About this file

ASHE 09-1012 Technical Specifications_Addendum 1

View the file

Other files

File Type Posted
FA5682-14-R-0004-0004.pdf PDF
ASHE_09_1012_BLANK_Est_REV_3_-_Copy.xls XLS spreadsheet
ASHE_09_1012_att_1_REV_3_-_Copy.pdf PDF
ASHE_09-1012_SOW_2014_REV3_-_Copy.doc DOC document
FA5682-14-R-0004-0003_-_Copy.doc DOC document
Solicitation_FA5682-14-R-0004_AMENDMENT_0002.doc DOC document
Attch_2_-_Solar_Panels_Dorms_Schematic.pdf PDF
Solicitation_FA5682-14-R-0004_AMENDMENT_0001.doc DOC document
Attch_1_-_Solar_Panels_Dorms_Attic.pdf PDF
ASHE_09-1012_CCEB_2014_REV__2_Final.xls XLS spreadsheet
Solicitation_FA5682-14-R-0004_(Solar_Panels_4_Dorms).doc DOC document
ADD__1_Attachment_Schematic_Drawing.pdf PDF
Master_Technical_Specifications.zip ZIP file
ASHE_09-1012_CCEB_2014.xls XLS spreadsheet
Design_Guide_ _Attachments.zip ZIP file
ASHE_09-1012_SOW_2014_REV_1.doc DOC document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE: FEB 2014

ADDENDUM # 1

TECHNICAL SPECIFICATIONS

PROJECT ASHE 09-1012

RENEWABLE: INSTALL SOLAR HEATING PANELS, 4 DORMS, fac# 1423, 1424, 1425, 1426

AREA F, AVIANO AIR BASE, ITALY

1. ADDENDUM # 1 SCOPE

Clarifications and implementation of the original Statement Of Work .

2. SCHEMATIC OF SOLAR HEATING PANELS

a. Attached PDF schematic drawing clarifies the works to be performed under the roof and in the boiler room considering 5ea systems of 10ea panels.

b. The “Drain back” panels and pipeline system shall be designed and installed to have a quick and complete emptying.

c. Minimum capacity of each drain back tank is 80 Lt.

d. Indicative power for each plate exchanger is 40 KW.

ASHE 09-1012 ADDENDUM #1

31CES/CEPM

Date: FEB 2014