This document is a Request for Quote (RFQ) / Solicitation for a Public Address System at the National Museum of the United States Air Force (NMUSAF). The government is seeking a commercial commodity to provide materials and install a public address system with corresponding server to cover the NMUSAF campus, including multiple buildings, exterior spaces, parking lots, and common areas.
The solicitation is a 100% Small Business Set-Aside under NAICS code 334310. The Period of Performance is 120 days after contract award. A site visit is scheduled for October 17, 2024, and quotes are due by October 24, 2024. The government will award a Firm Fixed Price contract to the responsible offeror submitting the lowest priced, technically acceptable quote, provided the price is fair and reasonable. Pricing must be provided for the base period and all option years. The contracting activity is the Air Force Life Cycle Management Center (AFLCMC) at Wright-Patterson Air Force Base.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE AIR FORCE
AIR FORCE LIFE CYCLE MANAGEMENT CENTER (AFMC)
WRIGHT-PATTERSON AIR FORCE BASE OHIO
19 November 2024
Public Address System Question & Answer
AGENCY AND CONTRACTING ACTIVITY: Operational Contracting Branch, Installation Contracting Division, Directorate of Contracting, Air Force Life Cycle Management Center, Air Force Material Command, Department of the Air Force.
AFLCMC/PZIBB
1940 Allbrook Dr.
Bldg. 1, Room 109 Wright-Patterson AFB, OH 45433-5344
Question: What are the existing 160 speakers in the hanger? If they are 70V, what are they tapped at?
(this is needed to calculate the amplifier sizes) Answer: Electro-Voice ELX200-12 with 70V 100W High Power Speaker Line Matching Transformer in Hangar Bay 1 and 2. Electro-Voice EVID 4.2 in Hanger bay 4 with 70v taps but not sure which wattage (7.5W,15W, 30W)
Question: How many zones all together? Will the Hanger Bays be split at all?
Answer: Hangar Bay 1 should split between the Early years and WWII Galleries. Hangar Bay 2 can all be on one zone. Hangar Bay 3 can all be one zone. Hangar bay 4 should split to allow for the event area in Space Gallery not to have PA sound bleed over when needed.
Question: Is background music required? if so, same music for all zones or selected by zone?
Answer: Yes background music should be selectable from different inputs. Each zone should be selectable to play whichever input is needed. Background music should be superseded by paging console and automated announcements when necessary.
Question: What sources are required for Paging? Microphone? How many? Where do they go?
Answer: Yes Please reference the SOW Section B-1-ii and Section B-1-iii. This will be located at the atrium information desk and will be the only paging unit.
Question: Is phone paging required?
Answer: No as I don’t think that is allowed with the Base VoIP telephone system.
Question: Could you provide the manufacturer, make and model of the existing Security Camera System because the statement of work specifies interface to it?
Answer: AXIS Camera Station S1296
DEPARTMENT OF THE AIR FORCE
AIR FORCE LIFE CYCLE MANAGEMENT CENTER (AFMC)
WRIGHT-PATTERSON AIR FORCE BASE OHIO
File details come from the government source that posted it. Updated .