Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part2.pdf
PDF 561 KB Posted
- Attached to
- Multiple Award Construction Contract (MACC) Italy Federal contract opportunity
- Solicitation number
- FA568219RA001
About this file
This document is a draft request for proposal for a multiple award construction contract to provide design-build construction services in Italy. Services may include grading, utilities, painting, roofing, building construction, electrical work, HVAC, fire suppression, fuel systems, generators, communications, abatement, and site work. The contract would have a one-year base period and four option years, with a minimum $2,500 task order amount and maximum $7 million task order value. The minimum guaranteed contract amount is $2,500 payable after mandatory training. The total maximum value for all contracts is estimated at $96 million. Comments on the draft attachments are due by April 19, 2019. Task orders will primarily be located at Aviano Air Base but could occur anywhere in Italy.
Attachment 10 ASHE 18-1025 Technical Specifications (Seed Project ) Part 2
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RENOVATE/EXPAND FAC. 939 ASHE18-1025
FINAL (100% design) SECTION 05500/R Page 77
Paragraph 1.2:
Delete “UNI 4634” and replace with “UNI EN ISO 15607 and any other regarding norm”.
Paragraph 1.3.1:
Delete:
a. Canopy
b. Panels for air handling unit casing
d. Fire extinguisher cabinet
e. Handrails
f. Steel louvers
Paragraph 1.3.2:
a. Canopy
b. Panels for air handling unit casing
d. Fire extinguisher cabinet
e. Handrails
f. Steel louvers
Paragraph 1.5:
Delete “UNI 4634” and replace with “UNI EN ISO 9606-1”.
Paragraph 2.1:
Delete “Law 1086” and replace with “D.M. 16 Feb 2007”.
Paragraph 2.1.8.2:
Add:
UNI EN ISO 4017 and UNI EN ISO 4018
2.1.8.3 Bolts and Studs
UNI EN ISO 898-1.
2.1.8.4 Screws
Provide hexagon head screws to conform to UNI EN ISO 4017. Slotted panhead tapping screws EN ISO 1481 slotted raised.
2.1.8.5 Washers
Provide plain washers to conform to UNI EN ISO 887 and UNI EN ISO 7089.
Provide comparable lock washers.
-- End of Section --
FINAL (100% design) SECTION 07112/R Page 78
SECTION 07112/R
BITUMINOUS DAMPPROOFING
Paragraph 1.0:
UNI 13108-6 (2006) Bituminous mixtures – Materials specifications - Part 6: Mastic Asphalt
UNI EN 13416 (2003) Flexible sheets for waterproofing -
Bitumen, plastic and rubber sheets for roof waterproofing - Rules for sampling
UNI EN 1849-1 (2002) Flexible sheets for waterproofing -
Determination of thickness and mass per unit area - Part 1: Bitumen sheets for roof waterproofing
D.M. 26 Jun 1984 Classification of Resistance to Fire and
Ratification of Materials for Fire
Prevention.
D.M. 15 Mar 2005 Classification of fire resistance of materials used in construction. Integrates
Italian requirements into the European classification system.
D.M. 16 Feb 2007 Classification of fire resistance of construction material and elements
D.M. 09 Mar 2007 Performance of resistance to fire in the activities subject to control by the
National Fire Department stabilizing criteria for determining the fire resistance performance.
UNI 8202-25 (1984) Building - Water proof sheets -
Determination of fire reaction
UNI 8490-3 (1984) Aqueous dispersions of polymers and copolymers - Test methods - Determination of viscosity by the Brookfield rotational viscometer
UNI 8898-3 (1987) Polimeric water proof sheets -
Elastomeric reinforced sheets -
Characteristics and acceptance limits
UNI EN 13707 (2013) Flexible sheets for waterproofing -
Reinforced bitumen sheets for roof waterproofing - Definitions and characteristics
-- End of Section –-
FINAL (100% design) SECTION 07220/R Page 79
Section 07220/R
ROOF INSULATION
Paragraph 1.1:
UNI 4157 (1987) Building. Bitumen for roofing.
Sampling and acceptance limits.
UNI 6541 (1969) Glass fiber materials for thermal and acoustical insulation. Resin bonded slabs. Determination of the Compressive
Requirements.
UNI 7891 (1978) Insulating materials. Determination of thermal conductivity by means of the heat flow meter method.
UNI EN 13165 (2003) Thermal insulation products for buildings - Factory made rigid polyurethane foam (PUR) products – Specification.
UNI EN 12086 (1999) Thermal insulating products for building applications - Determination of water vapor transmission properties.
UNI EN 1604 (1999) Thermal insulating products for dimensional stability under specified temperature and humidity conditions.
UNI EN 826 (1998) Thermal insulating products for compression behavior.
UNI EN ISO 845 (1997) Cellular plastics and rubbers.
Determination of apparent (bulk) density.
UNI EN ISO 844 (2014) Rigid cellular plastics -
Determination of compression properties
UNI EN ISO 845 (2009) Cellular plastics and rubbers -
Determination of apparent density
ISO 1209-1 (2007) Rigid cellular plastics -
Determination of flexural properties -
Basic bending test
ISO 1663 (2007) Rigid cellular plastics -
Determination of water vapour transmission properties
ISO 2796 (1986) Cellular Plastics, Rigid – Test for
Dimensional Stability
FINAL (100% design) SECTION 07220/R Page 80
ISO 2896 (2001) Rigid Cellular Plastics -
Determination of Water Absorption
ISO 4898 (2010) ( Rigid cellular plastics - Thermal insulation products for buildings -
Specifications
ISO 7616 (1986) Cellular plastics, rigid -
Determination of compressive creep under specified load and temperature conditions
ISO 8145 (1994) Thermal Insulation - Mineral Wool
Board for Over-Deck Insulation of Roofs -
Specification
ISO 8301 (1991) Thermal Insulation - Determination of Steady-State Thermal Resistance and
Related Properties – Heat Flow Meter
Apparatus
Prevention
National Fire Department stabilizing resistance performance
D.Lgs. 09 Apr 2008, n.81 Unified Text, Safety Regulations;
realization of Article 1 of the Law 3 Aug
2007, n. 123, in the area of safeguarding the health and safety on the work place.
FINAL (100% design) SECTION 07231/R Page 81
Section 07231/R
WALL INSULATION
UNI 6547 (1985) Mineral Fiber Boards for Thermal and
Acoustical Insulation. Determination of
Flexibility Index.
UNI 6823 (1998) Mineral Wool Products for Thermal and Acoustical Insulation - Determination of Non-Fibrous Material Content -
Floatation Method.
Add
UNI EN 822 (2013) Thermal Insulating Products for
Building Applications - Determination of
Length and Width
UNI EN 823 (2013) Thermal Insulating Products for
Thickness
UNI EN 824 (2013) Thermal Insulating Products for
Squareness
UNI EN 825 (2013) Thermal Insulating Products for
Flatness
UNI EN 826 (2013) Thermal Insulating Products for
Compression Behavior
UNI EN ISO 6946 (2008) Building Components and Building
Elements - Thermal Resistance - Calculation
Method
UNI EN ISO 7345 (1999) Thermal Insulation – Physical
Quantities and Definitions
UNI EN ISO 9229 (2008) Thermal insulation – Vocabulary
UNI EN 13162 (2013) Thermal insulation for construction
- Mineral Wood (MW) product, factory produced - Specifications
FINAL (100% design) SECTION 07231/R Page 82
Italian requirements
National Fire Department stabilizing resistance performance.
D.M. 26 Jun 1984 (Classification of Resistance to Fire and
Prevention.
FINAL (100% design) SECTION 07321/R Page 83
SECTION 07321/R
CLAY ROOFING TILE
ITALIAN LAWS AND NORMS
realization of Article 1 of the Law 03 Aug the health and safety on the work place
ITALIAN/EUROPEAN HARMONIZATION STANDARDS (UNI EN)(UNI ENV)(UNI EN ISO)
UNI 196.1-7 (1996) Test Method of Concrete.
UNI EN 413-1 (1996) Masonry Cement - Part 1 –
Specification.
UNI EN 413-2 (1996) Masonry Cement - Part 2 - Test
Methods.
UNI EN 538 (1997) Clay Roofing Tiles for Discontinuous
Laying - Flexural Strength Test.
UNI EN 539-1 (1997) Clay Roofing Tiles for Discontinuous
Laying - Determination of Physical
Characteristics. Part 1 - Impermeability
Test.
ITALIAN NATIONAL INSTITUTE FOR THE UNIFICATION OF STANDARDS (UNI)
PUBLICATIONS:
UNI 8635-1 (1984) Buildings - Tests of Products for
Discontinuous Roofing - Part 1 - Appearance and Preparation Examination.
UNI 8635-2 (1984) Buildings - Tests of Products for
Discontinuous Roofing - Part 2 -
Determination of Length.
UNI 8635-3 (1984) Buildings - Tests of Products for
Discontinuous Roofing - Part 3 -
Determination of Width.
UNI 8626 (1984) Buildings - Products for
Discontinuous Roofing; Characteristics, Sampling Plan and Limits of Acceptance.
UNI 9460 (1989) Discontinuous Roofing - Practical
Instruction Code for the Design and
Execution of Clay and Cement Tile Roofing.
ITALIAN / EUROPEAN HARMONIZATION STANDARDS (EN, UNI EN, ISO)
FINAL (100% design) SECTION 07321/R Page 84
UNI EN 196-1 (2016) Methods of testing cement - Part 1:
Determination of strength
UNI EN 196-2 (2013) Method of testing cement - Part 2:
Chemical analysis of cement
UNI EN 196-3 (2017) Methods of testing cement - Part 3:
Determination of setting times and soundness
UNI EN 196-4 (2008) Methods of testing cement - Part 4:
Quantitative determination of constituents
UNI EN 196-5 (2011) Methods of testing cement - Part 5:
Pozzolanicity test for pozzolanic cement
UNI EN 196-6 (2010) Methods of testing cement - Part 6:
Determination of fineness
UNI EN 196-7 (2010) Methods of testing cement - Part 7:
Methods of taking and preparing samples of cement
UNI EN 413 (2011) Masonry cement - Part 1: Composition, specifications and conformity criteria
UNI EN 538 (1997) Clay Roofing Tiles for Discontinuous
Laying - Flexural Strength Test
UNI EN 539-1 (2006) Clay roofing tiles for discontinuous laying - Determination of physical characteristics - Part 1: Impermeability test
UNI EN 539-2 (2013) Clay roofing tiles for discontinuous laying - Determination of physical characteristics - Part 2: Test for frost resistance
UNI EN 1024 (2012) Clay roofing tiles for discontinuous laying - Determination of geometric
UNI EN 1304 (2013) Clay roofing tiles and fittings -
Product definitions and specifications
UNI 9460 (2008) Discontinuous Roofing - Practical
Instruction Code for the Design and
Execution of Clay and Cement Tile Roofing
UNI EN 14437 (2005) Determination of the uplift resistance of installed clay or concrete tiles for roofing - Roof system test method
UNI CEN/TS 15087 (2006) Determination of the uplift resistance of installed clay and concrete interlocking tiles for roofing - Test method for mechanical fasteners
FINAL (100% design) SECTION 07321/R Page 85
Paragraph 1.6 SAFETY PRECAUTIONS
Delete “D.L. 624 and D.L. 494” and replace with “D.Lgs. 09 Apr 2008, n.81”
Paragraph 2.1 CLAY ROOFING TILES
Products meeting the requirements of these specifications are manufactured by the following:
PICA
Strada Montefeltro, 83
Pesaro (PS)
Tel: 0721/440-1
Fax: 0721/201-370
COTTO TOSCANO
52043 Castiglion Fiorentino (AR)
Tel: 0575/680-131
Fax: 0575/657-455
AGRICOLA INDUSTRIALE DELLA FAELLA S.P.A.
Castelfranco di Sopra (AR)
Tel: 055/914-6063
Fax: 055/965-651
FORNACE (GRUPPO SILA)
Via Ghiarola Nuova, 120
Fiorano Modenese (MO)
Tel: 0536/83-0232
Fax: 0536/83-27764
Products of other manufacturers meeting the requirements of these
Specifications are also acceptable.
Add the following sentence at the end of Paragraph 2.1:
"Other manufacturers meeting the requirements of this specification are acceptable.”
Paragraph “2.4 ROOF INSULATION AND VAPOR BARRIER”
Delete the whole paragraph.
FINAL (100% design) SECTION 07600/R Page 86
SECTION 07600/R
FLASHING AND SHEET METAL
Paragraph 1.1
ITALIAN LAWS AND NORMS
realization of Article 1 of the Law 03 Aug the health and safety on the work place
UNI EN 13605 (2004) Copper and copper alloys - Copper profiles and profiled wire for electrical purposes.
UNI 4157 (1987) Bitumen for Roofing. Sampling and
Acceptance Limits.
UNI 9001-2 (1987) Wrought primary aluminum and aluminum alloys. Aluminum group. Al 99,5
(1050 a).
UNI 5649-1 (1988) Copper. Wrought coppers. Qualities, requirements and tests.
UNI EN 10142 (2002) Continuously hot-dip zinc coated low carbon steels strip and sheet for cold forming. Technical Delivery Conditions.
UNI EN 10130 (2000) Cold rolled low carbon steel flat products for cold forming. Technical
Delivery Conditions.
UNI EN 10051 (2000) Continuously hot-rolled uncoated plate, sheet and strip of non-alloy and alloy steels. Tolerances on dimensions and shape.
UNI EN 10152 (1994) Electrolytically zinc coated cold rolled steel flat products. Technical delivery conditions.
UNI EN 485-1 (2016) Aluminum and Aluminum Alloys - Sheet, Strip and Plate - Part 1: Technical
Conditions for inspection and delivery
FINAL (100% design) SECTION 07600/R Page 87
UNI EN 485-2 (2016) Aluminium and aluminium alloys -
Sheet, strip and plate - Part 2: Mechanical properties
UNI EN 485-3 (2005) Aluminium and aluminium alloys -
Sheet, strip and plate - Part 3: Tolerances on dimensions and form for hot-rolled products
UNI EN 485-4 (1996) Aluminium and aluminium alloys -
Sheet, strip and plate - Part 4: Tolerances on shape and dimensions for cold-rolled products
UNI EN 755-3 (2008) Aluminium and aluminium alloys -
Extruded rod/bar, tube and profiles - Part
3: Round bars, tolerances on dimensions and form
UNI EN 755-4 (2008) Aluminium and aluminium alloys -
4: Square bars, tolerances on dimensions and form
UNI EN 755-5 (2008) Aluminium and aluminium alloys -
5: Rectangular bars, tolerances on dimensions and form
UNI EN 988 (1998) Zinc and zinc alloys -
Specifications for rolled flat products for building
UNI EN 1172 (2012) Copper and copper alloys - Sheet and strip for building purposes
UNI EN 1173 (2008) Copper and copper alloys - Material condition designation
UNI EN 1412 (2017) Copper and copper alloys - European numbering system
UNI EN ISO 9453 (2014) Soft solder alloys - Chemical compositions and forms)
UNI EN 10051 (2011) Continuously hot-rolled strip and plate/sheet cut from wide strip of non-alloy and alloy steels - Tolerances on dimensions and shape
UNI EN 10088-1 (2014) Stainless steels - Part 1: List of stainless steels
UNI EN 10088-2 (2014) Stainless steels - Part 2: Technical delivery conditions for sheet/plate and strip of corrosion resisting steels for general purposes
UNI EN 10130 (2007) Cold rolled low carbon steel flat products for cold forming - Technical delivery conditions
FINAL (100% design) SECTION 07600/R Page 88
UNI EN 10143 (2006) Continuously hot-dip coated steel sheet and strip - Tolerances on dimensions
UNI EN 10152 (2017) Electrolytically zinc coated cold rolled steel flat products for cold forming
- Technical delivery conditions
UNI EN 10346 (2015) Continuously hot-dip coated steel flat products for cold forming - Technical
UNI EN 13707 (2013) Flexible sheets for waterproofing -
Reinforced bitumen sheets for roof waterproofing - Definitions and
UNI EN ISO 15614-2 (2006) Specification and qualification of welding procedures for metallic materials -
Welding procedure test - Part 4: Finishing welding of aluminium castings
Paragraph 2.2.1 Steel Sheet, Zinc Coated (Galvanized)
Delete “UNI EN 10142” and replace with “UNI EN 10346”
Paragraph 2.2.3 Aluminum Alloy Sheet and Plate
Delete “UNI 9001-2” and replace with “UNI EN 485-1, UNI EN 485-2, UNI EN 485-
3, UNI EN 485-4, form alloy, and temper appropriate for use”
Paragraph 2.2.5 Solder
Delete “50 percent pig lead and 50 percent pure block tin” and replace with
“UNI EN ISO 9453”
Paragraph 2.2.8 Copper
Add: UNI EN 1412, UNI EN 1172, UNI EN 1173, cold-rolled temper
FINAL (100% design) SECTION 07920/R Page 89
SECTION 07920/R
JOINT SEALANTS
UNI EN 26927 (1992) Building Construction - Jointing.
Products - Sealants-Vocabulary.
UNI EN ISO 6927 (2012) Buildings and civil engineering works - Sealants – Vocabulary
Paragraph 1.4.3 Definitions and Abbreviations
Delete “UNI EN 26927” and replace with “UNI EN ISO 6927”
Paragraph 2.2
Add the following sentence at the end of paragraph:
FINAL (100% design) SECTION 08110/R Page 90
Section 08110/R
STEEL DOORS AND STEEL FRAMES
EN 9774 (1990) Thermal Insulation Materials
Application Categories and Basic
Requirements - Guidelines for the
Harmonization of International Standards and Other Specifications.
ISO 834 (1975) Fire Resistance Tests – Elements of
Building Construction; Amendment 1:1979;
Amendment 2: 1980.
ISO 3008 (1976) Fire-Resistance Tests - Door and
Shutter Assemblies.
ISO 3009 (1976) Fire Resistance Tests – Glazed
Elements.
ISO 4898 (1984) Cellular Plastics – Specification for Rigid Materials Used in the Thermal
Insulation of Buildings.
ISO 5925/1 (1981) Fire Tests - Evaluation of
Performance of Smoke Control Door
Assemblies - Part 1: Ambient Temperature
UNI 7962 Buildings, Doors, Terminology and
Symbology.
EN 9774 (2004) Thermal Insulation for Building
Application - Guidelines for Selecting
Properties.
ISO 834 (2003) Fire Resistance Tests – Elements of
Building Construction.
ISO 3008 (2007) Fire-Resistance Tests - Door and
Shutter Assemblies.
ISO 3009 (2003) Fire Resistance Tests - Elements of
Building Construction – Glazed Elements.
ISO 4898 (2010) Rigid Cellular Plastics – Thermal
Insulation Products for Buildings -
Specifications.
ISO 5925-1 (2007) Fire Tests – Smoke-control Door and
Shutter Assemblies - Part 1: Ambient and
Medium Temperature Leakage Tests.
FINAL (100% design) SECTION 08110/R Page 91
ASTM E 90 (2001) Standard Test Method for Laboratory
Measurement of Airborne Sound Transmission
Loss of Building Partitions and Elements
UNI EN 12519 (2005) Windows and Pedestrian Doors.
Terminology.
delivery conditions.
ISO 16283-1 (2014) Acoustics -- Field measurement of sound insulation in buildings and of building elements Airborne sound.
Paragraph 1.2.1
Delete “blast resistant” and read the sentence as follows: “Submit door and frame locations, architectural door number, fire rating and indication of the construction details referring to the submitted shop drawings.”
Paragraph 1.2.4
Delete “blast resistant” and read the sentence as follows: “Structural calculations.”
Paragraph 1.2.5
Delete: “Resistance to blast loads”
Add “REI tests.”
Paragraph 1.3.2
Delete: “and/or blast resistant” and read the sentence as follows:
“Contractor shall coordinate selection of steel door and frame materials and products specified herein with door hardware to ensure that fire rated assemblies meet all U.S. and Italian related requirements.”
Paragraph 1.4.1
Paragraph 2.1.4
Paragraph 3.1.4:
Delete from title and sentence: “Blast resistant”
FINAL (100% design) SECTION 08120/R Page 92
SECTION 08120/R
ALUMINUM DOORS, FRAMES AND SIDELIGHTS
Paragraph 1.1 Applicable publications:
UNI EN 288-4 (1993) Specification and Qualification of
Welding Procedures for Metallic Materials
- Part 4: Welding Procedure Tests for the
Arc Welding of Aluminum and its Alloys.
UNI EN ISO 10077-1 (2002) Thermal Performance of Windows, Doors and Shutters - Calculation of Thermal
Transmittance - Simplified Method.
UNI 10680 (1997) Aluminum and Aluminum Alloys.
Aluminum Alloys Thermal Break Profiles.
Requirements and Test Methods.
UNI EN ISO 15614-2 (2006) Specification and Qualification of
Welding Procedures for Metallic Materials -
Welding Procedure Test - Part 2: Arc Welding of Aluminum and its Alloys
UNI EN ISO 10077-1 (2018) Thermal performance of windows, doors and shutters - Calculation of thermal transmittance - Part 1: General
UNU EN 14024 (2005) Metal profiles with thermal barrier
- Mechanical performance - Requirements, proof and tests for assessment
Paragraph 1.2.4 Design data:
Paragraph 1.2.5 Test Reports:
Paragraph 2.2.1 Doors, Frames and Accessories:
Delete the end of fourth sentence:
“in any case they shall resist to the blast.”
Subparagraph “c.”:
“UNI EN 288-4.” in first sentence and the whole second sentence.
FINAL (100% design) SECTION 08120/R Page 93
“UNI EN ISO 15614-2.”
Subparagraph “f.”:
Delete the whole paragraph
Paragraph 2.2.4 Provisions for Glazing:
Delete last sentence.
Paragraph 2.2.5 Anchors:
Delete second sentence.
Paragraph 2.4.1 Available Manufacturers:
NORMANT SECURITY GROUP
3224 Mobile Hwy
Montgomery, AL 36108
ATTN: Steve Scoggin
Tel: (334) 286-4246
Fax: (334) 286-4399
Email: steve-scoggin@normantind.com
SAELZER GMBH
Dietrich-Bonhoeffer-Str.1-3
D-35037 Marburg
ATTN: Frank Rummler
Tel: 49 (0) 6421/938-100
Fax: 49 (0) 6421/938-190
Email: rummler@saelzer.de
Or suelzer@saelzer.de
PENSHER SKYTECH LTD
Felling Works, William Street, Felling, Gateshead
Tyne & Wear NE 100JP – U.K.
Tel: 0044(0)1914380455
Fax: 0044(0)19114302328
Not Used
Paragraph 2.9 FABRICATION OF ALUMINUM FRAMES:
Delete second and third sentence.
mailto:suelzer@saelzer.de
FINAL (100% design) SECTION 08120/R Page 94
Paragraph 2.10.1 Sizes, Clearance and Edge Treatment:
Delete from first sentence: “and not less than 75 mm thick, and in any case they shall resist to the blast.”
FINAL (100% design) SECTION 08210/R Page 95
Section 08210/R
WOOD DOOR
ISO-140/III Laboratory Measurement of Airborne Sound
Insulation of Building Elements.
UNI 3252 (1987) General Conditions for Physical
Mechanical Tests.
UNI 7961 (1987) Buildings, Doors, Criteria for
Classification.
UNI 8200 (1981) Buildings, Interior Doors. Impact
UNI 8328 (1981) Buildings Heat Test for Interior
Doors.
UNI EN 950 (2000) Door Shutter. Impact Test.
UNI 4143 (2011) Tests on wood - Axial split test
UNI EN 204 (2002) Classification of thermoplastic wood adhesives for non-structural applications
UNI EN 205 (2006) Adhesives - Wood adhesives for non-structural applications - Determination of tensile shear strength of lap joints
UNI EN 1191 (2011) Windows and doors. Resistance to repeated opening and closing – Test method
UNI EN 1634-1 (2001) Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Fire resistance test for door and shutter assemblies and openable windows
UNI EN 15269-3 (2012) Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware. Fire resistance of hinged and pivoted timber door sets and openable timber framed windows
UNI ISO 8275 (1985) Door sets - Vertical load test
FINAL (100% design) SECTION 08520/R Page 96
Section 08520/R
ALUMINUM WINDOW
PREN 12365-1 (1996) Building Hardware – Gaskets and
Weather-stripping for Doors, Windows, Shutters, and Curtain Walls. Part 1:
Performance Requirements and
Classification.
UNI EN 1026 (2001) Windows and Doors. Air Permeability.
Test Method.
UNI EN 12211 (2001) Windows and Doors - Resistance to
Wind Load - Test Method.
UNI EN 1027 (2001) Windows and Doors. Water Tightness.
Test Method.
UNI EN 288-4 (1993) Specification and Qualification of
Welding Procedures for Metallic Materials -
Part 4: Welding Procedure Tests for the Arc
Welding of Aluminum and its Alloys.
UNI EN 573-1 (1996) Aluminum and Aluminum Alloys -
Chemical Composition and Form of Wrought
Products - Part 1: Numerical Designation
System.
UNI EN 107 (1983) Methods of Testing Windows.
Mechanical Tests.
ISO 6613 (1980) Windows and Door Height Windows -
Air Permeability Test.
UNI EN 107 (1980) Methods of testing windows -
Mechanical tests
UNI EN 573-1 (2005) Aluminum and aluminum alloys -
Chemical composition and form of wrought products - Part 1: Numerical designation system
UNI EN 755-1/9 (2008) Aluminum and aluminum alloys -
Extruded rod/bar, tube and profiles
UNI EN 1026 (2001) Windows and doors – Air permeability
- Test method
UNI EN 1027 (2001) Windows and doors – Water tightness
- Test method
FINAL (100% design) SECTION 08520/R Page 97
UNI EN 12020-1 (2008) Aluminum and aluminum alloys.
Extruded precision profiles in alloys EN
AW-6060 and EN AW-6063 – Technical conditions for inspection and delivery
UNI EN 12020-2 (2008) Aluminum and aluminum alloys.
Extruded precision profiles in alloys EN
AW-6060 and EN AW-6063 - Tolerances on dimensions and form
UNI EN 12207 (2000) (EC 1-2007) Windows and doors - Air permeability – Classification
UNI EN 12206-1 (2005) Paints and varnishes. Coating of aluminum and aluminum alloys for architectural purposes. Coatings prepared from coating powder
UNI EN 12208 (2000) (EC 1-2007) Windows and doors – Water tightness – Classification
UNI EN 12210 (2001) Windows and doors - Resistance to wind load – Classification
UNI EN 12211 (2001) Windows and doors - Resistance to wind load - Test method
UNI EN 12519 (2005) Windows and Pedestrian Doors –
Terminology
UNI EN ISO 15614-2 (2006) Specification and qualification of welding procedures for metallic materials -
Welding procedure test - Part 4: Finishing welding of aluminum castings
UNI 3952 (1998) Aluminum and Aluminum Alloy Frames in Construction. Norms for the Selection, Use and Testing of Materials.
UNI 7697 (2015) Safety criteria for glazing application
FINAL (100% design) SECTION 08800/R Page 98
Section 08800/R
GLAZING
UNI EN 572-2 (1996) Glass in Building - Basic Sode Lime
Silicate Glass Products. Part 2: Float
Glass.
ISO 11600 (1993) Building Construction - Sealants -
Classification and Requirements.
UNI EN ISO 12543-1-6 (2000) Glazing in Building Construction -
Laminated and Laminated Safety Glass
Definitions and Descriptions of
Components/Appearance.
UNI 7697 (2002) Safety Criteria for Glazing.
UNI 10593/1 (1996) Glass for Building Construction, Insulating Glass - Generalities and
Dimensional Tolerances.
UNI 10593/2 (1996) Glass for Building Construction, Insulating Glass - Tests of Aging, Measurement of Penetration of Water Vapor and Requirements.
UNI 10593/3 (1996) Glass for Building Construction, Insulating Glass - Initial Type of Tests for the Measurement of the Speed of the Loss of Gas from Insulated Glass Filled with Gas.
UNI 10593/4 (1996) Glass for Building Construction, Insulating Glass - Method of Tests for
Determining the Physical Properties of
Sealing the Edges.
UNI EN 572-2 (2012) Glass in Building - Basic Sode Lime
Silicate Glass Products. Part 2: Float
Glass
UNI EN 572-3 (2012) Glass in Building - Basic Soda Lime
Silicate Glass Products. Part 3: Polished
Wired Glass
UNI EN 1279-1 (2004) Glass in Building – Insulating glass units - Part 1: Generalities, dimensional tolerances and rules for the system description
FINAL (100% design) SECTION 08800/R Page 99
UNI EN 1279-2 (2004) Glass in building – Insulating glass units - Part 2: Long term test method and requirements for moisture
UNI EN 1279-3 (2004) Glass in building – Insulating glass units - Part 3: Long term test method and requirements for gas leakage rate and for gas concentration tolerances
UNI EN 1279-4 (2004) Glass in building – Insulating glass units - Part 4: Methods of test for the physical attributes of edge seals
UNI EN ISO 11600 (2011) Building construction – Jointing products - Classification and requirements for sealants
UNI EN ISO 12543-2 (2011) Glass in building – Laminated glass and laminated safety glass Laminated safety glass
UNI 7142 (1988) Flat Glass - Tempered Glass for
Buildings and Furnishings
EC 1-2015 UNI 7697 (2015) Flat Glass - Glass in Building
Construction - Safety Criteria
FINAL (100% design) SECTION 08800/R Page 100
Section 09100/R
METAL SUPPORT ASSEMBLIES
UNI EN 10142 (2002) Continuously Hot Dip Zinc Coated Low
Carbon Steel Sheet and Strip for Cold
Forming - Technical Delivery Conditions, Including Amendment 1
UNI EN 10218-1 (1995) Steel Wire and Wire Products -
General, Part 1: Test Methods.
UNI EN 10218-2 (1997) Steel Wire and Wire Products -
General - Part 2, Wire Dimensions and
Tolerances
UNI 7344 (1985) Cold formed steel sections -
Requirements and tolerances.
UNI EN 10162 (2006) Cold-Formed Steel Profiles -
Technical supply conditions – Dimensional tolerances and on the transversal section
UNI EN 10218-1 (2012) Steel Wire and Wire Products -
General - Part 1, Test Methods
UNI EN 10218-2 (2012) Steel Wire and Wire Products -
General - Part 2, Wire Dimensions and
Tolerances flat products for cold forming. Technical
UNI EN 14195 (2015) Metal framing components for gypsum board system. Definitions, requirements and test methods
FINAL (100% design) SECTION 09212/R Page 101
SECTION 09212/R
EXTERIOR STUCCO
Paragraph 1.1 Applicable publications:
UNI ENV 413-1 (1994) Masonry Cement - Part 1:
Specification.
UNI EN 459-1 (2002) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria.
UNI EN 459-2 (2002) Building Lime - Part 2: Test Methods.
UNI EN 932-1 (1998) Tests for General Properties of
Aggregates - Part 1: Methods for Sampling.
UNI EN 932-3 (1998) Tests of General Properties of
Aggregates - Part 3: Procedure and
Terminology for Simplified Petrographic
Description.
UNI EN 413-1 (2011) Masonry cement - Part 1: Composition, UNI EN 413-2 (2016) Masonry cement - Part 2: Test methods
UNI EN 459-1 (2015) Building lime - Part 1: Definitions, UNI EN 459-2 (2010) Building lime - Part 2: Test methods
UNI EN 459-3 (2015) Building lime - Part 3: Conformity evaluation
UNI EN 932-1 (1998) Tests for general properties of aggregates - Part 1: Methods for sampling
UNI EN 932-3 (2004) Tests for general properties of aggregates - Part 3: Procedure and terminology for simplified petrographic description
UNI EN 1008 (2003) Mixing water for concrete -
Specification for sampling, testing and assessing the suitability of water, including water recovered from processes in the concrete industry, as mixing water for concrete
Paragraph 2.1.8
Add the following sentence at the end of paragraph:
FINAL (100% design) SECTION 09212/R Page 102
Paragraph 2.1.9: special humidity proof (deumidificante) plaster
Furnish and install special humidity proof (deumidificante) plaster up to
85 cm from floor type Caparol cycle or equal approved as follows:
- Rough mortar (rinzaffo) type Capatec Vorspritz 030
- micro-porous plaster type Capatec Sanierputz Rapid, above 15 cm from floor, total thickness equal to existing, about 2 – 2.,5 cm
Item includes any other work to provide a job performed in a workmanlike manner. Contractor to ensure even surface, equivalent thickness with non-humidity proof plaster.
Paragraph 2.1.10: reinforced plaster (rasantatura armata)
Furnish and install reinforced plaster (rasantatura armata) type Caparol cycle or equal approved as follows:
- One coat of high penetration acrylic resin base colorless primer, to consolidate surfaces, conform to DIN 4108.3, type Acryl Konsilidierug
- First layer thin plaster, type Capatec Klebe und- Armierungsmasse 186
- embed fiber glass mesh, 4 x 4 mm, 160 gr / m² conform to DIN 53854, overlap 10 cm, type Capatec Gewebe 650, consider extra mesh for areas that require more resistance.
- Second layer thin plaster, cover embedded mesh, total 1st and 2nd layers of thin plaster thickness 3 - 4 mm, type Capatec Klebe und-
Armierungsmasse 186
- One coat colored primer type Putzground
- one thin layer of finishing siloxane thin colored plaster, grade 1,00 mm, thickness 1 – 1,5 mm.
Item includes the removal of metal corner guards (paraspogoli) and installation on all corners of pvc corner guards with mesh, type Capatec
Gewebe Eckschutz 656/02. The Contractor during execution of plastering cycle will level uneven surfaces in order to have a nice smooth and uniform wall surface without defects. Strictly follow installation instructions during plastering cycle including curing time.
Transportation of resulting material to authorized dump and any other work including accessories to provide a job performed in a workmanlike manner. Contractor to ensure even surface, equivalent thickness with humidity proof plaster.
Paragraph 2.1.11: finishing plaster (rasante di finitura)
Furnish and install finishing plaster (rasante di finitura) type Caparol cycle or equal approved as follows:
- One coat of high penetration acrylic resin base colorless primer, to consolidate surfaces, conform to DIN 4108.3, type Acryl Konsilidierug
- One coat colored primer type Putzground
- One thin layer of finishing siloxane thin colored plaster, , grade 1,00 mm, thickness 1 – 1,5 mm.
FINAL (100% design) SECTION 09212/R Page 103
Item includes the removal of rusted metal corner guards (paraspigoli) and installation of pvc corner guards with mesh if necessary, type Capatec
Gewebe Eckschutz 656/02. Also the contractor during execution of plastering cycle will level uneven surfaces in order to have a nice smooth and uniform wall surface without defects. Strictly follow installation instructions during plastering cycle including curing time.
Transportation of resulting material to authorized dump and any other work including accessories provide a job performed in a workmanlike manner.
FINAL (100% design) SECTION 09220/R Page 104
Section 09220/R
INTERIOR PLASTER
UNI ENV 413-1 (1994) Masonry Cement - Part 1:
Specification
UNI EN 459-1 (2002) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria
UNI EN 459-2 (2002) Building Lime - Part 2: Test Methods
Description
UNI EN 413-1 (2011) Masonry Cement - Part 1:
Composition, specification and conformity criteria
UNI EN 413-2 (2005) Masonry Cement - Part 2: Test methods
UNI EN 459-1 (2015) Building Lime - Part 1:
Definitions, Specifications and Conformity
Criteria
UNI EN 459-2 (2010) Building Lime - Part 2: Test Methods
UNI EN 932-3 (2004) Tests of General Properties of
UNI EN 1008 (2003) Mixing Water for Concrete -
Specification for Sampling, Testing and
Assessing the suitability of Water, ..., as
Mixing Water for Concrete
Paragraph 2.11
Add at the end the following sentence: "Other manufacturers meeting the requirements of this specification are acceptable.”
FINAL (100% design) SECTION 09250/R Page 105
SECTION 09250/R
GYPSUM AND CEMENT BOARD
UNI 5371 (1984) Gypsum Rock for Manufacture of
Binders - Classification, Requirements and
Tests.
UNI EN 1363-1 (2001) Fire Resistance Tests – General
UNI EN 932-1 (1998) Tests for General Properties of
Aggregates. Part 1: Methods for Sampling.
Aggregates. Part 3: Procedure and
Description.
UNI EN 520 (2009) Gypsum Plasterboards - Definition, requirements and test methods
UNI 11424 (2015) Gypsum Plasterboards - Non-
Loadbering Plasterboard System on Metal
Frames - Installations
UNI EN 13501-1 (2009) Fire classifications of constructions products and building elements. Classification using test data from reaction to fire tests
UNI EN 13279-1 (2008) Gypsum binder and gypsum plastera.
Definitions and requirements
UNI EN 13963 (2014) Jointing materials for gypsum plasterboards. Definitions, requirements and test method
UNI EN 14566 (2009) Mechanical fasteners for gypsum plasterboard system. Definitions, requirements and test method
UNI EN 1627 (2011) Pedestrian doorsets, windows, curtain walling, grilles and shutters. Burglar resistance. Requirements and classification
Prevention
FINAL (100% design) SECTION 09250/R Page 106 activities subject to control by the
National Fire Department stabilizing resistance performance
Paragraph 2.1:
FINAL (100% design) SECTION 09310/R Page 107
Section 09310/R
CERAMIC AND STONE COMPOSITE TILE
UNI EN 87 (1992) Ceramic Floor and Wall Tiles -
Definitions, Classification, Characteristics and Marking
UNI EN ISO 10545-2 (2000) Ceramic tiles - Determination of dimensions and surface quality
UNI EN ISO 10545-3 (2000) Ceramic tiles - Determination of water absorption, apparent porosity, apparent relative density and bulk density
UNI EN 101 (1992) Ceramic Tiles. Determination of
Scratch Hardness of Surface According to
Mohs’ Scale.
UNI EN ISO 10545-11 (2000) Ceramic tiles - Determination of crazing resistance for glazed tiles
UNI EN ISO 10545-14 (2000) Ceramic tiles - Determination of resistance to stains
UNI EN ISO 10545-7 (2000) Ceramic tiles - Determination of resistance to surface abrasion for glazed tiles
UNI EN ISO 10545-12 (2000) Ceramic tiles - Determination of frost resistance
Regio Decreto No. 2231 (16.11.1939) Norms for Lime Acceptance.
UNI 8520-22 (1999) Aggregates for use in concrete -
Determinaton of potential reactivity of alcali in aggregates
UNI EN 14411 (2012) Ceramic tiles - Definition, classification, characteristics, assessment and verification of constancy of performance and marking
UNI EN 197-1 (2011) Cement - Composition, Specifications and Conformity Criteria - Part 1: Common
Cements
UNI EN 932-3 (2004) Tests for General Properties of
UNI EN 1015-11 (2007) Methods of test for mortar for masonry - Part 11: Determination of
FINAL (100% design) SECTION 09310/R Page 108 flexural and compressive strength of hardened mortar
UNI EN 12004 (2012) Adhesives for tiles - Requirements, evaluation of conformity, classification and designation
UNI EN 459-1 (2015) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria
UNI ENV 459-2 (2010) Building lime - Part 2: Test methods
UNI EN ISO 10545-1 (2014) Ceramic Tiles. Sampling and Basics for acceptance
UNI EN 13888 (2009) Grout for tiles - Requirements, evaluation of conformity, classification and designation
Paragraph 2.2:
FINAL (100% design) SECTION 09510/R Page 109
Section 09510/R
ACOUSTICAL CEILINGS
UNI EN 10113/1 (1994) Hot Rolled Products in Weldable Fine
Grain Structural Steels, Part 1, General
Delivery Conditions.
UNI EN 10113/2 (1994) Hot Rolled Products in Weldable Fine
Grain Structural Steels, Part 2, Delivery
Conditions for Normalized /Normalized
Rolled Steels.
UNI EN 10113/3 (1994) Hot Rolled Products in Weldable Fine
Grain Structural Steels, Part 3, Delivery Conditions for Thermomechanical
Rolled Steels.
UNI EN 10215 (1996) Continuously Hot-Dip Aluminum, Zinc
Coated Steel Strip and Sheet - Technical delivery Conditions.
UNI EN 10218-1 (1995) Steel Wire and Wire Products -
General, Part 1: Test Methods.
UNI EN 10244-2 (2001) Steel Wire and Wire Products - Non-ferrous Metallic Coatings on Steel Wire, Part 2: Zinc or Zinc Alloy coatings.
UNI EN 20140-9 (1998) Acoustics - Measurement of Sound
Insulation in Building and of Building
Elements - Part 9: Laboratory Measurement of Room-to-Room Airborne Sound
Insulation of a Suspended Ceiling with a
Plenum Above It.
UNI EN ISO 717-1 (1997) Acoustics - Rating of Sound
Insulation in Buildings, Part 1, Airborne
Sound Insulation.
UNI EN ISO 26927 (1992) Building Construction - Jointing
Products.
UNI 5958 (1985) Products of Mineral Fiber for
Thermal and Acoustical Insulation. Terms and Definitions.
UNI EN 10025-1 (2005) Hot rolled products of structural steels - Part 1: General technical delivery conditions
UNI EN 10025-3 (2005) Hot rolled products of structural steels - Part 3: Technical delivery
FINAL (100% design) SECTION 09510/R Page 110 conditions for normalized/normalized rolled weldable fine grain structural steels
UNI EN 10025-4 (2005) Hot rolled products of structural steels - Part 4: Technical delivery conditions for thermomechanical rolled weldable fine grain structural steels
EC 1-2015 UNI EN 10218-1 (2015) Steel Wire and Wire Products -
General, Part 1: Test Methods
EN 10244-2 (2009) Steel Wire and Wire Products - Non-ferrous Metallic Coatings on Steel Wire, Part 2: Zinc or Zinc Alloy Coatings
UNI EN ISO 10140-3 (2015) Acoustics – Laboratory measurement of sound insulation of building elements -
Part 3: Measurement of impact sound insulation
EC 1-2009 UNI EN ISO 10848-2 (2006) Acoustics – Laboratory measurement of the flanking transmission of airborne and impact sound between adjoining rooms -
Part 2: Application to light elements when the junction has a small influence
EC 1-2016 UNI EN 10346 (2015) Continuously hot-dip coated steel
UNI EN ISO 717-1 (2013) Acoustics - Rating of Sound
Insulation in Buildings, Airborne Sound
Insulation
UNI EN 16487 (2015) Acoustics - Test code for suspended ceilings - Sound absorption
UNI EN 16703 (2015) Acoustics - Test code for drywall systems of plasterboard with steel studs -
Airborne sound insulation
UNI EN ISO 6927 (2012) Buildings and civil engineering works - Sealant
Paragraph 3.1:
Replace: “UNI EN 10113/1” with “UNI EN 10025/1”; “UNI EN 10113/2” with “UNI
EN 10025/3”; “UNI EN 10113/3” with “UNI EN 10025/4”.
Paragraph 2.2
FINAL (100% design) SECTION 09510/R Page 111
FINAL (100% design) SECTION 09900/R Page 112
SECTION 09900/R
PAINTS AND COATINGS
UNI ISO 6504-1 (1990) Paints and Varnishes - Determination of Hiding Power - Part 1: Kubelka-Munk
Method for White and Light-Colored Paints.
UNI EN ISO 3251 (1998) Paints and Varnishes - Determination of Non-Volatile Matter of Paints, Varnishes and Binders for Paints and Varnishes.
UNI EN ISO 6504-1 (2006) Paints and Varnishes - Determination of Hiding Power - Kubelka-Munk Method for
White and Light-Colored Paints.
UNI EN ISO 3251 (2005) Paints, Varnishes and Plastic -
Determination of Non-Volatile Matter
Content.
UNI 8760 (1985) Systems for continuously applied plastic coatings - Criteria for Technical
Information
UNI EN ISO 17491-3 (2008) Protective clothing – Test methods for clothing providing protection against chemicals - Part 3: Determination of resistance to penetration by a jet of liquid
(jet test)
D.Lgs. 05 Feb 1997, n.22 Realization of CEE Requirements for
Disposal of Hazardous Waste Material and
Packaging of Waste Material
D.L. 09 Apr 2008, n.81 Unified Text, Safety Regulations;
classification system
FINAL (100% design) SECTION 10201/R Page 113
Section 10201/R
METAL WALL AND DOOR LOUVERS
UNI EN 10142 (2002) Continuously hot-dip zinc coated low carbon steels strip and sheet for cold forming - Technical delivery conditions.
UNI EN 10143 (1994) Continuously hot-dip metal coated steel sheet and strip. Tolerances on dimensions and shape.
UNI EN 10143 (2006) Continuously hot-dip coated steel sheet and strip - Tolerances on dimensions
UNI EN 10088-2 (2014) Stainless steels - Part 2: Technical delivery conditions for sheet/plate and strip of corrosion resisting steels for general purposes
EN ISO 15614-2 (2005) Specification and qualification of welding procedures for metallic materials - Welding procedure test
- Part 2: Arc welding of Aluminum and its alloys
UNI EN 485-1 (2009) Aluminum and Aluminum alloys -
Sheet, strip and plate - Part 1: Technical conditions for inspection and delivery
FINAL (100% design) SECTION 10400/R Page 114
Section 10400/R
IDENTIFICATION DEVICES
UNI EN 755/3-9 (1997-2002) Aluminum and aluminum alloys -
Extruded rod/bar, tube and profiles.
UNI EN 755-2 (2013) Aluminum and Aluminum alloys -
2: Mechanical properties
ISO 3522 (2007) Aluminum and Aluminum alloys -
Castings - Chemical composition and mechanical properties
ISO 8992 (2005) Fasteners - General Requirements for
Bolts, Screws, Studs and Nuts
FINAL (100% design) SECTION 10800/R Page 115
Section 10800/R
TOILET AND BATH ACCESSORIES
UNI 10088-1 (1997) Stainless steels. List of stainless steels
UNI EN 1036-1 (2008) Glass in building - Mirrors from silver-coated float glass for internal use
- Part 1: Definitions, requirements and test methods
FINAL (100% design) SECTION 12490/R Page 116
Section 12490/R
BLINDS
UNI 10818 (1999) Windows, doors, blinds and shutters
-Guidelines for installation
Add
UNI 10818 (2015) Windows, doors, blinds and shutters
-Guidelines for installation
FINAL (100% design) SECTION 13855/R Page 117
SECTION 13855/R
ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM
PART 1 - GENERAL
1.1 REFERENCES
THE PUBLICATIONS LISTED BELOW FORM A PART OF THIS SPECIFICATION TO THE EXTENT
REFERENCED. THE PUBLICATIONS ARE REFERRED TO IN THE TEXT BY THE BASIC
DESIGNATION ONLY.
ASME INTERNATIONAL (ASME)
ASME A17.1/CSA B44 (2010) Safety Code for Elevators and
Escalators
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41.1 (2002; R 2008) Guide on the Surges
Environment in Low-Voltage (1000 V and
Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on
Characterization of Surges in Low-Voltage
(1000 V and Less) AC Power Circuits
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2012) Life Safety Code
NFPA 72 (2010; TIA 10-4) National Fire Alarm and
Signaling Code
NFPA 90A (2009; Errata 09-1) Standard for the
Installation of Air-Conditioning and
Ventilating Systems
UNDERWRITERS LABORATORIES (UL)
UL 1971 (2002; Reprint Oct 2008) Signaling Devices for the Hearing Impaired
UL 228 (2006; Reprint Nov 2008) Door Closers-
Holders, With or Without Integral Smoke
Detectors
UL 268 (2009) Smoke Detectors for Fire Alarm
Systems
UL 464 (2009; Reprint Jan 2011) Standard for
Audible Signal Appliances http://www.approvalguide.com/
FINAL (100% design) SECTION 13855/R Page 118
UL 864 (2003; Reprint Jan 20110) Standard for
Control Units and Accessories for Fire
Alarm Systems
UL Electrical Construction (2009) Electrical Construction Equipment
Directory
UL Fire Prot Dir (2011) Fire Protection Equipment Directory
ITALIAN ELECTRO TECHNICAL COMMISSION (CEI)
CEI EN 61386-21 (CEI 23-81) (2011) Conduits and Accessories for
Electrical Installation - Part 21: Specific
Requirements for Rigid Conduits systems and
Accessories.
CEI 64-8 (2012; V1-2013; V2-2015; V3-2017; V4-2017)
Electrical Systems with Rated Voltage Not
Greater Than 1000V A.C. and 1500V D.C.
CEI EN 60529 (1997; V1-2000; A2-2014; Errata Corrige-
2017) Degrees of Protection Provided By
Enclosures (IP Code).
ITALIAN NATIONAL UNIFICATION (UNI)
UNI 9795 (2013) Fixed Automatic Fire Detection and alarm Systems – Design, Installation and maintenance.
ITALIAN/EUROPEAN HARMONIZATION STANDARDS (UNI EN) (UNI ENV) (UNI EN ISO)
UNI EN ISO 9001 (2015) Quality Management Systems –
1.2 RELATED REQUIREMENTS
Section 16050, "Basic Electrical Materials and Methods," applies to this section, with the additions and modifications specified herein.
1.5.3 Record Drawing Software
Replace the whole paragraph with the following:
Furnish one set of CD-ROMs or DVDs containing CAD based drawings in DWG format of as-built drawings and schematics.
2.2.2 System Operation
The fire alarm system shall comply with UNI 9795. The system shall be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to NFPA 72. The system shall have an interconnected riser loop having Class A supervision that shall not be located in the same room or shaft. The return portion of the loop shall be remote from the supply portion of the loop. Where three or more stairs are provided for egress from floors above grade, a single impairment cannot adversely affect more than 1/2 of any floor. The system shall operate in the alarm mode upon actuation of any alarm initiating device. The system shall remain in the alarm mode until initiating device(s) are reset and the fire alarm control
FINAL (100% design) SECTION 13855/R Page 119 panel is manually reset and restored to normal. The system shall provide the following functions and operating features:
a. The FACP and fire alarm control units, if used, shall provide power, annunciation, supervision, and control for the system.
b. Provide Class A signaling line circuits for each floor.
c. Provide Class B notification appliance circuits. The visual alarm notification appliances shall have the flash rates synchronized if installed in the same area of view. Class A type signalling circuit, shared by initiating device and notification appliances, is acceptable;
d. Provide electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control panel.
e. Provide an audible and visual trouble signal to activate upon a single break or open condition, or ground fault. The trouble signal shall also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory panel modules. Provide a trouble alarm silence feature which shall silence the audible trouble signal, without affecting the visual indicator. After the system returns to normal operating conditions, the trouble signal shall again sound until the trouble is acknowledged. A smoke sensor in the process of being verified for the actual presence of smoke shall not initiate a trouble condition.
f. Provide a notification appliance silencing switch which, when activated, will silence the audible signal appliance, but will not affect the visual alarm indicator, the liquid crystal display, or the automatic notification of the base security office. This switch shall be overridden upon activation of a subsequent alarm.
g. Provide alarm verification capability for smoke sensors. Alarm verification shall initially be set for 30 seconds.
h. Provide program capability via switches in a locked portion of the
FACP to bypass the automatic notification appliance circuits, fire reporting system air handler shutdown smoke control operation elevator recall door release features. Operation of this programming shall indicate this action on the FACP display.
i. Alarm, supervisory, and/or trouble signals shall be automatically transmitted to the base security office, (Fire Department).
j. Alarm functions shall override trouble or supervisory functions.
Supervisory functions shall override trouble functions.
k. The system shall be capable of being programmed from the panel’s keyboard. Programmed information shall be stored in non-volatile memory.
l. The system shall be capable of operating, supervising, and/or monitoring both addressable and non-addressable alarm and supervisory devices.
FINAL (100% design) SECTION 13855/R Page 120
m. There shall be no limit, other than maximum system capacity, as to the number of addressable devices which may be in alarm simultaneously.
n. Where the fire alarm system is responsible for initiating an action in another emergency control device or system, such as an HVAC system a smoke control system an elevator system, the addressable fire alarm relay shall be within 915 mm of the emergency control device.
o. An alarm signal shall automatically initiate the following functions:
(1) Transmission of an alarm signal to base security office.
(2) Visual indication of the device operated on the fire alarm control panel (FACP), and on the annunciator. Indication on the annunciator shall be by floor, zone or circuit, and type of device.
(3) Continuous actuation of all alarm notification appliances, except those in stairs or in elevator cabs.
(4) Release of doors held open by electromagnetic devices.
(5) Operation of the smoke control system.
(6) Operation of a smoke sensor in an elevator lobby or other location associated with the automatic recall of elevators, shall recall the elevators in addition to other requirements of this paragraph.
(7) Operation of a duct smoke sensor shall shut down the appropriate air handler in accordance with NFPA 90A in addition to other requirements of this paragraph.
p. A supervisory signal shall automatically initiate the following functions:
(1) Visual indication of the device operated on the FACP, and on the annunciator, and sound the audible alarm at the respective panel.
(2) Transmission of a supervisory signal to base security office.
q. A trouble condition shall automatically initiate the following functions:
(1) Visual indication of the system trouble on the FACP, and on the annunciator, and sound the audible alarm at the respective panel.
(2) Transmission of a trouble signal to base security office.
r. The maximum permissible elapsed time between the actuation of an initiating device and its indication at the FACP shall be 15 seconds.
s. The maximum elapsed time between the occurrence of the trouble condition and its indication at the FACP shall not exceed 200 seconds.
2.2.8.2 Capacity
FINAL (100% design) SECTION 13855/R Page 121
Replace “60 hours” with “48 hours”.
2.2.9.3 Alarm Wiring
Signaling line circuits and initiating device circuit field wiring shall be copper, 1 mmq (No. 18 AWG) size conductors at a minimum. Notification appliance circuit conductors, that contain audible alarm devices, other than speakers, shall be solid copper 1.50 mmq (No. 14 AWG) size conductors at a minimum. Speaker circuits shall be copper 1.50 mmq (No. 16 AWG) size conductors at a minimum. Wire size shall be sufficient to prevent voltage drop problems. Circuits operating at 24 VDC shall not operate at less than
21.6 volts. Circuits operating at any other voltage shall not have a voltage drop exceeding 10 percent of nominal voltage. Power wiring, operating at