About this file

This document provides details for a draft request for proposal for a multiple award construction contract in Italy. The scope of work includes design-build construction services for various repair, renovation, and minor construction projects at Aviano Air Base, Italy across multiple trades. Services may include grading, utilities, painting, roofing, building renovation, new construction, HVAC, fire suppression systems, fuel systems, electrical work, and asbestos, lead, and petroleum abatement. The contract will be a firm-fixed-price IDIQ awarded using a price-past performance tradeoff. The minimum guarantee is $2,500 USD with a maximum of $96 million total among all awards. The minimum task order is $2,500 and maximum is $7 million. Interested parties must submit any comments on the draft attachments by April 19, 2019. The solicitation is expected to be released in May 2019 through FBO.

Attachment 10 ASHE 18-1025 Technical Specifications (Seed Project ) Part 6 Part 3

View the file

Other files for this federal contract opportunity

Other files attached to Multiple Award Construction Contract (MACC) Italy, newest first.
File Type Posted
MACC Questions and Answers 11122019.pdf PDF
Attachment 12 ASHE 18-1025 CCEB (Seed project) REV 01.xlsx XLSX spreadsheet
Attachment 2 Section M REV 03.pdf PDF
29UOI0~1.PDF PDF
ATTACH~1.PDF PDF
FRLEQ0~1.PDF PDF
ATTACH~4.PDF PDF
83BLD0~1.PDF PDF
Attachment_2_Section_M_REV_02.pdf PDF
Attachment_3_CEN_-MACC_SOW_v3_REV_01.pdf PDF
ATTACH~1.DOC DOC document
ATTACH~2.DOC DOC document
ANNEX_E_-_ELECTRICAL_Part6.pdf PDF
ANNEX_E_-_ELECTRICAL_Part3.pdf PDF
ANNEX_E_-_ELECTRICAL_Part13.pdf PDF
ANNEX_S_-_STRUCTURAL_Part7.pdf PDF
ANNEX_E_-_ELECTRICAL_Part12.pdf PDF
ANNEX_S_-_STRUCTURAL_Part9.pdf PDF
ANNEX_S_-_STRUCTURAL_Part12.pdf PDF
ASHE_18-1025_Design_Analysis_(Seed_project).pdf PDF
ANNEX_A-D_-_MECHANICAL_Part1.pdf PDF
ANNEX_S_-_STRUCTURAL_Part5.pdf PDF
ANNEX_S_-_STRUCTURAL_Part10.pdf PDF
ANNEX_A-D_-_MECHANICAL_Part3.pdf PDF
ANNEX_S_-_STRUCTURAL_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part2_Part3.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part15_Part3.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part11.pdf PDF
Attachment_10_ASHE_18-1025_TS(Seed_project)_Part6_Part8.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part3.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part16_Part3.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part2_Part4.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part10_Part1.pdf PDF
Attachment_10_ASHE_18-1025_TS__Part6_Part5_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part1_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part17.pdf PDF
Attachment_13_Physical_Data.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part6.pdf PDF
Attachment_6_Experience_Overview_Sheet.pdf PDF
Attachment_5_Past_Performance_Questionnaire_(PPQ).pdf PDF
Attachment_1_Section_L.pdf PDF
Solicitation_-_FA568219RA001.pdf PDF
Attachment_3_CEN_-MACC_SOW_v3.pdf PDF
Questions_and_Answers_draft_RFP_FA568219RA0001_May_03_2019.pdf PDF
(draft)_Attachment_2_Section_M_20_March.pdf PDF
(draft)_Attachment_11_Construction_Cost_Estimate_Breakdown.xls XLS spreadsheet
(draft)_Attachment_4_Past_Performance_Information_(PPI).pdf PDF
(draft)_Attachment_6_Experience_Overview_Sheet.pdf PDF
(draft)_Attachment_9_Client_Authorization_Letter.pdf PDF
(draft)_Attachment_1_Section_L__20_March.pdf PDF
Show all 50

Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D is cl ai m er

: T hi s do cu m en ta tio n is n ot in te nd ed a s a su bs tit ut e fo r a nd is n ot to b e us ed fo r d et er m in in g su ita bi lit y or re lia bi lit y of th es e pr od uc ts fo r s pe ci fic u se r a pp lic at io ns

Jun 13, 2018

Product data sheet Characteristics

OVA38716

Exiway One - emergency light block- self-diagnosis- non-maintained- 2 h - 400 lm

Main Range Exiway Product name Exiway One Product or component type Emergency light fitting Device application Lighting Function Self-test Supply Non-maintained Number of batteries 1 x 4.8 V 4 Ah Ni-Cd (Nickel-Cadmium) battery Colour White Light source LED : 24 W Light source colour White Cover type Transparent Wiring device additional information Can be inhibited with rest mode via Teleur range of remote controls

Complementary Range compatibility Remote control [Ue] rated operational voltage 220...230 V at 50 Hz AC/DC Power consumption in VA Non-maintained : 5.6 VA Power consumption in W Non-maintained : 1.3 W Current consumption 24 mA Electrical insulation class Class II Autonomy 2 h Charging time 12 h Luminous flux Emergency condition : 400 lm Type of glass Fresnel glass Material Housing : plastic

Cover : plastic Device mounting Surface ceiling

Surface wall

Hanging ceiling Flush false ceiling Electrified track Flush wall

Height 146 mm Width 300 mm Depth 62 mm

Environment IP degree of protection IP65 IK degree of protection IK07 Ambient air temperature for operation 0...40 °C Fire resistance 850 °C Product certifications Aenor

IMQ

ENEC

Standards IEC 60695-2-10

EN/IEC 60598-2-22

Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1101 - Schneider Electric declaration of conformity

Schneider Electric declaration of conformity

REACh Reference contains SVHC above the threshold - Go to CaP for more details

Go to CaP for more details http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=export&pid=267689354&lang=en-us http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=check&pid=267689354&lang=en-us

CRISTAL WALL

TECHNICAL SHEET

LED emergency luminaire

Luminaire description

• CRISTAL WALL 24W 2H NOT MAINTAINED IP65

ENERGY TEST HF HIGH FLUX

Technical characteristics

• Function: Energy Test (Self-contained with self-diagnosis)

• Duration: 2h

• Type: N/M (Non Maintained)

• Medium flux in emergency: 1000lm

• Minimum flux in emergency (according to EN 60598-2-22):

963lm

• Battery: Ni-Cd 6V 5Ah

• Battery type: Nickel Cadmium

• Recharge time: 24h

• Power supply: 230Vac 50-60Hz

• Insulation class: II

• IP protection degree: IP65

• Working temperature: 0°C to +40°C

• Colour: Grey

• Compliant to European standards: EN 60598-1, EN 60598-

2-22, EN 61347-1, EN 61347-2-7, EN 61347-2-13, EN

62031, EN 62384

• Photobiological safety exempt group according to EN 62471

• Compliant to RoHS2 2011/65/UE

• Glow wire 850 °C

• Installation: wall, wall recessed box*, drywall recessed* (* with accessory)

• 5 year warranty (please read the Warranty terms)

Light source characteristics

• Type: LED

• Lamps: 40 LED

• Color temperature: 6000K

IP65

LINERGY Srl - Via A. De Gasperi, 9 - 63075 Acquaviva Picena (AP) - ITALY - Tel. +39 0735 5974 - Fax +39 0735 597474 - www.linergy.it - info@linergy.it

An UNI EN ISO 9001 certified company

Subject to change without notice.2018-A

Code CW24N20EGRT-HH Short code CW1315

Page 1 / 1

D is cl ai m er

: T hi s do cu m en ta tio n is n ot in te nd ed a s a su bs tit ut e fo r a nd is n ot to b e us ed fo r d et er m in in g su ita bi lit y or re lia bi lit y of th es e pr od uc ts fo r s pe ci fic u se r a pp lic at io ns

Jun 13, 2018

Product data sheet Characteristics

OVA38466E

Astro Guida - emergency exit sign - self-diagnosis

- maintained - 1 h

Main Range of product Astro Guida Range Exiway Product name Astro Guida Product or component type Emergency exit sign Function Self-test Supply Maintained Provided equipment 5 pictogram stickers

Bracket flag installation Wiring device additional information 5 pictogram stickers included

Brackets for flag installation included Can be inhibited with rest mode via Teleur range of remote controls

Complementary Range compatibility Remote control [Ue] rated operational voltage 230 V at 50 Hz Power consumption in VA 10 VA Electrical insulation class Class II Battery capacity 0.6 Ah 4.8 V Ni-Cd (Nickel-Cadmium) Autonomy 1 h Charging time 12 h Bulb type Cold cathode light 40000 h Visibility distance 24 m Device mounting Surface ceiling

Surface wall Hanging ceiling Electrified track Flag type bracket wall

Height 213 mm Width 261 mm

Depth 35 mm Product weight 0.76 kg

Environment IP degree of protection IP42 IK degree of protection IK06 Ambient air temperature for operation 0...40 °C Fire resistance 850 °C Standards EN 1838

EN 60598-2-22

IEC 50-11

IEC 695-2-1

EN 60695-2-10

Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1101 - Schneider Electric declaration of conformity

Schneider Electric declaration of conformity

REACh Reference contains SVHC above the threshold - Go to CaP for more details

Go to CaP for more details

Contractual warranty Warranty period 18 months http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=export&pid=65949702&lang=en-us http://www.reach.schneider-electric.com/DistantRequestDispatcher.aspx?action=check&pid=65949702&lang=en-us

E1ZNT

www.tele-online.com

Timers - Emergency light tester

ENYA series Timer for automatic test of emergency lights Integrated test key 1 change over contact Width 17.5mm Installation design

Technical data

1. Functions

Ws Single shot leading edge with control contact

2. Time ranges Time range reversible between

10min, 30min, 60min, 90min, 2h and 3h

3. Indicators Green LED U/t ON: indication of supply voltage Green LED U/t flashes: indication of time period t Green LED U/t flashes fast: abort of time period t Yellow LED ON/OFF: indication of relay output

4. Mechanical design Self-extinguishing plastic housing, IP rating IP 40 Mounted on DIN-rail TS 35 according to EN 60715 Mounting position: any Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 Tightening torque: max. 1Nm Terminal capacity:

1 x 0.5 to 2.5mm² with/without multicore cable end 1 x 4mm² without multicore cable end 2 x 0.5 to 1.5mm² with/without multicore cable end 2 x 2.5mm² flexible without multicore cable end

5. Input circuit Supply voltage: 230V AC Terminals: L-N Tolerance: -15% to +10% Rated frequency: 48 to 63Hz Rated consumption: 2VA (1.0W) Duty cycle: 100% Reset time: 500ms Ripple and noise at DC: - Drop out voltage: >30% of supply voltage Overvoltage category: III (in accordance with IEC 60664-1) Rated surge voltage: 4kV

6. Output circuit 1 change over contact Normally open contact Terminals: L-18 Rated voltage: 250V AC Switching capacity: 1250VA (5A / 250V AC)

Normally closed contact Terminals: L-16 Rated voltage: 250V AC Switching capacity: 2500VA (10A / 250V AC) If the distance between the devices is less than 5mm!

Switching capacity: 4000VA (16A / 250V AC) If the distance between the devices is greater than 5mm!

Start-up peak (20ms): 80A

Mechanical life: 30 x 106 operations Electrical life:

Resistive load: 105 operations at 16A 250V Lamp load: 80.000 operations at 1000W 250V

7. Accuracy Base accuracy: ±5% Adjustment accuracy: - Repetition accuracy: <2% Voltage influence: - Temperature influence: ≤1%

8. Ambient conditions Ambient temperature: -25 to +55°C Storage temperature -25 to +70°C Transport temperature: -25 to +70°C Relative humidity: 15% to 85%

(in accordance with IEC 60721-3-3 class 3K3) Pollution degree: 2, if built in 3

(in accordance with IEC 60664-1)

E1ZNT

www.tele-online.com

Connections Direct connection of emergency lights (I < 16A)

L N

PE

18 N

L

16 18

L

Emergency lights with integrated recharchable power cells

Switching emergency lights with contactor (I > 16A)

L N

PE

18 N

L

16 18

L

Emergency lights with integrated recharchable power cells

Functions Single shot leading edge with testkey (Ws) The supply voltage U must be constantly to the device (green LED U/t illuminated). Pressing the integrated test key forces the output relay R to switch into on-position (yellow LED illuminated), so the emergency ligths are disconnected from the mains and the set interval t begins (green LED U/t flashes). After the interval t has expired (green LED U/t illuminated), the output relay R switches into off-position (yellow LED not illuminated) and the emergency lights are reconnected to the mains.

During the interval, the test key can be operated any number of times.

Prolonged pressure on the test key (>2s) aborts the running test interval (green LED U/t flashes fast) and a further cycle can be started.

LED U/t

R Testkey

U t >2s

Dimensions

17,5mm 60mm m m

44mm5mm m m

RELEASE 2009/07

Subject to alterations and errors

Ordering information Types Functions Control contact Supply voltage Part. No.

E1ZNT 230V Ws Integrated test key 230V AC 110500

SCHEDULE OF WORK ITEMS

ANNEX 1 : DALI LIGHTING SYSTEM

NOTE

Data sheets shown specific products made by specific manufacturers: it’s not a prescription. The Contractor has the faculty to select different products having the equivalent features and performances, made by different manufacturers.

RENOVATE/EXPAND FAC. 939 ASHE18-1025

FINAL (100% design) SCHEDULE OF WORK ITEMS - ANNEX 1

1 Helvar | Data is subject to change without notice. www.helvar.com

Installation

ETHERNET

AC

DALI

DIGIDIM Router (905)

The 905 DIGIDIM Router uses an Ethernet connection (10/100 Mb/s) to control a local DALI network.

Basic functionality is available out of the box without any programming. Helvar’s Designer software allows for advanced configuration and functional programming of the router.

The system provides energy-saving features via presence detection and daylight harvesting. Further automation can be achieved through scheduled events.

A PC can be connected to the system for diagnostics and logging purposes if required, but there is no need for PC control in daily operation, as all data is stored within the system itself. The elimination of a central controller ensures that no single point of failure can cause a total system shutdown.

Key Features

• Support for 64 DALI devices.

• Built-in real-time clock.

• Can be networked together to form large scalable systems.

• Provides local as well as central control if required.

• Compatible with other Helvar routers (910/920).

• Integration with other building systems.

• Universal supply input.

(100–240) VAC

2Doc. D005378, issue 7 2016-11-07

Helvar 905 DIGIDIM Router: Datasheet

Technical Data

Inputs/Outputs

Dimensions (mm)

Connections Mains cable: Solid core up to 4 mm²

Stranded up to 2.5 mm² DALI cable: 2-wire mains rated,

0.5 mm² – 2.5 mm² Max. length: 300 m @ 1.5 mm²

Ethernet: 1 × RJ45 10/100 Mb/s, Cat 5E up to 100 m (Auto MDI/MDI-X crossover)

Power Mains supply: 100 VAC – 240 VAC (nominal)

85 VAC – 264 VAC (absolute) 45 Hz – 65 Hz

Power consumption: 13 VA (DALI subnet fully loaded) Power circuit protection: External protection max. 6 A.

Earth mandatory.

DALI output supply DALI-OUT current: 1 × 250 mA (current limited)

Mechanical data Dimensions: 9U – 160 mm × 100 mm × 58 mm Weight: 250 g Mounting: DIN Rail. Keep mains and DALI wiring separate from Ethernet cable.

IP code: IP30 (IP00 at connectors)

Operating and storage conditions Ambient temperature: 0 °C to +40 °C Relative humidity: Max. 90 %, noncondensing Storage temperature: –10 °C to +70 °C

Conformity and standards DALI data transfer: DALI standard IEC 62386, with

Helvar extensions EMC emission: EN 55022 Class A EMC immunity: EN 55024 Safety: EN 60950 Environment: Complies with WEEE and RoHS directives.

L N SC DA– DA+

ETHERNET

(to hub, switch or PC)