Appendix_D.pdf
PDF 191 KB Posted
- Attached to
- Composite Sanding Booth Monitoring Equipment
- Solicitation number
- FA8125-18-Q-0021
About this file
Appendix D
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sanding_Booth_Monitoring_Combo.pdf | ||
| Item_Description.docx | DOCX document | |
| SOW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX D
Sanding Booth Parameters
Equipment Parameter Gauge Installed
Range Alarm Type
Failure Mode
Comment
Booth Booth Pressure Y < 0 Email High Per OSHA/BEF Regulation
Booth Air Flow - Incoming
Y <=100 FPM Email Low Monitoring --> filter effectiveness
Booth Air Flow - Exhaust Y <=100 FPM Email Low Monitoring --> filter effectiveness
Booth First Stage Filter
DP
Y <=100 FPM Email Low Proactively plan for filter changes
Booth Second Stage Filter DP
Y <=100 FPM Email Low Proactively plan for filter changes
Booth Third Stage Filter
DP
Y <=100 FPM Email Low Proactively plan for filter changes
Booth Air Shower filter
DP
Y <=25 FPM Email Low Proactively plan for filter changes
Booth Compressed Air Y <50 FPM Email Low Monitoring Process Air
Booth Fan Exhaust Fan SB-1
RPM
Y 1800<Run<2200 Email Out of Range
Monitor for potential fan issues
Booth Fan Exhaust Fan SB-1 Temp.
Y >185' F Email High Monitor for potential fan issues
Booth Fan Exhaust Fan SB-1 Vibe.
Y 58<Hz<62 Email Out of Range
Monitor for potential fan issues
Booth Fan Exhaust Fan SB-2
RPM
Y 1800<Run<2200 Email Out of Range
Monitor for potential fan issues
Booth Fan Exhaust Fan SB-2 Temp.
Y >185' F Email High Monitor for potential fan issues
Booth Fan Exhaust Fan SB-2 Vibe.
Y 58<Hz<62 Email Out of Range
Monitor for potential fan issues
Booth Electricity Consumption
Y N/A N/A N/A Monitor --> Cost
File details come from the government source that posted it.