APPENDIX “A”

PERFORMANCE WORK STATEMENT

MAINTENANCE OF AUTOMATIC FIRE DETECTION/SUPPRESSION SYSTEMS

AVIANO & GHEDI (BRESCIA) AIR BASES

CONTENTS

SECTION
TITLE
I
Automatic Fire Detection Systems, Manual Stations & Transceivers, Aviano Air Base
II
Sprinkler Systems
III
Sprinkler Pumps & Air Compressors
IV
Standpipe Hoses
V
Kitchen Hood Chemical Extinguishing Systems
VI
Extinguishing Systems
VII
Medical Treatment Facility
VIII
MONACO Computerized Transceiver Systems
IX
Facilities requiring coordination
X
GHEDI Air Base
XI
Facilities Under Renovation, Automatic Fire Detection Systems, Manual Stations and Transceivers
XII
Future Facilities Currently Under Construction, Automatic Fire Detection Systems, Manual Stations and Transceivers

SECTION I

Automatic Fire Detection Systems,Manual Stations & Transceivers

Aviano Air Base

AREA “A-1”

1. Bldg # 103 EDIS/Public Health. System consists of a THERMOSTICK MAR-1A alarm station (15 zones), 64 heat detectors, 8 heat detectors water-proof, 6 smoke detectors on ceiling, 58 smoke detector above ceiling, 2 duct smoke detectors above ceiling, total of 58 smoke detectors placed over 3 meters, 58 repeaters, 1 switch, 11 manual stations, 1 manual station water-proof, 1 bell water-proof, 11 siren/strobe lights and 4 siren/strobe lights water-proof. MONACO transmitter.

2. Bldg # 106 Recreation Center. System consists of a NOTIFIER CFP 12-24 alarm station (8 zones), 1 heat detector, 2 smoke detectors on ceiling, 21 smoke detectors above ceiling, 10 duct detectors above ceiling, total of 31 detectors placed over 3 meters, 21 repeaters, 1 switch, 12 manual stations and 11 alarm bells. MONACO transmitter.

3. Bldg # 108 Life Skills Center. System consists of a THERMOSTICK MAR-1A alarm station (16 zones), 59 heat detectors, 1 heat detector water-proof, 2 smoke detectors on ceiling, 47 smoke detector above ceiling, 2 duct smoke detectors above ceiling, total of 49 smoke detectors placed over 3 meters, 47 repeaters, 2 switch, 9 manual stations, 1 manual station water-proof, 1 bell water-proof and 8 siren/strobe lights. MONACO transmitter.

4. Bldg # 110 Recreation Center and Parents Coop. System consists of a NOTIFIER alarm station (14 zones), 44 heat detectors, 5 heat detectors water-proof, 2 smoke detectors on ceiling, 45 smoke detector above ceiling, total of 45 detectors placed over 3 meters, 1 switch, 23 fire door holders, 7 manual stations and 9 siren/strobe lights. MONACO transmitter.

5. Bldg # 114 Kindergarten. System consists of a NOTIFIER AFP-400 alarm station (7 loops), 23 heat detectors, 5 heat detectors water-proof, 1 smoke detector on ceiling, 24 smoke detector above ceiling, total of 24 detectors placed over 3 meters, 24 repeaters, 1 switch, 3 motorized air dampers, 9 manual stations and 4 siren/strobe lights (no As Built, data is coming from different source, system shall be verified). MONACO transmitter.

6. Bldg # 116 Youth Activity Center. System consists of a NOTIFIER AFP-200 alarm station (1 loop), 1 remote panel LCD80, 3 additional power supply, 8 smoke detectors, 35 smoke detectors above ceiling, 4 duct smoke detectors, total of 35 detectors placed over 3 meters, 35 repeaters, 5 input modules, 9 output modules, 5 magnetic door holders, 19 manual stations, 50 siren/strobe lights, 4 acoustic/optic water-proof warning devices. MONACO transmitter.

7. Bldg # 117 Offices and Clinic. System consists of a THERMOSTICK alarm station (zones 10 + 6), 44 heat detectors, 4 heat detectors waterproof, 14 smoke detectors above ceiling, 2 duct smoke detectors, 1 duct smoke detector above ceiling, total of 8 detectors placed over 4 meters, 14 repeaters, 1 switch, 6 manual stations and 6 alarm bells. MONACO transmitter.

8. Bldg # 130 BOBS/Performance Improvement. System consists of 1 COE CLERICI alarm station (zones 4 + 4), 16 heat detectors, 4 heat detectors above ceiling, 4 repeaters, 4 manual stations and 4 alarm bells. MONACO transmitter.

9. Bldg # 145 Library. System consists of a COE CLERICI alarm station (zones 6 + 2), 7 heat detectors, 9 smoke detectors on ceiling, 3 switches, 6 manual stations and 5 alarm bells. MONACO transmitter.

10. Bldg # 147 Education Center. System consists of a NOTIFIER AFP-400 alarm station (2 loops), 1 remote panel, 35 heat detectors, 1 heat detectors with water-protection, 7 smoke detectors with water-protection, 17 smoke detectors on ceiling, 30 smoke detector above ceiling, 2 duct smoke detectors, total of 30 detectors placed over 3 meters, 32 repeaters, 6 input modules, 9 output modules, 2 isolating modules, 2 gas leak detectors, 1 solenoid valve, 4 manual stations and 8 siren/strobe lights. MONACO transmitter.

11. Bldg # 151 Schools. System consists of a NOTIFIER AM2020 alarm station (analog, 7 loops), 2 synoptic panels, 2 additional panel for kitchen hood extinguishing systems, 10 heat detectors, 31 smoke detectors on ceiling, 496 smoke detector above ceiling, 23 duct smoke detector, 23 addressable monitor modules, 24 addressable relay module, 42 isolating module, 496 repeaters, 24 magnetic holders, 24 fire rated doors, 51 manual stations, 102 speaker/strobe lights, 133 siren/strobe lights and 86 strobe lights. Above stage there are 6 heat and smoke evacuators operated by pressurized nitrogen, system not connected to fire alarm panel. MONACO transmitter.

12. Bldg # 168 Chapel Annex. System consists of a THERMOSTICK MAR-1 alarm station (8+1 zones), 27 heat detectors, 1 heat detector waterproof, 21 smoke detectors above ceiling, total of 28 detectors placed over 3 meters, total of 21 detectors placed over 4 meters, 21 repeaters, 4 manual stations, 1 manual station waterproof, 6 siren/strobe lights and 1 bell water-proof. MONACO transmitter.

13. Bldg # 170 Child Development Center. System consists of a THERMOSTICK alarm station (zones 13 + 3), 50 smoke detectors on ceiling, 7 duct smoke detectors above ceiling, total of 7 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, 1 repeater, 7 switches, 20 manual stations, 18 bells and 1 waterproof alarm bell. MONACO transmitter.

14. Bldg # 172 Chapel. System consists of a THERMOSTICK alarm station (18 zones), 46 heat detectors, 9 smoke detectors on ceiling, 30 smoke detectors above ceiling, 8 duct detectors above ceiling, total of 40 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, total of 6 detectors placed over 6 meters, 30 repeaters, 11 switches, 20 manual stations and 16 alarm bells. MONACO transmitter.

15. Bldg # 174 Old CDC. System consists of a BENTEL J-408 alarm station (8 zones), additional power supply BENTEL BXM 24/50-B, 6 heat detectors, 20 smoke detectors on ceiling, 15 smoke detectors above ceiling, total of 26 detectors placed over 3 meters, 15 repeaters, 6 manual stations and 10 alarm visual panels with recorded warning message. MONACO transmitter.

16. Bldg # 175 Laundry. System consists of a NOTIFIER S-5000 alarm station (zones 5 + 3), 20 heat detectors, 1 duct smoke detector, 4 gas detectors, total of 4 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 3 repeater, 3 switches, 4 manual stations, 4 alarm bells and 6 strobe-lights. MONACO transmitter.

17. Bldg # 176 Bowling Alley. System consists of a MONACO VULCAN alarm station (2 zones), 6 heat detectors, 20 smoke detectors on ceiling, 3 duct smoke detectors, total of 5 detectors placed over 3 meters, total of 13 detectors placed over 4 meters, 5 manual stations and 1 alarm bell. MONACO transmitter.

18. Bldg # 176 A Ten Pin INN. System consists of a COE CLERICI alarm station (4 zones), 8 heat detectors, 1 heat detector waterproof, 8 smoke detectors above ceiling, total of 8 detectors placed over 3 meters, 8 repeaters, 1 switch, 2 manual stations and 2 alarm bells. MONACO transmitter.

19. Bldg # 17811 Swimming Pool. System consists of a CERBERUS CZ-16 alarm station (8 zones), 6 heat detectors, 3 heat detectors waterproof, 5 manual stations, 3 bells and 3 alarm bells waterproof. MONACO transmitter.

20. Bldg # 179 Mini Mall. System consists of a NOTIFIER AFP-400 alarm station (2 loops), 1 remote panel LCD80, 2 heat detectors, 5 smoke detectors, 37 smoke detector above ceiling, 7 duct smoke detectors, 37 repeaters, 4 optical warning devices, 51 acoustic/optical warning devices, 17 manual stations, 5 input modules, 5 output modules, and total of 37 detectors placed over 4 meters. MONACO transmitter.

21. Bldg # 186 Multi, Union, Airman Attic, AAFES, etc. System consists of a THERMOSTICK MAR-1A alarm station (14 zones), 125 heat detectors, 9 heat detectors water-proof, 9 smoke detectors on ceiling, 1 switch, 24 manual stations, 15 siren/strobe lights and 3 bells. MONACO transmitter.

AREA “A-2”

22. Bldg # 218 Fire Station # 2. System, without transmitter, consists of a COE CLERICI alarm station (zones 5 + 3), 6 heat detectors, 19 heat detectors waterproof, 5 smoke detectors on ceiling, 7 smoke detectors above ceiling, total of 7 detectors placed over 3 meters, total of 7 detectors placed over 4 meters, 12 repeaters, 3 switches, 8 manual stations and 9 alarm bells. MONACO transmitter.

23. Bldg # 219 Dormitory. System consists of a THERMOSTICK alarm station (38 zones), 218 heat detectors, 60 heat detectors waterproof, 194 smoke detectors above ceiling, 3 duct smoke detectors, total of 194 detectors placed over 3 meters, 194 repeaters, 19 manual stations, 32 alarm bells and 3 switches leading electric equipment. There are also 188 local smoke detectors, with local buzzers, inside rooms for local detection that are connected to an advisor in facility manager’s office where a reset switch is placed. MONACO transmitter.

24. Bldg # 220 Offices. System consists of a CERBERUS alarm station (12 zones), 69 heat detectors, 70 smoke detectors on ceiling, 5 smoke detectors above ceiling, total of 5 detectors placed over 3 meters, 5 repeaters, 7 manual station and 10 alarm bells. MONACO transmitter.

25. Bldg # 224 Ground floor. New system consists of a NOTIFIER AM-1000 alarm station (1 loop), 30 heat detectors, 30 smoke detectors above ceiling, total of 30 detectors placed over 3 meters, 30 repeaters, 3 output modules, 5 input modules, 3 isolating modules, 5 manual stations and 5 siren/strobe lights. MONACO transmitter.

26. Bldg # 224 First floor - SATO. Old conventional system connected to addressable panel with 7 input modules and 2 output modules, 1 heat detector water-proof, 35 heat detectors, 25 smoke detectors on ceiling, 5 smoke detectors above ceiling, total of 5 detectors placed over 3 meters, 5 repeaters, 5 manual stations and 5 bells.

27. Bldg # 240 Gym Annex. System is connected to transmitter at Bldg 240 GYM, it consists of a CERBERUS CZ-16 alarm station (zones 15 + 1), 15 heat detectors, 24 smoke detectors above ceiling, 10 duct smoke detectors above ceiling, total of 34 detectors placed over 3 meters, 24 repeaters, 7 switches, 7 manual stations and 8 alarm bells.

28. Bldg # 240 Gym. System consists of a COE CLERICI alarm station (zones 9 + 3), 55 heat detectors, 20 heat detectors waterproof, 14 smoke detectors on ceiling, total of 9 detectors placed over 4 meters, total of 36 detectors placed over 6 meters, 1 repeater, 15 manual stations and 12 alarm bells. MONACO transmitter.

29. Bldg # 244 Buon Appetito. System consists of a THERMOSTICK MAR-1 alarm station (14 zones), 54 heat detectors, 20 heat detectors water-proof, 37 smoke detectors above ceiling, 9 duct smoke detectors, total of 37 detectors placed over 3 meters, 37 repeaters, 1 switch, 9 manual station, 13 sirens/strobe lights and 1 bell. MONACO transmitter.

30. Bldg # 248 DAPS & Home Fuel. System consists of a NOTIFIER AM-1000 alarm station (1 loop), 29 heat detectors, 11 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, 13 repeaters, 5 acoustic/optic warning devices, 6 manual stations, 1 isolating module, 1 output module, total of 13 detectors placed over 3 meters.

31. Bldg # 250 Airman Leadership School. System consists of a NOTIFIER S-5000 alarm station (zones 6 + 2), 1 additional power supply, 2 smoke detector, 22 smoke detectors above ceiling, 22 repeaters, 9 manual stations, 3 bells, 13 acoustic/optic warning devices. MONACO transmitter.

32. Bldg # 254 Dormitory. System consists of a NOTIFIER S-5000 alarm station (zones 26 + 14), 13 heat detectors water-proof, 162 smoke detectors above ceiling, 4 duct smoke detectors, total of 162 detectors placed over 3 meters, 166 repeaters, 1 switch, 23 manual stations and 42 siren/strobe lights. There are also 150 local smoke detectors, with local buzzers, inside rooms for local detection that are connected to an advisor in facility manager’s office where a reset switch is placed. MONACO transmitter.

33. Bldg # 256 Offices. System consists of a CERBERUS CZ-16 alarm station (zones 17 + 7), 68 heat detectors, 34 smoke detectors above ceiling, 1 duct smoke detector, total of 33 detectors placed over 3 meters, 33 repeaters, 1 switch, 8 manual stations and 10 alarm bells. MONACO transmitter.

34. Bldg # 258 Dormitory. System consists of a NOTIFIER S-5000 alarm station (zones 24 + 16), 11 heat detectors waterproof, 138 smoke detectors above ceiling, 3 duct smoke above ceiling, total of 138 detectors placed over 3 meters, 141 repeaters, 1 switch, 19 manual stations and 34 siren/strobe lights. There are also 124 local smoke detectors with local buzzers inside rooms for local detection, which are connected to an advisor in facility manager’s office where a reset switch is placed. MONACO transmitter.

35. Bldg # 263 Area 2 – Water Pump Station. System consists of a NOTIFIER Fire Star alarm station (3 zones), 1 smoke detector on ceiling, 7 smoke detectors above ceiling, 7 repeaters, 1 switch, 3 manual stations and 5 bells. MONACO transmitter.

AREA “C”

36. Bldg # 407 Offices & Appliance Shop. System consists of a THERMOSTICK alarm station (zones 16 + 4), 105 heat detectors, 11 heat detectors waterproof, 6 smoke detectors on ceiling, 46 smoke detectors above ceiling, 2 duct smoke detectors, total of 39 detectors placed over 3 meters, total of 7 detectors placed over 4 meters, total of 19 detectors placed over 6 meters, 46 repeaters, 17 manual stations and 23 siren/strobe lights. MONACO transmitter.

37. Bldg # 410 Offices & Multi Shops. System consists of a THERMOSTICK alarm station (9 zones), 42 heat detectors, 4 heat detectors waterproof, 2 smoke detectors on ceiling, 19 smoke detectors above ceiling, total of 5 detectors placed over 3 meters, total of 13 detectors placed over 4 meters, 19 repeaters, 11 switches, 15 manual stations and 13 sirens/strobe lights. MONACO transmitter.

38. Bldg # 411 Area C - Water Pump Station. System consists of a NOTIFIER AM-2020 (1 loop), 1 heat detector, 2 smoke detectors on ceiling, total 3 detectors placed over 4 meters, 3 output modules, 2 manual stations and 1 bell water-proof. MONACO transmitter.

39. Bldg # 416 Horizontal Shop. System consists of a THERMOSTICK MAR-1 alarm station (3+2 zones), 13 heat detectors, 5 smoke detectors on ceiling, 11 smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 8 manual station and 8 sirens/strobe lights. MONACO transmitter.

40. Bldg # 420 Electric Substation & storage. System consists of a COE CLERICI alarm station (4 zones), 4 heat detectors, 3 heat detectors waterproof, 3 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, 3 repeaters, 3 manual stations and 2 alarm bells. MONACO transmitter.

41. Bldg # 421 Exterior Electric Shop. System consists of a THERMOSTICK alarm station (zones 4 + 1), 5 heat detectors, 1 heat detector waterproof, 4 heat detectors above ceiling, 5 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 7 detectors placed over 3 meters, total of 2 detectors placed over 4 meters, 3 repeaters, 3 manual stations and 3 alarm bells. MONACO transmitter.

42. Bldg # 422 Area C – HWM Storage. System consists of a THERMOSTICK MAR-1A alarm station (6 zones), 16 heat detectors, 1 smoke detector on ceiling, total of 1 detector over 3 meters, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 5 siren/strobe lights. MONACO transmitter.

43. Bldg # 424 Offices. System consists of a BENTEL J-408 alarm station (zones 4 + 4), 10 heat detectors, 1 heat detectors waterproof, 8 smoke detectors above ceiling, 2 duct smoke detectors, total of 8 detectors placed over 4 meters, 9 repeaters, 2 air dampers, 1 switch, 3 manual stations and 3 alarm bells. MONACO transmitter.

44. Bldg # 428 Offices. System consist of a THERMOSTICK alarm station (zones 3 + 1), 4 heat detectors, 1 heat detector waterproof, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 3 repeaters, 2 manual stations and 2 alarm bells. MONACO transmitter.

45. Bldg # 430 Offices, Warehouse & Shop. System consists of a THERMOSTICK alarm station (18 zones), 18 heat detectors, 14 heat detectors waterproof, 15 smoke detectors on ceiling, 7 smoke detectors above ceiling, total of 5 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, total of 4 detectors placed over 6 meters, 7 repeaters, 10 switches, 19 manual stations and 21 siren/strobe lights. MONACO transmitter.

AREA “D”

46. Bldg # 554 Lodge. System consists of a THERMOSTICK MAR-1 alarm station (5 fire detection + 2 GDU gas leak detection zones), 16 heat detectors, 1 heat detector waterproof, 4 smoke detectors on ceiling, 11 smoke detectors above ceiling, 1 duct smoke detector, total of 20 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 11 repeaters, 3 Lp gas detectors, 4 manual stations, 1 manual station waterproof, 1 Lp gas warning light, 5 siren/strobe lights, 1 bell and 1 bell waterproof. MONACO transmitter.AREA “E”

AREA “E”

47. Bldg # 600 Multi Offices & Control Room. System consists of a NOTIFIER S-500 alarm station (16 zones), 114 heat detectors, 7 heat detectors waterproof, 16 smoke detectors on ceiling, 109 smoke detectors above ceiling, total of 103 detectors placed over 3 meters, 103 repeaters, 17 manual stations and 25 alarm bells. MONACO transmitter.

48. Bldg # 604 Italian Carabinieri Offices & Electric Substation. System consists of a THERMOSTICK MAR-1 alarm station (zones 5+2), 13 heat detectors, 2 heat detectors waterproof, 3 smoke detectors on ceiling, 11 smoke detectors above ceiling, total of 21 detectors placed over 3 meters, total of 8 detectors placed over 4 meters, 4 manual stations, 1 manual station waterproof, 3 siren/strobe lights, 1 bell and 1 bell waterproof. MONACO transmitter.

49. Bldg # 606 AFN & Offices. System consists of a COE CLERICI alarm station (zones 7 + 1), 25 heat detectors, 6 smoke detectors on ceiling, 19 smoke detectors above ceiling, total of 12 detectors placed over 3 meters, total of 5 detectors placed over 4 meters, 17 repeaters, 1 switch, 8 manual stations and 4 alarm bells. MONACO transmitter.

50. Bldg # 620 Security Forces Kennel Section Office. System consist of a COE CLERICI alarm station (zones 5 + 3), 6 heat detectors, 7 heat detectors waterproof, 1 smoke detector on ceiling, 6 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, 6 repeaters, 1 switch, 5 manual stations and 2 alarm bells. MONACO transmitter.

51. Bldg # 623 Hard Shelter Communication. System consists of a NOTIFIER S-5000 alarm station (zones 6 + 2), 6 heat detectors waterproof, 4 smoke detectors on ceiling, 6 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 10 detectors placed over 3 meters, 1 switch, 1 manual station and 3 alarm bells. MONACO transmitter.

52. Bldg # 624 Office. System consists of a COE CLERICI alarm station (4 zones), 4 heat detectors, 1 smoke detector on ceiling, 2 manual stations and 2 alarm bells. MONACO transmitter.

53. Bldg # 627 31 CONS Annex. System consists of a CERBERUS CZ-16 alarm station (zones 6 + 2), 14 heat detectors, 7 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 4 alarm bells. MONACO transmitter.

AREA “F”

54. Bldg # 898 Visitor Center. System consists of a CERBERUS MZ-4 alarm station (4 zones), 3 heat detectors, 1 smoke detector on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 3 repeaters, 1 switch, 2 manual stations and 2 alarm bells. MONACO transmitter.

55. Bldg # 904 Offices. System consists of a THERMOSTICK alarm station (16 zones), 101 heat detectors, 11 heat detectors waterproof, 1 smoke detector on ceiling, 68 smoke detectors above ceiling, total of 68 detectors placed over 3 meters, 68 repeaters, 18 manual stations and 18 alarm bells. MONACO transmitter.

56. Bldg # 9041 Area F – HWM Storage. System consists of a THERMOSTICK MAR-1A alarm station (6 zones), 16 heat detectors, 1 smoke detector on ceiling, total of 1 detector over 3 meters, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 5 siren/strobe lights. MONACO transmitter.

57. Bldg # 9042 Field Training Center. System consists of a NOTIFIER AFP-200 alarm station (1 loop), 21 heat detectors, 2 smoke detectors on ceiling, 9 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 11 detectors placed over 4 meters, 3 output modules, 5 input modules, 2 isolating modules, 11 repeaters, 5 manual stations, 1 bell and 6 siren/strobe lights. MONACO transmitter.

58. Bldg # 907 PMEL Laboratory. System consists of a THERMOSTICK MAR-1 alarm station (6 zones) and 1 methane gas leak detection control, 30 heat detectors, 4 heat detectors water-proof, 1 smoke detector on ceiling, 23 smoke detectors above ceiling, 5 duct smoke detectors, 1 gas leak detector, total of 30 detectors placed over 3 meters, total of 23 detectors placed over 4 meters, 23 repeaters, 1 switch, 9 manual station, 12 siren/strobe lights and 1 bell. MONACO transmitter.

59. Bldg # 908 Electric Substation. System consists of a THERMOSTICK MAR-1 alarm station (zones 3+2), 6 heat detectors, 7 heat detectors waterproof, 4 smoke detectors on ceiling, total of 17 detectors placed over 4 meters, 2 manual stations, 2 manual stations waterproof, 2 bells and 2 bells waterproof. MONACO transmitter.

60. Bldg # 909 Visitor Center. System consists of a NOTIFIER S-5000 alarm station (2 zones), 2 smoke detectors on ceiling, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 1 switch, 3 repeaters, 1 manual station and 2 siren/strobe lights. MONACO transmitter.

61. Bldg # 914 Snack Bar. System consists of a NOTIFIER AM-1000 alarm station (1 loop), 3 heat detectors with water-protection, 6 heat detectors, 1 smoke detector on ceiling, 4 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, total of 4 detectors placed over 4 meters, 4 repeaters, 4 manual stations and 4 siren/strobe lights. MONACO transmitter.

62. Bldg # 916 Heat Plant. System consists of a NOTIFIER SFP-400 alarm station (4 zones), 4 heat detectors waterproof, 1 switch, 4 manual stations, 1 trouble bell and 7 siren/strobe lights. MONACO transmitter.

63. Bldg # 918 Electric Substation. System consists of a THERMOSTICK MAR-1 alarm station (zones 2+2), 8 heat detectors, 7 smoke detectors on ceiling, total of 15 detectors placed over 3 meters, 3 manual stations, 2 siren/strobe lights and 1 bell. MONACO transmitter.

64. Bldg # 919 Bunker. System consists of a THERMOSTICK MAR-1 alarm station (zones 3+2), 3 heat detectors, 12 smoke detectors on ceiling, 3 manual stations and 3 siren/strobe lights. MONACO transmitter.

65. Bldg # 920 Trans. Alert and Protocol. System consists of a THERMOSTICK alarm station (zones 2 + 1), 3 heat detectors, 2 heat detectors water-proof, 3 smoke detectors above ceiling, total of 3 detectors placed over 3 meters, 3 repeaters, 2 manual stations and 2 alarm bells. MONACO transmitter.

66. Bldg # 921 Hangar # 1 – Multi Offices. System consists of a THERMOSTICK alarm station (zones 14 + 7), 67 heat detectors, 1 heat detector explosion proof, 3 smoke detectors on ceiling, 14 smoke detectors above ceiling, 10 duct smoke detectors, 2 duct smoke detectors above ceiling, total of 27 detectors placed over 3 meters, total of 4 detectors placed over 4 meters, 16 repeaters, 6 fire doors, 6 magnetic door holders, 26 manual stations, 22 alarm bells and 1 alarm bell explosion proof. MONACO transmitter.

67. Bldg # 925 Mezzanine (system is only for the two store offices placed inside hangar #2). System consists of a CERBERUS CZ-16 alarm station (8 zones), 24 heat detectors, 2 duct smoke detectors, total of 1 detector placed over 3 meters, total of 1 detector placed over 4 meters, 1 switch, 9 manual stations and 7 alarm bells. MONACO transmitter.

68. Bldg # 925 NDI Laboratory. System consists of 1 COE CLERICI alarm station (zones 4 + 2), 1 heat detector, 1 heat detector waterproof, 7 heat detectors explosion proof, 1 smoke detector above ceiling, 1 duct smoke detector on ceiling, 1 duct smoke detectors above ceiling, total of 2 detectors placed over 3 meters, 2 repeaters, 5 air dampers, 2 switches, 1 manual station, 2 manual stations explosion proof, 2 alarm bells and 3 alarm bells explosion proof. MONACO transmitter.

69. Bldg # 933 TF Offices & Terminal Freight. System is connected to transmitter at Bldg 933 TMO, it consists of a COE CLERICI alarm station (zones 7 + 1), 2 heat detectors, 21 heat detectors waterproof, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, total of 21 detectors placed over 4 meters, 1 switch, 7 manual stations and 3 alarm bells.

70. Bldg # 933 NTP Terminal Passengers. System consists of a COE CLERICI alarm station (13 zones), 33 heat detectors, 4 heat detectors waterproof, 13 smoke detectors above ceiling, 1 duct smoke detector, total of 9 detectors placed over 3 meters, total of 5 detectors placed over 4 meters, 14 repeaters, 3 switches, 11 manual stations and 8 alarm bells. MONACO transmitter.

71. Bldg # 933 ATOC Offices. System is connected to transmitter at Bldg 933 NTP, it consists of a NOTIFIER FIRESTAR alarm station (zones 3 + 1), 7 heat detectors, 1 switch, 5 manual stations and 3 alarm bells.

72. Bldg # 936 Offices. System consists of a THERMOSTICK alarm station (3 zones), 11 heat detectors, 3 heat detectors waterproof, 7 smoke detectors above ceiling, 1 duct smoke detector, total of 8 detectors placed over 3 meters, 8 repeaters, 3 manual stations and 3 alarm bells. MONACO transmitter.

73. Bldg # 939 EOL. System consists of a THERMOSTICK alarm station (6 zones), 17 heat detectors, 3 heat detectors waterproof, 1 smoke detector on ceiling, 12 smoke detectors above ceiling, 1 duct smoke detector, total of 14 detectors placed over 3 meters, 12 repeaters, 3 air dampers, 1 switch, 4 manual stations and 5 alarm bells. MONACO transmitter.

74. Bldg # 940 Offices. System consists of a NOTIFIER AM-2000 alarm station (1 loop), 62 heat detectors, 1 smoke detector, 39 smoke detectors above ceiling, 39 repeaters, 7 manual stations, 12 acoustic/optic warning devices, 8 input modules, 1 output module, and total of 39 detectors placed over 3 meters. MONACO transmitter.

75. Bldg # 940 A Hard Ops. System consists of a NOTIFIER AM-1000 alarm station (1 loop), 1 additional power supply, 22 heat detectors, 15 smoke detectors on ceiling, 2 duct smoke detectors above ceiling, 17 repeaters, 3 acoustic/optic warning devices, 2 manual stations, 1 isolating module, 1 input module, 2 output modules, total of 17 detectors placed over 3 meters. MONACO transmitter.

76. Bldg # 94003 Army – Vehicle Maintenance. System consists of a NOTIFIER S-5000 alarm station (zones 2), 6 heat detectors, 6 smoke detectors, total of 12 detectors placed over 4 meters, 1 switch, 2 manual stations and 2 siren/strobe lights. MONACO transmitter.

77. Bldg # 941 Photo Lab. System consists of a COE CLERICI alarm station (zones 9 + 3), 31 heat detectors, 3 heat detectors waterproof, 31 smoke detectors above ceiling, 2 duct smoke detectors above ceiling, total of 33 detectors placed over 3 meters, 31 repeaters, 1 switch, 6 manual stations and 7 alarm bells. MONACO transmitter.

78. Bldg # 944 Storage. System consists of a NOTIFIER S-500 alarm station (zones 4 + 4), 5 heat detectors, 5 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 3 detectors placed over 3 meters, total of 6 detectors placed over 4 meters, 6 repeaters, 2 switches, 2 manual stations and 2 bells. MONACO transmitter.

79. Bldg # 1000 Fuel Transportation. System consists of a COE CLERICI alarm station (4 zones), 1 heat detector, 17 heat detectors waterproof, total of 16 detectors placed over 4 meters, 5 manual stations and 2 alarm bells. MONACO transmitter.

80. Bldg # 1004 Motor Pool. System consists of a COE CLERICI alarm station (8 zones), 12 heat detectors, 8 smoke detectors above ceiling, total of 8 detectors placed over 3 meters, 8 repeaters, 1 switch, 3 manual stations and 4 alarm bells. MONACO transmitter.

81. Bldg # 1005 System is connected to alarm station at Bldg 1004, it consists of 3 heat detectors, 1 heat detector waterproof, 2 heat detectors above ceiling, 2 smoke detectors above ceiling, total of 4 detectors placed over 3 meters, 2 repeaters, 3 manual stations and 3 alarm bells.

82. Bldg # 1006 System is connected to alarm station at bldg 1004, it consists of 3 heat detector, 3 smoke detector above ceiling, total of 3 detectors placed over 3 meters, total of 1 detector placed over 4 meters, 3 repeaters, 2 manual stations and 2 alarm bells.

83. Bldg # 1010 Vehicle Maintenance. System consists of a NOTIFIER CFP 12-24 alarm station (10 zones), 25 smoke detectors, 2 smoke detectors above ceiling, 6 duct smoke detectors above ceiling, 8 repeaters, 25 manual stations, 11 bells, 11 acoustic/optical warning devices, 1 switch stops HVAC equipment, total of 8 detectors placed over 3 meters. MONACO transmitter.

84. Bldg # 1013 Prefabricated Offices. System consists of a COE CLERICI alarm station (3 zones), 4 heat detectors, 1 heat detectors waterproof, 4 smoke detectors above ceiling, total of 4 detectors placed over 3 meters, 1 repeater, 1 switch, 1 manual station and 1 alarm bell. MONACO transmitter.

85. Bldg # 1014 Fuel Section Offices. System consist of a THERMOSTICK alarm station (zones 6 + 1), 13 heat detectors, 1 heat detector waterproof, 15 smoke detectors above ceiling, total of 15 detectors placed over 3 meters, 15 repeaters, 3 switches, 5 manual stations and 4 alarm bells. MONACO transmitter.

86. Bldg # 1015 Fuel Section Office & Break Room. System consists of a THERMOSTICK MAR-1 alarm station (zones 2+2), 5 heat detectors, 1 manual station and 1 siren/strobe light. MONACO transmitter.

87. Bldg # 10161 Paint Booth External Structure. System consists of a NOTIFIER S-500 (7 zones), 5 smoke detectors, 4 manual stations, 3 siren/strobe lights, 1 siren/strobe light water-proof, 1 switch leading warm air generator, closes motorized air dampers and stops ventilation, total of 5 detectors placed over 6 meters. MONACO transmitter.

88. Bldg # 10161 Spray Booth Cabin. Independent automatic detection and warning system for spray and drying chamber consists of a NOTIFIER AM-200 control panel (2 zones), 6 heat detectors water-proof, 2 magnetic contacts (safety purposes) on doors, 2 motorized air dampers on ventilation, 2 tamper switches on dampers, 2 twin (4) manual stations, 1 siren/strobe light and 4 twin (8) acoustic/optic warning devices. Panel is connected to existing NOTIFIER S-500 fire control panel.

89. Bldg # 1019 LE desk and Armory. System consists of a COE CLERICI alarm station (7 zones), 4 heat detectors, 1 heat detector waterproof, 1 smoke detector on ceiling, 3 manual stations and 3 alarm bells. MONACO transmitter.

90. Bldg # 1020 Offices. System is connected to transmitter at Bldg 1019, it consists of 15 heat detectors, 1 heat detector waterproof, 3 manual stations and 3 alarm bells.

91. Bldg # 1023 Fire Station # 3. System consists of a CERBERUS alarm station (12 zones), 24 heat detectors, 7 heat detectors waterproof, 7 smoke detectors on ceiling, total of 5 detectors placed over 6 meters, 5 repeaters, 13 manual stations and 7 alarm bells. The main MONACO D-500 computer system is installed in this building.

92. Bldg # 1027 Dental Clinic. System consists of a THERMOSTICK alarm station (zones 4 + 4), 15 heat detectors, 3 smoke detector on ceiling, 12 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 13 detectors placed over 3 meters, 12 repeaters, 1 switch, 2 manual stations and 2 alarm bells. MONACO transmitter.

93. Bldg # 10271 Medical Clinic. System consists of a NOTIFIER AFP-400 alarm station (analog, 1 loop), 2 smoke detector above ceiling, 1 duct smoke detector, total of 2 detectors placed over 4 meters, 1 switch, 7 manual stations, 4 alarm bells, 6 siren/strobe lights and 9 strobe lights. MONACO transmitter.

94. Bldg # 1029 Base Supply. System consists of a NOTIFIER S-500 alarm station (zones 8 + 4), 1 fire door, 7 manual stations and 8 alarm bells. MONACO transmitter.

95. Bldg # 1029 A Inside 1029 warehouse there are 8 groups of prefab offices. Their systems are connected to Bldg 1029 alarm station total consists of 13 heat detectors, 2 smoke detectors, 12 manual stations and 12 alarm bells.

96. Bldg # 10295 Prefab Offices. System consists of a THERMOSTICK alarm station (4 zones), 14 heat detectors, 14 smoke detectors above ceiling, 1 duct smoke detector, total of 15 detectors placed over 3 meters, 15 repeaters, 2 switches, 4 manual stations and 2 alarm bells. MONACO transmitter.

97. Bldg # 10296 Area F – HWM Storage. System consists of a THERMOSTICK MAR-1A alarm station (6 zones), 16 heat detectors, 1 smoke detector on ceiling, total of 1 detector over 3 meters, total of 16 detectors placed over 4 meters, 3 switches, 5 manual stations and 5 siren/strobe lights. MONACO transmitter.

98. Bldg # 1032 Pharmacy Hazard Accumulation Point. System consists of a THERMOSTICK alarm station (zones 10 + 1) with 3 GDU modules for gas detectors, 7 heat detectors, 1 heat detector waterproof, 8 heat detectors explosion proof, 7 smoke detectors above ceiling, 1 duct smoke detectors explosion proof, total of 7 detectors placed over 3 meters, total of 14 detectors placed over 4 meters, 7 repeaters, 3 gas detectors, 3 fire doors in bay, 1 switch, 1 manual station, 3 manual stations explosion proof, 1 alarm bell, 2 siren/strobe lights, 3 visual advisors explosion proof and 3 sirens explosion proof. MONACO transmitter.

99. Bldg # 1035 Storage. System consists of a COE CLERICI alarm station (zones 5 + 3), 11 heat detectors explosion proof, 7 manual stations explosion proof and 5 alarm bells explosion proof. MONACO transmitter.

100. Bldg # 1036 Multi Storages & Ground Maintenance. System consists of a MONACO VULCAN alarm station (zones 5 + 5), 18 heat detectors waterproof, total of 18 detectors placed over 6 meters, 6 manual stations and 3 alarm bells. MONACO transmitter.

101. Bldg # 1037 Readiness. System consists of a THERMOSTICK alarm station (zones 7 + 1), 17 heat detectors, 9 heat detectors waterproof, 1 smoke detector on ceiling, 13 smoke detectors above ceiling, total of 11 detectors placed over 3 meters, total of 2 detectors placed over 4 meters, total of 6 detectors placed over 6 meters, 13 repeaters, 1 switch, 7 manual station and 9 alarm bells. MONACO transmitter.

102. Bldg # 10372 AAFES Storage. System consists of a THERMOSTICK MAR-1 (4 zones), 10 heat detectors, total of 8 detectors placed over 3 meters, 2 manual stations and 2 siren/strobe lights. MONACO transmitter.

103. Bldg # 1046 Power Production. System consists of a CERBERUS CZ-16 alarm station (zones 7 + 1), 12 heat detectors, 3 smoke detectors on ceiling, 9 smoke detectors above ceiling, total of 9 detectors placed over 4 meters, total of 6 detectors placed over 6 meters, 9 repeaters, 1 switch, 5 manual stations and 5 alarm bells. MONACO transmitter.

104. Bldg # 10461 Fuel Systems Maintenance. System consists of a THERMOSTICK alarm station (zones 6 + 1), 7 heat detectors, 1 heat detector waterproof, 3 heat detectors explosion-proof, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, total of 3 detectors placed over 6 meters, 2 repeaters, 6 switches, 3 manual stations, 3 manual stations explosion proof, 2 alarm bells and 1 alarm bell explosion proof. MONACO transmitter.

105. Bldg # 10462 Damage Control Center. System consists of a THERMOSTICK alarm station (2 zones), 9 smoke detectors on ceiling, 6 smoke detectors above ceiling, total of 6 detectors placed over 3 meters, 6 repeaters, 1 switch, 3 air dampers, 2 manual stations, 2 siren/strobe lights and 2 strobe lights. MONACO transmitter.

106. Bldg # 1048 Liquid Fuels Admin. System consists of a THERMOSTICK alarm station (zones 24 + 1), 17 heat detectors, 2 heat detectors waterproof, 3 heat detectors explosion-proof, 3 smoke detectors on ceiling, 18 smoke detectors above ceiling, 3 duct smoke detectors above ceiling, total of 18 detectors placed over 3 meters, total of 3 detectors placed over 4 meters, 21 repeaters, 6 gas (fuel vapors) detectors, 8 switches, 4 manual stations, 3 manual stations explosion proof, 4 alarm bells, 3 alarm bells explosion proof and 1 strobe/light. MONACO transmitter.

107. Bldg # 1053 Army Storage. System consists of a THERMOSTICK alarm station (zones 7 + 1), 34 heat detectors, 2 heat detectors water proof, 6 smoke detectors on ceiling, total of 30 detectors placed over 6 meters, 7 manual stations, 3 optic/acoustic advisors and 1 alarm bell. MONACO transmitter.

108. Bldg # 1064 Electric Substation. System consists of a THERMOSTICK MAR-1 alarm station (zones 2+2), 7 heat detectors, 3 smoke detectors on ceiling, total of 9 detectors placed over 3 meters, total of 1 detector placed over 6 meters, 2 manual stations and 2 bells. MONACO transmitter.

109. Bldg # 1097 LOX Plant Admin. System consists of a THERMOSTICK alarm station (zones 3 + 2), 11 heat detectors, 2 smoke detectors above ceiling, total of 2 detectors placed over 3 meters, total of 9 detectors placed over 6 meters, 2 repeaters, 1 switch, 3 manual stations, 1 alarm bell and 3 siren/strobe lights. MONACO transmitter.

110. Bldg # 1099 LOX Plant. System consists of one THERMOSTICK (5 zones) alarm station for the explosion-proof sensors and one COE CLERICI (4 zones) alarm stations, 5 heat detectors, 2 heat detectors waterproof, 14 heat detectors explosion proof, 1 smoke detector on ceiling, 2 smoke detectors above ceiling, 1 duct smoke detector, total of 2 detectors placed over 3 meters, total of 11 detectors placed over 4 meters, 2 repeaters, 2 flame detectors explosion proof, 1 switch, 2 manual stations, 2 manual stations explosion proof, 3 alarm bells, 2 alarm bells explosion proof and 2 strobe lights explosion proof. MONACO transmitter.

111. Bldg # 1100 System consists of a COE CLERICI alarm station (zones 8 + 1), 15 heat detectors, 2 heat detectors waterproof, 2 duct smoke detectors above ceiling, total of 2 detectors placed over 3 meters, 14 repeaters, 2 switches, 5 manual stations and 3 alarm bells. MONACO transmitter.

112. Bldg # 1121 Comm. System consists of a COE CLERICI alarm station (4 zones), 1 heat detector waterproof, 4 smoke detectors on ceiling, total of 1 detector placed over 3 meters, 4 manual stations and 4 alarm bells. MONACO transmitter.

113. Bldg # 1131 Evacuated Offices. System consists of a COE CLERICI alarm station (4 zones), 7 heat detectors, 2 heat detectors waterproof, 4 smoke detectors above ceiling, total of 4 detectors placed over 3 meters, 4 repeaters, 3 manual stations and 3 alarm bells. MONACO transmitter.

114. Bldg # 1133 Evacuated Offices. System consists of a COE CLERICI alarm station (zones 10 + 2), 29 heat detectors, 7 heat detectors waterproof, 2 smoke detectors on ceiling, 21 smoke detectors above ceiling, 1 duct smoke detector, total of 22 detectors placed over 3 meters, 24 repeaters, 17 manual stations and 9 alarm bells. MONACO transmitter.

115. Bldg # 1135 Evacuated Offices. System consists of a THERMOSTICK MAR-1 alarm station (zones 4+2), 21 heat detectors, 2 smoke detectors on ceiling, 14 smoke detectors above ceiling, total of 14 detectors placed over 3 meters, 14 repeaters, 3 manual stations and 3 siren/strobe/lights. MONACO transmitter.

116. Bldg # 1135 (() Alternate Command Post. System consists of a MONACO VULCAN alarm station (6 zones), 7 heat detectors, 6 smoke detectors on ceiling, 1 manual station and 1 alarm bell. MONACO transmitter.

117. Bldg # 1140 Offices outside Hush House. System consists of a THERMOSTICK alarm station (zones 4 + 4), 4 heat detectors, 3 smoke detectors above ceiling, 1 duct smoke detector, total of 3 detectors placed over 3 meters, 3 repeaters, 2 switches, 2 manual stations and 2 bells. MONACO transmitter.

118. Bldg # 1143 Victor 73. System consists of a COE CLERICI alarm station (4 zones), 17 heat detectors, 1 duct smoke detector, 1 ait damper, 4 manual stations and 2 alarm bells. MONACO transmitter.

119. Bldg # 1163 Fuel Cell Maintenance Facility. System consists of a NOTIFIER S-5000 (6 zones), 2 smoke detectors on ceiling, 2 duct smoke detectors, total of 2 detectors placed over 6 meters, 10 manual stations and 14 siren/strobe lights. MONACO transmitter..

120. Bldg # 1197 Sierra 65. System consists of a CERBERUS CZ-16 alarm station (zones 4 + 4), 30 heat detectors, 8 manual stations and 1 alarm bell. MONACO transmitter.

121. Bldg # 1198 Sierra 66. System consists of a CERBERUS CZ-16 alarm station (zones 3 + 5), 10 heat detectors, 3 manual stations and 4 bells. MONACO transmitter.

122. Bldg # 1226 Offices. System consists of a CERBERUS CZ-16 alarm station (zones 5 + 3), 14 heat detectors, 2 heat detectors water-proof, 14 smoke detectors above ceiling, 1 duct smoke detector, total of 14 detectors placed over 3 meters, 14 repeaters, 3 air dampers, 2 switches, 5 manual stations and 4 alarm bells. MONACO transmitter.

123. Bldg # 1227 SFS Storage. System consists of a NOTIFIER AM-1000 (1 loop), 18 heat detectors, 4 smoke detectors on ceiling, 2 smoke detectors above ceiling, 2 repeaters, 5 manual stations, 2 acoustic/optical warning devices, 2 input modules, 1 output module, total of 18 detectors placed over 4 meters. MONACO transmitter.

124. Bldg # 1230 Old offices. System consists of 12 input modules (5 zones), 1 heat detector water-proof, 26 heat detectors, 26 smoke detectors above ceiling, total of 26 detectors placed over 3 meters, 26 repeaters, 1 output module, 1 gas leak detector, 1 solenoid valve, 8 manual stations, 1 siren/strobe light and 4 bells. System connected to transmitter moved at addition.

125. Bldg # 1230 New addition. System consists of a NOTIFIER AM-2000 (1 loop), 16 heat detectors, 1 heat detector with water protection, 13 smoke detectors above ceiling, total of 13 detectors placed over 3 meters, 13 repeaters, 3 manual stations and 2 siren/strobe lights. MONACO transmitter.

126. Bldg # 1231 Offices. System connected alarm station at Bldg 1230, consists of 2 zones, 13 heat detectors above ceiling, 2 heat detector water-proof, 13 smoke detectors above ceiling, total of 28 detectors placed over 3 meters and 1 manual station.

127. Bldg # 1234 Flying Training Center. System consists of a FCI alarm station (2 zones), 1 heat detector water-proof, 3 heat detectors explosion-proof, 1 smoke detector on ceiling, total of 5 detectors placed over 3 meters, 1 manual station, 3 manual stations explosion-proof, 1 alarm bell and 3 alarm bells explosion-proof. MONACO transmitter.

128. Bldg # 1243 Electric Substation. System consists of a THERMOSTICK MAR-1 alarm station (zones 3+2), 8 heat detectors, 4 smoke detectors on ceiling, total of 12 detectors placed over 3 meters, 4 manual stations and 4 bells. MONACO transmitter.

129. Bldg # 1270 Offices and work shop. System consists of a COE CLERICI alarm station (4 zones), 2 heat detector water-proof, 9 heat detectors, 1 heat detector above ceiling, 2 smoke detectors on ceiling, 1 duct smoke detector, total of 4 detectors placed over 4 meters, 5 manual stations, 2 siren/strobe light and 1 bell. MONACO transmitter.

130. Bldg # 1302 New Control Tower. Automatic detection system consists of ZETLER mod. SOLO alarm station (2 loops), 1 additional power supply, 26 smoke/heat detector on ceiling, 11 smoke/heat detectors in the tunnel, 20 smoke/heat detectors above ceiling, 20 repeaters, 14 acoustic/optical warning devices, 23 manual stations, 12 input modules, and 20 output modules. MONACO transmitter.

131. Bldg # 1302 New Control Tower. Connected on main fire alarm panel there is also an automatic fire suppression system using ARGON consisting of 4 NOTIFIER mod. USD-N control stations (2nd, 5th, 7th, and 9th floor), each panel has a manual activator, leading total of 9 optic warning devices, and total of 8 inhibiting switches on doors and windows. Each system is independent but upon activation all warning devices will operate through the entire facility. Each USD-N controls equivalent extinguishing product discharge valves and individual air dampers on ventilation system. At each floor, upon first detector activation particular warning signal is generated, second activated detector will start a 30 seconds count down (allowing occupants lo leave room) after which extinguishing product discharge occurs. Also manual push button on USD-N will initiate the 30 seconds count down; discharge will be inhibited if door or window is left open.

132. Bldg # 1305 Electric Substation. System consists of a THERMOSTICK MAR-1 alarm station (zones 3+2), 17 heat detectors, 5 smoke detectors on ceiling, total of 22 detectors placed over 3 meters, 6 manual stations, 2 siren/strobe lights and 3 bells. MONACO transmitter.

133. Bldg # 1307 RAPCON. System consists of a NOTIFIER S-5000 alarm station (15 zones), 17 smoke detectors on ceiling, 27 smoke detector above ceiling, 15 smoke detectors under floor, 2 duct smoke detectors, total of 44 detectors placed over 3 meters, 47 repeaters, 7 manual station, 8 siren/strobe lights and 5 strobe light. MONACO transmitter.

134. Bldg # 1325 31 CS. System consists of a THERMOSTICK alarm station (zones 6 + 2), 3 heat detectors, 5 heat detectors waterproof, 1 heat detector explosion proof, 8 smoke detectors on ceiling, 1 duct smoke detector, 5 manual stations and 4 alarm bells. MONACO transmitter.

135. Bldg # 1328 31 CS. System is connected to transmitter at Bldg 1325, it consists of a CERBERUS CZ-16 alarm station (zones 4 + 4), 6 heat detectors, 6 smoke detectors on ceiling, 2 manual station and 3 bells.

136. Bldg # 1333 Entomology. System consists of a CERBERUS CZ-16 alarm station (zones 5 + 3), 15 heat detectors, 5 smoke detectors above ceiling, 6 duct smoke detectors, total of 9 detectors placed over 3 meters, total of 5 detectors placed over 4 meters, 5 repeaters, 3 flame detectors, 1 air damper, 2 switches, 6 manual stations and 5 alarm bells. MONACO transmitter.

137. Bldg # 1334 Hazard Accumulation Point. System is 220 V and it consists of 2 manual stations waterproof, 2 alarm bells, without transmitter.

138. Bldg # 1335 603rd AFCS. System consists of a NOTIFIER S-5000 alarm station (zones 10 + 6), 1 heat detector waterproof, 1 smoke detector on ceiling, 39 smoke detectors above ceiling, 1 duct smoke detector, total of 40 detectors placed over 4 meters, 39 repeaters, 2 switches, 6 manual stations and 8 alarm bells. MONACO transmitter.

139. Bldg # 1338 Golf storage. System consists of a THERMOSTICK alarm station (zones 2 + 1), 6 heat detectors, total of 6 detectors placed over 4 meters, 2 manual stations and 2 alarm bells. MONACO transmitter.

140. Bldg # 1341 Electric Substation. System consists of a NOTIFIER S-500 alarm station (zones 2 + 6), 1 smoke detector on ceiling, 1 manual station and 1 siren/strobe light. MONACO transmitter.

141. Bldg # 1342 603rd Offices. System consists of a NOTIFIER S-5000 alarm station (zones 7 + 9), 1 heat detector waterproof, 1 smoke detector on ceiling, 36 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 38 detectors placed over 4 meters, 2 switches, 6 manual stations and 6 alarm bells. MONACO transmitter.

142. Bldg # 1360 Head Quarters. System consists of a COE CLERICI alarm station (17 zones), 80 heat detectors, 8 heat detectors waterproof, 1 smoke detector on ceiling, 45 smoke detectors above ceiling, 3 duct smoke detectors, total of 3 detectors placed over 3 meters, total of 55 detectors placed over 4 meters, 45 repeaters, 7 air dampers, 1 switch, 8 manual stations and 12 alarm bells. MONACO transmitter.

143. Bldg # 1360 C.P. Command Post. System is connected to transmitter at Bldg 1360, it consists of a THERMOSTICK alarm station (5 zones), 21 heat detectors, 12 smoke detectors above ceiling, 15 smoke detectors under floor, 2 duct smoke detectors, total of 12 detectors placed over 3 meters, 28 repeaters, 1 switch, 6 manual stations and 9 alarm bell.

144. Bldg # 1360 W.T. Wing Tip. System consists of a THERMOSTICK MAR-1A (11 zones), 23 heat detectors, 2 smoke detectors on ceiling, 23 smoke detectors above ceiling, total of 25 detectors placed over 3 meters, 23 repeaters, 1 switch, 3 manual stations and 7 siren/strobe lights. MONACO transmitter.

145. Bldg # 1362 Offices. System consists of a THERMOSTICK alarm station (7 zones), 17 heat detectors, 4 heat detectors waterproof, 1 smoke detector on ceiling, 12 smoke detectors above ceiling, 1 duct smoke detector above ceiling, total of 1 detector placed over 3 meters, total of 12 detectors placed over 4 meters, 12 repeaters, 1 air damper, 1 switch, 6 manual stations and 7 alarm bells. MONACO transmitter.

146. Bldg # 1379 603rd Offices. System consists of a NOTIFIER S-5000 alarm station (zones 8 + 8), 1 heat detector waterproof, 1 smoke detector on ceiling, 32 smoke detectors above ceiling, 1 duct smoke detectors above ceiling, total of 1 detector placed over 3 meters, total of 31 detectors placed over 4 meters, 1 switch, 4 manual stations and 4 alarm bells. MONACO transmitter.

147. Bldg # 1380 603rd Vehicle Maintenance. System consists of NOTIFIER AM2020 alarm station (2 loop), 2 smoke…