AFRL/RRS SOLICITATION FA8751-11-R-0006 – REPLACE FIRE ALARM SYSTEM

COMPREHENSIVE QUESTIONS AND ANSWERS

POSTED TO FEDBIZOPPS ON 2 August 2011 Question 1 Can you please send us the contact information of the company or distributor that AFRL consulted in reference to the distribution of the array speaker (Wide Area Mass Notification) shown in drawing 10-0005-02 (sheet 2 of 46)?

Answer 1

Jim Leonard at ATI Systems jleonard@atisystem.com
Kyle Berry at Cooper Industries kyle.berry@cooperindustries.com
Bill franks at Monaco billf@monaco.com

Question 2

1. RFP drawings required that the fire alarm and mass notification system are to be provided with two (2) independent wiring systems. It is the intent to provide a separate circuit for visual devices as well as audio devices or visual devices only. Attached, we are providing our interpretation of the contract.

Question: Can you please confirm that our interpretation of the contract is correct?

2. Per RFP 16721 (page 26) sections 3.03.B.1.d and 3.03.B.1.e, requires that junction boxes associated with the fire alarm system is painted “red” and junction boxes associated with the mass notification system is painted “yellow”.

Question: Can all wires serving both systems be located in the same conduit/cable tray? What is the requirement of identifying the junction boxes when the conduit serves the fire alarm/mass notification systems speakers?

Answer 2

1. Two notification appliance circuit power extenders complete with their own separate class A wiring systems are required. The notification appliance circuits serve the visual notification devices.

2. All wiring shall comply with NFPA 72. Junction boxes which serve fire alarm/mass notification shall be identified by a distinctive paint scheme (determined by AFRL) or through the use of permanent labels stating “Fire Alarm/Mass Notification”.

Question 3 Graphical work station is explained in spec, Incidental work station is not, but shown on riser drawing. Is the incidental work station for only viewing alarm, troubles, supervisory, etc. of the fire alarm mass network system, like a fire alarm remote annuciator or is it a actual workstation without control.

Answer 3 Refer to specification section 16722 for information pertaining to the incident management system.

Other files for this federal contract opportunity

Other files attached to Repair Fire Alarm System, newest first.
File Type Posted
FA8751-11-R-0006 RFI 20 Answered.doc DOC document
FA8751-11-R-0006 RFI 21 Answered.doc DOC document
RFP Q A 3 —
Addendum No. 2 dated 4 August 2011 RFP FA8751-11-R-0006 Attach 7.pdf PDF
FA8751-11-R-0006 RFI 11 Answered.doc DOC document
FA8751-11-R-0006-02.pdf PDF
FA8751-11-R-0006 additional information 3 Aug 2011.doc.docx DOCX document
Addendum 1 dated 26 July 2011 RFP FA8751-11-R-0006.pdf PDF
FA8751-11-R-0006 attach 3R.docx DOCX document
FA8751-11-R-0006-01.pdf PDF
11r6 rfp attch 5R site visit form.doc DOC document
FA8751-11-R-0006 additional information 26 July 2011.docx DOCX document
RFP Q A 1 —
FA8751-11-R-0006 RFI 1 Answered.doc DOC document
FA8751-11-R-0006 RFI Request Form.doc DOC document
FA8751-11-R-0006 additional information 19 July 2011.doc.docx DOCX document
11R6 attach 4.docx DOCX document
Drawings —
11r6 rfp attch 5 site visit form.doc DOC document
11R0006 Specs.zip ZIP file
FA8751-11-R-0006 attach 3.docx DOCX document
Drawings —
FA8751-11-R-0006.pdf PDF
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .