Open Loops Open Loops - Makeup Water (Check Only)

Parameter Range Parameter

Conductivity (micromhos/cm) 825-875 Conductivity (micromhos/crn) pH (pH scale) 8-9 Hardness (ppm)

Hardness (ppm) 400-480 P Alkalinity (ppm)

P Alkalinity (ppm) 20-40 M Alkalinity (ppm)

M Alkalinity (ppm) 300-400 Chlorides (ppm)

Chlorides (ppm) 40-80

Inhibitor (ppm) 10-15

Cycles 2-5

BioCount (colonies/ml) Olp Slide <1000

RSI (Ryznar Stability Index) 5-6

Closed Loops - Molybdate Based Closed Loops - Glycol Based

Parameter Range Parameter Range

Conductivity (micromhos/cm) 1200-1500 Conductivity (micromhos/cm) 1500-2500 pH (pH scale) 9.0-10.5 pH(pH�le) 9.0-10.5

Molybdate (ppm) 10-30 Orthophosphate Inhibitor (ppm) <1000

Fe(ppm) 0

Cu(ppm) 0

% Glycol by Volume 30%

Freeze Point (dearees F) 5-10