Attachment_A-Wet_Chemical_Systems_ITM_Tasks.xlsx

XLSX spreadsheet 11 KB Posted

Attached to
Fire Suppression Maintenance
Solicitation number
FA5004-15-T-0008
Issued by

About this file

Attachment A- Wet Chemical Systems

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Wet Chemical Systems ITM Tasks
Ensure all Inspection, Testing & Maintenance performed is accomplished IAW with NFPA 17 Standard for Wet Chemical Extinguishing Systems 09 Edition
FrequencyComponentTaskFinding
Semi-annual1. Piping1. Inspect piping for obstructions

2. Storage Vessels 1. Inspect agent container for condition

2. Verify storage pressure of propellant

3. Agent 1. Verify quantity and quality of agent

4. Actuators 1. Inspect manual actuators for accessibility.

2. Inspect detection devices (fusible links or heat detectors) for contamination, and clean.

3. Test actuation system without agent release

4. Verify interfaces (gas shutoff, power shutoff) operate properly.

5. Certification Tag 1. Ensure a certification tag is attached to the system.