Att10b_230053_Combined_Environmental_Report.pdf
PDF 4 MB Posted
- Solicitation number
- FA813725R0037
About this file
This document is an Asbestos Inspection Report for Building 3202 at Tinker Air Force Base, revealing significant asbestos contamination in the roofing materials. The inspection, conducted on February 20, 2024, by Civil Engineering Environmental (CEIE), identified asbestos-containing material (ACM) in the black/gray roofing across five sampled locations. Laboratory analysis by QuantTEM Laboratories confirmed 15% chrysotile asbestos presence in each sample, with the roof described as antiquated, damaged, and even featuring a small tree growing on the southwest corner.
The report recommends Class II asbestos work for the non-friable Category II material when the roof is replaced or repaired. The building, constructed in 1942, shows significant roof damage, with samples taken from north, south, west, east, and center locations all testing positive for asbestos. The findings align with the broader federal contract opportunity (Solicitation Number FA813725R0037) for replacing the valve and fuel tank at Building 3202, which involves major upgrades to civil, architectural, structural, mechanical, and electrical systems, with a projected construction cost between $1,000,000 and $5,000,000.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| WWYK230053 B3202 Replace Vault and Fuel Tank RFI log COR Signed.pdf | ||
| Wage Determination OK.pdf | ||
| Solicitation - FA813725R0037.pdf | ||
| 2023 TAFB Fire Protection Standard.pdf | ||
| 2024 TAFB Electrical Standards.pdf | ||
| 03202A1.pdf | ||
| 03202A2.pdf | ||
| 03202A7.pdf | ||
| 20080290.pdf | ||
| 03202A6.pdf | ||
| 03202A8.pdf | ||
| 03202A3.pdf | ||
| 03202A4.pdf | ||
| 230053_Submittal_Register.pdf | ||
| 230053 - Drawings - 30MAY2025.pdf | ||
| 230053_STATEMENT OF WORK.pdf | ||
| 230053_Design Narrative.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
72 ABW/CEIE
ASBESTOS INSPECTION REPORT PAGE 1 OF 5
Project Information
Project Name Engineering Evaluation Project ID 14043285
Project Building 3202 Year Constructed 1942
Room/Post Location Roof Historical Samplings No
Requestor Joe Uhl Inspector(s) Michael Green; Laura Duck
Inspection Date 20 Feb 2024 Prepared By
Sampling Information:
Sample ID - Location Material Classification Condition Hazard Friable Analysis Results
RMB320201
North
Black/Gray Roof Material Misc Significant Damage
ACM NF PLM Asbestos Present
Chrysotile 15%
RMB320202
South
Black/Gray Roof Material Misc Significant Damage
ACM NF PLM Asbestos Present
Chrysotile 15%
RMB320203
West
Black/Gray Roof Material Misc Significant Damage
ACM NF PLM Asbestos Present
Chrysotile 15%
RMB320204
East
Black/Gray Roof Material Misc Significant Damage
ACM NF PLM Asbestos Present
Chrysotile 15%
RMB320205
Center
Black/Gray Roof Material Misc Significant Damage
ACM NF PLM Asbestos Present
Chrysotile 15%
Photos:
Page | 2
Condition:
Surfacing/Misc. Materials:
• Good Condition: Material with no visible damage or deterioration or showing only very limited damage or deterioration.
• Some Damage: Material crumbling, blistered, water-stained, gouged, marred, or abraded covering less than one tenth of the surface if the damage is evenly distributed (one quarter if the damage is localized).
• Significant Damage: Material crumbling, blistered, hanging from surface, deteriorated, adhesive failure, water-stained, gouged, marred, or abraded covering more than one tenth if the damage is evenly distributed (one quarter if the damage is localized).
Hazard:
• ACM = Asbestos Containing Material; defined by the EPA as any material containing more than 1 percent asbestos.
Friable:
• Friable = Material, when dry, may be crumbled, pulverized, or reduced to powder by hand pressure, and includes previously nonfriable material that becomes damaged to the extent that it is now friable.
• NF = Nonfriable; Material, when dry may not be crumbled, pulverized, or reduced to powder by hand pressure.
Analysis/Results:
• PLM = Polarized Light Microscopy; Asbestos Present or Asbestos Not Present
• PACM = Presumed Asbestos Containing Material; TSI and SM found in buildings constructed no later than 1980.
Inspection Observations:
• Civil Engineering Environmental (CEIE) conducted an inspection of the roofing materials located on bldg. 3202. The roof appears to be antiquated and damaged. The roof also has a small tree growing on the southwest corner.
Findings:
• Black and Gray roofing/flashing contains asbestos.
Recommendations:
• Class II asbestos work for Cat II NF material when roof is replaced/repaired.
PLM and CoC Page 3-5
Page | 3
Page | 4
Page | 5
| Scanned from a Xerox Multifunction Printer.pdf |
| Inspection Report - B3202 Roof - EVAL 14043285.pdf |
| Asbestos inspection report Page 1 of 5 |
| Project Information |
| Sampling Information: |
| Photos: |
| Condition: |
| Hazard: |
| Friable: |
| Analysis/Results: |
| Inspection Observations: |
| Findings: |
| Recommendations: |
| PLM and CoC Page 3-5 |
| Project ID |
| Project Name |
| Year Constructed |
| Project Building |
| Historical Samplings |
| Room/Post Location |
| Inspector(s) |
| Requestor |
| Prepared By |
| Inspection Date |
| Results |
| Analysis |
| Friable |
| Condition |
| Classification |
| Material |
| Sample ID - Location |