QUESTIONS_AND_ANSWERS_2.pdf
PDF 76 KB Posted
- Attached to
- Repair OSI Office B709 Federal contract opportunity
- Solicitation number
- FA663318B0001
About this file
These questions were submitted before the deadline and were not posted 26 June 2018
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Tab_G-4_-_Primary_Elec_Distribution_Sys_-_One_Line_Diagram_-_20180419.pdf | ||
| B709_OneLineDiagram.png | PNG image | |
| B813_Panels.png | PNG image | |
| B709_FinishSchedule.pdf | ||
| 24x36_934th_AW_Bldg_709_Elect_Addendum_1_06-20-18.pdf | ||
| B709_CarpetFinish.png | PNG image | |
| 11x17_934th_AW_Bldg_709_Elect_Addendum_1_06-20-18.pdf | ||
| B709_questions_answers.pdf | ||
| Motorola_Antenna.pdf | ||
| MFR_Amendments_amend.pdf | ||
| 20180622_Solicitation_OSI.pdf | ||
| 20171221_Drawings.pdf | ||
| _Vol_2_-_Bldg_709_-_Corrected_15_June_2018.pdf | ||
| FA663318B0001_Sol.pdf | ||
| _Vol_1_-_Bldg_709_-_Corrected_15_June_2018.pdf | ||
| 20180202_WD.pdf | ||
| Financial_Responsibility_Sheet.doc | DOC document | |
| sign_in_site_visit.pdf | ||
| 20171221_Drawings.pdf | ||
| 20171221_Specs.pdf | ||
| Financial_Responsibility_Sheet.doc | DOC document | |
| SF_24_Bid_Bond_Form.pdf | ||
| 20180202_WD.pdf | ||
| FA663318B0001.pdf |
Show all 24
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Q&A 2
According to Drawing Note #2 on Systems Plan E1.4, the "Contractor is to terminate cables to existing patch panel termination location to be provided by Owner during construction" (within Comm Room 129). Is it safe to assume that there is enough space in the patch panels to accommodate the added cabling?
"No."
Will the Owner be providing any additional patch panels if needed?
"No."
If so, will they be loaded or unloaded?
"Unloaded."
Will the data outlets require 4 cables in the TV locations as is with all the other data outlets shown?
"No"
C2/E4.1 shows gray cable for voice and green cable for data, however Specification 271000 Section 2.3.1.1 states the cable shall be blue. Please clarify.
"There is no longer a requirement for the separation of voice and data cables. All cable will be CAT6 or greater."
Specification 271000 Section 2.4.1 states "Each outlet/connector shall be wired T568B", yet on C2/E4.1 it asks for T568A configuration for the NIPRNET cables. Please clarify.
"Only T568B is to be used."