Attachment I - ACE HVAC Salient Characteristics_2_Oct_24.pdf

PDF 56 KB Posted

Attached to
3rd Wing XP ACE HVAC Systems
Solicitation number
FA500025QHVAC
Issued by

About this file

This is a salient characteristics document dated October 2, 2024, detailing technical requirements for eleven 5-ton HVAC/Environmental Control Units (ECUs) for the Department of the Air Force Pacific Air Forces.

The units must provide a minimum 61,000 BTU/HR cooling capacity and 2,000 CFM, with 14-inch diameter integrated supply and return connections. Each unit requires a metal frame cart with all-terrain wheels, braking system, and stacking capability. The ECUs must not exceed dimensions of 65" x 40" x 55" or 700 pounds per unit, and must operate on single phase 50A 125/250V power with a 30-50 foot UL-rated power cord. Additional requirements include an integrated thermostat system with a 20-foot cord, protective controller case, CAT 5 with RJ45 connectors, and flexible supply/return ducts between 5-25 feet in length.

View the file

Other files

File Type Posted
3rd Wing XP ACE HVAC Systems_Solicitation QandA_3_Jan 2025.docx DOCX document
ACE_HVAC_Combo.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC System Salient Characteristics 2 October 2024

Quantity: 11 units

Requirements:

- 5-Ton

- Minimum of 61,000 BTU/HR cooling capacity

- Minimum of 2,000 CFM

- ECU must have 14-inch diameter integrated supply and return connections (adaptations acceptable as long as all other salient characteristics are met).

o Each unit must include a 14-inch diameter flexible supply duct and a 14-inch diameter flexible return ducts with a means to securely attach to the inlet and outlet ports of the HVAC, each a minimum of 5-foot in length, no longer than 25 feet

- Equipped with integrated thermostat system/controller with a minimum of 20-foot cord o Controller must be equipped with a protective case for transportation and storage when not in use must be provided for the thermostat/controller

▪ The connection between thermostat/controller and HVAC unit must be CAT

5 with RJ45 connectors

- Each unit must be equipped with a metal frame cart o Cart must be steerable o Be equipped with an integrated braking system o Cart must enable the stacking of multiple HVAC units o Cart must include integrated top rack o Cart must include wheels/tires designed for, and capable of transportation on all terrain environments

▪ Wheels/tires designed for hard surfaces are not acceptable

- ECU total over dimensions must not exceed:

o 65-inches long o 40-inches wide o 55-inches tall

- ECU and all attachments must not exceed total overall weight of 700 pounds per unit

- ECU must only accept Single phase 50A 125/250V power

- ECU must include a minimum of a 30-foot and a maximum of 50-foot, UL-Rated power supply cord with 50A CS6365 plug