FA4855-19-Q-A030
Building 12 Alarm Solicitation
Questions and Government Responses
1. Your drawing shows an entry reader, but no exit reader at the main entrance. Should there also be an exit reader?
Government Response: Exit readers are optional and not required for this requirement.
2. In the “Statement of Work” document:
1.1 Primary Place of Performance Installation will occur on Cannon AFB, NM. Replace
Advantor System with Vindicator IDS and Network into IDS V5 at building 12
North.
There is no IDS V5 in building 12 North, is this referring to the IDS V5 in bulding 12 South?
Government Response: Attachment 1, Statement of Work, was updated to reflect “IDS V5 in building 12 South.”