Question
Can we have a single line diagram provided for this project? The padmount switch manufacturer is requesting one from us.
Answer
Single line diagram attached.
Question Will one (1) or two (2) 15kV, 4-way, air break, sectionalizing padmount switches need to be provided for this project?
Answer
Per Coded Note 5 on Sheet E-1 of contract drawings, "Provide (2) 15kV, 4-way, air break sectionalizing switches." Two switches are required.