79 RGS Hard-Wired Power Panel Salient Characteristics.pdf
PDF 191 KB Posted
- Attached to
- 79 RQS - Hangar Aircraft Frequency Converter
- Solicitation number
- FA487725QA482
About this file
This document is a Salient Characteristics specification for a Hard-wired Aircraft Power Panel intended for the 79th RGS (Rescue Group Squadron). The specification details precise electrical requirements for a power panel with specific input and output voltage parameters: 380-480V input (3-phase, 50/60 Hz) with a full load input current of 93A, and an output of 115V L-N / 200V L-L (3-phase, 4-wire, 400 Hz). The required features include a built-in maintenance diagnostic system, digital touch screen control panel, external USB communications port, internal step-up transformer, input surge protection, and an AC output contactor with aircraft safety interlock. Additionally, the specification requires a 1-year warranty and includes accessories such as a 60-foot AC output cable with an aircraft plug and a floor or wall-mounted cable saddle.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS
FOR
Hard-wired Aircraft Power Panel
1.0. SCOPE OF WORK:
All proposed products shall meet or exceed the following minimum specifications outlined in this Salient Characteristics. All items shall be delivered to the 79th RGS.
1.1. PRODUCT PERFORMANCE SPECIFICATION:
Item must meet the following minimum specifications:
SPECIFICATIONS
Headers Please adjust Headers to item requirement
Electrical Requirement:
Input: 380 to 480 V +10%/-15%, 3-phase, 50/60 Hz; full load input current 93 A (at 480 VAC)
Output: 115 V L-N / 200 V L-L, 3-phase, 4-wire, 400 Hz Warranty: 1 Year
Features: Built-in maintenance diagnostic system Digital touch screen control panel External communications port access, front panel USB 208 to 480 V internal step up transformer Input surge protection IAW IEEE C62.41, Category B 5% Max. AC input current distortion, IGBT active front end AC output contactor “connect/disconnect” device with aircraft safety interlock Electronic Operator and Maintenance Manual
Accessories: AC output cable, 60 feet, banded multiple conductors with aircraft plug and safety interlock
Floor or wall-mounted cable saddle
File details come from the government source that posted it. Updated .