QUESTIONS_AND_ANSWERS_2.pdf

PDF 76 KB Posted

Attached to
Repair OSI Office B709 Federal contract opportunity
Solicitation number
FA663318B0001
Issued by
Department of the Air Force Reserve Command

About this file

These questions were submitted before the deadline and were not posted 26 June 2018

View the file

Other files for this federal contract opportunity

Other files attached to Repair OSI Office B709, newest first.
File Type Posted
Tab_G-4_-_Primary_Elec_Distribution_Sys_-_One_Line_Diagram_-_20180419.pdf PDF
B709_OneLineDiagram.png PNG image
B813_Panels.png PNG image
B709_FinishSchedule.pdf PDF
24x36_934th_AW_Bldg_709_Elect_Addendum_1_06-20-18.pdf PDF
B709_CarpetFinish.png PNG image
11x17_934th_AW_Bldg_709_Elect_Addendum_1_06-20-18.pdf PDF
B709_questions_answers.pdf PDF
Motorola_Antenna.pdf PDF
MFR_Amendments_amend.pdf PDF
20180622_Solicitation_OSI.pdf PDF
20171221_Drawings.pdf PDF
_Vol_2_-_Bldg_709_-_Corrected_15_June_2018.pdf PDF
FA663318B0001_Sol.pdf PDF
_Vol_1_-_Bldg_709_-_Corrected_15_June_2018.pdf PDF
20180202_WD.pdf PDF
Financial_Responsibility_Sheet.doc DOC document
sign_in_site_visit.pdf PDF
20171221_Drawings.pdf PDF
20171221_Specs.pdf PDF
Financial_Responsibility_Sheet.doc DOC document
SF_24_Bid_Bond_Form.pdf PDF
20180202_WD.pdf PDF
FA663318B0001.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q&A 2

According to Drawing Note #2 on Systems Plan E1.4, the "Contractor is to terminate cables to existing patch panel termination location to be provided by Owner during construction" (within Comm Room 129). Is it safe to assume that there is enough space in the patch panels to accommodate the added cabling?

"No."

Will the Owner be providing any additional patch panels if needed?

"No."

If so, will they be loaded or unloaded?

"Unloaded."

Will the data outlets require 4 cables in the TV locations as is with all the other data outlets shown?

"No"

C2/E4.1 shows gray cable for voice and green cable for data, however Specification 271000 Section 2.3.1.1 states the cable shall be blue. Please clarify.

"There is no longer a requirement for the separation of voice and data cables. All cable will be CAT6 or greater."

Specification 271000 Section 2.4.1 states "Each outlet/connector shall be wired T568B", yet on C2/E4.1 it asks for T568A configuration for the NIPRNET cables. Please clarify.

"Only T568B is to be used."