Questions-Responses_2.pdf
PDF 89 KB Posted
- Attached to
- Repair Office Areas, Bldg 801 Federal contract opportunity
- Solicitation number
- FA6633-15-B-0008
About this file
Questions-Responses Set 2 23 Jul 15
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA6633-15-B-0008_0002_Repair_Office_Areas _Bldg_801.pdf | ||
| Questions-Responses_1.pdf | ||
| 20150721_Site_Visit_Attendees.pdf | ||
| FA6633-15-B-0008_0001_Repair_Office_Areas _Bldg_801.pdf | ||
| 20150717_Wage_Determination_MN36.pdf | ||
| FA6633-15-B-0008_Repair_Office_Areas _Bldg_801.pdf | ||
| SF_24_Bid_Bond_Form.pdf | ||
| Drawings.pdf | ||
| Financial_Responsibility_Sheet.pdf | ||
| 20150612_Wage_Determination_MN_36.pdf | ||
| Specifications.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Site Visit Questions & Responses – SET #2
FA6633-15-B-0008/QJKL 14-0018
Repair Office Areas, Bldg 801, Minneapolis ARS, MN
SET #2 – 23 July 2015
1. QUESTION: Has there been any hazardous materials testing done in this area, specifically the paint and floor tiles?
RESPONSE: We have not done any testing, however we did not run into any hazardous materials when doing the other portion of this space.
2. QUESTION: The mechanical drawings show a return air plenum ceiling, there is an existing wood ceiling, is the ceiling getting fire rated or does the return need to be ducted?
RESPONSE: Because the area between the new ceiling and roof deck is going to remain sprinklered, a fire rated coating is not required by code.
23 July 2015 Page 1
File details come from the government source that posted it. Updated .