Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part4.pdf
PDF 1 MB Posted
- Attached to
- Multiple Award Construction Contract (MACC) Italy Federal contract opportunity
- Solicitation number
- FA568219RA001
About this file
This is a pre-solicitation notice for an indefinite delivery indefinite quantity multiple award construction contract for design-build construction services in Italy. The scope of work includes projects involving grading, water and sewer lines, painting, roofing, building renovation, new construction, electrical substation construction, structural work, HVAC, refrigeration, fire suppression, fuel pipelines and storage, power and utilities, generators, public address systems, fire alarms, telephones, and asbestos, lead, and petroleum abatement and disposal. The contract will have a one-year base period and four option years, with a minimum $2,500 guaranteed amount for each awardee and a total maximum value of $96 million. The minimum task order is $2,500 and maximum is $7 million. Comments on the draft attachments are due by April 19, 2019. The solicitation will be issued through FBO, with performance primarily at Aviano Air Base in Italy.
Attachment 10 ASHE 18-1025 Technical Specifications (Seed Project ) Part 4
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENOVATE/EXPAND FAC. 939 ASHE18-1025
FINAL (100% design) ADDITIONAL SECTION 230900 Page 229
Provide a Points Schedule in tabular form for each HVAC system, with the indicated columns and with each row representing a hardware point, network point or configuration point in the system.
a. When a Points Schedule was included in the Contract Drawing package, use the same fields as the Contract Drawing with updated information in addition to the indicated fields.
b. When Point Schedules are included in the contract package, items requiring contractor verification or input have been shown in angle brackets ("<" and ">"), such as < > for a required entry or <value> for a value requiring confirmation. Complete all items in brackets as well as any blank cells. Do not modify values which are not in brackets without approval.
Points Schedule Columns must include:
3.2.10.1 Point Name
The abbreviated name for the point using the indicated naming convention.
3.2.10.2 Description
A brief functional description of the point such as "Supply Air Temperature".
3.2.10.3 DDC Hardware Identifier
The Unique DDC Hardware Identifier shown on the DDC Hardware Schedule and used across all drawings for the DDC Hardware containing the point.
3.2.10.4 Settings
The value and units of any setpoints, configured setpoints, configuration parameters, and settings related to each point.
3.2.10.5 Range
The range of values, including units, associated with the point, including but not limited to a zone temperature setpoint adjustment range, a sensor measurement range, occupancy values for an occupancy input, or the status of a safety.
3.2.10.6 Input or Output (I/O) Type
The type of input or output signal associated with the point. Use the following abbreviations for entires in this column:
a. AI: The value comes from a hardware (physical) Analog Input
b. AO: The value is output as a hardware (physical) Analog Output c. BI: The value comes from a hardware (physical) Binary Input
d. BO: The value is output as a hardware (physical) Binary Output
e. PULSE: The value comes from a hardware (physical) Pulse Accumulator
Input
f. NET-IN: The value is provided from the network (generally from another device). Use this entry only when the value is received from another device as part of scheduling or as part of a sequence of operation, not when the
FINAL (100% design) ADDITIONAL SECTION 230900 Page 230 value is received on the network for supervisory functions such as trending, alarming, override or display at a user interface.
g. NET-OUT: The value is provided to another controller over the network. Use this entry only when the value is transmitted to another device as part of scheduling or as part of a sequence of operation, not when the value is transmitted on the network for supervisory functions such as trending, alarming, override or display at a user interface.
3.2.10.7 Object and Property Information
The Object Type and Instance Number for the Object associated with the point. If the value of the point is not in the Present_Value Property, then also provide the Property ID for the Property containing the value of the point.
Any point that is displayed at the front end or on an LDP, is trended, is used by another device on the network, or has an alarm condition must be documented here.
3.2.10.8 Network Data Exchange Information (Gets Data From, Sends Data
To)
Provide the DDC Hardware Identifier of other DDC Hardware the point is shared with.
3.2.10.9 Override Information (Object Type and Instance Number)
For each point requiring an Override, indicate if the Object for the point is Commandable or, if the use of a separate Object was specifically approved by the Contracting Officer, provide the Object Type and Instance Number of the Object to be used in overriding the point.
3.2.10.10 Trend Object Information
For each point requiring a trend, indicate if the trend is Local or Remote, the trend Object type and the trend Object instance number. For remote trends provide the DDC Hardware Identifier for the device containing the trend Object in the Points Schedule notes.
3.2.10.11 Alarm Information
Indicate the Alarm Generation Type, Event Enrollment Object Instance Number, and Notification Class Object Instance Number for each point requiring an alarm. (Note that not all alarms will have Event Enrollment Objects.
3.2.10.12 Configuration Information
Indicate the means of configuration associated with each point.
a. For Operator Configurable Points indicate BACnet Object and Property information (Name, Type, Identifiers) containing the configurable value. Indicate whether the property is writable always, or only when Out_Of_Service is TRUE.
b. For Configurable Points indicate the BACnet Object and Property information as for Operator Configurable points, or identification of the configurable settings from within the engineering software for the device or identification of the hardware settings on the device.
3.2.11 Riser Diagram
The Riser Diagram of the Building Control Network may be in tabular form, and must show all DDC Hardware and all Network Hardware, including network terminators. For each item, provide the unique identifier, FINAL (100% design) ADDITIONAL SECTION 230900 Page 231 common descriptive name, physical sequential order (previous and next device on the network), room identifier and location within room. A single riser diagram must be submitted for the entire system.
3.2.12 Control System Schematics
Provide control system schematics in the same form as the control system schematic Contract Drawing with Contractor updated information. Provide a control system schematic for each HVAC system.
3.2.13 Sequences of Operation
Provide HVAC control system sequence of operation and in the same format as the Contract Drawings. Within these drawings, refer to devices by their unique identifiers. Submit sequences of operation for each HVAC system.
3.2.14 Controller, Motor Starter and Relay Wiring Diagram
Provide controller wiring diagrams as functional wiring diagrams which show the interconnection of conductors and cables to each controller and to the identified terminals of input and output devices, starters and package equipment. Show necessary jumpers and ground connections and the labels of all conductors. Identify sources of power required for control systems and for packaged equipment control systems back to the panel board circuit breaker number, controller enclosures, magnetic starter, or packaged equipment control circuit. Show each power supply and transformer not integral to a controller, starter, or packaged equipment. Show the connected volt-ampere load and the power supply volt-ampere rating. Provide wiring diagrams for each HVAC system.
3.3 CONTROLLER TUNING
Tune each controller in a manner consistent with that described in the ASHRAE FUN SI and in the manufacturer's instruction manual. Tuning must consist of adjustment of the proportional, integral, and where applicable, the derivative (PID) settings to provide stable closed-loop control. Each loop must be tuned while the system or plant is operating at a high gain (worst case) condition, where high gain can generally be defined as a low-flow or low-load condition. Upon final adjustment of the PID settings, in response to a change in controller setpoint, the controlled variable must settle out at the new setpoint with no more than two (2) oscillations above and below setpoint. Upon settling out at the new setpoint the controller output must be steady. With the exception of naturally slow processes such as zone temperature control, the controller must settle out at the new setpoint within five (5) minutes. Set the controller to its correct setpoint and record and submit the final PID configuration settings with the O&M Instructions and on the associated Points Schedule.
3.4 START-UP
3.4.1 Start-Up Test
Perform the following startup tests for each control system to ensure that the described control system components are installed and functioning per this specification.
Adjust, calibrate, measure, program, configure, set the time schedules, and otherwise perform all necessary actions to ensure that the systems function as indicated and shown in the sequence of operation and other contract documents.
3.4.1.1 Systems Check
An item-by-item check must be performed for each HVAC system
FINAL (100% design) ADDITIONAL SECTION 230900 Page 232
3.4.1.1.1 Step 1 - System Inspection
With the system in unoccupied mode and with fan hand-off-auto switches in the OFF position, verify that power and main air are available where required and that all output devices are in their failsafe and normal positions.
Inspect each local display panel to verify that all displays indicate shutdown conditions.
3.4.1.1.2 Step 2 - Calibration Accuracy Check
Perform a two-point accuracy check of the calibration of each HVAC control system sensing element and transmitter by comparing the value from the test instrument to the network value provided by the DDC Hardware. Use digital indicating test instruments, such as digital thermometers, motor-driven psychrometers, and tachometers. Use test instruments with accuracy at least twice as accurate as the specified sensor accuracy and with calibration traceable to National Institute of Standards and Technology standards. Check one the first check point in the bottom one-third of the sensor range, and the second in the top one-third of the sensor range.
Verify that the sensing element-to-DDC readout accuracies at two points are within the specified product accuracy tolerances, and if not recalibrate or replace the device and repeat the calibration check.
3.4.1.1.3 Step 3 - Actuator Range Check
With the system running, apply a signal to each actuator through the DDC Hardware controller. Verify proper operation of the actuators and positioners for all actuated devices and record the signal levels for the extreme positions of each device. Vary the signal over its full range, and verify that the actuators travel from zero stroke to full stroke within the signal range. Where applicable, verify that all sequenced actuators move from zero stroke to full stroke in the proper direction, and move the connected device in the proper direction from one extreme position to the other. For valve actuators and damper actuators, perform the actuator range check under normal system pressures.
3.4.1.2 Weather Dependent Test
Perform weather dependent test procedures in the appropriate climatic season.
3.4.2 Start-Up Testing Report
Submit 4 copies of the Start-Up Testing Report. The report may be submitted as a Technical Data Package documenting the results of the tests performed and certifying that the system is installed and functioning per this specification, and is ready for the Performance Verification Test (PVT).
3.5 PERFORMANCE VERIFICATION TEST (PVT)
3.5.1 PVT Procedures
Prepare PVT Procedures explaining step-by-step, the actions and expected results that will demonstrate that the control system performs in accordance with the sequences of operation, and other contract documents. Submit 4 copies of the PVT Procedures. The PVT Procedures may be submitted as a Technical Data Package.
3.5.1.1 Sensor Accuracy Checks
Include a one-point accuracy check of each sensor in the PVT procedures.
3.5.1.2 Endurance Test
FINAL (100% design) ADDITIONAL SECTION 230900 Page 233
Include a a one-week endurance test as part of the PVT during which the system is operated continuously. Use the building control system BACnet Trend Log or Trend Log Multiple Objects to trend all points shown as requiring a trend on the Point Schedule for the entire endurance test. If insufficient buffer capacity exists to trend the entire endurance test, upload trend logs during the course of the endurance test to ensure that no trend data is lost.
3.5.1.3 PVT Equipment List
Include in the PVT procedures a control system performance verification test equipment list that lists the equipment to be used during performance verification testing. For each piece of equipment, include manufacturer name, model number, equipment function, the date of the latest calibration, and the results of the latest calibration
3.5.2 PVT Execution
Demonstrate compliance of the control system with the contract documents. Using test plans and procedures approved by the Government, software capable of reading and writing COV Notification Subscriptions, Notification Class Recipient List Properties, event enrollments, demonstrate all physical and functional requirements of the project. Show, step-by-step, the actions and results demonstrating that the control systems perform in accordance with the sequences of operation. Do not start the performance verification test until after receipt of written permission by the Government, based on Government approval of the PVT Plan and Draft As- Builts and completion of balancing. UNLESS GOVERNMENT WITNESSING OF A TEST IS SPECIFICALLY WAIVED BY THE GOVERNMENT, PERFORM ALL TESTS WITH A GOVERNMENT WITNESS. Do not conduct tests during scheduled seasonal off periods of base heating and cooling systems. If the system experiences any failures during the endurance test portion of the PVT, repair the system repeat the endurance test portion of the PVT until the system operates continuously and without failure for the specified endurance test period.
3.5.3 PVT Report
Prepare and submit a PVT report documenting all tests performed during the PVT and their results. Include all tests in the PVT procedures and any additional tests performed during PVT. Document test failures and repairs conducted with the test results.
Submit four copies of the PVT Report. The PVT Report may be submitted as a Technical Data Package.
3.6 OPERATION AND MAINTENANCE (O&M) INSTRUCTIONS
Provide HVAC control System Operation and Maintenance Instructions which include:
a. HVAC control system sequences of operation formatted as indicated.
b. Procedures for the HVAC system start-up, operation and shut-down including the manufacturer's supplied procedures for each piece of equipment, and procedures for the overall HVAC system.
c. As-built HVAC control system detail drawings formatted as indicated.
d. Routine maintenance checklist. Provide the routine maintenance checklist arranged in a columnar format, where the first column lists all installed devices, the second column states the maintenance activity or that no maintenance required, the third column states the frequency of the maintenance activity, and the fourth column is used for additional comments or reference.
e. Qualified service organization list, including at a minimum company name, contact name and phone number.
f. Start-Up Testing Report.
FINAL (100% design) ADDITIONAL SECTION 230900 Page 234
g. Performance Verification Test (PVT) Procedures and Report.
Submit 2 copies of the Operation and Maintenance Instructions, indexed and in booklet form. The Operation and Maintenance Instructions may be submitted as a Technical Data Package.
3.7 MAINTENANCE AND SERVICE
Provide services, materials and equipment as necessary to maintain the entire system in an operational state as indicated for a period of one year after successful completion and acceptance of the Performance Verification Test. Minimize impacts on facility operations.
a. The integration of the system specified in this section into a Utility Monitoring and Control System must not, of itself, void the warranty or otherwise alter the requirement for the one year maintenance and service period.
Integration into a UMCS includes but is not limited to establishing communication between devices in the control system and the front end or devices in another system.
b. The changing of configuration properties must not, of itself, void the warranty or otherwise alter the requirement for the one year maintenance and service period.
3.7.1 Description of Work
Provide adjustment and repair of the system including the manufacturer's required sensor and actuator (including transducer) calibration, span and range adjustment.
3.7.2 Personnel
Use only service personnel qualified to accomplish work promptly and satisfactorily. Advise the Government in writing of the name of the designated service representative, and of any changes in personnel.
3.7.3 Scheduled Inspections
Perform two inspections at six-month intervals and provide work required. Perform inspeations in June and December. During each inpection perform the indicated tasks:
a. Perform visual checks and operational tests of equipment.
b. Clean control system equipment including interior and exterior surfaces.
c. Check and calibrate each field device. Check and calibrate 50 percent of the total analog inputs and outputs during the first inspection. Check and calibrate the remaining 50 percent of the analog inputs and outputs during the second major inspection. Certify analog test instrumentation accuracy to be twice the specified accuracy of the device being calibrated. Randomly check at least 25 percent of all binary inputs and outputs for proper operation during the first inspection. Randomly check at least 25 percent of the remaining binary inputs and outputs during the second inspection. If more than 20 percent of checked inputs or outputs failed the calibration check during any inspection, check and recalibrate all inputs and outputs during that inspection.
d. Run system software diagnostics and correct diagnosed problems. e. Resolve any previous outstanding problems.
3.7.4 Scheduled Work
This work must be performed during regular working hours, Monday through Friday, excluding Federal holidays.
FINAL (100% design) ADDITIONAL SECTION 230900 Page 235
3.7.5 Emergency Service
The Government will initiate service calls when the system is not functioning properly. Qualified personnel must be available to provide service to the system. A telephone number where the service supervisor can be reached at all times must be provided. Service personnel must be at the site within 24 hours after receiving a request for service. The control system must be restored to proper operating condition.
3.7.6 Operation
After performing scheduled adjustments and repairs, verify control system operation as demonstrated by the applicable tests of the performance verification test.
3.7.7 Records and Logs
Keep dated records and logs of each task, with cumulative records for each major component, and for the complete system chronologically. Maintain a continuous log for all devices, including initial analog span and zero calibration values and digital points. Keep complete logs and provide logs for inspection onsite, demonstrating that planned and systematic adjustments and repairs have been accomplished for the control system.
3.7.8 Work Requests
Record each service call request as received and include its location, date and time the call was received, nature of trouble, names of the service personnel assigned to the task, instructions describing what has to be done, the amount and nature of the materials to be used, the time and date work started, and the time and date of completion. Submit a record of the work performed within 5 days after work is accomplished.
3.7.9 System Modifications
Submit recommendations for system modification in writing. Do not make system modifications, including operating parameters and control settings, without prior approval of the Government.
3.8 TRAINING
Conduct a training course for 4 operating staff members designated by the Government in the maintenance and operation of the system, including specified hardware and software. Conduct 32 hours of training at the project site within 30 days after successful completion of the performance verification test. The Government reserves the right to make audio and visual recordings (using Governemnt supplied equipment)of the training sessions for later use. Provide audiovisual equipment and other training materials and supplies required to conduct training. A training day is defined as 8 hours of classroom instruction, including two 15 minute breaks and excluding lunchtime, Monday through Friday, during the daytime shift in effect at the training facility.
3.8.1 Training Documentation
Prepare training documentation consisting of:
a. Course Attendee List: Develop the list of course attendees in coordination with and signed by the Controls shop supervisor.
b. Training Manuals: Provide training manuals which include an agenda, defined objectives for each lesson, and a detailed description of the subject matter for each lesson. When presenting portions of the course material by audiovisuals, deliver copies of those audiovisuals as a part of the printed training manuals.
FINAL (100% design) ADDITIONAL SECTION 230900 Page 236
3.8.2 Training Course Content
For guidance in planning the required instruction, assume that attendees will have a high school education, and are familiar with HVAC systems. During the training course, cover all of the material contained in the Operating and Maintenance Instructions, the layout and location of each controller enclosure, the layout of one of each type of equipment and the locations of each, the location of each control device external to the panels, the location of the compressed air station, preventive maintenance, troubleshooting, diagnostics, calibration, adjustment, commissioning, tuning, and repair procedures. Typical systems and similar systems may be treated as a group, with instruction on the physical layout of one such system. Present the results of the performance verification test and the Start-Up Testing Report as benchmarks of HVAC control system performance by which to measure operation and maintenance effectiveness.
3.8.3 Training Documentation Submittal Requirements
Submit hardcopy training manuals and all training materials on CD-ROM. Provide one hardcopy manual for each trainee on the Course Attendee List and 2 additional copies for archive at the project site. Provide 2 copies of the Course Attendee List with the archival copies. Training Documentation may be submitted as a Technical Data Package.
FINAL (100% design) ADDITIONAL SECTION 230900 Page 237
APPENDIX A
QC CHECKLIST FOR BACNET SYSTEMS
This checklist is not all-inclusive of the requirements of this specification and should not be interpreted as such.
Instructions: Initial each item in the space provided (1 1) verifying that the requirement has been met.
This checklist is for (circle one:)
Pre-Construction QC Checklist Submittal Post-Construction QC Checklist Submittal Close-out QC Checklist Submittal
Items verified for Pre-Construction, Post-Construction and Closeout QC Checklist
Submittals:
1 All DDC Hardware is numbered on Control System Schematic Drawings. 1 1
2 Signal lines on Control System Schematic are labeled with the signal type. 1 1
3 Local Display Panel (LDP) Locations are shown on Control System
Schematic drawings.
1 1
Items verified for Post-Construction and Closeout QC Checklist Submittals:
4 All sequences are performed as specified using DDC Hardware. 1 1
5 Training schedule and course attendee list has been developed and coordinated with shops and submitted.
Items verified for Closeout QC Checklist Submittal:
6 Final As-built Drawings, including all Points Schedule drawings, accurately represent the final installed system.
1 1
7 Programming software has been submitted for all programmable controllers. 1 1
8 All software has been licensed to the Government.
9 O&M Instructions have been completed and submitted. 1 1
10 Training course has been completed. 1 1
FINAL (100% design) ADDITIONAL SECTION 230900 Page 238
QC CHECKLIST FOR BACNET SYSTEMS
11 All DDC Hardware is installed on a BACnet ASHRAE 135 network using either MS/TP in accordance with Clause 9 or IP in accordance with Annex J.
1 1
12 All DDC Hardware is BTL listed. 1 1
13 Communication between DDC Hardware is only via BACnet using standard services, except as specifically permitted by the specification.
Non-standard services have been fully documented in the DDC Hardware
Schedule.
1 1
14 Scheduling, Alarming, and Trending have been implemented using the standard BACnet Objects for these functions.
1 1
15 All Properties indicated as required to be Writeable are Writeable and
Overrides have been provided as indicated
(QC Representative Signature) (Date)
FINAL (100% design) ADDITIONAL SECTION 230913 Page 239
SECTION 23 09 13
INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
11/15
PART 1 GENERAL
1.1 SUMMARY
This section provides for the instrumentation control system components excluding direct digital controllers, network controllers, gateways etc. that are necessary for a completely functional automatic control system.
When combined with a Direct Digital Control (DDC) system, the Instrumentation and Control Devices covered under this section must be a complete system suitable for the control of the heating, ventilating and air conditioning (HVAC) and other building-level systems as specified and indicated.
a. Install hardware to perform the control sequences as specified and indicated and to provide control of the equipment as specified and indicated.
b. Install hardware such that individual control equipment can be replaced by similar control equipment from other equipment manufacturers with no loss of system functionality.
c. Install and configure hardware such that the Government or their agents are able to perform repair, replacement, and upgrades of individual hardware without further interaction with the installing Contractor.
1.1.1 Verification of Dimensions
After becoming familiar with all details of the work, verify all dimensions in the field, and advise the Contracting Officer of any discrepancy before performing any work.
1.1.2 Drawings
The Government will not indicate all offsets, fittings, and accessories that may be required on the drawings.
Carefully investigate the mechanical, electrical, and finish conditions that could affect the work to be performed, arrange such work accordingly, and provide all work necessary to meet such conditions.
1.2 RELATED SECTIONS
Related work specified elsewhere.
Section 23 09 00 INTRUMENTATION AND CONTROL FOR HVAC
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL (AMCA) AMCA 500-D (2012) Laboratory Methods of Testing Dampers for Rating
AMCA 511 (2010) Certified Ratings Program for Air Control Devices
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
FINAL (100% design) ADDITIONAL SECTION 230913 Page 240
ANSI C12.1 (2008) Electric Meters Code for Electricity Metering
ASME INTERNATIONAL (ASME)
ASME B16.15 (2013) Cast Copper Alloy Threaded Fittings Classes 125 and 250
ASME B16.34 (2017) Valves - Flanged, Threaded and Welding End
ASME B40.100 (2013) Pressure Gauges and Gauge Attachments
CEI (ITALIAN ELECTROTECHNICAL COMMITTEE
CEI EN 61326-3-1 (2018) Electrical equipment for measurement, control and laboratory - Electromagnetic compatibility requirements Part 3-1: Immunity requirements for safety systems and equipment designed to perform safety functions (functional safety) - General industrial applications
CEI EN 50491-5-2 (2011)General requirements for home and building electronic systems (HBES) and building automation and control systems (BACS) Part 5-2: Electromagnetic compatibility (EMC) requirements for HBES / BACS devices used in residential, commercial environments and light industry
CEI EN 50491-5-3 (2011)General requirements for electronic systems for home and building (HBES) and building automation and control systems (BACS) Part 5-3: Electromagnetic compatibility (EMC) requirements for HBES / BACS devices used in industrial environments
CEI EN 55022/A1 (2001) Information technology equipment Radio interference features Limits and methods of measurement
CEI EN 55022/A2 (2013) Information technology equipment - Radio disturbance characteristics - Limits and methods of measurement
CEI EN 55022 (2009) Information technology equipment - Radio disturbance characteristics - Limits and methods of measurement
CEI-EN 61326-1 (2013) Electrical equipment for measurement, control and laboratory - Electromagnetic compatibility requirements Part 1: General requirements
FLUID CONTROLS INSTITUTE (FCI)
FCI 70-2 (2013) Control Valve Seat Leakage
IEC (INTERNATION ELECTROTECHNICAL COMMISSION)
60730-2-9 (2015)Automatic electrical controls - Part 2-9: Particular requirements for temperature sensing control
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 142 (2007; Errata 2014) Recommended Practice for Grounding of Industrial and Commercial Power Systems - IEEE Green Book
IEC (INTERNATIONAL ELECTROTECHNICAL COMMISSION)
IEC 60529 (1989) Degrees of protection provided by enclosures (IP Code)
FINAL (100% design) ADDITIONAL SECTION 230913 Page 241
IEC 60730-1 (2013) Automatic electrical controls - Part 1: General requirements
IEC 60730-2-8 Automatic electrical controls for household and similar use - Part 2-8: Particular requirements for electrically operated water valves, including mechanical requirements
ITALIAN/EUROPEAN HARMONIZATION STANDARDS (UNI EN)(UNI ENV)(CEI EN) (UNI EN ISO)(UNI ISO)
CEI 64-8 (2017) Electrical installations for users with a nominal voltage not exceeding 1 000 V in alternating current and 1 500 V in direct current
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C12.20 (2015) Electricity Meters - 0.1, 0.2, and 0.5 Accuracy Classes
NEMA/ANSI C12.10 (2011) Physical Aspects of Watthour Meters - Safety Standards
CE STANDARD AND LAWS (EUROPEAN COMMUNITY)
DIRECTIVE 2014/35 (2014)Low Voltage Directive
DIRECTIVE 2014/30/EU (2014)Electromagnetic compatibility Directive
CEI ITALIAN ELECTROTECHNICAL COMMITTEE STANDARDS
CEI EN 61558-2-13 (2009) Safety of transformers, reactors,power supply units and similar products for supply voltages up to 1 100 V – Part 2-13: Particular requirements and tests for auto transformers and power supply units incorporating auto transformers
ITALIAN LAWS AND NORMS (D.M.) (LAW) (CIRC.)
D.Lgs 19 may 2016 n.86 (2016) Implementation of Directive 2014/35 / EU on the harmonization of the laws of the Member States relating to making available on the market electrical equipment intended for use within certain voltage limits
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2; TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6; TIA 17-7;
TIA 17-8; TIA 17-9; TIA 17-10; TIA 17-11; TIA 17-12; TIA 17-13; TIA 17-14) National Electrical Code
NFPA 90A (2018) Standard for the Installation of Air Conditioning and Ventilating Systems
UNDERWRITERS LABORATORIES (UL)
UL 5085-3 (2006; Reprint Nov 20121) Low Voltage Transformers - Part 3: Class 2 and Class 3 Transformers
UL 555 (2006; Reprint Aug 2016) UL Standard for Safety Fire Dampers
UL 555S (2014; Reprint Aug 2016) UL Standard for Safety Smoke Dampers
1.4 SUBMITTALS
FINAL (100% design) ADDITIONAL SECTION 230913 Page 242
Submittal requirements are specified in Section 23 09 00 INTRUMENTATION AND CONTROL FOR HVAC.
1.5 DELIVERY AND STORAGE
Store and protect products from the weather, humidity, and temperature variations, dirt and dust, and other contaminants, within the storage condition limits published by the equipment manufacturer.
1.6 INPUT MEASUREMENT ACCURACY
Select, install and configure sensors, transmitters and DDC Hardware such that the maximum error of the measured value at the input of the DDC hardware is less than the maximum allowable error specified for the sensor or instrumentation.
PART 2 PRODUCTS
2.1 EQUIPMENT
2.1.1 General Requirements
All products used to meet this specification must meet the indicated requirements, but not all products specified here will be required by every project. All products must meet the requirements both Section 23 09 00 INTRUMENTATION AND CONTROL FOR HVAC and this Section. All systems, devices and other electrical equipment will be compliance to the DIRECTIVE 2014/30/EU, DIRECTIVE 2014/35, D.Lgs 19 may 2016 n.86. The grade of protection of the devices shall be compliance to the IEC 60529 and IEC 60730-1. Where applicable the equipment shall be compliance also to the CEI EN 50491-5-2, CEI EN 50491-5-3, CEI EN 55022, CEI EN 55022/A1, CEI EN 55022/A2
2.1.2 Operation Environment Requirements
Unless otherwise specified, provide products rated for continuous operation under the following conditions:
2.1.2.1 Pressure
Pressure conditions normally encountered in the installed location.
2.1.2.2 Vibration
Vibration conditions normally encountered in the installed location.
2.1.2.3 Temperature
a. Products installed indoors: Ambient temperatures in the range of 0 to 50 degrees C and temperature conditions outside this range normally encountered at the installed location.
b. Products installed outdoors or in unconditioned indoor spaces: Ambient temperatures in the range of -37 to +66 degrees C and temperature conditions outside this range normally encountered at the installed location.
2.1.2.4 Humidity
FINAL (100% design) ADDITIONAL SECTION 230913 Page 243
10 to 95 percent relative humidity, noncondensing and also humidity conditions outside this range normally encountered at the installed location.
2.2 WEATHERSHIELDS
Provide weathershields constructed of galvanized steel painted white, unpainted aluminum, aluminum painted white, or white PVC.
2.3 WIRE AND CABLE
Provide wire and cable meeting the requirements of NFPA 70 and NFPA 90A and CEI 64-8in addition to the requirements of this specification and referenced specifications.
2.3.1 Terminal Blocks
For terminal blocks which are not integral to other equipment, provide terminal blocks which are insulated, modular, feed-through, clamp style with recessed captive screw-type clamping mechanism, suitable for DIN rail mounting, and which have enclosed sides or end plates and partition plates for separation.
2.3.2 Control Wiring for Binary Signals
For Control Wiring for Binary Signals, provide 18 AWG (1.02 mm diameter) copper or thicker wire rated for 300-volt service.
2.3.3 Control Wiring for Analog Signals
For Control Wiring for Analog Signals, provide 18 AWG (1.02 mm diameter) or thicker, copper, single- or multiple-twisted wire meeting the following requirements:
a. minimum 50 mm (2 inch) lay of twist b. 100 percent shielded pairs c. at least 300-volt insulation
d. each pair has a 20 AWG tinned-copper drain wire and individual overall pair insulation
e. cables have an overall aluminum-polyester or tinned-copper cable-shield tape, overall 20 AWG tinned-copper cable drain wire, and overall cable insulation.
2.3.4 Power Wiring for Control Devices
For 24-volt circuits, provide insulated copper 18 AWG or thicker wire rated for 300 VAC service. For 120-volt circuits, provide 14 AWG or thicker stranded copper wire rated for 600-volt service.
2.3.5 Transformers
Provide UL 5085-3 or CEI EN 61558-2-13approved transformers. Select transformers sized so that the connected load is no greater than 80 percent of the transformer rated capacity.
2.4 AUTOMATIC CONTROL VALVES
Provide valves with stainless-steel stems and stuffing boxes with extended necks to clear the piping insulation.
Provide valves with bodies meeting ASME B16.34 or ASME B16.15 pressure and temperature class ratings based on the design operating temperature and 150 percent of the system design operating pressure. Unless otherwise
FINAL (100% design) ADDITIONAL SECTION 230913 Page 244 specified or indicated, provide valves meeting FCI 70-2 Class III leakage rating. Provide valves rated for modulating or two-position service as indicated, which close against a differential pressure indicated as the Close-Off pressure and which are Normally-Open, Normally-Closed, or Fail-In-Last-Position as indicated. The valves and actuators shall be compliance to IEC 60730-2-8
2.4.1 Valve Type
2.4.1.1 Liquid Service 150 Degrees F or Less
Use ball valves except that butterfly valves may be used for sizes 100 mm and larger.
2.4.2 Valve Flow Coefficient and Flow Characteristic
2.4.2.1 Two-Way Modulating Valves
Provide the valve coefficient (Kv) indicated. Provide equal-percentage flow characteristic for liquid service except for butterfly valves. .
2.4.2.2 Three-Way Modulating Valves
Provide the valve coefficient (Kv) indicated. Provide linear flow characteristic with constant total flow throughout full plug travel.
2.4.3 Two-Position Valves
Use full line size full port valves with maximum available (Kv).
2.4.4 Ball Valves
2.4.4.1 Liquid Service Not Exceeding 66 Degrees C
a. Valve body and connections:
(1) valves 38 mm and smaller: bodies of brass or bronze, with threaded or union ends
(2) valves from 51 mm to 76 mm inclusive: bodies of brass, bronze, or iron. 50 mm valves with threaded connections; valves from 63 to 76 mm with flanged connections.
b. Ball: Stainless steel or nickel-plated brass or chrome-plated brass.
c. Seals: Reinforced Teflon seals and EPDM O-rings. d. Stem: Stainless steel, blow-out proof.
e. Provide valves compatible with a solution of 50 percent ethylene or propylene glycol.
2.4.5 Pressure Independent Control Valves (PICV)
Provide pressure independent control valves which include a regulator valve which maintains the differential pressure across a flow control valve. Pressure independent control valves must accurately control the flow from 0-100 percent full rated flow regardless of changes in the piping pressure and not vary the flow more than plus or minus 7 percent at any given flow control valve position when the PICV differential pressure lies between the manufacturer's stated minimum and maximum.
The rated minimum differential pressure for steady flow must not exceed 34.5 kPa across the PICV. Provide ball type valves meeting the indicated requirements for ball valves. Provide valves with a flow tag listing full rated
FINAL (100% design) ADDITIONAL SECTION 230913 Page 245 flow and minimum required pressure drop. Provide valves with factory installaed Pressure/Temperature ports ("Pete's Plugs") to measure the pressure drop to determine the valve flow rate.
2.4.6 Duct-Coil and Terminal-Unit-Coil Valves
For duct or terminal-unit coilsm provide control valves with either screw typeends. Provide flare nuts for each flare-type end valve.
2.5 DAMPERS
2.5.1 Damper Assembly
Provide single damper sections with blades no longer than 1.2 m and which are no higher than 1.8 m and damper blade width of 203 mm or less. When larger sizes are required, combine damper sections. Provide dampers made of steel, or other materials where indicated and with assembly frames constructed of 2.8 mm minimum thickness galvanized steel channels with mitered and welded corners. Steel channel frames constructed of 1.5 mm minimum thickness are acceptable provided the corners are reinforced.
a. Flat blades must be made rigid by folding the edges. Blade-operating linkages must be within the frame so that blade-connecting devices within the same damper section must not be located directly in the air stream.
b. Damper axles must be 13 mm minimum, plated steel rods supported in the damper frame by stainless steel or bronze bearings. Blades mounted vertically must be supported by thrust bearings.
c. Provide dampers which do not exceed a pressure drop through the damper of 10 Pa at 5 m/s in the wide-open position. Provde dampers with frames not less than 50 mm in width. Provide dampers which have been tested in accordance with AMCA 500-D.
2.5.2 Operating Linkages
For operating links external to dampers, such as crank arms, connecting rods, and line shafting for transmitting motion from damper actuators to dampers, provide links able to withstand a load equal to at least 300 percent of the maximum required damper-operating force without deforming. Rod lengths must be adjustable. Links must be brass, bronze, zinc-coated steel, or stainless steel. Working parts of joints and clevises must be brass, bronze, or stainless steel. Adjustments of crank arms must control the open and closed positions of dampers.
2.5.3 Damper Types
2.5.3.1 Flow Control Dampers
Provide opposed blade type dampers for outside air, return air, relief air, exhaust, face and bypass dampers.
Blades must have interlocking edges. The channel frames of the dampers must be provided with jamb seals to minimize air leakage. Unless otherwise indicated, dampers must meet AMCA 511 Class Class 1 requirements.
Outside air damper seals must be suitable for an operating temperature range of -40 to +75 degrees C. Dampers must be rated at not less than 10 m/s air velocity.
2.5.3.2 Mechanical Rooms and Other Utility Space Ventilation Dampers
Provide utility space ventilation dampers as indicated. Unless otherwise indicated provide AMCA 511 class 3 dampers. Provide dampers rated at not less than 7.6 m/s air velocity.
2.5.3.3 Smoke Dampers
FINAL (100% design) ADDITIONAL SECTION 230913 Page 246
Provide smoke-damper and actuator assemblies which meet the current requirements of NFPA 90A, UL 555, and UL 555S. For combination fire and smoke dampers provide dampers rated for 121 degrees C Class II leakage per
UL 555S.
2.6 SENSORS AND INSTRUMENTATION
Unless otherwise specified, provide sensors and instrumentation which incorporate an integral transmitter.
Sensors and instrumentation, including their transmitters, must meet the specified accuracy and drift requirements at the input of the connected DDC Hardware's analog-to-digital conversion.
2.6.1 Analog and Binary Transmitters
Provide transmitters which match the characteristics of the sensor. Transmitters providing analog values must produce a linear 4-20 mAdc, 0-10 Vdc signal corresponding to the required operating range and must have zero and span adjustment. Transmitters providing binary values must have dry contacts rated at 1A at 24 Volts AC.
2.6.2 Network Transmitters
Sensors and Instrumentation incorporating an integral network connection are considered DDC Hardware and must meet the DDC Hardware requirements of Sectionof 23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL SYSTEMS when used in a BACnet network.
2.6.3 Temperature Sensors
Provide the same sensor type throughout the project. Temperature sensors may be provided without transmitters. Where transmitters are used, the range must be the smallest available from the manufacturer and suitable for the application such that the range encompasses the expected range of temperatures to be measured. The end to end accuracy includes the combined effect of sensitivity, hysterisis, linearity and repeatability between the measured variable and the end user interface (graphic presentation) including transmitters if used. All devices will be compliance60730-2-9
2.6.3.1 Sensor Accuracy and Stability of Control
2.6.3.1.1 Conditioned Space Temperature
Plus or minus 0.3 degrees C over the operating range.
2.6.3.1.2 Unconditioned Space Temperature
a. Plus or minus 0.6 degrees C over the range of -1 to +55 degrees C AND
b. Plus or minus 2 degrees C over the rest of the operating range.
2.6.3.1.3 Duct Temperature
Plus or minus 0.3 degrees C
2.6.3.1.4 Outside Air Temperature
a. Plus or minus 1 degree C over the range of -35 to +55 degrees C AND
b. Plus or minus 0.6 degrees C over the range of -1 to +40 degrees C.
FINAL (100% design) ADDITIONAL SECTION 230913 Page 247
2.6.3.1.5 High Temperature Hot Water
Plus or minus 2 degrees C.
2.6.3.1.6 Chilled Water
Plus or minus 0.4 degrees C over the range of 2 to 18 degrees C.
2.6.3.1.7 Dual Temperature Water
Plus or minus 1 degree C.
2.6.3.1.8 Heating Hot Water
2.6.3.1.9 Condenser Water
2.6.3.2 Transmitter Drift
The maximum allowable transmitter drift: 0.1 degrees C per year.
2.6.3.3 Point Temperature Sensors
Point Sensors must be encapsulated in epoxy, series 300 stainless steel, anodized aluminum, or copper.
2.6.3.4 Temperature Sensor Details
2.6.3.4.1 Room Type
Provide the sensing element components within a decorative protective cover suitable for surrounding decor.
Digital display type with override command
2.6.3.4.2 Duct Probe Type
Ensure the probe is long enough to properly sense the air stream temperature.
2.6.3.4.3 Duct Averaging Type
Continuous averaging sensors must be one foot in length for each 0.1 square m of duct cross-sectional area, and a minimum length of 1.5 m.
2.6.3.4.4 Pipe Immersion Type
Provide minimum 7.6 cm immersion. Provide each sensor with a corresponding pipe-mounted sensor well, unless indicated otherwise. Sensor wells must be stainless steel when used in steel piping, and brass when used in copper piping.
2.6.3.4.5 Outside Air Type
Provide the sensing element rated for outdoor use
FINAL (100% design) ADDITIONAL SECTION 230913 Page 248
2.6.4 Relative Humidity Sensor
Relative humidity sensors must use bulk polymer resistive or thin film capacitive type non-saturating sensing elements capable of withstanding a saturated condition without permanently affecting calibration or sustaining damage. The sensors must include removable protective membrane filters. Where required for exterior installation, sensors must be capable of surviving below freezing temperatures and direct contact with moisture without affecting sensor calibration. When used indoors, the sensor must be capable of being exposed to a condensing air stream (100 percent relative humidity) with no adverse effect to the sensor's calibration or other harm to the instrument. The sensor must be of the wall-mounted or duct-mounted type, as required by the application, and must be provided with any required accessories. Sensors used in duct high-limit applications must have a bulk polymer resistive sensing element. Duct-mounted sensors must be provided with a duct probe designed to protect the sensing element from dust accumulation and mechanical damage. Relative humidity (RH) sensors must measure relative humidity over a range of 0 percent to 100 percent with an accuracy of plus or minus 2 percent. RH sensors must function over a temperature range of 4.4 to 57.2 degrees C and must not drift more than 1 percent per year.
2.6.5 Carbon Dioxide (C02) Sensors
Provide photometric type C02 sensors with integral transducers and linear output. Carbon dioxide (C02) sensors must measure C02 concentrations between 0 to 2000 parts per million (ppm) using non-dispersive infrared (NDIR) technology with an accuracy of plus or minus 50 ppm and a maximum response time of 1 minute. The sensor must be rated for operation at ambient air temperatures within the range of 0 to 50 degrees C and relative humidity within the range of 20 to 95 percent (non-condensing). The sensor must have a maximum drift of 2 percent per year. The sensor chamber must be manufactured with a non-corrosive material that does not affect carbon dioxide sample concentration. Duct mounted sensors must be provided with a duct probe designed to protect the sensing element from dust accumulation and mechanical damage. The sensor must have a calibration interval no less than 5 years.
2.6.6 Differential Pressure Instrumentation
2.6.6.1 Differential Pressure Sensors
Provide Differential Pressure Sensors with ranges as indicated or as required for the application. Pressure sensor ranges must not exceed the high end range indicated on the Points Schedule by more than 50 percent. The over pressure rating must be a minimum of 150 percent of the highest design pressure of either input to the sensor.
The accuracy must be plus or minus 1 percent of full scale. The sensor must have a maximum drift of 2 percent per year. The sensor will be compliance to the CEI EN 55022, CEI EN 55022/A1, CEI EN 55022/A2 and CEI EN
61326-3-1, CEI-EN 61326-1
2.6.6.2 Differential Pressure Switch
Provide differential pressure switches with a user-adjustable setpoint which are sized for the application such that the setpoint is between 25 percent and 75 percent of the full range. The over pressure rating must be a minimum of 150 percent of the highest design pressure of either input to the sensor. The switch must have two sets of contacts and each contact must have a rating greater than it's connected load. Contacts must open or close upon rise of pressure above the setpoint or drop of pressure below the setpoint as indicated.. The sensor will be compliance to the CEI EN 55022, CEI EN 55022/A1, CEI EN 55022/A2 and CEI EN 61326-3-1, CEI-EN 61326-
2.6.7 Flow Sensors
2.6.7.1 Airflow Measurement Array (AFMA)
2.6.7.1.1 Airflow Straightener
FINAL (100% design) ADDITIONAL SECTION 230913 Page 249
Provide AFMAs which contain an airflow straightener if required by the AFMA manufacturer's published installation instructions. The straightener must be contained inside a flanged sheet metal casing, with the AFMA located as specified according to the published recommendation of the AFMA manufacturer. In the absence of published documentation, provide airflow straighteners if there is any duct obstruction within 5 duct diameters upstream of the AFMA. Air-flow straighteners, where required, must be constructed of 3 mm aluminum honeycomb and the depth of the straightener must not be less than 40 mm.
2.6.7.1.2 Resistance to Airflow
The resistance to air flow through the AFMA, including the airflow straightener must not exceed 20 Pa at an airflow of 10 m/s. AFMA construction must be suitable for operation at airflows of up to 25 m/s over a temperature range of 4 to 49 degrees C.
2.6.7.1.3 Outside Air Temperature
In outside air measurement or in low-temperature air delivery applications, provide an AFMA certified by the manufacturer to be accurate as specified over a temperature range of -29 to +49 degrees C.
2.6.7.1.4 Pitot Tube AFMA
Each Pitot Tube AFMA must contain an array of velocity sensing elements. The velocity sensing elements must be of the multiple pitot tube type with averaging manifolds. The sensing elements must be distributed across the duct cross section in the quantity and pattern specified or recommended by the published installation instructions of the AFMA manufacturer.
a. Pitot Tube AFMAs for use in airflows over 3.0 m/s must have an accuracy of plus or minus 5 percent over a range of 2.5 to 12.5 m/s.
b. Pitot Tube AFMAs for use in airflows under 3.0 m/s must have an accuracy of plus or minus 5 percent over a range of 0.6 to 12.5 m/s.
2.6.7.1.5 Electronic AFMA
Each…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .