QA for 1305.pdf
PDF 570 KB Posted
- Solicitation number
- FA568223R0009
About this file
This document includes a federal contract solicitation and related technical specifications for renovating a medium voltage substation facility at Aviano Air Base in Italy. The solicitation seeks offers for renovating the 1305th Area F medium voltage substation, including replacing equipment, upgrading systems, and completing all necessary electrical work. Offerors must hold a current Statement of Capabilities certification in category OG10. The estimated contract value is between $500,000 and $1,000,000. The performance is required on a lump sum basis. An organized site visit will be held at the specified location and date. The work must be performed in Italy and in compliance with Italian labor law DLgs. 81/2008. Offers are due by the date and time established in the amended solicitation and must be submitted to the designated office. Interested firms should monitor the solicitation for any changes using the watch list feature.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0003 SF 30 Released.pdf | ||
| Amendment 0002 SF 30 Released.pdf | ||
| SUB.1305 Samples analysis.pdf | ||
| ASHE 21-1047 Add1.pdf | ||
| ASHE 21-1047 CCEB REV1.xlsx | XLSX spreadsheet | |
| Amendment 0001 SF 30 released.pdf | ||
| Solicitation - FA568223R0009.pdf | ||
| ASHE 21-1047_Dwgs_100.pdf | ||
| AVIANO MASTERSPECS 2020.pdf | ||
| ASHE 21-1047_Tech Specs.pdf | ||
| CCEB 21-1047.xls | XLS spreadsheet | |
| ASHE 21-1047_PSC.pdf |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
30 June 2023
Questions and answers
PPI 1
Part IV - Item nr. 8) are quick couplings required to connect the test load?
Answer
Yes. On page 2 an example of one of the quick connect receptacles used by Power Pro.
PPI 2.
Part IV - Item nr. 22) do you confirm that stranded bare underground copper cord, must be with sect. 1x240 mm2 ?
Asnwer
Yes. See sheet E-7 for schematic of the grounding system.
ASCO's SERIES 300 Dual Purpose Quick Connect Power Panels provide a reliable, convenient, and economical way to connect a either a standby generator or Load Bank for testing. These units are available in models ranging from 150 to 4000 Amps, they are designed to provide years of trouble-free service. The panels are ETL listed to UL 891 Standards. Together with an ASCO transfer switch, Dual Purpose Panels provide a connection for temporary power during maintenance or repair of a permanent source.
Dual Purpose Quick Connect Panels are an economical solution for reliably supplying temporary power during a utility outage or maintenance work.
150A-800A Wall Mount Dual Purpose QCP with Disconnect
Breaker between Sources
800A-2000A Pad Mount Dual Purpose QCP
(No Breaker)
2400A-4000A Pad Mount Dual Purpose QCP
(No Breaker)
Features
• Dual Purpose Panels are Listed to UL 891 Standards by ETL
• Provides a convenient, economical and reliable means of connecting an alternate power source and a load bank to a power distribution system
• Utilizes standard Series 16 Single Pole quick connect receptacles
• Rated up to 600V
• Capacities from 150A to 4000A
• Lockable doors to prevent unauthorized entry
• Flip covers for output Provide both supplementary backup power and load testing connectivity through a single device.
Standard Accessories
• Phase rotation monitor with fuses
• Auto Start Destination Switch allows the User to choose which generator can be started by the ATS
• 2-Wire Banana Terminal Post for easy connection of Engine Start circuit from Portable Generator
• Load Dump Receptacle - L1-15 Twist Lock Receptacle provided for easy load dump Circuit Connection
• Standard Aluminium Type 3R enclosure is weatherproof with or without cables connected
• Available in a stainless steel enclosure option for corrosive environments
• Castell D-Lok mounted on lower housing door preventing access to Portable generator camlocks when permanent Generator is in use
• Disconnect Breaker with K-Bolt interlock provided on 150A-800A Wall mounted units
• 800A-4000A models ship with a second K-Bolt to mount on the job site's permanent generator
Provide both supplementary backup power and load testing connectivity through a single device.
The SERIES 300 Dual-Purpose Quick Connect Power Panel is the singular solution for connecting load banks for testing and providing "backup-for-the-backup" according to NEC 700.3 requirements.
SERIES 300 Dual Purpose Quick Connect Power Panel
Data Sheet
Rating Standard Connection Type Mounting Dimensions Shipping
Weight (lbs) Internal
Connection
150-800A Cam Lock (1-2 rows) Wall Mount 31"w x 49"h x 26"d 120-160 Single 100 - 350 MCM (150-250A or 250 - 350 MCM Lugs (400-800A)
800A-2000A Cam Lock (2-5 rows) Pad Mount 31"w x 57"h x 50"d 294-361 Double 500 - 800 MCM Lugs
2400A-4000A Cam Lock (6-10 rows) Pad Mount 48"w x 57"h x 50"d 534-632 Double 500 - 800 MCM Lugs www.ascopower.com customercare@ascopower.com 1-800-800-ASCO (2726)
© February 2021. Publication 2071
ASCO Power Technologies 160 Park Avenue, Florham Park, NJ 07932
Notes:
1 25% Ground is standard on all Dual Purpose Quick Connect Panels.
2100% Neutral provided for portable generator connections, No Neutral camlocks are provided for Load Bank.
3 B0 is used to denote Quick connect panel with a breaker. This option only available for 150A-800A units.
Catalog Information
3QC D C N A 3 0400 F B0 F
SERIES Input/ Output
Connector Type Ground1 Neutral2 Poles/
Phase Amps Volts/Color Code Accessories3 Enclosure
3QC D =
Dual
Purpose
C = Cam Lock N = minimum of 25% grounding ampacity
A = 100% Rated Neutral
3 0150
F ≤ 240V Black, Red, Blue
N ≤ 480V Brown, Orange, Yellow
R ≤ 600V Black, Black, Black
B0= None 150A-800A Wall Mount
00= None
800A-4000A Pad Mount
F = Type 3R
S = 316 Stainless Steel Type 3R
Sample connection diagram for 150A-800A Wall Mount Dual Purpose QCP with Disconnect Breaker between Sources
Sample connection diagram for 800A-4000A Pad Mount Dual Purpose QCP (No Breaker)
Permanent Generator
Permanent Gen Breaker
TO LOAD
UTILITY
Temporary Generator
E L N
TO LOAD
Male CamlocksFemale Camlocks
K
K
Permanent Generator
Permanent Gen Breaker
TO LOAD
UTILITY
Temporary Generator
E L N
TO LOAD
Male CamlocksFemale Camlocks
K
K
ASCO SERIES 300 Dual Purpose Quick Connect Power Panel
File details come from the government source that posted it. Updated .