APPENDIX D

Sanding Booth Parameters

Equipment Parameter Gauge Installed

Range Alarm Type

Failure Mode

Comment

Booth Booth Pressure Y < 0 Email High Per OSHA/BEF Regulation

Booth Air Flow - Incoming

Y <=100 FPM Email Low Monitoring --> filter effectiveness

Booth Air Flow - Exhaust Y <=100 FPM Email Low Monitoring --> filter effectiveness

Booth First Stage Filter

DP

Y <=100 FPM Email Low Proactively plan for filter changes

Booth Second Stage Filter DP

Y <=100 FPM Email Low Proactively plan for filter changes

Booth Third Stage Filter

DP

Y <=100 FPM Email Low Proactively plan for filter changes

Booth Air Shower filter

DP

Y <=25 FPM Email Low Proactively plan for filter changes

Booth Compressed Air Y <50 FPM Email Low Monitoring Process Air

Booth Fan Exhaust Fan SB-1

RPM

Y 1800<Run<2200 Email Out of Range

Monitor for potential fan issues

Booth Fan Exhaust Fan SB-1 Temp.

Y >185' F Email High Monitor for potential fan issues

Booth Fan Exhaust Fan SB-1 Vibe.

Y 58<Hz<62 Email Out of Range

Monitor for potential fan issues

Booth Fan Exhaust Fan SB-2

RPM

Y 1800<Run<2200 Email Out of Range

Monitor for potential fan issues

Booth Fan Exhaust Fan SB-2 Temp.

Y >185' F Email High Monitor for potential fan issues

Booth Fan Exhaust Fan SB-2 Vibe.

Y 58<Hz<62 Email Out of Range

Monitor for potential fan issues

Booth Electricity Consumption

Y N/A N/A N/A Monitor --> Cost