal for the exterior surface is NOT permitted except for below listed items. The use of fiberglass material for the vent/fan hoods and door rain shield is required.
7.1. Any metallic materials used for the shelter skids, doors, or other small attachments on the exterior must be made of stainless steel, hot-dipped galvanized steel, or marine grade aluminum.
7.2. The predominate majority of equipment shelters are of fiberglass construction. In rare instances, the FAALC customer requires a portable concrete and/or steel shelter. In those cases, the fiberglass shelter manufacturer must be responsible for procuring the required concrete or steel shelter shell from an approved concrete or steel manufacturer and assuring its full and complete compliance with specifications herein. The shelter manufacturer will be responsible for the installation of interior finishes, electrical boxes/fixtures, HVAC units and exterior doors to insure appearance and functionality consistency with fiberglass shelters.
8.0 Manufacturing Time requirements - As a part of the solicitation, the manufacturer must respond with their proposed timeline of shelter deliveries. However, at no time must shelter deliveries exceed forty-five (45) days beyond delivery order submittal to the manufacturer. Exceptions to this rule are spelled out in the contract documentation, e.g., large order requirements.
9.0 Shelter Size – Shelter manufacturer must provide shelters with the following standard dimensions. Dimensions given (with exception of ceiling height) are nominal exterior dimensions. A larger size is acceptable if the shelter manufacturer has a factory standard. Manufacturer’s larger size shelters must not be greater in size than allowed for transport over the United States’ continental highway system.
9.1. Although these are the standard sizes that will be used under this contract, the contract is not limited to these sizes and/or configuration. Different configurations of shelters must be available under this contract at negotiated costs. Shelter manufacturers must be able to produce at minimum, shelters of 32-foot by 50-foot in exterior size. Shelters in excess of 18’ width must be configured as shelter “halves” and will include shelter manufacturer assembly at the final destination.
9.2. 10-foot by 20-foot by 8-foot minimum interior ceiling height
9.3. 10-foot by 16-foot by 8-foot minimum interior ceiling height
9.4. 10-foot by 12-foot by 8-foot minimum interior ceiling height
9.5. 8-foot by 12-foot by 8 minimum interior ceiling height
9.6. 8-foot by 16-foot by 8-foot minimum interior ceiling height
9.7. 6-foot by 8-foot by 8-foot minimum interior ceiling height
9.8. 12-foot by 26-foot by 8-foot minimum interior ceiling height (Runway Status Light [RWSL] Building). The RWSL buildings are unique in the requirement that they must meet heavier floor loading requirements with 1200 lb. Constant Current Regulator/Master Lighting Controller (CCR/MCL) cabinets. The shelter must have the capability to be lifted with units installed, maximum quantity of four (4), along with equipment cabinet rack and other standard shelter items e.g., workbench cabinet, etc. See specific RWSL shelter drawings for additional details.
10.0 Operating Environment – The shelters must be dust-proof and watertight. The shelters must be capable of withstanding any probable combination of the following conditions without mechanical or electrical damage or degradation of performance below that specified herein:
10.1. Environment temperature range of minus (-) 58 to plus (+) 158 degrees Fahrenheit.
10.2. Wind velocities up to 170 miles per hour (mph) when secured in place.
10.3. Exposure to corrosive/salt atmosphere as encountered in coastal areas, e.g., Florida.
10.4. Rainfall as encountered in coastal areas, e.g., Washington.
10.5. Snow/ice as encountered in northern states, e.g., Alaska.
10.6. Relative humidity up to 100% with any temperature specified above.
11.0 Structural – Each in-place structure, including all components, connections and attachments, must be designed to satisfy the following conditions. Design must conform to all requirements for “essential facilities” of current edition of the Uniform Building Code (UBC).
11.1. Seismic – Worst Case Per ASCE 7-10.
11.2. Wind - ASCE 7-10. 170 mph Risk Category IV, Exposure C.
11.3. Floor live load – 300 pounds per square foot (PSF) and a concentrated load of 175 pounds on a 3-inch round disk anywhere over the floor surface.
11.4. Roof live load – 70 psf.
12.0 Floor – The following or equal are minimum requirements for the floor:
12.1. Sub-flooring must be constructed of minimum one and one/eighth inch exterior grade tongue-and-groove plywood on the inside; wood or steel channel floor joists (sized and spaced to meet loading), and ½ inch exterior grade plywood, or equal, on the outside. The ½ inch plywood must be protected by spraying/ rolling (minimum ¼ inch mixture) of vinyl ester resin and chopped fiberglass or equivalent, and final finish of gelcoat on the exterior before installation onto the skid. A solid layer of minimum 26GA G90 sheet metal is required below the vapor/moisture barrier to be used as a rodent barrier.
12.2. Interior of the floor must be covered with commercial grade no-wax vinyl flooring or FAA-approved equal or better. A 4-inch vinyl base or equivalent must be provided at the walls.
12.3. The floor must provide a minimum insulation value of R-11 composed of closed-cell polyiso foam core bonded to glass fiber reinforced aluminum facers on both sides.
13.0 Roof – The shelter roof must support a live load of 70 psf. The following or equal are minimum requirements for the roof:
13.1. The roof must be sloped a minimum of ¼ inch per foot to prevent water from standing. The interior ceiling must provide a support structure of sufficient strength which is flat, level and perpendicular to shelter walls to support electrical fixtures, hardware, cable trays, etc. when mounted by either the manufacturer or end-user. Maximum distance between support members must be no greater than 8” inches
13.2. Ceiling finish must be minimum ½” plywood coated with white poly finish. Oriented Strand Board (OSB) substrates will not be allowed.
13.3. The roof must provide a minimum insulation value of R-30. Roof insulations must be high density, closed cell spray foam with required 15-minute thermal barrier coating per International Building Code (IBC).
14.0 Walls – The following specifications or equivalent are minimum requirements for the walls:
14.1. The interior walls must provide a surface support structure of sufficient strength to support up to 150 lbs.
of electrical fixtures, hardware, etc. when mounted by either the manufacturer or end-user without the use of Unistrut, additional framing or through wall bolting.
14.2. Interior wall finish must be minimum ¾” plywood coated with white poly finish for all interior wall surfaces.
The use of OSB boards is not permitted.
14.3. The walls must provide a minimum insulation value of R-19 composed of closed-cell polyiso foam core bonded to glass fiber reinforced aluminum facers on both sides. No fiberglass batt insulation or loose material insulation must be used within the walls.
14.4. The shelter must have complete internal framing members with a minimum depth of 3.5” resulting in an overall wall thickness of 5” or more. The shelter assembly cannot rely on fiberglass interior/exterior finish for the overall structural integrity. The fiberglass coating is nonstructural and for environmental protection only.
14.5. Exterior wall structural sheathing must be rated to mount electrical items up to 350 lbs. without the need for additional reinforcements.
14.6. Exterior wall fiberglass coating must be a vinyl ester resin with chipped strand fiberglass. Mixture must be applied at a minimum 3/16” thickness and be completely seamless from wall to wall and wall to roof intersections. After fiberglass process is complete, a marine grade Gelcoat (Armorcote) with Ultraviolet (UV) inhibitors must be applied to a minimum dry film thickness of minimum 24 mils.
14.7. Fiberglass laminated materials or injection/vacuum molded; fiberglass reinforced plastic (FRP) foam core wall assemblies are not acceptable.
15.0 Door – The door must be of sufficient depth and strength to provide durability, insulation, and security to the structure. Manufacturer’s door must be equivalent or superior design to JRJ Alum-Fab part number D- C\D00053HL (hinge left) or D-C\D00053HR (hinge right).
15.1. The door width must be specified in the individual specification drawings, minimum 34” opening or clearance. Door height must be a minimum of 6 feet 8 inches. Exterior door surface color must match or blend with exterior paint markings of shelter.
15.2. Door must be constructed with minimum 3/16” thick marine grade aluminum exterior door leaf with .100” interior skin assembled into ¼” thick marine grade aluminum fully welded frame; entire door must be painted with epoxy/polyurethane coating.
15.3. The door must be mounted with three (3) stainless steel container door security type hinges or equivalent.
The hinges must be tamper-resistant with preferred location on the inside of door and frame to prevent vandalism.
15.4. The entire door must be seamless (no visible seams) or welded.
15.5. The door must provide a minimum insulation value of R-10.
15.6. The door must close and latch at a minimum of three points by means of ½” solid stainless-steel rod to provide a positive watertight seal. This latching mechanism must be controlled by a single actuator which latches the door at three or more points.
15.7. The jimmy-proof lock set must be equipped with a heavy-duty best lock cylinder. The lock cylinder must have a removable construction core and be provided with two (2) construction core master keys and one
(1) construction core control key (final keying to be completed by others). All shelters leaving the manufacturer will be keyed identically. The exterior lock entry must be covered to avoid dust, dirt, or water entry.
15.7.1. The manufacturer must supply the FAALC with ten construction master keys upon first, standard delivery. Additional keys must be made available upon request over the life of the contract.
15.8. The door seal or gasket must be constructed of a heavy-duty material. Minimum thickness of the material must be 3/8-inch and no less than one inch in width. The door seal must be mounted in such a way as to provide protection against damage from entry of personnel or equipment into and out of the shelter and minimize deterioration of the seal from the natural elements. Seals mounted on a flat doorframe structure do not provide such protection. When properly closed, the seal must provide protection from water entry into the shelter against strong, hurricane-strength winds. Door and frame interface must be of a clamshell design configuration.
15.9. An industrial duty hydraulic door closure is required as a means of supporting or holding the door in an open position and prevention against damage from wind.
15.10. A loose-shipped fiberglass rain hood over the door is required. The rain hood must extend beyond each side of the door by a minimum of three (3) inches. The rain hood must extend away from the building a minimum of twenty inches (20” deep).
15.11. Doors must be available in both left and right hinge models with no increase in contract price for materials and/or installation.
16.0 Skids – The shelter must be mounted on an I-beam skid made of all-welded steel construction. Entire skid assembly must be hot-dipped galvanized after fabrication and welding is complete. Skid must provide the necessary strength for hoisting and lifting and to meet all other requirements specified herein. Skids must be provided with a means of lifting, e.g., lifting eyes, on each of the four corners; these points must extend beyond the edge of the shelter or alternative means provided to protect the shelter exterior during lifting. In addition to the shelter weight, these lifting points must be sufficient to carry a minimum of 1500 lbs. internal to the shelter.
See generic drawings for typical equipment placement and weight. The steel floor joists must be welded to the skid. Typical skid construction includes heavy “I” beam longitudinal runners braced at each end with secondary C-channels for floor joists, and heavy channel for perimeter support. The skid must be designed to fit the foundation plans developed by the shelter manufacturer.
16.1. Offloading and placement of shelters is frequently performed by forklift. A skid framework design is required which accommodates such movement without compromising safety and prevents damage to the shelter floor. For that reason, all shelters must be equipped with the following beam configurations:
16.1.1. Shelters 8’ or less in width must have a minimum of three full-length longitudinal I-beam runners.
16.1.2. Shelters >8’ in width must have a minimum of four full-length longitudinal I-beam runners.
16.1.3. Shelters >12’ in width must have a minimum of five full-length longitudinal I-beam runners.
16.1.4. Enclosed forklift pockets fully integrated into the skid base must be offered as a separately priced option.
17.0 Electrical/Power Requirements (reference Attachment 3 for location): Electrical installations must conform to the latest edition of the National Electrical Code (NEC), FAA-C-1217, FAA-STD-019, IEE-1100, and in accordance with the following requirements. If specifications are in conflict, the FAA requirement must take precedence over the NEC. In no case, however, must the NEC be violated. All components used must be rated heavy duty, industrial or commercial.
17.1. Bonding: The panel board enclosure, disconnect, double throw, Transient Voltage Surge Suppressor (TVSS), utility and generator service entrance raceway and grounding bar must be effectively bonded together. Internal bonding jumpers must be minimum #6 AWG copper conductor between all grounding bushings 1.5” and larger and #12 AWG for 1.25” and smaller. If otherwise not indirectly or directly bonded, bond conduits using a minimum 6 AWG bonding conductor. Conduit raceways that are less than
1.5 in. trade size or less than 10 ft in length are exempt from the bonding requirement. Neutral bar must be isolated from the grounding bar in the panel board. Only at the main disconnect must neutral and ground be bonded together utilizing same AWG as the system ungrounded conductors. Grounding bar connection points for the panel must exceed breaker capacity by a minimum 50%. Raceways, enclosures, and conduits must not be used as a means of acceptable bonding.
17.2. Main Panel: Square-D NQ30L1C, (or equivalent) 100A capacity – Main Lug Only – with door-in-door cover. In addition to manufacturer installed components, the shelter manufacturer must install at minimum three (3) 20A spare breakers in the panel. A bolt-in type breaker or equivalent must be used. A double-hinge panel is required.
17.2.1. Square-D NQ30L2C (or equivalent) 200A capacity with door-in-door cover option must be offered as a separately priced option.
17.3. Fusible Disconnect: Square- D H223N (or equivalent) 100A heavy duty disconnect must be equipped with an NLN-type 100A fuse each leg.
17.3.1. Square-D H224N (or equivalent) 200A capacity option must be offered as a separately priced option.
17.3.2. Spare fuses must be supplied with each unit. (2 each standard shelter, 3 each RWSL shelters).
17.4. Main Distribution Wire Duct: 6”x6” wireway with hinged covers must be provided for all service entrance wiring to the disconnect, TVSS, and panelboard wiring.
17.4.1. Additional 6”x6” wireway with hinged covers must be offered as a separately priced option.
17.5. Wiring size: All 100 AMP utility and/or generator wiring must consist of a minimum #2 THHN/THWN-2 for ungrounded conductors, grounded conductor, and system ground. This must also be applicable to all 100 AMP feeder connections and 100 AMP branch circuits.
17.6. Wiring size: All 200 AMP utility and/or generator wiring must consist of a minimum 4/0 THHN/THWN-2 for ungrounded conductors, grounded conductor, and system ground. This must also be applicable to all 200 AMP feeder connections and 200 AMP branch circuits.
17.7. Runway Status Light (RWSL): Shelters must contain 480V service as specified in the FAA drawings. The shelter manufacturer must build and price accordingly with no substitution of components. Typical installation contains a 480V disconnect (NEMA 3), 480V panel (NEMA 3), transformer, and 120/240 V, 200Amp (NEMA 3) panel.
17.8. Surge Arrestor: The manufacturer must install an FAA approved and certified TVSS device in the power system of the shelter. This unit must be lifetime tested and pass such tests at a recognized testing facility with FAA observation. Conducted tests must be FAA approved to meet FAA requirements as designated by the FAA Power Service Office (AJW-22). Final approving authority falls to the above-specified office of the Government. The specified TVSS must be UL listed. TVSS units must be installed inline as a direct pass-through connection. T-connections are not allowed.
17.8.1. Surge Arrestor manufacture must be Rayvoss (120-2S-M3-3-06-A) or equivalent
17.8.2. 200A capacity (120-2S-N1-3-06-A must be offered as a separately priced option.
17.9. Grounding Plates: The manufacturer must install in accordance with the specifications. Plate size is provided in the FAA specifications. The Government must provide plate design.
17.9.1. For the 6x8 shelters, one ground plate is required. The Government must provide the location for mounting of the plate. Plate covers must be designed and labeled per FAA-STD-019f.
17.9.2. For shelters 8x12 and larger; the manufacturer must provide two ground plates, Main Ground and Supplemental Ground and placed as designated by the Government. Plate covers must be designed and labeled per FAA-STD-019f.
17.9.3. The manufacturer must install 1-1/2” Schedule 80 PVC conduit through the floor for installation of the main and supplemental (if applicable) ground conductors. The PVC must end at a point approximately 8 inches from the ground plate(s) and must have a means to extend the PVC on the exterior of the shelter to the site counterpoise.
17.9.4. Lugs used within the shelter must be hexagonally crimped Per FAA-STD-019f.
17.9.5. The manufacturer must install 1-1/4” Schedule 80 PVC conduit through the floor for installation of the door ground conductors (hinge side).
17.10. Interior Outlets: The manufacturer must install 20A industrial-grade electrical outlets, minimum 1 per wall, spaced every (4) - (6) feet, 18 inches above floor unless otherwise directed.
17.10.1. One ground fault interrupter (GFI) powered outlet must t be mounted on the interior wall, near the door.
17.11. Interior LED lights: The manufacturer must install 40-watt input light-emitting diode (LED) linear fixtures;
(6) each in 12x26, (4) each in 10x20, 10x16, 10x12, and 8x16, (3) each in 8x12, and (2) each in 6x8 shelter. Minimum distance from walls for ceiling installation is 12 inches. All fixtures are to be mounted
(2) inches below ceiling surface on Unistrut to allow conduit to run between fixture and ceilings.
17.11.1. Interior lighting circuits must use UL approved fixtures, switches, and lamps with wiring that conforms to NFPA-70.
17.11.2. LED lamps/elements must be used in all light fixtures.
17.11.3. All Lighting must be of the type that is filtered to prevent radio frequency interference (RFI), Certification on LED driver being FCC 47 CFR Part 15 Subpart B (Class B) compliant is required.
17.11.4. Each lighting circuit must be supplied with its own on/off switch at the entrance. For shelters equipped with two (2) exterior doors a three-way on/off switch must be provided at each entrance.
17.11.5. Battery-powered interior emergency lighting must be provided. Emergency lighting must automatically illuminate in the event power fails and must extinguish when power is restored (Lithonia ELM2L-M12 or equivalent).
17.12. Exterior LED light: must have wire guard, be photoelectric and override switch controlled.
17.13. Ground bushings: must be installed on all conduits at every termination point and bonded to equipment grounding system as per 4.2. FAA-STD-019f.
17.14. Skid Grounding: The manufacturer must install four (4) grounding lug/stud bolts locations, two (2) studs each at 1-inch separation, on all four (4) corners of the shelter skid and must be readily accessible for tie-in to the local grounding grid. Each grounding connector (field installed by others must tie to the skid with two (2) bolts/studs welded to the skid. The two-stud connection points must be masked or covered during the galvanizing process so that bare metal is available beneath. This connection point must accommodate a standard 4/0 long barrel crimp lug with 1” hole spacing. The 3/8” studs must be a minimum of 1-1/2” length to accommodate the lug, (1)a standard washer, (2) Belleville washers, and (1) nut for proper grounding per FAA specs 019f.
17.15. Metal Component Grounding: All large metal components of the shelter; e.g., door, must be grounded to the building skid. Final determination of those metal components which require grounding must be made by the Government. A heavy duty dual flat braided ground strap with (2) hole pads are required between door leaf and door frame.
17.16. Electrical conduit penetrations: The shelter structure/skid must be built such that vertical conduits mounted on any interior wall can penetrate directly through the floor. On any (2) opposing walls, generally the longer walls for a rectangular structure, the ability to extend a 2-inch vertical conduit down the wall, through the floor, and into the ground below the structure without interference from the main skid beams is required. Conduit access from outside the shelter must be available on the long walls; e.g., inset front/rear skid beam. For the remaining (2) opposing walls, the ability to install a 4-inch vertical conduit without skid interference is required.
17.16.1. Penetrations for electrical conduit, (i.e., power input,) must be of a threaded union fully welded to a bulkhead plate, painted, then mounted to the shelter exterior in a manner where attachment can be made in the field, e.g., LB connection. The bulkhead plate must be seal welded so as to not allow water penetration into the wall. The bulkhead plate must be securely mounted to prevent turning and must have sealant applied between the plate and exterior shelter surface to prevent water penetration into the wall.
17.16.2. Conduit exit points for grounding must be installed at a 45o angle prior to application of chopped fiberglass resulting in a sealed wall penetration. Conduits must extend 3” beyond exterior wall surface. Ground conduits must not be installed directly below incoming power penetration/bulkhead plate.
17.16.3. At no point must a simple or single bead of caulking, silicon, etc. be considered adequate or allowable for wall penetrations.
18.0 Environmental Requirements (see drawing for location): The manufacturer must install national manufacturer HVAC units for which warranty or repair service is readily available.
18.1. HVAC units must be a vertical packaged wall mount unit with electrical heat and air conditioning for installation on exterior shelter surface.
18.2. HVAC units must provide a minimum of 1T minimum cooling and 3KW heating capacity.
18.3. HVAC condenser and evaporator coils must be phenolic coated.
18.4. HVAC units must be thermostatically controlled.
18.5. HVAC must be equipped with a service disconnect readily accessible from the shelter exterior.
18.6. Multiple HVAC units with lead/lag controller must be offered as a separately priced option.
18.7. A wall-penetrating window-style unit with a minimum of 1T minimum cooling and 3KW heating capacity must be offered as a separately priced option.
18.8. Mini-split HVAC units (separate compressor and fan assembles) with a minimum of 1T minimum cooling and 3KW heating capacity must be offered as a separately priced option.
19.0 Openings – Wall openings for door, air conditioners, fans, vents, etc., must be adequately framed in place with structural members and must be 100% fiberglass/resin matt wrapped prior to application of exterior chopped fiberglass with a minimum of 1-inch overlap from the outside, across the entire wall depth and continued to the interior side with a 1” wrap. All attachments to the shelter exterior must be adequately caulked with a silicone product to seal for water penetrations.
20.0 Paint Configuration -The exterior must be Gel-coated white and orange, checkerboard pattern, using existing color and configuration specifications. Exterior surfaces for the door, hoods, rain cap, and boxes must match the desired paint scheme.
20.1. As listed in the specification, paint must be gloss, Marine Grade Armorcote gel-coat material. UV inhibitors must be used to protect Gel coat from fading and/or bleeding.
20.2. Shelter Manufacturer must allow for the use of other Gel coat/paint colors in a solid format at no additional charge to the Government.
20.3. Shelter Manufacturer must also offer an aggregate earth tone Stoneflake finish as a separately priced option.
21.0 FAA Inspection – The Federal Aviation Administration (FAA) or designated representative must, during any normal working hours, be permitted to view the work process. Shelter manufacturer must correct the work on any part of the job if such work is not being done in accordance with this specification. The shelter must be made available for final inspection at shelter manufacturer’s plant before shipment.
22.0 Submittals Process
22.1. Submittals – Transmittal letters identifying the contents of the submittal must accompany all submittals.
Submittals must accompany the manufacturer’s proposal. Submittals must be complete, detailed, and assembled in sets. Lack of completeness or inadequate description will be justification for disapproval.
22.1.1. Within two weeks after each delivery order (DO) is awarded, the manufacturer must submit an electronic copy (AutoCAD) of the individual site-specific design for FAA COR review. Design approvals and/or changes will be accomplished at that time. A final FAA customer review may be a part of this review process.
22.1.2. The checking, marking, or approval of the shop drawings and/or product data by the FAA must not be construed as a complete check, but will indicate only that the general method of construction and detailing is satisfactory. Approval will not relieve the manufacturer of the responsibility for the dimensions and design of adequate connections, details, and satisfactory construction of all work.
22.1.3. The manufacturer must only take direction for changes under this contract from the Contracting Officer (CO). Any changes that incur additional costs must be approved through the CO. Any changes directed by the FAA field or other customers should be directed to the CO/COR. The manufacturer is responsible for additional costs incurred if this process is not followed.
22.2. FAA Approvals
22.2.1. Approved as Submitted – If drawings are indicated “approved as submitted,” (typically via email) the approved revision of the shop drawings or product data will be identified as having received such approval by an appropriate and consistent drawing revision control process. After submittal has been approved, the FAA will permit no substitution without written approval.
22.2.2. Approved as Noted – If drawings are marked “approved as noted,” the shop drawings or product data is satisfactory contingent upon manufacturer performance of corrections, notations, or both and, if accepted, does not require re-submittal.
22.2.3. Not Approved – If drawings are marked “not approved,” the shop drawing or submittal data do not meet job requirements and the manufacturer must resubmit. If shop drawings or submittal data are disapproved, the manufacturer must resubmit the corrected material, in the same quantity as specified for the original submittal.
22.3. Samples – The Government reserves the right to request samples of any products or materials proposed for use on this project. A core of the wall penetration from the electrical input must be shipped with each shelter.
23.0 Transportation – The proposed price(s) must be quoted freight on board (FOB) destination, Oklahoma City, OK.
Transportation of direct-ship shelters to points within the US must also be freight on board (FOB) destination as detailed within the contract documents. The shelter manufacturer must submit any additional shipping charges in the original quote for direct site shipments.
23.1. Items that might be damaged during transportation, e.g., rain hoods, exterior light, lighting elements, must be removed and properly packaged for shipment. The shelter itself must be designed to withstand repeated hoisting or lifting stress in loading/off-loading for shipment by truck, and to properly withstand all road shock, which may be encountered during such means of transportation. Provisions, as necessary, to allow hoisting without damage to the shelter or equipment installed prior to shipment must be included, e.g., lifting eyes, bolt-on lifting plates, cable guides. Shelter manufacturer must also provide hardware necessary for shelter-to-slab connection.
23.2. All damage incurred during shipment from the manufacturer’s facility to any designated destination is the responsibility of the shelter manufacturer.
23.3. The shelter manufacturer must have the capability to ship their product overseas and arrive in a safe manner with no damage. Forklift pockets integrated into the shelter frames are required for overseas shipments.
23.4. The shelter manufacturer is responsible for coordinating off-loading equipment for the FAA’s “direct ship” sites, except for the FAA Logistics Center. The shelter manufacturer will submit these costs along with any additional shipping charges in the original quote for direct site shipments. It is the FAA’s option to use this off-loading process.
24.0 Storage
24.1. The shelter manufacturer must have facilities available to be able to store shelters, pending site readiness, in small quantities for periods up to six months. Storage of these shelters must be at no cost to the Government for up to 60 days. Storage beyond the 60-day period must be offered as a separately priced option.
24.2. The manufacturers’ shelters can be stored at FAA facilities for extended periods of time, up to three years, under non-powered conditions. During the manufacturing process or prior to shipment, the shelter manufacturer will provide a means to protect entry points, openings, and penetrations to the shelter from weather, insects, and/or other pests in anticipation of these extended periods. Components within the shelter susceptible to damage or deterioration from humidity, condensation and/or other factors must be protected as well. Such damage or deterioration must be covered under the manufacturer warranty.
Shelters must be washed or re-coated as required for a like-new appearance prior to shipment at no cost to the FAA.
25.0 Warranties – Warranties and/or guarantees must be required and must include, but are not limited to, the following terms. Warranty work must be performed by the manufacturer at the FAALC or the final destination at no additional cost to the FAA.
25.1. Shelter manufacturer must provide a warranty for a minimum of five (5) years on the shelter against defects in materials, leaks (including but not limited to door gasket leaks and factory wall penetrations), workmanship, corrosion, and design deficiencies, and must make repairs and replacements at no cost to the FAA. Repairs made must resemble a like-new condition. The shelter manufacturer must have the capability to make all repairs at any FAA designated site.
25.2. This warranty must also cover all components of the shelter for a minimum of one year, unless otherwise specified, including but not limited to: door (5 years), door seals, door mechanisms, hoods, vents, and all electrical and/or mechanical components.
25.3. The HVAC system must be warranted for a minimum of one year on parts and labor and five (5) years on the air conditioner compressor.
25.4. Shelter manufacturer must provide the FAA with certificates of guarantees and warranties normally provided by manufacturers of all equipment and materials not listed above.
25.5. Warranties for the shelter and all products used on or in the shelter, including but not limited to any and all electrical, heat and AC components, will commence at such time the shelter arrives at its final destination/installation. Holding, staging, or storage areas such as FAA Logistics Center, other FAA/DOD staging areas or the manufacturer’s storage are not considered the final destination unless so designated by the Government. For the purpose of the warranty of all products and the shelter on stored units, the warranty must commence two (2) years after the date of initial delivery.
26.0 Quality Assurance
26.1. Workmanship – The shelter manufacturer must perform all fabrication and assembly in a professional workmanlike manner, in accordance with approved industry practices and in conformity with this specification. Exterior shelter finish must be true and plumb with no surface imperfections. Interior shelter component installation (electrical, etc.) must be installed plumb and level. The completed shelters must conform to applicable portions of the International Building Code (IBC), International Mechanical Code (IMC), National Electric Code (NEC) and International Energy Conservation Code (IECC).
26.1.1. The shelter manufacturer must ensure that internal manufacturing drawings and specifications are highly detailed and followed to great extent as to the construction of the shelter and layout of electrical components, including conduits, boxes, and major components within the electrical area.
Problems and issues that require corrective action cause costly delays to the Government, both at the FAALC and potentially at field sites.
26.1.2. The manufacturer must perform tests on the shelter electrical and environmental systems to ensure proper operation. The manufacturer must provide documentation with each shelter on the performance of the HVAC unit. Tests must include, but not limited to; high & low pressures on the refrigerant and voltage readings on all electrical components while operating, torque sheets.
26.1.3. The shelter manufacturer must be responsible for the repair or rework of all major issues or discrepancies discovered after delivery. A plan for repair or rework must be submitted in writing to the CO/COR within three business days after notification of the problem. The rework must be accomplished within ten business days. Repairs must be accepted by the Government to close issue. If the manufacturer cannot perform the rework within the stated period, the Government will correct the problem and invoice the manufacturer on a time-and-materials basis based upon the FAALC current Manufacturer rate. This invoice amount will be applied as a credit on future shelter orders.
26.1.4. In cases where corrective actions from the manufacturer will cause significant delays to the Government, the Government reserves the right to make necessary corrections and apply appropriate charges back to the manufacturer. If related problems persist, the government can take corrective action with the manufacturer in the form of returned shipments and delinquency penalties. (Reference contract section F 3)
26.2. Leakage Testing – The shelter manufacturer must factory test the completed shelter by concentrating a water spray of not less than 250 pounds per square inch (psi) aimed at the roof and each side, including doors, environmental units, and related structure. If leaks are discovered, shelter manufacturer must make repairs and/or change the design accordingly and repeat tests until shelters are completely watertight. The Government reserves the right to witness these tests.
27.0 Hazardous Materials - No asbestos containing materials (ACM) nor lead based paint (LBP) must be used in any fashion during the shelter manufacturing process. Shelter manufacturer must provide written certification of compliance in each shelter documentation packet.
28.0 Priced separately, add/alter options: The shelter manufacturer must have the capability/capacity to deliver the following add/alter options in full compliance with the specifications listed herein and the terms and conditions of the contract. These options will be priced separately from the basic shelter cost and may be revised during the course of the contract to address new requirements. Notes are provided for those options requiring further details and requirements. Those options without notes are considered self-explanatory.
CLIN# Shelter Size and Orientation 001 10’ x 20’ Left designation 002 10' x 20' Right designation 003 10’ x 16’ Left designation 004 10’ x 16’ Right designation 005 10’ x 12’ Left designation 006 10’ x 12’ Right designation 007 8’ x 16’ Left designation 008 8’ x 16’ Right designation 009 8’ x 12’ Left designation 010 8’ x 12’ Right designation 011 6’ x 8’ Left designation 012 6’ x 8’ Right designation 013 12' x 26' Left RWSL shelter 014 12' x 26' Right RWSL shelter 015 Increase width of 12’ long building in 2’ increments 016 Increase width of 16’ long building in 2’ increments 017 Increase width of 20’ long building in 2’ increments 018 Increase length of 8’ wide building in 2’ increments 019 Increase length of 10’ wide building in 2’ increments 020 Increase length of 12’ wide building in 2’ increments 021 Increase ceiling height in 1' increments per sq ft.
022 100A double-throw switch and stainless-steel exterior tap box (recommended) 023 Add 25' of #4 Type W cord with non-insulated ferrules 024 Exchange 100A tap box for Appleton receptacle 025 Add Appleton plug with 25' of #4 Type W cord 026 Exchange 100A tap box for Hubbell 4100RS2WR receptacle 027 Add HBL4100PS2WR PS plug 3P4W, 100 amp, 600v s2 rev gen plug with 25 ft cord 028 Exchange 100A tap box for Pass and Seymour PS 4100 R12-W 029 Exchange 100A tap box for Pass and Seymour PS 4100 MIR-12W 030 Add Pass and Seymour plug with 25' of #4 Type W cord 031 Upgrade to 200 Amp service (includes panel, disconnect and TVSS) 032 200A double-throw switch and stainless-steel exterior tap box (recommended) 033 Add 25' of 2/0 Type W cord with non-insulated ferrules 034 Exchange 200A tap box for Appleton receptacle 035 Add Appleton plug with 25' of 2/0 Type W cord 036 Exchange 200A tap box for Hubbell 4100RS2WR receptacle 037 Add HBL4100PS2WR PS plug 3P4W, 200A, 600v s2 rev gen plug with 25 ft cord 038 Exchange 200A tap box for Pass and Seymour PS 4100 R12-W 039 Exchange 200A tap box for Pass and Seymour PS 4100 MIR-12W 040 Add Pass and Seymour plug with 25' of 2/0 Type W cord 041 Additional 100A disconnect (loose shipped) 042 Additional 200A disconnect (loose shipped) 043 Additional 100A TVSS (installed/wired) 044 Additional 200A TVSS (installed/wired) 045 Additional 100A TVSS (loose shipped)
046 Additional 200A TVSS (loose shipped) 047 Additional 6”x6” wireway per foot 048 Add exterior receptacle protected by GFCI 049 Add 100A entrance plate (loose shipped) 050 Add 200A entrance plate (loose shipped) 051 Add exhaust fan & vent 052 Add second 1-ton HVAC with MC 4002 lead/lag controller 053 HVAC Economizer upgrade 054 1.5-ton Bard HVAC with 3K heat element 055 Add 1.5-ton stainless steel enclosure (SS not available in 1T unit) 056 2-ton Bard HVAC with heat 3K element 057 Add 2-ton stainless steel enclosure 058 Add second 2-ton HVAC with lead/lag controller 059 Increase heat element from 3K to 5K 060 Ductless mini-split system HVAC (loose-shipped unit exterior gutter kit and service lines) 061 Addition of second ductless mini-split system 062 Addition of mini-split compressor bracket (loose ship gutter kit and refrigerant lines) 063 1 ton window A/C with 3K heat element 064 Add 48" baseboard strip heater (ea.)
065 Add 96" baseboard strip heater (ea.)
066 Remove AC unit 067 Hot-dipped galvanized 50"Wx36"Dx6"H landing platform (grate style) 068 Add (1) step/riser and welded handrails to sides of steps and platform for platform heights greater than 7" 069 Add (1) additional steps/risers for platform heights greater than 14".
070 Concrete shelter (custom quoted) 071 Termite resistant shelter per sq. ft.
072 Add additional 3' door 073 Upgrade 3' door to 4' door 074 Add 6' double door 075 Loose-ship 3-compartment exterior J-box (aluminum) 076 Loose-ship 3-compartment exterior J-box (stainless steel) 077 Exterior lightning protection package (air terminals, halo, down conductors) per sq. ft.
078 Install additional ground plate(s) 079 Loose-ship additional ground plate(s) 080 Stamped PE drawings 081 Drafter fee for custom layout shelter/drawing 082 30 days storage beyond initial 60 days 083 Provide and install 12" Aluminum cable tray with 4" sides and 9" rung spacings per ft.
084 Provide and install 12" Gold Chromate Communications style tray per ft.
085 Add forklift pockets10' wide skid 086 Add forklift pockets12' wide skid 087 Aggregate stone-flake exterior in lieu of checkerboard per shelter sq ft.
088 All white exterior in Lieu of Checkerboard per shelter sq ft.
089 OEM field support 090 Expedited manufacture 091 E/G Shelter 092 100 Amp with 30 Breakers 093 Remove exhaust fan 094 1T Bard HVAC 095 Coated Coils
096 Custom Built Shelter 097 Shipping and Crane Offload
Priced separately, add/alter options:
1. Increase or deduct width, length, and height: The manufacturer must develop a standard cost structure to be able to allow for increases (or decreases) in shelter sizes, in two feet length and width increments and height in one-foot increments from standard shelter sizes. Materials, shipping, and escort costs must be considered as well.
2. Additions to the standard power layout the capability to use a generator to power the internal systems when commercial power is off-line. A 100-amp SQ-D DTU223RB (or equal) manual double-throw switch and 304 Stainless Steel Nema 4X Tap Box with finger safe Distribution Lugs for Field Generator will be added to the configuration with only minor changes allowed to the original layout.
3. Adds 200 Amp service. Exchanges 100 Amp electrical service items for 200 Amp service components including Fusible Disconnect (SQ-D H224N) – 200A – 150A NLN type fuse each leg; Main Panel (SQ-D NQ30L2C) – 200A capacity – Main Lug Only; and Rayvoss TVSS unit…