1. Can site provide drawings, room layout or elect one-line drawings of existing UPS system?

· No

2. Is existing UPS systems rated at 60kVA?

· Yes

3. Are we reusing existing feeders (input &output) and breakers?

· Yes

4. Is the existing UPS single feed or duel feed?

· Single

5. Is there a loading dock at the building?

· Yes

6. Is the UPS room located on first or second floor? If second floor we need elevator rating capacity?

· First

7. What’s the distance from loading dock to UPS room?

· 0 Feet

8. Is floor protection required during transfer of equipment in building during demo and install?

· No

9. Is there a clear unobstructed path from loading dock to UPS room for demo and install of equipment?

· Yes

10. Is RMP (remote monitor panel) required?

· Yes

11. Is REPO required for the UPS system?

· Yes