1) Question: Is a HEPA vacuum on site? How wide is the vacuum mouth?

Answer: There is a HEPA vacuum on site with a 24 inch mouth.

2) Question: Does the vaccum have attachments for cleaning the walls?

Answer: There are no wall attachments with the vacuum.

3) Question: Will the Base provide the replacement filters (Pre‐filters and HEPA filters) for the air handling system?

Answer: The contractor must source, buy, and replace these filters.

4) Question: Is the plywood for the Baffles 1/4 inch sheets combined together totaling 1/2 inch of plywood?

Answer: The steel plate should be covered with one sheet of 19 mm (0.75 in) and one sheet of

11 mm (0.4375 in) plywood.