JA-4_Drawings.pdf
PDF 4 MB Posted
- Attached to
- Low Bay Office Lighting FTQW 11-1502 Federal contract opportunity
- Solicitation number
- FA5004-17-B-C005
About this file
JA-4 Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_and_Answers_Low_Bay.pdf | ||
| JA-3_Additional_Construction_Documents.pdf | ||
| FA5004-17-B-C005-0002.pdf | ||
| JA-2_Specifications.pdf | ||
| JA-4_Drawings.pdf | ||
| FA5004-17-B-C005-0001.pdf | ||
| JA-3_Additional_Construction_Documents.pdf | ||
| JA-3_Additional_Construction_Documents.pdf | ||
| JA-5_AF_Form_66.pdf | ||
| JA-6_Wage_Determination.pdf | ||
| JA-2_Specifications.pdf | ||
| FA5004-17-B-C005.pdf | ||
| JA-1_Other_Contract_Requirements.pdf | ||
| JA-4_Drawings.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G
FA5004-17-B-C005-0001 EIELSON AFB, AK ATTACHMENT JA-4 DRAWINGS
NORTH ARROWS
ROOM NUMBER
SCALE
TITLE
SHEET LOCATION
DETAIL NUMBER
A A4
SHEET LOCATION
SECTION NUMBER
DETAIL NUMBER
OFFICE
SHEET LOCATION
A A4
G000 TITLE SHEET
G001 GENERAL INFORMATION
DWG
DRAWING TITLE
SCALE
GOVERNING CODES:
2012 INTERNATIONAL BUILDING CODE - IBC
2012 INTERNATIONAL FIRE CODE - IFC
2015 NFPA 101 LIFE SAFETY CODE
2014 NFPA 70 - NATIONAL ELECTRICAL CODE - NEC
AUTHORITY HAVING JURISDICTION
E001 N/A GENERAL LIGHTING SCHEDULES, CRITERIA AND DETAILS
E101 3110 BUILDING 3110 LIGHTING DEMO PLAN
E201 3110 BUILDING 3110 LIGHTING PLAN
E101 2268 BUILDING 2268 LIGHTING DEMO PLAN
E201 2268 BUILDING 2268 LIGHTING PLAN
E101 3343 BUILDING 3343 MAIN FLOOR LIGHTING DEMO PLAN AREA 1
E102 3343 BUILDING 3343 MAIN FLOOR LIGHTING DEMO PLAN AREA 2
E103 3343 BUILDING 3343 SECOND FLOOR LIGHTING DEMO PLANS
E201 3343 BUILDING 3343 MAIN FLOOR LIGHTING PLAN AREA 1
E202 3343 BUILDING 3343 MAIN FLOOR LIGHTING PLAN AREA 2
E203 3343 BUILDING 3343 SECOND FLOOR LIGHTING PLANS
E101 3303 BUILDING 3303 LIGHTING DEMO PLAN
E201 3303 BUILDING 3303 LIGHTING PLAN
E101 1216 BUILDING 1216 LIGHTING DEMO PLANS
E201 1216 BUILDING 1216 LIGHTING PLANS
E101 1127 BUILDING 1127 LIGHTING DEMO PLAN
E201 1127 BUILDING 1127 LIGHTING PLAN
G
E
ELECTRICAL SYMBOL LEGEND
NOTE KEY - INDICATES NOTES APPLICABLE ON EACH SHEET
A3 LIGHTING FIXTURE TYPE - SEE LIGHTING FIXTURE SCHEDULE
SWITCHES UP 4'-0", UON: SPST; THREE-WAY
PILOT LIGHT SWITCH: LIGHTED IN 'OFF' POSITION
OCCUPANCY SENSOR, CEILING OR WALL UP 7'-6" AFF, UON ('X'=TYPE)
SURFACE OR PENDANT MOUNTED FIXTURE -
SEE LIGHTING FIXTURE SCHEDULE
WALL MOUNTED FIXTURE - SEE LIGHTING FIXTURE SCHEDULE
RECESSED DOWNLIGHT FIXTURE - SEE LIGHTING FIXTURE SCHEDULE
RECESSED OR SURFACE CEILING MOUNTED FIXTURE - SEE LIGHTING
FIXTURE SCHEDULE
FILLED TRIANGLE PATTERN INSIDE DEPICTED FIXTURE, TO INCLUDE
EMERGENCY BALLAST INTEGRAL TO FIXTURE
WALL MOUNTED LINEAR FIXTURE - SEE LIGHTING FIXTURE SCHEDULE
NL INDICATES NIGHT LIGHT FIXTURE - NOT ON SWITCHED CIRCUIT
WALL MOUNTED EMERGENCY FIXTURE - SEE LIGHTING FIXTURE SCHEDULE
EMERGENCY EXIT LIGHTING UNIT WITH ARROWS WHERE SHOWN: CEILING
MOUNTED; WALL MOUNTED - SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD: FLUSH MOUNTED, SURFACE MOUNTED
JUNCTION BOX
WP WEATHERPROOF
UON UNLESS OTHERWISE NOTED
LOW VOLTAGE CONTROL CABLE - OCCUPANCY SENSOR INTERCONNECTIONS
CONCEALED CONDUIT (NOTE A BELOW)
EXPOSED CONDUIT (NOTE A BELOW)
INDICATES HOME-RUN (NUMBER OF ARROWS = NUMBER OF CIRCUITS)
(NOTE B BELOW)
OSX
L
ALL BRANCH CIRCUITS 2#12, 1/2" C. TO 20A., 1P. CIRCUIT BREAKER U.O.N.
e.g. A-30(4 #8, 3/4" C. TO 40/3) INDICATES CIRCUIT BREAKER 30
IN PANEL 'A' FEEDS TO EQUIPMENT FROM A 40 A. 3P. CIRCUIT BREAKER WITH
4 #8 AWG WIRES RUN IN 3/4" CONDUIT.
A. NO. OF WIRES (IF OTHER THAN 2) INDICATED BY NO. OF SLASHES
( = TWO 'HOT' WIRES AND TWO NEUTRAL WIRES )
B. HOME-RUN DESIGNATION: 'A' = PANELBOARD NOTATION, '-2,4' = CIRCUIT
NUMBERS
C. INSTALL INSULATED GROUNDING CONDUCTOR, SIZED IN ACCORDANCE
WITH NEC REQUIREMENTS IN ALL FEEDER AND BRANCH CIRCUIT
CONDUITS.
SYMBOLS SHOWN ABOVE ARE DRAWN AS THEY ARE USED ON THE
DRAWINGS TO INDICATE NEW WORK OR NEW LOCATIONS OF EXISTING
EQUIPMENT. EXISTING EQUIPMENT TO BE ABANDONED IN PLACE, REMOVED
OR RELOCATED IS SHOWN USING THE SAME SYMBOLS BUT DRAWN WITH
DASHED LINES.
GENERAL PROJECT NOTES
1. THE PROJECT'S MAIN GOALS ARE TO REPLACE THE EXISTING INEFFICIENT FLUORESCENT (PREDOMINANTLY T12 TYPE) LIGHTING SYSTEMS WITH
NEW ENERGY EFFICIENT AND LONG LIFE LED LIGHTING THROUGHOUT MOST OCCUPIED AREAS OF THE BUILDINGS INCLUDED WITHIN THE
PROJECT.
2. FLUORESCENT BALLASTS WITHIN THE WORK WHICH WILL BE DEMOLISHED HAVE NOT BEEN IDENTIFIED AS TO WHETHER THEY CONTAIN PCB'S OR NOT. CONTRACTOR SHALL TAKE RESPONSIBILITY FOR REMOVAL, TESTING, AND APPROPRIATE DISPOSAL OF THESE BALLASTS REMOVED FROM THE BUILDING. CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR SAFE DISPOSAL OF THE FLUORESCENT LAMPS REMOVED DURING THE DEMOLITION PHASE OF THE PROJECT AND PROVIDE DOCUMENTATION OF PROPER DISPOSAL OF FLUORESCENT LAMPS AND BALLASTS
CONTAINING PCP'S.
2.1. WITHIN THE DEMOLITION DRAWING SOME LIGHTS HAVE NUMBERS ASSOCIATED WITH THEM FROM THE AS-BUILT INFORMATION OR SITE INVESTIGATIONS. THESE NUMBERS ARE INTENDED TO PROVIDE AN ESTIMATED NUMBER OF LAMPS WITHIN THE GIVEN FIXTURE.
- FOR EXAMPLE A 'T2' LIGHT WOULD INDICATE THE LIGHT CONTAIN 2 (FLUORESCENT) LAMPS. THIS WILL ASSIST THE CONTRACTOR IN
DEVELOPING A COST FOR DISPOSAL OF THESE QUANTITY OF LAMPS.
3. EXISTING HOME RUN CIRCUITS TO THE LIGHTING SYSTEM MAY BE RE-UTILIZED AS THE NEW LIGHTING POWER USAGE WILL BE LOWER THAN EXISTING. THESE EXISTING HOME RUN CIRCUITS AND WIRING SHALL REMAIN MOSTLY AS-IS FOR THE WORK. WITHIN THE ROOMS ADDITIONAL WORK WILL BE INCLUDED TO ACCOMMODATE THE NEW LIGHTING AND/OR CONTROLS FOR THESE SYSTEMS.
4. THE CONTRACTOR SHALL PROVIDE NEW CIRCUIT CONDUCTORS AS NEEDED TO SUPPORT FINAL CONNECTIONS TO THE NEW LIGHTS; CONTROLS INCLUDING OCCUPANCY SENSORS AND SWITCHING. WHERE EXISTING CONDUITS ARE SUITABLE FOR ROUTING THE NEW CIRCUIT CONDUCTORS THEY MAY BE RE-USED. WHERE NEW BOXES OR CONNECTIONS REQUIRE NEW CONDUIT SYSTEMS, THE CONTRACTOR SHALL PROVIDE THESE
SYSTEMS TO PRODUCE A FULLY FUNCTIONAL LIGHTING AND/OR CONTROL SYSTEM.
5. CONDUCTORS UTILIZED FOR LOW VOLTAGE CONNECTIONS (FOR EXAMPLE USED IN OCCUPANCY SENSORS AND LOW VOLTAGE 0-10V DIMMING SYSTEMS) MAY UTILIZE PLENUM RATED CABLES FOR THESE INTER-CONNECTIONS AND ARE NOT SPECIFICALLY REQUIRED TO BE ROUTED IN
RACEWAY SYSTEMS. CABLES SHALL HOWEVER BE SUPPORTED PER NEC REQUIREMENTS.
6. LIGHTING FIXTURE WHIPS WHICH PROVIDE BOTH POWER AND LOW VOLTAGE CONTROL FUNCTIONS MAY UTILIZE MC CABLES SPECIFICALLY INTENDED FOR THIS PURPOSE. CONTRACTOR SHALL PROVIDE APPROPRIATE SEPARATION OF THESE SYSTEMS IN THE ASSOCIATED JUNCTION
BOXES AS APPLICABLE TO NEC ARTICLES.
7. CIRCUITS AND PANEL SCHEDULES ASSOCIATED WITH THE LIGHTING WORK SHALL BE TRACED AND VERIFIED PRIOR TO WORK. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL PROVIDE NEW TYPEWRITTEN CIRCUIT IDENTIFICATIONS WITHIN NEW PANELS
SCHEDULES FOR ALL AFFECTED CIRCUITS.
8. FACILITIES INCLUDED WITHIN THIS WORK SHALL REMAIN IN OPERATION THROUGHOUT THE CONSTRUCTION PROCESS AND CONTRACTOR SHALL COORDINATE THE WORK IN SUCH A WAY AS TO MINIMIZE IMPACTS TO NORMAL OPERATIONS FOR THE FACILITIES. THIS COORDINATION MAY INCLUDE AFTER HOURS OR WEEKEND WORK TO ACCOMMODATE THE REPLACEMENT OF THE LIGHTING SYSTEMS. CONTRACTOR SHALL ENSURE THE PROJECT AREAS ARE CLEANED UP AND OPERATIONAL FOR BUILDING USERS AS REQUIRED TO MINIMIZE THESE IMPACTS.
9. NEW EXTERIOR LIGHTS SHOWN ON DRAWINGS ARE TO REPLACE EXISTING LIGHTS WHERE INSTALLED. WHERE NO EXISTING LIGHTS EXIST NO ADDITIONAL WORK WILL BE INDICATED FOR THE BUILDING WITH EXCEPTION OF ADDITIONAL EXTERIOR EMERGENCY EGRESS LIGHTING WHICH IS
REQUIRED BY CODE.
10. ROOM NUMBERS NOTED ON DRAWINGS WERE ASSIGNED USING AVAILABLE AS-BUILT INFORMATION AND OTHER SOURCES, BUT MAY NOT MATCH SPECIFICALLY THE NUMBERING CONVENTION WITHIN THE ACTUAL FACILITY. THESE NUMBERS WERE USED TO COORDINATE LIGHTING CALCULATIONS WITH THE ROOMS IN THE DESIGN EFFORT. THE CONTRACTOR SHALL COORDINATE WITH EACH FACILITY ON THE SPECIFIC NUMBERING OR LETTERING CONVENTION AND ROOM NAME ALLOCATIONS FOR THE SPACES AFFECTED BY THE CONSTRUCTION EFFORT AND AS
BUILT THESE IDENTIFICATIONS ON THE REDLINED DRAWINGS.
11. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURES THROUGHOUT ARE IS INTENDED TO DEPICT THE APPROXIMATE NUMBER OF T12 OR T8 LAMPS WHICH WILL NEED TO BE DISPOSED OF AS PART OF THE WORK; I.E F2 = 2-LAMPS, F3= 3 LAMPS, ECT... T5 TYPE LAMPS ARE IDENTIFIED WITH AN 'H' PREFIX. LIGHTS WITHOUT ANY ID ARE EITHER HID OR INCANDESCENT LAMPS WITH NO SPECIAL DISPOSAL REQUIREMENTS
12. PROVIDE ARCHITECTURAL DEMOLITION REQUIRED TO ACCOMMODATE NEW WORK.
13. WHERE FINISHES CALL TO 'MATCH EXISTING': MATERIAL, FINISH AND COLOR TO MATCH EXISTING ADJACENT MATERIAL, FINISH AND COLOR TO
THE GREATEST EXTENT POSSIBLE.
14. WHERE LIGHTING FIXTURES ARE DEMOLISHED AT ACOUSTIC CEILING TILE GRIDS TO REMAIN: PROVIDE PROVIDE INFILL ACOUSTIC TILE AT
REMOVED FIXTURE LOCATION; CEILING TILE TO MATCH EXISTING.
15. WHERE LIGHTING FIXTURES ARE DEMOLISHED AT HARD LIDS AND NEW FIXTURES DON'T COVER THE EXISTING PENETRATIONS OR DEMOLISHED LIGHT FIXTURE FOOTPRINT COMPLETELY: PATCH, REPAIR, AND REFINISH SURFACES TO MATCH EXISTING.
15.1. IF 50% OF FIXTURE PENETRATIONS AT ROOM ARE BEING PATCHED, PAINT ENTIRE CEILING AREA OF ROOM.
15.2. IF MORE THAN 50% OF FIXTURE PENETRATIONS REQUIRE NO WORK, BLEND PAINTED AREA OF PATCHED LOCATIONS TO MATCH EXISTING, APPROXIMATELY 4SF PER LOCATION.
16. WHERE WALL MOUNTED LIGHT FIXTURES ARE DEMOLISHED: PATCH, REPAIR, AND PAINT WALL TO MATCH EXISTING.
16.1. IF THREE OR MORE FIXTURE PATCHES OCCUR ON ONE WALL, PAINT ENTIRE AREA OF WALL TO MATCH EXISTING.
16.2. IF LESS THAN THREE FIXTURE PATCHES ARE REQUIRED ON ONE WALL, BLEND PAINTED AREA OF PATCHED LOCATION TO MATCH EXISTING, APPROXIMATELY 4SF PER LOCATION.
17. WHERE PENDANT LIGHTS ARE REMOVED AND/OR REPLACED, NEW CEILING FINISHES ARE NOT REQUIRED.
LIGHTING FIXTURE SCHEDULE
TYPE NOMINAL
POWER
LUMEN
CCT
DESCRIPTION MOUNTING
HEIGHT
BASIS OF DESIGN
A1 20W 2,380 4000K
2'X4' RECESSED LAY-IN FLAT PANEL LED
TROFFER WITH EVENLY DISPERSED LOW
GLARE ILLUMINATION OVER THE FACE OF
THE LIGHT, 120-277V DIMMABLE.
RECESSED
CEILING
DECO
SFP-LED-24-20-40-UNV
(PROVIDE EM FOR EMERGENCY
BACKUP OR SMK IF SURFACE MTD)
A2 31W 3,700 4000K
SAME AS A1 WITH HIGHER LUMEN OUTPUT. RECESSED
CEILING
DECO
SFP-LED-24-30-40-UNV
A3 41W 4,800 4000K
SAME AS A1 WITH HIGHER LUMEN OUTPUT. RECESSED
CEILING
DECO
SFP-LED-24-40-40-UNV
B1 20W 2,380 4000K
1'X4' SURFACE MOUNT FLAT PANEL LED
TROFFER WITH EVENLY DISPERSED LOW
GLARE ILLUMINATION OVER THE FACE OF
THE LIGHT, 120-277V DIMMABLE.
RECESSED
CEILING
DECO
SFP-LED-14-20-40-UNV-SMK
(PROVIDE EM FOR EMERGENCY
BACKUP OR SMK IF SURFACE MTD)
B2 31W 3,700 4000K
SAME AS B1 WITH HIGHER LUMEN OUTPUT. RECESSED
CEILING
DECO
SFP-LED-14-30-40-UNV-SMK
B3 41W 4,800 4000K
SAME AS B1 WITH HIGHER LUMEN OUTPUT. RECESSED
CEILING
DECO
SFP-LED-14-40-40-UNV-SMK
C1 20W 2,130 4000K
2'X2' RECESSED LAY-IN FLAT PANEL LED
TROFFER WITH EVENLY DISPERSED LOW
GLARE ILLUMINATION OVER THE FACE OF
THE LIGHT, 120-277V DIMMABLE.
RECESSED
CEILING
DECO
SFP-LED-22-20-40-UNV
(PROVIDE EM FOR EMERGENCY
BACKUP OR SMK IF SURFACE MTD)
C2 30W 3,160 4000K
SAME AS C1 WITH HIGHER LUMEN OUTPUT. RECESSED
CEILING
DECO
SFP-LED-22-30-40-UNV SMK
C3 40W 4,760 4000K
SAME AS C1 WITH HIGHER LUMEN OUTPUT. RECESSED
CEILING
DECO
SFP-LED-22-40-40-UNV SMK
D1 65W 8,100 4000K
ECONOMY 2' HIGH/LOW BAY LED LIGHT
FIXTURE, AREAS WITH MOUNTING HEIGHTS
FROM 10 TO 40 FT, MULTI-VOLT DRIVER.
FROSTED LENS FOR EVEN DISTRIBUTION.
PENDANT DECO
DHL-LP-LED-2-65-40-UNV-F
(PROVIDE EM OPTION AS SHOWN)
D2 90W 11,600 4000K
SAME AS D1 WITH HIGHER LUMEN OUTPUT. PENDANT DECO
DHL-LP-LED-2-90-40-UNV-F
D3 135W 17,050 4000K
SAME AS D1 WITH HIGHER LUMEN OUTPUT. PENDANT DECO
DHL-LP-LED-2-135-40-UNV-F
ER 10.85W
6 VDC
INPUT
COLD WEATHER RATED, ARCHITECTURAL
EMERGENCY LIGHTING REMOTE FIXTURE.
POWERED VIA FIXTURE TYPE 'EX'.
WALL LITHONIA LIGHTING
ELA-AFNR-DB-FWD
ET 5W
6-12 VDC
INPUT
INTERIOR TWIN HEAD ARCHITECTURAL
EMERGENCY LIGHTING REMOTE FIXTURE.
POWERED VIA FIXTURE TYPE 'EX'.
WALL LITHONIA LIGHTING
ELA W T L24 LP03VS
EX 3.3W 17,500
4000K
LED EXIT SIGN WITH WHITE
THERMOPLASTIC HOUSING, GREEN/RED
LETTERING, AND A HIGH-OUTPUT 6V/12W
LEAD-ACID BATTERY. POWERS FIXTURE
TYPE 'ER'.
WALL LITHONIA LIGHTING
LHQM-S-W-3-(G/R)-HO RO
(MATCH LETTERING COLOR FOR
REMAINDER OF EXIT LIGHTS FOR
EACH SPECIFIC FACILITY)
G1 60W 6,700 4000K
4' INDUSTRIAL VAPORTIGHT LED WITH
METAL HOUSING INSIDE A FIBERGLASS
SHELL, MULTI-VOLT DRIVER.
SURFACE
OR
PENDANT
DECO
DWH-LED-6-60-40-UNV
G2 100W 10,875 4000K
4' ENCLOSED VAPOR TIGHT LED WITH
METAL HOUSING INSIDE A FIBERGLASS
SHELL, POLYCARBONATE LENS AND
INTEGRATED MOTION SENSOR,
MULTI-VOLT DRIVER.
SURFACE
OR
PENDANT
DECO
DWP-LED-100-40-UNV-PC-MS
H1 25W 2,560 4000K
4' ROUND SURFACE MOUNT WITH DIE
FORMED CHANNEL AND FROSTED DIFFUSE
LENS, MULTI-VOLT DRIVER.
SURFACE DECO
DACH-LED-4-25-40-UNV-R
H2 35W 3,710 4000K
SAME AS H1 EXCEPT 4' LONG AND WITH
HIGHER OUTPUT.
SURFACE DECO
DACH-LED-4-35-40-UNV-R
H3 45W 5,415 4000K
SAME AS H1 EXCEPT 4' LONG AND WITH
HIGHER OUTPUT.
SURFACE DECO
DACH-LED-4-50-40-UNV-R
J1 35W 3,325 4000K
4' LINEAR SUSPENDED DIRECT LED
LUMINAIRE ACRYLIC DIFFUSER AND
ALUMINUM BODY, MULTI-VOLT DRIVER.
PENDANT DECO
BEAM-LED-4-35-()-40-UNV
J2 45W 4,275 4000K
SAME AS J1 WITH HIGHER LUMEN OUTPUT PENDANT DECO
BEAM-LED-4-45-()-40-UNV
M1 18W 1,500 4000K
6" LED RETROFIT CAN LIGHT FOR
INSTALLATION IN EXISTING HOUSING,
120-277V
RECESSED DECO
DLED-E-RET-6-18-40-UNV
N1 137W 25,100 4000K
LOW PROFILE HIGH BAY FIXTURE WITH
POLYCARBONATE LENS AND ALUMINUM
HEAT SINKS. MULTI-VOLT DRIVER.
PENDANT
+35' GYM
+16' POOL
LUMAX
HBRLED251L4K24-9CP
N2 460W 59,000 4000K
SIMILAR TO N1, BUT DIFFERENT LUMEN
OUTPUT.
PENDANT
+35' AFF
LUMAX
HBRLED629L4K48-9CP
N3 69W 9,400 4000K
SIMILAR TO N1, BUT DIFFERENT LUMEN
OUTPUT.
PENDANT
+35' GYM
LUMAX
HBRLED94L4K24-9CP
NE 137W 25,100
4000K
SAME AS N1, BUT ONLY USED FOR
EMERGENCY OPERATIONS
PENDANT
+35' GYM
LUMAX
HBRLED251L4K24-9CP
R1 15W 1,077 4000K
OUTDOOR GENERAL PURPOSE ROUND
CAST LED FLUSH MOUNT FIXTURE, 120V
SURFACE LITHONIA
OLCFM 15 WH
S1 30W 3,045 4000K
MEDIUM WALL PACK LED LIGHT WITH
ALUMINUM BODY, MOUNTED ABOVE DOOR,
120-277V WITH PHOTOCELL OPTION.
SURFACE DECO DECO-LED-30-40-UNV-BZ-PC
T1 94W 9,500 4000K
2X4 RECESSED FIXTURE FOR
RACQUETBALL COURT INSTALLATION,
TEMPERED GLASS LENS AND HEAVY DUTY
ALUMINUM HOUSING, MULTI-VOLT DRIVER.
RECESSED
CEILING
1ST SOURCE LIGHTING
RSD RCFM24 494 40 OTG U
(PROVIDE EM OPTION WHERE
SHOWN ON DRAWINGS)
U1 15W 1,240 4000K
SURFACE MOUNT RETROFIT KIT FOR
MOUNTING TO JUNCTION BOXES AND
INCLUDES TRIM RING, 120V.
SURFACE
CEILING
DECO
DLED-FRET-6-15-40-120-WH-RM
V1 30W 3,050 4000K
VANDAL RESISTANT CANOPY LIGHT WITH
SYMMETRICAL DISTRIBUTION AND MULTI
LEVEL MOTION SENSING CONTROL,
MUTLT-VOLT DRIVER.
SURFACE
CEILING
DECO
D536-LED-30-40-UNV-BL-BI-MSL2
W1 30W 3,040 4000K
QUARTER SPHERE WALL LIGHT WITH TYPE
IV DISTRIBUTION PHOTOCELL, MULTI-VOLT
DRIVER AND EM BACKUP.
SURFACE
WALL
DECO
D441-LED-30-40-UNV-BL-T4-BL-PC-EM
X1 29W 3,000 4000K
HALF-ROUND VERTICAL WALL SCONCE
WITH LED ELEMENTS AND MULTI-VOLT
DRIVER, GRAPHITE METALLIC COLOR.
SURFACE
WALL
SHAPER
673-37-W-L840-UNV-GRM
INV-250 & INV-400 EMERGENCY LIGHTING INVERTER UNITS:
INVERTERS FOR EMERGENCY LIGHTS BASIS OF DESIGN ARE PHILLIPS BODINE ELI-S-250 AND ELI-S-400 UNITS.
EMERGENCY LIGHTING REMOTE HEAD UNIT
SWITCH CONTROL FOR EXTERIOR LIGHTSEXT
Donald L. Hopkins
No. EE10582
ITEMS TYPICALLY SHOWN ON DEMOLITION
DRAWINGS WITH LIGHT DASHED LINES ARE TO BE
DEMOLISHED AS PART OF THE WORK UNLESS
SPECIFICALLY NOTED ON DRAWING FOR REUSE (R)
EXISTING TO REMAIN(E)
CABLE VAULT AREA
WITH WALL MOUNT
INCANDESCENT GLOBES
AND METAL PROTECTIVE
COVERS TO REMAIN
STORAGE/
ELECTRIC
MECH RM
BACKUP
POWER
OFFICE
112 ROOM
ROOM
VESTIBULE
V2
HALLWAY
H1
HALL
H2
VESTIBULE
V1
RESTROOM
JANITOR
RESTROOM
STORAGE
OFFICE
MECH
ROOM
VAULT
105ASTORAGE
SERVERS/
SWITCHES
106a
HALLWAY
H3
SERVERS/
SWITCHES
106c
CEILING GRID IN THIS AREA
TO BE DEMOLISHED
PANEL 'C'
PANEL 'M'
PANEL 'BATT ROOM'
PANEL 'GM'
PANEL 'MDP'
PANEL 'GMDP'
CT CAN & METER
SHUNT TRIP
PANEL 'D' &
DISCONNECT THROUGH WALL ABOVE
CEILING VENTS (TYP)
PANEL '??'
PANEL '??'
PANEL 'B'
SERVERS/
SWITCHES
106b
H4 FIXTURES IN THIS AREA USE T5HO LAMPS
E101
BUILDING 3110 LIGHTING DEMO PLAN
1/4"=1'-0"
E
GENERAL NOTES
1. THE EXISTING CEILING GRID AND ANY LAY-IN TILES IN ROOM 106b TO BE REMOVED BY THE CONTRACTOR AND DISPOSED OF. COORDINATE THIS
WORK TO HAVE THE MINIMAL IMPACTS TO THE NORMAL OPERATIONS OF THE FACILITY DURING THIS DEMOLITION EFFORT. EXISTING LIGHTING MAY REMAIN FOR USE AS TEMPORARY LIGHTING IF SUPPORTED BY OTHER MEANS THAN THE CEILING GRID DURING THIS EFFORT. CONTRACTOR TO ALSO TAKE CARE TO MINIMIZE THE DEBRIS WHICH MAY HAVE COLLECTED ON THESE TILES FROM ENTERING THE SENSITIVE ELECTRONIC EQUIPMENT BELOW OR IMPACTING THE COMMUNICATIONS CABLES IN THE AREA. CONTRACTOR SHALL PROVIDE DROP CLOTHS OR OTHER PROTECTION NEEDED SO THE EQUIPMENT IS PROTECTED. NOTE NORMAL PLASTIC SHEETS MAY INTRODUCE STATIC WHEN DEPLOYED OR REMOVED SO THIS NEEDS TO BE
TAKEN INTO ACCOUNT WHEN THE PROTECTION IS SELECTED.
2. MECHANICAL DUCTS AND DIFFUSERS WHICH ARE CURRENTLY LOCATED WITHIN THE CEILING GRID TO BE INDEPENDENTLY SUPPORTED AND REMAIN
IN PLACE IN THE EXISTING LOCATIONS.
3. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURE IS INTENDED TO DEPICT THE APPROXIMATE NUMBER OF T12 LAMPS WHICH WILL NEED TO BE DISPOSED OF AS PART OF THE WORK; I.E F2 = 2-LAMPS, F3= 3 LAMPS, ECT... T5 TYPE LAMPS ARE IDENTIFIED WITH AN 'H' PREFIX. LIGHTS WITHOUT ANY ID ARE EITHER HID OR INCANDESCENT LAMPS WITH NO SPECIAL DISPOSAL REQUIREMENTS.
Donald L. Hopkins
No. EE10582
A2
A2
A1 A1
A1 A1
A1
A1
A1
A1
A1 A1 A1 A1 A1 A2
A1 A1
A2
A2
B1
H3
H1
A1
(E)
(E)
(E)
(E)
(E)
EX
EX
EX
EX
D1
D1
D1
D1
R1
S1ER
ER
ER
S1
PANEL 'C'
PANEL 'M'
PANEL 'BATT ROOM'
PANEL 'GM'
PANEL 'MDP'
PANEL 'GMDP'
CT CAN & METER
SHUNT TRIP
PANEL '??'
PANEL 'D' &
DISCONNECT
THROUGH WALL ABOVE
CEILING VENTS (TYP)
PANEL '??'
PANEL 'B'
STORAGE/
ELECTRIC
MECH RM
BACKUP
POWER
OFFICE
112 ROOM
ROOM
VESTIBULE
V2
HALLWAY
H1
HALL
H2
VESTIBULE
V1
RESTROOM
JANITOR
RESTROOM
STORAGE
OFFICE
MECH
ROOM
VAULT
105ASTORAGE
SERVERS/
SWITCHES
106a
HALLWAY
H3
SERVERS/
SWITCHES
106c
SERVERS/
SWITCHES
106b
(E)
(E)
E201
BUILDING 3110 LIGHTNG PLAN
1/4"=1'-0"
E
GENERAL NOTES
1. LIGHTING WITHIN THE SERVERS/SWITCHES AREAS CONTAINS A NUMBER OF DUCTS, CABLE TRAYS, EQUIPMENT RACKS AND OTHER EQUIPMENT
WHICH HAVE THE POTENTIAL TO IMPACT THE LOCATION OF THE NEW LIGHTING. THE CONTRACTOR SHALL COORDINATE WITH THE USERS AND ADJUST AS NEEDED THE FINAL LOCATION OF THE LIGHTS SHOWN IN THESE AREAS SO THEY PROVIDE THE OPTIMAL ILLUMINATION OF THE
EQUIPMENT WHICH REQUIRES IT.
2. THE EXISTING CEILING GRID AND ANY LAY-IN TILES IN ROOM 106b TO BE REMOVED BY THE CONTRACTOR AND DISPOSED OF. COORDINATE THIS WORK TO HAVE THE MINIMAL IMPACTS TO THE NORMAL OPERATIONS OF THE FACILITY DURING THIS DEMOLITION EFFORT. EXISTING LIGHTING MAY REMAIN FOR USE AS TEMPORARY LIGHTING IF SUPPORTED BY OTHER MEANS THAN THE CEILING GRID DURING THIS EFFORT. CONTRACTOR TO ALSO TAKE CARE TO MINIMIZE THE DEBRIS WHICH MAY HAVE COLLECTED ON THESE TILES FROM ENTERING THE ELECTRONIC EQUIPMENT BELOW. CONTRACTOR SHALL PROVIDE DROP CLOTHS OR OTHER PROTECTION NEEDED SO THE EQUIPMENT IS PROTECTED. NOTE NORMAL PLASTIC SHEETS MAY INTRODUCE STATIC WHEN DEPLOYED OR REMOVED SO THIS NEEDS TO BE TAKEN INTO ACCOUNT WHEN THE PROTECTION
IS SPECIFIED.
Donald L. Hopkins
HVAC
ENTRY
SERVER
ROOM
NET ADMIN
MECHANICAL
12bOFFICE
OFFICE
OFFICE
MECHANICAL
RESTROOM
106 ECO REPAIR
ROOM
CONFERENCE
OFFICE
OFFICE
OFFICE
ROOM
OFFICE
102ENTRY
RESTROOM
JANITOR
ALCOVE
HELP DESK
MECHANICAL
12a
E101
BUILDING 2268 LIGHTING DEMO PLAN
3/16"=1'-0"
E
GENERAL NOTES
1. THE LIGHT FIXTURES WITHIN THE FACILITY WHICH ARE IDENTIFIED WITH A 'F2' DESIGNATION ARE MEANT TO DESCRIBE THE APPROXIMATE
NUMBER OF T12 LAMPS PRESENT IN THE FIXTURE WHICH WILL NEED TO BE DISPOSED OF IN THE PROJECT. LIGHTS WITHOUT ANY ID ARE
EITHER HID OR INCANDESCENT LAMPS WITH NO SPECIAL DISPOSAL REQUIREMENTS.
Donald L. Hopkins
HVAC
ENTRY
SERVER
ROOM
NET ADMIN
MECHANICAL
12b
OFFICE
OFFICE
OFFICE
MECHANICAL
RESTROOM
ECO REPAIR
ROOM
CONFERENCE
OFFICE
OFFICE
OFFICE
ROOM
OFFICE
ENTRY
RESTROOM
JANITOR
ALCOVE
HELP DESK
MECHANICAL
12a
E201
BUILDING 2268 LIGHTING PLAN
3/16"=1'-0"
E
Donald L. Hopkins
B-13
OPEN OFFICE
B-11
VAULT
LOBBY
B-8
STORAGE
B-5
AB ROOM
ELECTRICAL
ROOM
B-3
STORAGE
B-2
STORAGE
B-1
LOBBY
B-15
CARDIO
GYMNASIUM
B-7
MASSAGE
B-10
STORAGE
B-13b
SECURE
OFFICE
STORAGE
STORAGE
STORAGE
RACQUETBALL 3RACQUETBALL 4
HALL
HALL HALL
B-12
ENTRY
STAIR
STAIR
STAIR
STAIR
E N
TR
Y
E N
TR
Y
B-13c
CASH CAGE
(E)
(E)
(E)
(E)
(E)
(E)
PANEL 'A2'
A2-2,4,6(E) A2-1,3,5
PANEL 'C'
PANEL 'E1'
PANELS 'J' & 'L'
'L' CONTROLLED BY
LIGHTING CONTACTOR
PANEL 'B'
PANEL 'A'
(E)
(E)
E101
BUILDING 3343 GYMNASIUM TO LOBBY FIRST FLOOR DEMO LIGHTING PLAN AREA 1
3/32"=1'-0"
E
GENERAL NOTES
1. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURE IS INTENDED TO DEPICT THE APPROXIMATE NUMBER OF T12 LAMPS WHICH WILL NEED TO BE DISPOSED OF AS PART OF THE WORK; I.E F2 = 2-LAMPS, F3= 3 LAMPS, ECT... LIGHTS WITHOUT ANY ID ARE EITHER HID OR INCANDESCENT LAMPS WITH NO SPECIAL DISPOSAL
REQUIREMENTS.
Donald L. Hopkins
C-1/3
DUMBBELL
ROOM
HOT TUB
SHOWERS
SAUNA
STEAM ROOM
SWIMMING POOL
REST RM
STEAM ROOM
STORAGE
SHOWERS
SAUNA
B-19
AEROBICS
C-11
FREE WEIGHT ROOM
DV
DRESSING ROOM
B-20
OFFICE
H A
LL
LAUNDRY
LOCKER
ROOM
REST RM
B-24
REST RM
REST RM
REST RM
REST RM
REST RM
REST RM
JC
S H
O W
ER
S H
O W
ER
B-23
STORAGE
FRONT DESK
ENTRY
HALL
HALL
L
HALL
HALL
HALL
HALL
HALL
HALL
H A
LL
C-10
STORAGE
LOCKER
ROOM
LOCKER
ROOM
LOCKER
ROOM
LOCKER
ROOM
STAIR
STAIR
STAIR
B-26
OFFICE
POOL DECK
UNDER POOL AREA
F2F2
F2F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2F2F2F2
F2F2F2F2
F2F2
F2
F2
F2
F2
F2
F2
F2
F2
F2 F2 F2 F2 F2
F2 F2 F2
F2
F2 F2
F2
F2
F2
F2
F2
F2 F2
F2
F2F2
PANEL 'D' PANEL 'G'
PANEL 'H'
PANEL 'DA'
PANEL 'HA'
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2 b b b b ba a a a a a
F2
F2 a
LIGHTS ON BOTTOM OF
SOFFIT FOR DUCTS
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2 F2 F2
F2 F2 F2
F2 F2 F2
F2 F2 F2
NL
NL
NL
NL
NL
AREA
ENTERS
MENS
LOCKER
ROOM
AREA
ENTERS
MENS
LOCKER
ROOM
SOFFITSOFFIT
PENDANT LIGHTS FOR POOL AREA
ARE CORD/PLUG CONNECTED (TYP)
(E)
(E)
(E)
(E) (E) (E)
(E)
SWIMMING POOL AREA LIGHTING
CONTROLLED VIA LIGHTING
CONTACTORS AND SWITCHES
E102
BUILDING 3343 LOBBY TO POOL FIRST FLOOR DEMO LIGHTING PLAN AREA 2
3/32"=1'-0"
E
GENERAL NOTES
1. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURE IS INTENDED TO DEPICT THE APPROXIMATE NUMBER OF T12 LAMPS WHICH WILL NEED TO BE DISPOSED OF AS PART OF THE WORK; I.E F2 = 2-LAMPS, F3= 3 LAMPS, ECT... LIGHTS WITHOUT ANY ID ARE EITHER HID OR
INCANDESCENT LAMPS WITH NO SPECIAL DISPOSAL REQUIREMENTS.
Donald L. Hopkins
LIGHT SWITCHES AND INDICATOR LIGHTS FOR
EMERGENCY BALLASTS AND TEST SWITCH
RB2
STORAGE
RB1
STORAGE
STORAGE ROOMS AT COURT LEVEL
VIEWING ROOM AT UPPER LEVEL
RB2
VIEWING
RB1
VIEWING
HALL
IR
MECHANICAL
POOL SEATING
RB2
ENTRY
RB1
ENTRY
RACQUETBALL 1RACQUETBALL2
PANEL 'J'
J-1,3,5 J-2,4,6
VIEWING ROOM AT UPPER LEVEL
PANEL 'G'
THIS AREA ILLUMINATED BY POOL SEATING LIGHTS
BREAK ROOM
STORAGE
UNDER
GYM
SEATING
NL
NL
NL
E103
BUILDING 3343 SECOND FLOOR GYM AREA S DEMO PLAN
3/32"=1'-0"
E
E103
BUILDING 3343 SECOND FLOOR POOL AREA N DEMO PLAN
3/32"=1'-0"
GENERAL NOTES
1. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURE IS INTENDED TO DEPICT THE APPROXIMATE NUMBER OF T12 LAMPS WHICH WILL NEED TO BE DISPOSED OF AS PART OF THE WORK;
I.E F2 = 2-LAMPS, F3= 3 LAMPS, ETC... LIGHTS WITHOUT ANY ID ARE EITHER HID OR INCANDESCENT LAMPS WITH NO SPECIAL DISPOSAL REQUIREMENTS.
SPECIFIC NOTES
Donald L. Hopkins
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2 N2
N2
N2
N2
N2 N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
A3
A3 A3
A3 A3
B1
B1
B1 B1
C2
A2
A2
U1
U1
U1 U1
A2
A2
A2
A2
A2
A2
A2
A2
A2 A2 A2
A2A2
B1
B-13
OPEN OFFICE
B-11
VAULT
LOBBY
B-8
STORAGE
B-5
AB ROOM
ELECTRICAL
ROOM
B-3
STORAGE
B-2
STORAGE
B-1
LOBBY
B-15
CARDIO
GYMNASIUM
B-7
MASSAGE
B-10
STORAGE
B-13b
SECURE
OFFICE
STORAGE
STORAGE
STORAGE
HALL
HALL HALL
B-12
ENTRY
STAIR
STAIR
STAIR
STAIR
E N
TR
Y
E N
TR
Y
B-13c
CASH CAGE
(E)
(E)
(E)
(E)
(E)
T1
T1
T1
T1
T1
T1
T1
T1
RACQUETBALL 3RACQUETBALL 4
(E)
PANEL 'A2'
A2-2,4,6 (E)
A2-1,3,5
T1 c
T1
T1 b
T1
T1 b
T1
T1 a
T1
N2
N2
N2 N2 N2
N1
PANEL 'C'
PANEL 'E1'
A3
A3
A3 A3 A3 A3 A3
A3A3A3A3A3
A3 A3 A3 A3 A3
U1 U1
1 1
V1
V1
V1
V1
V1
C1
C1
V1
W1
N1
N1
PANELS 'J' & 'L'
'L' CONTROLLED BY
LIGHTING CONTACTOR
PANEL 'B'
400W INVERTER
V1
V1
EX
EX
EX
EX
c b b aa b b c a b b c a a a a b b b b
(E)
E201
BUILDING 3343 GYMNASIUM TO LOBBY FIRST FLOOR LIGHTING PLAN AREA 1
3/32"=1'-0"
E
SPECIFIC NOTES
REPLACE PANELS IN COURT CEILING (8 PANELS) WHERE LIGHTING IS NOT RE-INSTALLED TO FILL HOLES FROM DEMOLITION OF FIXTURES. PANELS TO
MATCH ADJACENT PANELS.
N1 TYPE LIGHTING IN GYM AREA TO BE CONNECTED TO EMERGENCY POWER INVERTER TO PROVIDE REQUIRED ILLUMINATION DURING POWER OUTAGES.
THESE LIGHTS PROVIDE REQUIRED ILLUMINATION COVERAGE FOR THE GYMNASIUM AREA INCLUDING THE UPPER SEATING AREAS.
Donald L. Hopkins
A1 A1
N1 N1 N1
N1
N1 N1 N1
N1
C1
HOT TUB
SHOWERS
SAUNA
STEAM ROOM
SWIMMING POOL
REST RM
STEAM ROOM
STORAGE
SHOWERS
SAUNA
C-11
FREE WEIGHT ROOM
DV
DRESSING ROOM
B-20
OFFICE
H A
LL
STORAGE
LOCKER
ROOM
REST RM
REST RM
REST RM
REST RM
REST RM
REST RM
JC
S H
O W
ER
S H
O W
ER
FRONT DESK
ENTRY
HALL
HALL
L HALL HALL
HALL
HALL
HALL
HALL
H A
LL
C-10
STORAGE
LOCKER
ROOM
LOCKER
ROOM
LOCKER
ROOM
LOCKER
ROOM
STAIR
STAIR
STAIR
B-26
OFFICE
POOL DECK
UNDER POOL AREA
G2G2
G2
G1
G2
G2
G1
PANEL 'D'
PANEL 'H'
PANEL 'DA'
PANEL 'HA'
G2
G1
G2 G2G1
G2
G1
G1 G2 G1 G1
NL
NL
NL
NL
A3
A3
A3 A3
A3
A3
A3
A3
A3
A3
A3
A3
A3 A3
A3
A3
A1 A1 A1
A1A1A1
U1
A1 A1
A1 A1
A1
A1 A1
A1
A1 A1
NL NL
NL
A1 A1
A1 A1
A1 A1
A1 A1 A1
A1 A1
A1 A1 A1
A1 A1 A1 A1 A1 A1
LIGHTS ON BOTTOM OF
SOFFIT FOR DUCTS
SOFFITSOFFIT
C-1/3
DUMBBELL
ROOM
B-19
AEROBICS
U1
(E)
(E)
X1 X1
X1
X1
EX
EXEX
EX
EX
EX
AREA
ENTERS
MENS
LOCKER
ROOM
(E) (E)
U1
SWIMMING POOL AREA LIGHTING TO
BE RE-CONNECTED TO EXISTING
CONTROLS VIA LIGHTING
CONTACTORS AND SWITCHES
G2 TYPE LIGHTS HAVE INTEGRAL OCCUPANCY
SENSORS SO DO NOT NEED ADDITIONAL CONTROLS
SWITCH TO REMAIN TO CONTROL NIGHT LIGHT
FIXTURES SO THEY MAY BE TURNED OFF IF DESIRED,
BUT THIS WILL NOT INTERFERE WITH EMERGENCY
CIRCUIT WHICH SHALL BE UNSWITCHED
E202
BUILDING 3343 LOBBY TO POOL FIRST FLOOR LIGHTING PLAN AREA 2
3/32"=1'-0"
E
Donald L. Hopkins
STORAGE ROOMS AT COURT LEVEL
CONNECT TO EXISTING SWITCH
H1
H1
H1 H1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
T1
C1 C1
HALL
IR
MECHANICAL
POOL SEATING
RB1
ENTRY
RB2
ENTRY
RB1
VIEWING
RB2
VIEWING
RB1
STORAGE
RB2
STORAGE
PANEL 'G'
A1
A1 A1
A1
VIEWING ROOM AT UPPER LEVEL
PANEL 'J'
VIEWING ROOM AT UPPER LEVEL
CENTER ROOM AT UPPER LEVEL
X1X1
N1N1N1
250W INVERTER
a b b c a b b cc b b a c b b a
RACQUETBALL 2RACQUETBALL 1
A1
A1 A1
A1 A1
A1
A1
A1 A1
A1A1
A1
J2
J2
J2
J2
J2
J2
J2
J2
J2
STORAGE
UNDER
GYM
SEATING
(E)
(E)
NL
N1
N1
N1
N1
N1
EX
EX
EX
EX
BREAKROOM
E203
BUILDING 3343 SECOND FLOOR GYM AREA S LIGHTING PLAN
3/32"=1'-0"
E
E203
BUILDING 3343 SECOND FLOOR POOL AREA N LIGHTING PLAN
3/32"=1'-0"
Donald L. Hopkins
PANEL 'L4'
PANEL 'L2'
PANEL 'L3'
MAIN DISCONNECT
& 3-PANELS
E101
BUILDING 3303 LIGHTING DEMO PLAN
1/4"=1'-0"
E
GENERAL NOTES
1. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURE IS INTENDED TO DEPICT THE APPROXIMATE NUMBER OF T12 LAMPS WHICH
WILL NEED TO BE DISPOSED OF AS PART OF THE WORK; I.E F = 2-LAMPS, F = 4 LAMPS.
2. ROOMS WHICH HAVE BANKS OF 3-WAY LIGHT SWITCHES NEAR THE ENTRY DOORS TO CONTROL VARIOUS LIGHTS WITHIN THE SPACE AS IDENTIFIED BY THE LETTER (a,b,c,...) WITHIN THE LIGHT FIXTURE. WHERE NO SWITCH APPEARED TO CONTROL THE
LIGHTS, THIS IS IDENTIFIED WITH A 'NS' DESIGNATION WITHIN THE LIGHT FIXTURE.
Donald L. Hopkins
PANEL 'L3'
PANEL 'L2
PANEL 'L4'
MAIN DISCONNECT
& 3-PANELS
E201
BUILDING 3303 LIGHTING PLAN
1/4"=1'-0"
E
Donald L. Hopkins
ROOM
VESTIBULE
ELEV
E1
STAIR
S1
ROOM
ELEV
E2
STAIR
S2
ROOM
ROOM
ELEV
E3
STAIR
S3
ROOM
ELEV
E4
STAIR
S4
ROOM
ELEV
E5
STAIR
S5
ROOM
ELEV
E6
STAIR
S6
ROOM
ELEV
E7
STAIR
S7
ROOM
ELEV
E8
STAIR
S8
ROOM
ELEV
E9
STAIR
S9
ROOM
ELEV
E10
STAIR
S10
ROOM
ROOM
ROOM
ROOM
E101
BLDG 1216 1ST FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 4TH FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 2ND FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 5TH FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 3RD FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 6TH FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 7TH FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 8TH FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 9TH FLOOR DEMO PLAN
3/16"=1'-0"
E101
BLDG 1216 10TH FLOOR DEMO PLAN
3/16"=1'-0"
E101 3/16"=1'-0"
E
GENERAL NOTES
1. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURE IS INTENDED TO DEPICT THE APPROXIMATE NUMBER OF T12 LAMPS WHICH WILL
NEED TO BE DISPOSED OF AS PART OF THE WORK; I.E F2 = 2-LAMPS, F3= 3 LAMPS, ECT...
Donald L. Hopkins
S1
ROOM
VESTIBULE
ELEV
E1
STAIR
S1
ROOM
ELEV
E2
STAIR
S2
ROOM
ROOM
ELEV
E3
STAIR
S3
ROOM
ELEV
E4
STAIR
S4
ROOM
ELEV
E5
STAIR
S5
ROOM
ELEV
E6
STAIR
S6
ROOM
ELEV
E7
STAIR
S7
ROOM
ELEV
E8
STAIR
S8
ROOM
ELEV
E9
STAIR
S9
ROOM
ELEV
E10
STAIR
S10
ROOM
ROOM
ROOM
ROOM
E201
BLDG 1216 1ST FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 4TH FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 2ND FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 5TH FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 3RD FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 6TH FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 7TH FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 8TH FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 9TH FLR LIGHTING PLAN
3/16"=1'-0"
E201
BLDG 1216 10TH FLR LIGHTING PLAN
3/16"=1'-0"
E201 3/16"=1'-0"
E
SPECIFIC NOTES
Donald L. Hopkins
SHOP
SHOP
OFFICE
BREAK
ROOM
STORAGE
OFFICE
OFFICE
RESTROOM
RESTROOM
MECH
ROOM
LOADING
BAY
PARTS
STORAGE
TOOL
ROOM
OFFICE
OFFICE
OFFICE
SHOP
STORAGE
PLAN
LAYOUT
NETWORK
111a
ROOM OPEN TO ABOVE
E101
BUILDING 1127 LIGHTING DEMO PLAN
1/8"=1'-0"
E
GENERAL NOTES
1. THE NUMERICAL DESIGNATION IN THE LIGHT FIXTURE IS INTENDED TO DEPICT THE
APPROXIMATE NUMBER OF T12 LAMPS WHICH WILL NEED TO BE DISPOSED OF AS PART
OF THE WORK; I.E F2 = 2-LAMPS, F3= 3 LAMPS, ETC...
Donald L. Hopkins
SHOP
SHOP
OFFICE
BREAK
ROOM
STORAGE
OFFICE
OFFICE
RESTROOM
RESTROOM
MECH
ROOM
LOADING
BAY
PARTS
STORAGE
TOOL
ROOM
OFFICE
OFFICE
OFFICE
SHOP
STORAGE
PLAN
LAYOUT
NETWORK
111a ROOM OPEN TO ABOVE
E201
BUILDING 1127 LIGHTING PLAN
1/8"=1'-0"
E
Donald L. Hopkins