Attachment I - ACE HVAC Salient Characteristics_2_Oct_24.pdf
PDF 56 KB Posted
- Attached to
- 3rd Wing XP ACE HVAC Systems
- Solicitation number
- FA500025QHVAC
About this file
This is a salient characteristics document dated October 2, 2024, detailing technical requirements for eleven 5-ton HVAC/Environmental Control Units (ECUs) for the Department of the Air Force Pacific Air Forces.
The units must provide a minimum 61,000 BTU/HR cooling capacity and 2,000 CFM, with 14-inch diameter integrated supply and return connections. Each unit requires a metal frame cart with all-terrain wheels, braking system, and stacking capability. The ECUs must not exceed dimensions of 65" x 40" x 55" or 700 pounds per unit, and must operate on single phase 50A 125/250V power with a 30-50 foot UL-rated power cord. Additional requirements include an integrated thermostat system with a 20-foot cord, protective controller case, CAT 5 with RJ45 connectors, and flexible supply/return ducts between 5-25 feet in length.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 3rd Wing XP ACE HVAC Systems_Solicitation QandA_3_Jan 2025.docx | DOCX document | |
| ACE_HVAC_Combo.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC System Salient Characteristics 2 October 2024
Quantity: 11 units
Requirements:
- 5-Ton
- Minimum of 61,000 BTU/HR cooling capacity
- Minimum of 2,000 CFM
- ECU must have 14-inch diameter integrated supply and return connections (adaptations acceptable as long as all other salient characteristics are met).
o Each unit must include a 14-inch diameter flexible supply duct and a 14-inch diameter flexible return ducts with a means to securely attach to the inlet and outlet ports of the HVAC, each a minimum of 5-foot in length, no longer than 25 feet
- Equipped with integrated thermostat system/controller with a minimum of 20-foot cord o Controller must be equipped with a protective case for transportation and storage when not in use must be provided for the thermostat/controller
▪ The connection between thermostat/controller and HVAC unit must be CAT
5 with RJ45 connectors
- Each unit must be equipped with a metal frame cart o Cart must be steerable o Be equipped with an integrated braking system o Cart must enable the stacking of multiple HVAC units o Cart must include integrated top rack o Cart must include wheels/tires designed for, and capable of transportation on all terrain environments
▪ Wheels/tires designed for hard surfaces are not acceptable
- ECU total over dimensions must not exceed:
o 65-inches long o 40-inches wide o 55-inches tall
- ECU and all attachments must not exceed total overall weight of 700 pounds per unit
- ECU must only accept Single phase 50A 125/250V power
- ECU must include a minimum of a 30-foot and a maximum of 50-foot, UL-Rated power supply cord with 50A CS6365 plug