Amendment_1_Q&A.pdf
PDF 12 KB Posted
- Attached to
- Rotating Frequency Converter Installation Federal contract opportunity
- Solicitation number
- FA4897-18-Q-0006
About this file
Amendment 1, Questions and Answers
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment_1_Attachment_1.pdf | ||
| Amendment_1_Attachment_7.pdf | ||
| Amendment_1_Attachment_8.pdf | ||
| Amendment_1_Attachment_6.pdf | ||
| Amendment_1_Attachment_3.pdf | ||
| Amendment_1_Attachment_4.pdf | ||
| Amendment_1_Attachment_5.pdf | ||
| Amendment_1_Attachment_2.pdf | ||
| Attachment_2_WD.pdf | ||
| Attachment_3_BAP.pdf | ||
| Attachment_4_SFS_30.pdf | ||
| FA4897-18-Q-0006_RFC_Install_Combo.pdf | ||
| Attachment_1_SOW.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ FA4897-18-Q-0006
Amendment 1
RFC Install--Questions and Answers 28 February 2018
Q. Is this a new installation or replacement of existing Rotating Frequency Converters?
A. This will be a new install. (See Amendment 1_Attachment 1)
Q. What is the Rotating Frequency Converter KVA? (Manufacturer, rated KVA, Frequency, Horizontal or Vertical configuration) A. This will be an install of new Solid State Frequency Converters. The manufacturer is Cavotec INTE US, Inc. They are rated at 125 KVA/100 kW with 60 Hz power at 480 VAC.
Q. Will we be required to form a new concrete pad?
A. They will go on an existing pad. (See Amendment 1_Attachment 2 and Amendment 1_Attachment 3)
Q. If this is a new installation, where is the existing power?
A. Input power for existing Frequency Converters is in an adjacent room to the one being used for install. (See Amendment 1_Attachment 4)
Q. If this is a new installation, we need to know where the output is going to (equipment).
A. Output power is also in adjacent room and consists of eight disconnect switches, four for each frequency converter. Four are connected to breaker boxes inside Frequency Converter shed and run to disconnect switches along back fence. The other four are connected to a breaker box on the back outside of the Frequency converter shed and the connections are right next to the breaker box. (See Amendment 1_Attachment 5, Amendment 1_Attachment 6, Amendment 1_Attachment 7, and Amendment 1_Attachment 8)
Q. Can you please provide a hand sketch with the Power Supply location of the Converter and Output equipment?
Amendment 1_Attachments 1-8.
Q. The room size and if we can use a forklift or will be necessary other systems to lift and place on designated spot?
A. The room is 13' x 36' with overhead doors for forklift access. (Air Force will provide a fork lift and driver to put equipment in place or move as needed)