Revised_Drawing_26_May_16.pdf
PDF 5 MB Posted
- Attached to
- Upgrade Electrical Components, Portales Substation Enclosure Federal contract opportunity
- Solicitation number
- FA4855-16-B-0005
About this file
corrected revised Drawing 26 May 16
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A/C A/E A
AB
ABAN
ABC
ABT
AC
ACK
ACP
ACST
AD
ADDL
ADH
ADJ
AF
AFF
AFG
AGGR
Al
AIC
ALIG
ALT
ALUM
AM
AMB
ANC
AO
AP
APRX
APVD
ARCH
ASSY
AT
ATC
ATM
AUTO
AUX
AVE
AVG
AWG
AWT
B TO B
BAL
BBD
BC
BD
BE
BF
BITUM
BKG
BL
BLDG
BLK
BLKG
BM
BOC
BOD
BOG
BOL
BOP
BOR
BOT
BOU
BP
BRG
BRGP
BRKT
BS
BTU
BTW
BTWLD
BU
BUR
BW
BYP
C TO C
C&G c
CAB
CAP
CAT
CAV
CB
CCB
ccw
CDF
CE
CER
CF
CFL
CHBD
CHO
CHFR
CHH
Cl
CIP
CIPB
CIRC
CJ
CKT
CL
CLG
AIR CONDITIONING
ARCHITECT /ENGi NEER
AMPERE
ANCHOR BOLT
ABANDON
AGGREGATE BASE COURSE
ABOUT
ALTERNATING CURRENT
ACKNOWLEDGE
ACOUSTIC CEILING PANEL,
ASPHALTIC CONCRETE PAVEMENT
ACOUSTIC
ADDENDUM, AREA DRAIN
ADDITIONAL
ADHESIVE
ADJUSTABLE, ADJACENT
AMP FRAME, AMP FUSE
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
AGGREGATE
AREA INLET, ANALOG INPUT
AMPS INTERRUPTING CAPACITY
ALIGNMENT
ALTERNATE, ALTITUDE
ALUMINUM
ACOUSTICAL MATERIAL
AMBIENT
ANCHOR
ANALOG OUTPUT
ACCESS PANEL
APPROXIMATE
APPROVED
ARCHITECTURAL
ASSEMBLY
ACOUSTICAL TILE, AMP TRIP
ACOUSTICAL TILE CEILING
ATMOSPHERE
AUTOMATIC
AUXILIARY
AVENUE
AVERAGE
AMERICAN WIRE GAGE
ACOUSTICAL WALL TILE
BACK TO BACK
BALANCE
BULLETIN BOARD
BASE CABINET, BOTTOM CHORD,
BOLT CENTER, BOLT CIRCLE
BOARD
BOTH ENDS, BELL END
BOTH FACES, BOTTOM FACE,
BLIND FLANGE, BOARD FEET
BITUMINOUS
BACKING
BASE LINE
BUILDING
BLOCK
BLOCKING
BENCHMARK, BEAM
BACK OF CURB
BOTTOM OF DUCT
BOTTOM OF GRILLE
BOTTOM OF LOUVER, BOLLARD
BOTTOM OF PIPE
BOTTOM OF REGISTER
BOTTOM
BOTTOM OF UNIT
BASE PLATE
BEARING
BEARING PLATE
BRACKET
BOTH SIDES
BRITISH THERMAL UNIT
BETWEEN
BUTT WELD
BELL UP, BUILT-UP
BUILT -UP ROOFING
BOTH WAYS
BYPASS
CENTER TO CENTER
CURB AND GUTTER
I
CHANNEL SHAPE, CENTIGRADE, CONDUIT
CABINET
CAPACITY
CATALOG, CATALOGIORY
CAVITY
CATCH BASIN
CONCRETE BLOCK
COUNTER CLOCKWISE
CONTROLLED-DENSITY FILL
CONCRETE EDGE
CERAMIC
CUBIC FEET (FOOT)
COUNTER FLASHING
CHALKBOARD
CHORD
CHAMFER
COMMUNICATION HANDHOLE
CURB INLET
CAST-IN-PLACE
CONCRETE INTERLOCKING PAVER
BALLAST
CIRCULATION, CIRCULAR
CONSTRUCTION JOINT
CIRCUIT
CENTERLINE, CLASS, CLOSE
CEILING
CLKG
CLR
CMH
CMP
CMU
co
COL
COM
COMB
COMM
COMP
CON
CONC
CONN
CONST
CONT
COOR
CORR
CP
CPLG
CRL
csc
CSK
css
CT
CTJ
CTR
CTRL
CVT
cu cw
CY
d D
DB
OBA
DBL
DC
DEG
DEG C
DEG F
DEMO
DEP
DEPT
DET
DI
DIA
DIAG
DIFF
DIM
DISCH
DIST
DIV
DL
DMJ
DMPF
DN
DO
DP
DPDT
DPST
DS
DT
DUP
DWG
DWL
DWR
E
EA
EC
ECC
ED
EDB
EE
EF
EFF
EHH
EIFS
EJ
EL
ELEC
EMBD
EMER
EMH
ENCL
ENGR
ENTR
EOP
EQ
EQUIP
EQUIV
ES
ESEW
EST
EW
EWC
EWEF
EWTB
EXC
EXH
EXP
EXST
EXT
CAULKING
CLEAR
I
COMMUNICATION MANHOLE
CORRUGATED METAL PIPE
CONCRETE MASONRY UNIT
CLEANOUT, CONCRETE OPENING
COLUMN
COMMON
COMBINATION
COMMUNICATION
COMPOSITION, COMPRESSIBLE,
COMPOSITE
CONCENTRIC
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
CORROSIVE, CORRUGATED
CHECKER PLATE, CONTROL POINT
COUPLING
CORROSION-RESISTANT LINING
COMPRESSION SLEEVE COUPLING
COUNTERSINK
CLINIC SERVICE SINK
CERAMIC TILE
CONTRACTION JOINT
CENTER
CONTROL
CULVERT
COPPER, CUBIC
CLOCKWISE
CUBIC YARD
PENNY (NAIL MEASURE)
DEEP, DIFFUSER, DRAIN
DUCT BANK, DECIBEL, DRY BULB
DEFORMED BAR ANCHOR
DOUBLE
DIRECT CURRENT
DEGREE
DEGREE CENTIGRADE
DEGREE FAHRENHEIT
DEMOLITION
DEPRESSED
DEPARTMENT
DETAIL
DROP INLET, DUCTILE IRON, DIGITAL INPUT
DIAMETER
DIAGONAL, DIAGRAM
DIFFERENTIAL, DIFFERENCE
DIMENSION
DISCHARGE
DISTANCE, DISTRIBUTION
DIVISION
DEAD LOAD
DOUBLE MECHANICAL JOINT
DAMP PROOFING
DOWN
DISSOLVED OXYGEN, DIGITAL OUTPUT, DITTO
DEPTH
DOUBLE POLE, DOUBLE THROW
DOUBLE POLE, SINGLE THROW
DOWN SPOUT
DOUBLE TEE, DRIP TRAP ASSEMBLY
DUPLICATE
DRAWING
DOWEL
DRAWER
EAST
EACH, EXHAUST AIR
ELECTRICAL CONTRACTOR
ECCENTRIC
EQUIPMENT DRAIN
ELECTRICAL DUCT BANK
EACH END
EACH FACE
EFFLUENT, EFFICIENCY
ELECTRICAL HANDHOLE
EXTERIOR INSULATION &
FINISH SYSTEM
EXPANSION JOINT
ELBOW, ELEVATION
ELECTRICAL
EMBEDDED
EMERGENCY
ELECTRICAL MANHOLE
ENCLOSURE
ENGINEER
ENTRANCE
EDGE OF PAVEMENT
EQUAL
EQUIPMENT
EQUIVALENT
EACH SIDE, EQUAL SPACE,
EMERGENCY SHOWER
EMERGENCY SHOWER AND EYE WASH
ESTIMATE
EACH WAY, EMERGENCY
EYE/FACE WASH
ELECTRIC WATER COOLER
EACH WAY, EACH FACE
EACH WAY, TOP AND BOTTOM
EXCAVATION
EXHAUST
EXPANSION, EXPOSED
EXISTING
EXTERIOR, EXTERNAL, EXTENSION
B 10/9/2015 100% REVIEW SUBMITTAL
A 9/15/2014 65% DESIGN SUBMITTAL
ISSUE DATE DESCRIPTION
F TO F
F&B
FAB
FB
FBD
FBG
FBM
FBO
FC
FCA
FD
FDC
FDR
FDTN
FE
FEC
FES
FEXT
FF
FG
FH
FIG
FIN
FJT
FL
FLEX
FLG
FLOR
FLR
FLS
FN
FO
FOB
FOC
FOF
FOM
FOS
FOT
FPT
FR
FRP
FRTM
FS
FT
FTG
FUR
FURN
FUT
FV
FW
FWD
FWE
FXTR
G
GA
GAL
GALV
GB
GC
GD
GEN
GFCI
GFMU
GG
GJ
GL
GLB
GND
GP
GR
GRTG
GSB
GT
GVL
GW
GWB
GYP
H
HB
HBD
HC
HD
HDR
HDW
HEX
HGR
HH
HID
HM
HORIZ
HP
HPC
HPS
HPT
HR
HS
HSS
HT
HTG
HV
HVAC
HWD
HWL
HYO
HZ
FACE TO FACE
FACE AND BYPASS
FABRICATE
FLOOR BEAM
FIBERBOARD
FIBERGLASS
I
BOARD FOOT MEASURE
FURNISHED BY OWNER
FLUSHING CONNECTION
FLANGED COUPLING ADAPTER
FLOOR DRAIN
FLEXIBLE DUCT CONNECTION
FEEDER
FOUNDATION
FLANGED END
FIRE EXTINGUISHER CABINET
FLARED END SECTION
FIRE EXTINGUISHER
FAR FACE, FACTORY FINISH, FLAT FACE
FINISHED GRADE
FIRE HYDRANT
FIGURE
FINISH
FLUSH JOINT
FLOW, FLOW LINE
FLEXIBLE
FLANGE
FLUORESCENT
FLOOR
FLASHING, FLUSH
FENCE
FINISHED OPENING, FIBER OPTIC
FLAT ON BOTTOM
FACE OF CONCRETE, FACE OF CURB
FACE OF FINISH
FACE OF MASONRY
FACE OF STUDS
FLAT ON TOP
FEMALE PIPE THREAD
FRAME
FIBERGLASS REINFORCED PLASTIC
FIRE RETARDANT TREATED MATERIAL
FLOOR SINK, FAR SIDE
FEET, FOOT
FOOTING, FITTING
FURRED, FURRING
FURNITURE, FURNISH
FUTURE
FACE VELOCITY
FIELD WELD, FIRE WALL
FORWARD
FURNISHED WITH EQUIPMENT
FIXTURE
GRILLE, GROUND
GAGE (METAL THICKNESS)
GALLON
GALVANIZED
GRAB BAR, GRADE BREAK
GROOVED COUPLING
GUARD
GENERAL
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FACE MASONRY UNIT
GUTTER GRADE
GROOVED JOINT
GLASS
GLASS BLOCK, GLULAM BEAM
GROUND
GUY POLE
GRADE
GRATING
GYPSUM SHEATHING BOARD
GREASE TRAP
GRAVEL
GUY WIRE
GYPSUM WALLBOARD
GYPSUM HARDBOARD
HIGH
HOSE BIBB
HARDBOARD
HANDICAPPED, HOLLOW CORE, HORIZONTAL
CURVE, HORIZONTAL CENTERLINE
HEAD, HOT DIP
HEADER
HARDWARE
HEXAGONAL
HANGER
HAN DH OLE
HIGH-INTENSITY DISCHARGE
HOLLOW METAL
HORIZONTAL
HIGH POINT, HORSEPOWER
HORIZONTAL POINT OF CURVATURE
HIGH-PRESSURE SODIUM
HORIZONTAL POINT OF TANGENCY
HOSE REEL, HOUR
HEADED STUD, HIGH STRENGTH
HOLLOW STRUCTURAL SHAPE
HEIGHT
HEATING
HIGH VOLTAGE
HEATING, VENTILATING AND
AIR CONDITIONING
HARDWOOD
HIGH WATER LEVEL
HYDRAULIC
HERTZ, CYCLES PER SECOND
PROJECT MANAGER TOM FURNE
ID
IE
IF
IH
IMP
IN
INC
INF
INSTR
INSUL
INT
INTR
INV
IPS
IPT
IR
IRR
ISO
JB
JCT
JF
JST
JT
K
KB
KCMIL
KD
KO
KSI
KW
L
LAD
LAM
LATL
LB
LCTB
LDG
LOR
LE
LF
LG
LH
LIN
LIQ
LLH
LLV
LMLU
LNG
LOC
LP
LPS
LR
LT
LTD
LTG
LTL
LTNG
LV
LVL
LVR
LW
LWC
LWL
MA
MACH
MAINT
MAN
MATL
MAX
MB
MBR
MC
MCB
MCJ
MDMJ
MECH
MED
MFR
MH
MIN
MIR
MISC
MJ
ML
MLO
MMB
MO
MOD
MON
MPT
MRGWB
MS
MSL
MT
MU
MULL
MV
MW
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
PROJECT NUMBER 236097
I
INSIDE DIAMETER, INTERIOR DIMENSION
INVERT ELEVATION, FOR EXAMPLE
INSIDE FACE
INTAKE HOOD
IMPACT
INCH
INCLUDE, INCANDESCENT
INFLUENT
INSTRUMENTATION
INSULATION
INTERIOR, INTERSECTION
INTERMEDIATE, INTERIOR
INVERT
IRON PIPE SIZE
INTERNAL PIPE THREAD
INSIDE RADIUS, IRON ROD
IRRIGATION
ISOMETRIC
JUNCTION BOX
JUNCTION
JOINT FILLER
JOIST
JOINT
KIP
KNEE BRACE
THOUSAND CIRCULAR MILS
KNOCK DOWN
KNOCK OUT
KIPS PER SQUARE INCH
KILOWATT
ANGLE, LENGTH, LAVATORY, LINTEL
LADDER
LAMINATE
LATERAL
LAG BOLT, POUND
LIQUID CHALK AND TACK BOARD
LANDING
LEADER
LIFTING EYE
LINEAR FOOT
LONG
LEFT HAND
LINEAR
LIQUID
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LIQUID MARKER LECTURE UNIT
LONGITUDINAL
LOCATION
LOW POINT
LOW-PRESSURE SODIUM
LONG RADIUS
LEFT
LIMITED
LIGHTING
LINTEL
LIGHTNING
LOW VOLTAGE
LAMINATED VENEER LUMBER
LOUVER
LIGHTWEIGHT
LIGHTWEIGHT CONCRETE
LOW WATER LEVEL
MIXED AIR
MACHINED
MAINTENANCE
MANUAL
MATERIAL
MAXIMUM
MACHINE BOLT
MEMBER
MECHANICAL CONTRACTOR,
MECHANICAL COUPLING,
MOMENT CONNECTION
METAL CORNER BEAD
MASONRY CONTROL JOINT
MODIFIED DOUBLE MECHANICAL JOINT
MECHANICAL
MEDIUM
MANUFACTURER
MANHOLE, METAL HALIDE
MINIMUM
MIRROR
MISCELLANEOUS
MECHANICAL JOINT
MASONRY LINTEL
MAIN LUGS ONLY
MEMBRANE
MASONRY OPENING
MODULAR, MODIFY
MONUMENT
MALE PIPE THREAD
MOISTURE-RESISTANT
GYPSUM WALLBOARD
MOP SINK
MEAN SEA LEVEL
MOUNT
MASONRY UNIT
MULLION
MEDIUM VOLTAGE
MONITORING WELL
N
NA
NAT
NC
NEG
NF
NIC
NO
NOM
NPS
NPT
NS
NTS
NWL
0 TO 0
OA
oc
OCPD
OD
OED
OF
OFCI
OFOI
OG
OH
OPNG
OPP
OPT
OR
ORD
ORIG
OVFL
OVHG
oz p
PA
PAR
PB
PBD
PC
PCC
PCF
PCT
PE
PED
PEN
PERF
PERM
PERP
PF
PFMU
PH
Pl
PKG
PL
PLAS
PLAT
PLBG
PLF
PNEU
POL
POS
pp
PRC
PREF
PREFAB
PRELIM
PREP
PRES
PRI
PROP
PROT
PS
PSF
PSI
PSIA
PSIG
PST
PT
PTN
PVC
PVMT
PWD
PWJ
PZ
Q
QT
QTR
QTY
QUAL
I
NORTH, NEUTRAL
NOT APPLICABLE
NATURAL, NATIONAL
NORMALLY CLOSED
NEGATIVE
NEAR FACE, NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN, NUMBER
NOMINAL
NOMINAL PIPE SIZE
NATIONAL PIPE THREAD
NEAR SIDE
NOT TO SCALE
NORMAL WATER LEVEL
OUT TO OUT
OUTSIDE AIR, OVERALL
ON CENTER
OVER CURRENT PROTECTION DEVICE
OUTSIDE DIAMETER
OPEN END DUCT
OUTSIDE FACE, OFFICE FURNISHING
OWNER FURNISHED CONTRACTOR
INSTALLED
OWNER FURNISHED OWNER INSTALLED
ORIGINAL GROUND
OVERHEAD
OPENING
OPPOSITE
OPTIONAL
OUTSIDE RADIUS
OVERFLOW ROOF DRAIN
ORIGINAL
OVERFLOW
OVERHANG
OUNCE
PAINT
PUBLIC ADDRESS
PARALLEL, PARAPET
PANIC BAR, PULL BOX
PARTICLE BOARD
POINT OF CURVE, PIECE, PRECAST
POINT OF COMPOUND CURVATURE
POUNDS PER CUBIC FOOT
PERCENT
PLAIN END
PEDESTAL
PENETRATION
PERFORATED
PERMANENT
PERPENDICULAR
POWER FACTOR
PREFACED MASONRY UNIT
PHASE
POINT OF INTERSECTION
PACKAGE
PLATE, PROPERTY LINE,
PRECAST LINTEL
PLASTER
PLATFORM
PLUMBING
POUNDS PER LINEAR FOOT
PNEUMATIC
POLISH
POSITIVE, POSITION
POLYPROPYLENE, POWER POLE
POINT OF REVERSE CURVATURE
PREFINISHED
PREFABRICATED
PRELIMINARY
PREPARE
PRESSURE
PRIMARY
PROPERTY, PROPOSED
PROTECTION
PIPE SUPPORT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH ABSOLUTE
POUNDS PER SQUARE INCH GAGE
PRESTRESSED
POINT, POINT OF TANGENCY
PARTITION
POLYVINYL CHLORIDE, POINT OF
VERTICAL CURVE
PAVEMENT
PLYWOOD
PLYWOOD WEB JOIST
PIEZOMETER
RATE OF FLOW
QUARRY TILE
QUARTER
QUANTITY
QUALITY
R&R R&S R
RA
RB
RCPT
RD
REC
RECD
RECT
RED
REF
REINF
REM
REQD
RESIL
RET
REV
RF
RFG
RFL
RGH
RGS
RGS-PVC
RH
RL
RLFA
RND
RNG
RO
ROW
RPM
RR
RSP
RT
RVT
RY
s
SA
SAMU
SAN
SB
SC
SCH
SCH EM
SCN
SE
SEC
SECT
SEP
SF
SG
SH
SHT
SHTG
SIL
SIM
SJ
SL
SLTD
SLV
SMLS
SOG
SP
SPA
SPEC
SPLY
SPST
SPT
SQ
SR
SS
SST
ST
STA
STD
STIF
STIR
STL
STOR
STR
SUB
sue
SUSP
SY
SYM
SYMM
SYN
SYS
T&B T&G T
TA
TAN
TBM
TCE
TEF
TEMP
THD
THK
THRESH
TKBD
CANNON AFB
I
REMOVE AND REPLACE
REMOVE AND SALVAGE
RADIUS, REGISTER, RISER
RETURN AIR
RESILIENT BASE, ROCK BERM
RECEPTACLE
ROOF DRAIN
RECESS
RECEIVED
RECTANGULAR
REDUCER
REFERENCE
REINFORCING
REMOVE
REQUIRED
RESILIENT
RETAINING, RETURN
REVISION, REVERSE
RESILIENT FLOORING
ROOFING
REFLECTED, REFLECTOR
ROUGH
RIGID GALVANIZED STEEL
PVC COATED RGS
RELIEF HOOD, RIGHT HAND,
RELATIVE HUMIDITY
REQUIRED LAP
RELIEF AIR
ROUND
RUNNING
ROUGH OPENING
RIGHT-OF-WAY
REVOLUTIONS PER MINUTE
RAILROAD
ROCK SLOPE PROTECTION
RIGHT
RESILIENT VINYL TILE
READY
SOUTH, SINK
SUPPLY AIR
SOUND-ABSORBING MASONRY UNIT
SANITARY
SPLASH BLOCK
SOLID CORE
SCHEDULE
SCHEMATIC
SCREEN
STEEL/ALUMINUM EDGE
SECONDARY, SECONDS
SECTION
SEPARATE
SQUARE FOOT, SILT FENCE
SHEET GLASS, SEALANT GROOVE
SHOWER
SHEET
SHEATHING
SILENCE
SIMILAR
SLAB JOINT
SLOPE, STEEL LINTEL
SLOTTED
SLEEVE
SEAMLESS
SLAB ON GRADE
SOUNDPROOF, STANDPIPE
SPACING
SPECIFICATION
SUPPLY
SINGLE POLE SINGLE THROW
SET POINT
SQUARE
SHORT RADIUS
SERVICE SINK
STAINLESS STEEL
STREET
STATION
STANDARD
STIFFENER
STIRRUP
STEEL
STORAGE
STRUCTURAL, STRAIGHT
SUBSTITUTE
SUCTION
SUSPENDED
SQUARE YARD
SYMBOL
SYMMETRICAL
SYNTHETIC
SYSTEM
TOP AND BOTTOM
TONGUE AND GROOVE
TILE, TREAD
TOILET ACCESSORY, TEMPERED AIR
TANGENT
TEMPORARY BENCHMARK
TEMPORARY CONSTRUCTION EASEMENT
TROWELED EPOXY FLOORING
TEMPORARY, TEMPERATURE
THREAD
THICK
THRESHOLD
TACK BOARD
TOB
TOC
TOD
TOF
TOG
TOL
TOM
TOP
TOPO
TOS
TOW
TP
TPD
TPG
TR
TRANS
TRD
TYP
u
UG
ULT
UNFN
UNO
UTIL
v
VA
VAC
VAR
VB
VC
VCP
VCT
VEL
VENT
VERT
VERTS
VG
VIF
VIN
VOL
VPC
VPI
VPT
vs
VTR
vwc
W/ W/O w
WB
WC
WD
WF
WG
WH
WI
WL
WLD
WM
WP
WS
WSCT
WT
WTHP
WWF
XP
XS
XSECT
XXS
YH
YS
I 8
TOP OF BOLT, TOP OF BANK,
TOP OF BEAM, TOP OF BERM
TOP OF CURB, TOP OF CONCRETE
TOP OF DUCT
TOP OF FOOTING
TOP OF GRATING
TOLERANCE, TOP OF LEDGER
TOP OF MASONRY
TOP OF PLATE
TOPOGRAPHY
TOP OF SLAB, TOP OF STEEL,
TOE OF SLOPE
TOP OF WALL
TOILET PARTITION, TELEPHONE POLE,
TOE PLATE, TRAP PRIMER
TOILET PAPER DISPENSER
TOPPING, THROUGH PLATE GIRDER
TRANSOM
TRANSITION
TRENCH DRAIN
TYPICAL
URINAL
UNDERGROUND
ULTIMATE
UNFINISHED
UNLESS NOTED OTHERWISE
UTILITY
VENT, VELOCITY, VOLT
VOLT AMPERE
VACUUM
VARNISH, VARIABLE,
VOLT AMPERES REACTIVE
VAPOR BARRIER, VINYL BASE,
VALVE BOX
VERTICAL CURVE
VITRIFIED CLAY PIPE
VINYL COMPOSITION TILE,
VERTICAL CENTERLINE
VELOCITY
VENTILATION
VERTICAL
VERTICAL REINFORCING
VERTICAL GRAIN
VERIFY IN FIELD
VINYL
VOLUME
VERTICAL POINT OF CURVATURE
VERTICAL POINT OF INTERSECTION
VERTICAL POINT OF TANGENCY
VERSUS, VAPOR SEAL
VENT THROUGH ROOF
VINYL WALL COVERING
WITH
WITHOUT
WATT, WEST, WIDE, WINDOW, WIRE,
WIDE FLANGE BEAM
WOOD BASE
WATER CLOSET, WATER COLUMN
WOOD, WIDTH
WIDE FLANGE, WASH FOUNTAIN
WIRE GLASS, WATER GAGE
WALL HYDRANT, WEEP HOLE
WROUGHT IRON
WATER LEVEL
WELDED
WIRE MESH
WEATHERPROOF
WATERSTOP, WATER SURFACE
WAINSCOT
WEIGHT, WATER TIGHT
WATERPROOF, WORKING POINT
WELDED WIRE FABRIC
EXPLOSION-PROOF
EXTRA STRONG
CROSS SECTION
DOUBLE EXTRA STRONG
YARD HYDRANT
YIELD STRENGTH
GENERAL NOTES:
1. THESE ABBREVIATIONS APPLY TO THE ENTIRE SET
OF CONTRACT DRAWINGS.
2. LISTING OF ABBREVIATIONS DOES NOT IMPLY THAT
ALL ABBREVIATIONS ARE USED IN THE CONTRACT
DRAWINGS.
3. ABBREVIATIONS SHOWN ON THIS SHEET INCLUDE
VARIATIONS OF A WORD. FOR EXAMPLE, "MOD"
MAY MEAN MODIFY OR MODIFICATION; "INC" MAY
MEAN INCLUDED OR INCLUDING AND "REINF" MAY
MEAN EITHER REINFORCE OR REINFORCING.
4. SEE INSTRUMENTATION LEGEND SHEET FOR
PROJECT-SPECIFIC EQUIPMENT SYMBOLS,
EQUIPMENT ABBREVIATIONS, AND PIPING SYSTEM
ABBREVIATIONS.
ABBREVIATIONS
UPGRADE PORTALES SUBSTATION
0 1/2" 1" FILENAME OOG-01.dwg SHEET
NEW MEXICO 2014 --- SCALE AS NOTED OOG-01
D c
B
A
MATERIALS IN PLAN/SECTION
sums WffiJ 1·~:.··I ti I I I I I I I I It
11 I I 11 t .... , ... ,.,", .. ,., .. ,.,f
I I I I ... '
~SSSSSSSj
1zz:a 1111111111
R'9:@(51 I. . . ·, :<· . .... I
~«if ~ l!!!!i!!!!~!!!!!H!!!!I
IXI
IZI
ACOUSTICAL CEILING TILE (SECTION)
ASPHALT (PLAN OR SMALL-SCALE SECTION)
ASPHALT (LARGE-SCALE SECTION)
BATT INSULATION (SECTION)
BRICK MASONRY (PLAN AND/OR SECTION)
CHECKERED PLATE (PLAN)
CONCRETE (PLAN AND/OR SECTION)
CONCRETE MASONRY (PLAN AND/OR
SECTION)
DEMOLITION (PLAN AND/OR SECTION)
EARTH (SECTION)
FILTER POINT MAT (PLAN)
FINISHED WOOD (SECTION)
GLULAM LUMBER (SECTION)
GRANULAR FILL (SECTION)
GRATING (SECTION)
GRATING (PLAN)
GROUT (SECTION)
GYPSUM BOARD (SECTION)
METAL (SECTION)
ORIENTED STRAND BOARD (SECTION)
PARTICLE BOARD (SECTION)
PLYWOOD (LARGE-SCALE SECTION)
PLYWOOD (SMALL-SCALE SECTION)
PRECAST CONCRETE (PLAN AND/OR
SECTION)
RIGID INSULATION (SECTION)
RIPRAP (PLAN AND/OR SECTION)
SAND (SECTION)
SOD (SECTION)
WEEP JOINT MORTAR
PROTECTION SYSTEM (SECTION)
WOOD - CONTINUOUS (SECTION)
WOOD BLOCKING (SECTION)
2 3 4
GENERAL SYMBOLOGY
D
ARROW INDICATES
DIRECTION OF
PLAN NORTH -~
PLAN
1/4" = 1'-0"
PLAN TITLE
,,---- SECTION LETTER
FLAG INDICATES DIRECTION
OF SECTION CUT-~-
xxx ----
SHEET WHERE SECTION
IS LOCATED
SECTION CUT MARKER
SECTION
3/8" = 1'-0"
SECTION LETTER -~
SHEET WHERE
SECTION VIEW IS
FIRST CUT * _ _/
SECTION TITLE
~DETAIL NUMBER
~SHEET WHERE DETAIL
IS LOCATED *
DETAIL MARKER
N xxx
FOR REFERENCING DETAILS INCLUDED IN DRAWING SET.
( xxxxxxxxx)
DETAIL MARKER
FOR REFERENCING DETAILS BOUND IN
SPECIFICATIONS OR SEPARATE VOLUME.
DETAIL NUMBER ----.-.
DETAIL
3 11 = 1'-0"
SHEET WHERE DETAIL
WAS CALLED OUT * ---
DETAIL TITLE
.-.---ELEVATION NUMBER
----ARROW INDICATES
POINT OF VIEW
----SHEET WHERE ELEVATION
IS LOCATED *
SINGLE ELEVATION OR PHOTO MARKER
A c
B
,,,-- ELEVATION NUMBER
ARROW INDICATES POINT OF
VIEW ELEVATION
----INDICATES SHEET WHERE
ELEVATION IS LOCATED
MULTIPLE ELEVATION OR PHOTO MARKER
ELEVATION
3" = 1'-0"
ELEVATION
IDENTIFICATION
NUMBER -------..
SHEET WHERE POINT
OF VIEW MARKER CAN
BE FOUND *
ELEVATION TITLE
* EXCEPTIONS WHERE THE SHEET NUMBER IS REPLACED BY A
DASH (-).
1) FOR COMMON DETAILS, SECTIONS, ELEVATIONS OR DETAILS
THAT ARE CUT OR CALLED OUT ON MULTIPLE SHEETS.
2) SECTIONS, ELEVATIONS OR DETAILS THAT ARE LOCATED ON
THE SAME SHEET THEY ARE CUT OR CALLED OUT ON.
B 10/9/2015 100% REVIEW SUBMITTAL
A 9/15/2014 65% DESIGN SUBMITTAL
ISSUE DATE DESCRIPTION
~-TARGET ELEVATION
ARCHITECTURAL
ROOM
NAME
I xx-xx I x
< x >
ROOM NUMBER
DOOR NUMBER
COLUMN GRID LINE
WALL TYPE
WINDOW TYPE
LOUVER
ACCESSORY, FURNITURE,
AND MISCELLANEOUS
EQUIPMENT IDENTIFIER
KEY NOTE DESIGNATION M KEY NOTE NUMBER
GENERAL LINE SYMBOLOGY
---------- 4-HOUR FIRE RATED WALL
--------- 3-HOUR FIRE RATED WALL
2-HOUR FIRE RATED WALL
--- --- 1-HOUR FIRE RATED WALL
COLUMN GRID LINE/CENTERLINE
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
PROJECT NUMBER 236097
IDENTIFICATION SYMBOLOGY
PIPING
FIGURE ( 36-PLE ) EXAMPLE
LINE SIZE ------~-1_,l,__1 --- 36"
SERVICE PLANT EFFLUENT
EQUIPMENT IDENTIFICATION
ALTERNATIVE 1
I NPWP2023 I
FIGURE EXAMPLE
SERVICE ____ 1_._~l_l~l~ __ INDICATES
ABBREVIATION 11 I NON-POTABLE WATER
EQUIPMENT _
ABBREVIATION --------<>--1:---0---- INDICATES PUMP
BUILDING OR
STRUCTURE ------+--'--- BUILDING 20
NUMBER
EQUIPMENT ----------<>------PUMP 23
NUMBER
FIGURE
SERVICE
ABBREVIATION
EQUIPMENT
ABBREVIATION
ALTERNATIVE 2
jNPWP-23
1 EXAMPLE
11 I INDICATES -------e---7-1---7-1--- NON-POTABLE WATER
--------~--- INDICATES PUMP
EQUIPMENT PUMP 23 NUMBER ----------
SHEET NAMING CONVENTION
AREA DESIGNATION
TO BE EDITED ON AN A PROJECT BASIS. TO BE
DETERMINED BY THE PROJECT MANAGER, THEN ADDED TO
THE GENERAL LEGEND.
EXAMPLE:
01 BUILDING OR AREA NAME
02 BUILDING OR AREA NAME
03 BUILDING OR AREA NAME
DISCIPLINE DESIGNATOR & DISCIPLINE ORDER
G GENERAL
V SURVEYING/MAPPING
X DEMOLITION
C CIVIL
L LANDSCAPING
U MULTI-DISCIPLINE
S STRUCTURAL
A ARCHITECTURAL
D PROCESS
M MECHANICAL (HVAC)
P PLUMBING
F FIRE PROTECTION
E ELECTRICAL
Y INSTRUMENTATION
DRAWING lYPE DESIGNATOR
0 GENERAL (SYMBOLS, LEGENDS)
1 PLANS
2 ELEVATIONS
3 SECTIONS
4 LARGE SCALE VIEWS
5 DETAILS
6 SCHEDULES AND DIAGRAMS
8 PROFILES
9 3D REPRESENTATIONS
EXAMPLE
GRAVITY THICKENER ARCHITECTURAL SECTION, SHEET 01
I o I 5
AREA DESIGNATION
I A I
DISCIPLINE DESIGNATOR
I 3
SHEET TYPE DESIGNATOR
I o I 1
SHEET NUMBER
CANNON AFB
UPGRADE PORTALES SUBSTATION
0 1/2" - -
GENERAL NOTES:
1. THIS IS A STANDARD SHEET SHOWING COMMON
SYMBOLOGY. ALL SYMBOLS ARE NOT NECESSARILY
USED ON THIS PROJECT.
2. SCREENING OR SHADING OF WORK IS USED TO
INDICATE EXISTING COMPONENTS OR TO
DE-EMPHASIZE PROPOSED IMPROVEMENTS TO
HIGHLIGHT SELECTED TRADE WORK. REFER TO
CONTEXT OF EACH SHEET FOR USAGE.
GENERAL LEGEND
1" FILENAME OOG-02.dwg SHEET
--- OOG-02 NEW MEXICO 2014 SCALE NOT TO SCALE
D c
B
1 I 2 I 3
PIPING SYMBOLOGY
VALVES
SINGLE LINE DOUBLE LINE ISOLATION
--[><J---- +- I GI -+ BALL VALVE
--[><J---- +- I/I -+ BUTTERFLY VALVE
--[><Jf--- -E~f.1F:=:3-+ DIAPHRAGM VALVE
--[><Jf--- --e=3"'8<$3~3-+ GATE VALVE
--[><J---- --e=:==i&•~F:=""'*- GLOBE VALVE
--[><JI--- --e~&U:3'3 ~"'"'*- KNIFE GATE VALVE
--[><JI--- --e===:===\.yVf::=~""''*- NEEDLE VALVE
--[><JI--- --eo:=::==J:E:;!:!:~3~""''*- PINCH VALVE
--[><JI--- --e=3-I $•-i'I =:=3-+ PLUG VALVE
--e::~I CJi'~~ THREE-WAY BALL VALVE
--e==i-<I ~·-i'I =:=3-+ THREE-WAY PLUG VALVE
CONTROL
----{of-- --e=:::::'=*ICGl -+ BALL CHECK VALVE
--N --e=~f'J:i==:=:3-+ CHECK VALVE
--l·(f---- ~~-IF:=03-+ DOUBLE-DISK CHECK VALVE
-----<; <J ; +- I ..::i I -+ CONE VALVE
~OR~~
x
OR~
x
PRESSURE RELIEF VALVE
PRESSURE-REDUCING VALVE
AIR RELEASE VACUUM VALVE
A = AIR RELEASE
VAC = VACUUM
-~I--- --e=~J==:=3-+ PRESSURE-REGULATING VALVE
3-WAY CONTROL VALVE
MISCELLANEOUS
~ BACKFLOW PREVENTER
------[J,[}--- WATER METER
----1:E3: VARIABLE AREA METER
---1:1: UNION
I\) WYE-STRAINER
--(D PENETRATION THROUGH STRUCTURE
191 FLEXIBLE HOSE OR TUBING
--t\J FLEXIBLE PIPING CONNECTION
_ __,D LINE SIZE CHANGE (CONCENTRIC REDUCER)
LINE SIZE CHANGE (ECCENTRIC REDUCER)
G: LINE TURNING DOWN
0>+1---- LINE TURNING UP
-;1 BLIND FLANGE
- PIPE BREAK
NOTE:
MISCELLANEOUS SYMBOLOGY SHOWN IS FOR SINGLE-LINE
PIPING. DOUBLE-LINE PIPING SYMBOLS ARE SIMILAR.
MISCELLANEOUS
t1 tdl
Ll ----t[
----::i
---oco
HB-X
HR-X
/T/7777
FD-X
PIPE JOINT (SEE SPECS FOR
REQUIREMENTS)
COMPRESSION SLEEVE TYPE
COUPLING
FLANGED COUPLING ADAPTER
(FCA)
FLEXIBLE CONNECTION
HARNESSED MECHANICAL
COUPLING
PRESSURE GAGE (W/COCK)
TRAP
QUICK DISCONNECT
CAM & GROOVE COUPLING
CAP OR PLUG
INTERIOR CLEANOUT
HOSE VALVE, HOSE BIBB, OR
FLUSHING CONNECTION
HOSE RACK
FLOOR DRAIN
X = TYPE DESIGNATED IN SPECIFICATIONS
oBU yBu lo
PIPE IN SECTION
BELL UP (PLAN)
BELL UP (SECTION OR SCHEMATIC)
DRAIN (SECTION OR SCHEMATIC)
AIR TOOL ASSEMBLY
AUTOMATIC VALVE STATION
PRESSURE-REDUCING STATION
PLUMBING SYMBOLOGY
-------VT-------- VENT (VT)
POTABLE WATER, COLD (PWC)
POTABLE WATER, HOT (PWH)
B 10/9/2015 100% REVIEW SUBMITTAL
A 9/15/2014 65% DESIGN SUBMITTAL
ISSUE DATE DESCRIPTION
I 4 I 5
HVAC SYMBOLOGY
t t t
~24x18
C2J
Q I c--: I I
[I lj t 18x24 t t 18" DIA + f-1 R oRID +
+-(R OR(D +
f :::: 1 8 x 2 4:::: :::: :::: + t
T 9'-10" / B 9'-0"
18x10 + m
BDD
[VD,
f.__,_____t r +~,____-+ t I t tf---+-I-+ t>---+-F-+
SUPPLY AIR OR OUTSIDE AIR
DUCT UP (SECTION CUT, FIRST
DIMENSION DUCT WIDTH)
SUPPLY AIR OR OUTSIDE AIR
DUCT DOWN (NO SECTION CUT)
RETURN AIR DUCT UP (SECTION
CUT)
RETURN AIR DUCT DOWN (NO
SECTION CUT)
EXHAUST AIR DUCT UP (NO
SECTION CUT)
EXHAUST AIR DUCT DOWN
(NO SECTION CUT)
ROUND ELBOW UP
ROUND ELBOW DOWN
TRANSITION - DOUBLE SIDED
TRANSITION - ONE SIDED
TRANSITION -
RECTANGULAR TO ROUND DUCT
STANDARD BRANCH -
FOR SUPPLY AIR W/EXTRACTOR
AND RETURN AIR W/O EXTRACTOR
ELBOW - W/TURNING VANE
(RECTANGULAR)
ELBOW - W/TURNING VANES
(RECTANGULAR), SMOOTH RADIUS
GOOSENECK HOOD (COWL)
RECTANGULAR DUCT OR OPENING
SIZE - FIRST NUMBER INDICATES
SIZE OF SIDE SHOWN
ROUND DUCT SIZE
RECTANGULAR DUCT INCLINE -
RISE OR DROP IN RESPECT
TO THE AIR FLOW
ROUND DUCT INCLINE -
RISE OR DROP IN RESPECT
TO THE AIR FLOW
HIDDEN DUCT
DUCT ELEVATION TAG
ABOVE FINISH FLOOR
PRESSURE/TEMPERATURE TEST
PLUG (PETE PLUG OR EQUAL)
SOUND ATTENUATOR
SPLITTER DAMPER
VD = VOLUME DAMPER
BDD = BACKDRAFT DAMPER
MOTOR OPERATED DAMPER
FIRE DAMPER
SMOKE DAMPER
SMOKE AND FIRE DAMPER
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
PROJECT NUMBER 236097
f1--_..__I -f
SIZE nr SIZE n_EFM
SIZE
t ~~~CFM SIZE t a-LCFM
SIZE
t "'IAD + f g:)AD +
PLAN SECTION
UC 3/ 4"
AIR
FLOW
I
FLEXIBLE CONNECTION
FLEXIBLE DUCT
ACOUSTICAL LINING -
DUCT DIMENSIONS FOR NET
FREE AREA
SUPPLY AIR REGISTER OR
GRILLE - W/DUCT-MOUNTED
EXTRACTOR
EXHAUST AIR OR RETURN
AIR REGISTER OR GRILLE
EXHAUST AIR OR RETURN
AIR REGISTER OR GRILLE
SUPPLY AIR ASSEMBLY
SQUARE DIFFUSER
SUPPLY AIR ASSEMBLY
ROUND DIFFUSER
WALL LOUVER
ACCESS DOOR
UNDERCUT DOOR 3/4"
ACCESS DOOR OR
ACCESS PANEL IN
DUCTWORK
INTAKE OR
RELIEF HOOD
DOOR GRILLE
BACKDRAFT DAMPER
EXHAUST ROOF
VENTILATOR PROPELLER
OR CENTRIFUGAL TYPE
PROPELLER WALL FAN
ROOM AIR CONDITIONING
UNIT
6 I
HVAC CONTROL SYMBOLOGY
I RC I
I HOA I
EJ
--D--c s
NO
NC
TEMPERATURE CONTROLLER
TEMPERATURE TRANSMITTER
TEMPERATURE SWITCH
THERMOSTAT
TEMPERATURE INDICATOR
PERCENTAGE TIMER
RECEIVER CONTROLLER
HAND-OFF-AUTO
MOTOR STARTER
DAMPER ACTUATOR
PRESSURE INDICATOR
FREEZE STAT
FIRE STAT
DIFFERENTIAL PRESSURE
SWITCH
SMOKE DETECTOR
FLOW SWITCH
PRESSURE SWITCH
TIME DELAY
MINIMUM POSITION RELAY
SIGNAL
ANALOG OUTPUT
ANALOG INPUT
DIGITAL OUTPUT
DIGITAL INPUT
COMMON PORT
SIGNAL PORT
NORMALLY OPEN
NORMALLY CLOSED
BALANCING VALVE
I RHC I
I TA I
I TOA I
RESISTANCE HEATING CONTACTOR
INTAKE/EXHAUST LOUVER
SUPPLY, RETURN OR
EXHAUST FAN
AIR FILTER
CANNON AFB
TEST-AUTO
TEST -OFF-AUTO
ELECTRIC SIGNAL
PIPING
BULB-TYPE THERMOSTAT
UPGRADE PORTALES SUBSTATION
0 1/2" - -
I 8
AIR FLOW SCHEMATIC AND
TEMPERATURE CONTROL
DIAGRAM SYMBOLOGY
1%
VFD
H /C Ir. CAV
CHILLED WATER
COOLING COIL
HOT WATER
HEATING COIL
DIRECT EVAPORATIVE
COOLER
DIRECT EXPANSION
COOLING COIL
ELECTRIC HEATING
COIL
VFD (VARIABLE
FREQUENCY DRIVE)
CONSTANT AIR VOLUME
BOX WITH REHEAT COIL
VARIABLE AIR VOLUME
BOX WITH REHEAT COIL
MISCELLANEOUS SYMBOLOGY
GENERAL NOTES:
MIST ELIMINATOR
ACTIVATED CARBON OR
CHEMICAL FILTER
CENTRIFUGAL PUMP
SPRAY NOZZLE/HUMIDIFIER
1. THIS IS A STANDARD PROCESS, MECHANICAL AND PLUMBING
SYMBOLOGY SHEET. ALL SYMBOLS ARE NOT NECESSARILY
USED ON THIS PROJECT.
2. SCREENING OR SHADING OF WORK IS USED TO INDICATE
EXISTING COMPONENTS OR TO DE-EMPHASIZE PROPOSED
IMPROVEMENTS TO HIGHLIGHT SELECTED TRADE WORK.
REFER TO CONTEXT OF EACH SHEET FOR USAGE.
3. SEE INSTRUMENTATION LEGEND SHEET FOR PROJECT-SPECIFIC
EQUIPMENT SYMBOLS, EQUIPMENT ABBREVIATIONS, AND
PIPING SYSTEM ABBREVIATIONS.
MECHANICAL LEGEND
1" FILENAME OOG-03.dwg SHEET
--- OOG-03 NEW MEXICO 2014 SCALE NOT TO SCALE
D
1--c
0 x 0 x
) 20A OR ) 100AF
3p BOAT o o 3P
OL
D
LZJATS
I
LOW - VOLTAGE CIRCUIT BREAKER (CB).
RATINGS AND NO. OF POLES AS SHOWN.
WHEN SPECIFIC TYPE IS REQUIRED, X INDICATES
TYPE.
TYPES:
MCCB - MOLDED CASE
ICCB - INSULATED CASE
LVP - LOW - VOLTAGE POWER
MCP - MOTOR CIRCUIT PROTECTOR
(RATING PER CONNECTED LOAD)
SEPARATELY MOUNTED CIRCUIT BREAKER; SEE
ELECTRICAL ONE - LINE DIAGRAM OR
SCHEDULE FOR DESCRIPTION
GROUND FAULT PROTECTION
MEDIUM - VOLTAGE CIRCUIT BREAKER
FUSE, SIZE, AND NUMBER OF FUSES AS NOTED
FUSED CUTOUT, CURRENT RATING, FUSE SIZE,
AND NUMBER OF POLES AS NOTED
FUSIBLE SWITCH, CURRENT RATING, FUSE SIZE,
AND QUANTITY AS NOTED
NON-FUSED SWITCH, CURRENT RATING, AND
NUMBER OF POLES AS NOTED
DISCONNECT OR DRAWOUT CONNECTION
MAGNETIC MOTOR STARTER AND
SEPARATELY MOUNTED COMBINATION MAGNETIC
MOTOR STARTER
MOTOR CONTROLLER AND
SEPARATELY MOUNTED MOTOR CONTROLLER WITH
SHORT CIRCUIT PROTECTION AND DISCONNECT
MOTOR STARTER AND CONTROLLER SUBSCRIPTS:
A - MAGNETIC STARTER NEMA SIZE
B - STARTER TYPE
NONE - FULL VOLTAGE NON-REVERSING (FVNR)
FVR - FULL VOLTAGE REVERSING
2S - TWO SPEED
RVAT - REDUCED VOLTAGE AUTO TRANSFORMER
C - CONTROL DIAGRAM OR CONTROLS
SCHEDULE NUMBER (IF REQUIRED)
D - CONTROLLER TYPE
VFD - VARIABLE FREQUENCY DRIVE
SS - SOLID STATE
SEPARATELY MOUNTED COMBINATION MOTOR
STARTER OR CONTROLLER; SEE ELECTRICAL
ONE - LINE DIAGRAM OR SCHEDULE FOR
DESCRIPTION
THERMAL OVERLOAD ELEMENT
THERMAL OVERLOAD RELAY CONTACT
DISCONNECT OR SAFETY SWITCH, 30A, 3P,
NON-FUSED UNLESS OTHERWISE NOTED
MOTOR WITH DESIGN HORSEPOWER
(WHEN INDICATED)
GENERATOR
TRANSFER SWITCH, CURRENT RATING, AND
NUMBER OF POLES AS NOTED
ATS - AUTOMATIC
MTS - MANUAL
TRANSFORMER
l::.. 3-PHASE, 3-WIRE DELTA CONNECTION
'11. 3-PHASE, 4-WIRE GROUNDED WYE
CONNECTION
SWITCHBOARD OR PANELBOARD; NAME, VOLTAGE,
PHASE, NUMBER OF WIRES WHEN INDICATED
l;_;J CPT r"l --3E--t e
I
..1..
I
+ OR-t- OR -
@OR+
CD
-H l l
3 I
NON-MOTOR LOAD WITH DESIGN KVA, KW, OR
AMP
CONTROL POWER TRANSFORMER (CPT)
VOLTAGE TRANSFORMER (VT OR PT)
CURRENT TRANSFORMER (CT)
UTILITY WATT-HOUR METER PER UTILITY
REQUIREMENTS
DIGITAL METERING PACKAGE
RUN TIME METER
GROUND
LIGHTNING ARRESTER
LOW VOLTAGE SURGE PROTECTIVE DEVICE
ELECTRICAL CONNECTION
NO ELECTRICAL CONNECTION
SOLENOID VALVE
CONTROL/RELAY COIL; X INDICATES TYPE,
Y INDICATES LOOP NO. WHEN USED
TYPES:
CR - CONTROL RELAY
DP - DEFINITE PURPOSE RELAY
LC - LIGHTING CONTACTOR
M - MOTOR STARTER
PC - PHOTO CELL
TC - TIME CLOCK
TR - TIMING RELAY
NORMALLY OPEN CONTACT (N.O.)
NORMALLY CLOSED CONTACT (N.C.)
NORMALLY OPEN TIME DELAY RELAY CONTACT
WITH TIME DELAY ON CLOSING AFTER COIL IS
ENERGIZED
NORMALLY CLOSED TIME DELAY RELAY CONTACT
WITH TIME DELAY ON OPENING AFTER COIL IS
ENERGIZED
NORMALLY OPEN TIME DELAY RELAY CONTACT
WITH TIME DELAY ON OPENING AFTER COIL IS
DE-ENERGIZED
NORMALLY CLOSED TIME DELAY RELAY CONTACT
WITH TIME DELAY ON CLOSING AFTER COIL IS
DE-ENERGIZED
NORMALLY OPEN TEMPERATURE SWITCH;
CLOSE ON RISING TEMPERATURE
NORMALLY CLOSED TEMPERATURE SWITCH;
OPEN ON RISING TEMPERATURE
NORMALLY OPEN FLOW SWITCH;
CLOSE ON INCREASING FLOW
NORMALLY CLOSED FLOW SWITCH;
OPEN ON INCREASING FLOW
o----c
---0---
OFF
HAND I AUTO x xoo
I --"C"Iu oox
I 0 0 ala
---0-- -osi-01---
IZI
IZP
Q)
I I
[QJ~
lz Q 19
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
B 10/9/2015 1 00% REVIEW SUBMITTAL
A 9/15/2014 65% DESIGN SUBMITTAL
ISSUE DATE DESCRIPTION PROJECT NUMBER 236097
I
NORMALLY OPEN LEVEL SWITCH,
CLOSE ON RISING LEVEL
NORMALLY CLOSED LEVEL SWITCH,
OPEN ON RISING LEVEL
NORMALLY OPEN PRESSURE SWITCH,
CLOSE ON INCREASING PRESSURE
NORMALLY CLOSED PRESSURE SWITCH,
OPEN ON INCREASING PRESSURE
NORMALLY OPEN LIMIT SWITCH,
CLOSE ON REACHING LIMIT
NORMALLY CLOSED LIMIT SWITCH,
OPEN ON REACHING LIMIT
FIELD WIRING EXTERNAL TO CONTROL PANEL
INTERLOCK; X INDICATES TYPE
TYPES:
E - ELECTRICAL
M - MECHANICAL
K - KEY
3 POSITION SELECTOR SWITCH, MAINTAINED CONTACTS;
UNLESS OTHERWISE NOTED, 2-POSITION SIMILAR
NORMALLY OPEN PUSHBUTTON, MOMENTARY
CONTACT UNLESS OTHERWISE NOTED
NORMALLY CLOSED PUSHBUTTON, MOMENTARY
CONTACT UNLESS OTHERWISE NOTED
INDICATING LIGHT, X INDICATES LENS COLOR
PUSH TO TEST INDICATING LIGHT, X INDICATES
LENS COLOR
LENS COLORS:
R - RED
G - GREEN
B - BLUE
TRANSFORMER
SELECTOR SWITCH
PUSHBUTTON
Y - YELLOW
W - WHITE
A - AMBER
INSTRUMENTATION/CONTROL DEVICE
CONTROL PANEL INTEGRAL OR PROVIDED WITH
ASSOCIATED EQUIPMENT
CONTROL PANEL WITH DISCONNECT SWITCH INTEGRAL OR
PROVIDED WITH ASSOCIATED EQUIPMENT
JUNCTION OR PULL BOX
PANELBOARD (250V TO 600V)
PANELBOARD (LESS THAN 250V)
ELECTRICAL EQUIPMENT ENCLOSURE: SWITCHBOARD,
MOTOR CONTROL CENTER, CONTROL PANEL, OR OTHER
EQUIPMENT AS INDICATED
PHOTOCELL
CEILING/PENDANT-MOUNTED LUMINAIRE - HID,
COMPACT FLUORESCENT, OR INCANDESCENT
WALL-MOUNTED LUMINAIRE - HID, COMPACT
FLUORESCENT, OR INCANDESCENT
CEILING/PENDANT-MOUNTED FLUORESCENT
FIXTURE
WALL-MOUNTED FLUORESCENT FIXTURE
CEILING/PENDANT-MOUNTED FLUORESCENT
FIXTURE NORMAL/EMERGENCY
WALL-MOUNTED FLUORESCENT FIXTURE
NORMAL/EMERGENCY
EMERGENCY LIGHT FIXTURE, 2 ATTACHED HEADS
AS SHOWN
EMERGENCY LIGHT, REMOTE MOUNTED HEAD
I
II I II
----0
--LIGE--
6 I
DOUBLE-FACED CEILING OR WALL-MOUNTED
EXIT LIGHT; DIRECTIONAL ARROWS (IF REQUIRED)
AS INDICATED ON PLANS
SINGLE-FACED CEILING OR WALL-MOUNTED EXIT
LIGHT; DIRECTIONAL ARROWS (IF REQUIRED) AS
INDICATED ON PLANS
AREA OR ROADWAY LIGHT - POLE-MOUNTED
LIGHTING FIXTURE SUBSCRIPTS:
X - INDICATES FIXTURE TYPE PER LIGHTING
FIXTURE SCHEDULE
Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD
z - INDICATES CONTROLLING SWITCH (IF REQUIRED)
TOGGLE SWITCH
SUBSCRIPTS:
X - INDICATES TYPE
NONE - SINGLE POLE
3 - THREE-WAY
4 - FOUR-WAY
HP - TOGGLE SWITCH, HORSEPOWER RATED
K - KEY SWITCH
TE - MANUAL MOTOR STARTER WITH THERMAL ELEMENT
P - PILOT LIGHT
L - LIGHTED HANDLE
Y - INDICATES CONTROLLING SWITCH (IF REQUIRED)
SPECIAL-PURPOSE RECEPTACLE AS DEFINED ON PLANS
PLUG-IN RECEPTACLE STRIP, QUANTITY AND SPACING OF
RECEPTACLES AS NOTED OR SPECIFIED
TELECOMMUNICATIONS OUTLET JUNCTION BOX
QUAD-DUPLEX RECEPTACLE, TWO NEMA 5-20R
UNDER COMMON COVER PLATE
DUPLEX RECEPTACLE, NEMA 5-20R
SIMPLEX RECEPTACLE, NEMA 5-20R
SUBSCRIPTS:
X - INDICATES TYPE
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD
CONDUIT TURNING UP
CONDUIT TURNING DOWN
HOME RUN TO PANEL, 2 #12, 1 # 12G IN
3/ 4"C UNLESS OTHERWISE NOTED
UNDERGROUND ELECTRIC LINE
CIRCUIT RUN BETWEEN DEVICES EXPOSED IN
NON-ARCHITECTURALLY FINISHED AREAS;
CONCEALED IN ARCHITECTURALLY FINISHED
AREAS. CONDUIT AND CONDUCTOR SIZES SHALL
BE THE SAME AS THE HOMERUN FOR THE
CIRCUIT.
CONDUIT RUN BETWEEN DEVICES CONCEALED IN
NON-ARCHITECTURALLY FINISHED AREAS OR
UNDER FLOOR SLAB. CONDUIT AND CONDUCTOR
SIZES SHALL BE THE SAME AS THE HOMERUN
FOR THE CIRCUIT.
CIRCUIT HASH MARKS (WHEN INDICATED); LONG,
SHORT, SINGLE DOT, AND DOUBLE DOT
REPRESENT PHASE, NEUTRAL, EQUIPMENT
GROUND, AND ISOLATED EQUIPMENT GROUND,
RESPECTIVELY. #12 IN 3/4" CONDUIT UNLESS
OTHERWISE INDICATED.
CIRCUIT CONTINUATION
CONDUIT STUBBED OUT AND CAPPED
CONDUIT TAG OR CIRCUIT NUMBER - WIRE AND
CONDUIT SIZE AS SPECIFIED IN CIRCUIT
SCHEDULE ON THE SHEETS
GROUND CABLE
GROUND ROD
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL PANEL
FIRE ALARM MANUAL PULL STATION
CDxAND cDx
CDx
GENERAL NOTES:
I 8
FIRE ALARM CONTROL RELAY
FIRE ALARM CONTACT, FLOW SWITCH
FIRE ALARM CONTACT, TAMPER SWITCH
FIRE ALARM CONTACT, PRESSURE SWITCH
SMOKE AND DUCT DETECTOR
SUBSCRIPT:
I - IONIZATION TYPE
P - PHOTOELECTRIC TYPE
HEAT DETECTOR
SUBSCRIPT:
R/C - RATE COMPENSATION
R/F - COMBINATION RATE OF RISE
AND FIXED TEMP
R - RATE OF RISE
F - FIXED
ALARM BELL
ALARM HORN
ALARM FLASHING LIGHT
ALARM BELL AND FLASHING LIGHT
COMBINATION UNIT
ALARM HORN AND FLASHING LIGHT
COMBINATION UNIT
SUBSCRIPT:
NONE - GENERAL ALARM
DEVICE
F - FIRE ALARM DEVICE
CURRENT TRANSFORMER
SHORTING TERMINAL BLOCK
BREAKER CONTROL SWITCH
LOCAL/REMOTE CONTROL
SWITCH
POLE
1. THIS IS A STANDARD ELECTRICAL SYMBOLOGY SHEET. NOT ALL
SYMBOLS MAY BE USED ON THIS PROJECT.
2. SCREENING OR SHADING OF WORK IS USED TO INDICATE EXISTING
COMPONENTS OR TO DE-EMPHASIZE PROPOSED IMPROVEMENTS
TO HIGHLIGHT SELECTED TRADE WORK. REFER TO CONTEXT OF EACH
SHEET FOR USAGE.
3. SEE P&ID LEGEND SHEET FOR PROJECT-SPECIFIC EQUIPMENT
SYMBOLS, EQUIPMENT ABBREVIATIONS, AND PIPING SYSTEM
ABBREVIATIONS.
CANNON AFB ELECTRICAL LEGEND
UPGRADE PORTALES SUBSTATION
0 1/2" 1" FILENAME OOG-04.dwg
SHEET
2014 --- OOG-04 NEW MEXICO SCALE AS NOTED
D c
B
1 I 2 I
COMMUNICATION SYMBOLOGY
WALL MOUNTED TELEPHONE OUTLET
WALL MOUNTED DATA OUTLET
WALL MOUNTED COMBINATION TELEPHONE AND DATA OUTLET
ft++ OR [)~-
RECESSED FLOOR MOUNTED TELEPHONE OUTLET
RECESSED FLOOR MOUNTED DATA OUTLET
RECESSED FLOOR MOUNTED COMBINATION TELEPHONE AND DATA
OUTLET
ANTENNA
AUDIO/VISUAL SYMBOLOGY
I PAHE I
c::::J<l
PTZ
TELEVISION OUTLET
CEILING MOUNT SPEAKER
WALL MOUNT SPEAKER
SPEAKER SUBSCRIPTS:
X - INDICATES HEIGHT
HORN TYPE TRANSDUCER
VOLUME CONTROL
HEAD END EQUIPMENT
FLOOR MOUNTED MICROPHONE JACK
WALL MOUNTED MICROPHONE JACK
SECURllY SYMBOLOGY
DOOR POSITION SWITCH
COMBINATION ELECTRIC DOOR STRIKE AND
POSITION SWITCH
PROXIMITY CARD READER
PROXIMITY CARD READER WITH KEYPAD
DUAL TECHNOLOGY MOTION DETECTOR
REQUEST TO EXIT MOTION DETECTOR
REQUEST TO EXIT PUSH BUTION
GLASS BREAK DETECTOR
CCTV CAMERA
PAN/TILT/ZOOM WHEN INDICATED
SECURITY EQUIPMENT CABINET
REMOTE KEYPAD/CONTROL STATION
B 10/9/2015
A 9/15/2014
ISSUE DATE
1 00% REVIEW SUBMITIAL
65% DESIGN SUBMITIAL
DESCRIPTION
3 I 4
MASS NOTIFICATION SYMBOLOGY
[B:l
IMFCPI
0i1
EXTERIOR LOCATION HIGH POWER SPEAKER ARRAY
(HSPA)
LOCAL OPERATING CONSOLE
TEXT MESSAGE DISPLAY UNIT
MASS NOTIFICATION SYSTEM CONTROL PANEL
COMBINATION SPEAKER/STROBE NOTIFICATION APPLIANCE
SPEAKER NOTIFICATION APPLIANCE
STROBE NOTIFICATION APPLIANCE
CEILING MOUNTED SPEAKER
WALL MOUNTED SPEAKER
COMBINATION MASS NOTIFICATION/FIRE ALARM CONTROL
PANEL
COMBINATION MASS NOTIFICATION/FIRE ALARM SPEAKER
NOTIFICATION APPLIANCE
COMBINATION MASS NOTIFICATION/FIRE ALARM STROBE
NOTIFICATION APPLIANCE
COMBINATION MASS NOTIFICATION/FIRE ALARM STROBE
NOTIFICATION APPLIANCE
LENS:
FIRE ALARM - CLEAR
MASS NOTIFICATION - AMBER
EMERGENCY ALARM SYMBOLOGY
[Ij::> ALARM BELL
[£]<l ALARM HORN
~ ALARM FLASHING LIGHT
E£E ALARM BELL AND FLASHING LIGHT COMBINATION UNIT
IT:§ ALARM HORN AND FLASHING LIGHT COMBINATION UNIT
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
PROJECT NUMBER 236097
s I 6
CONTROL SYMBOLOGY
--Lr + OR -t- OR -1-
@OR+
CD
-H-
1 l a----c
--0--
OFF
HAND AUTO
~~ xoo -·i-- oox -
I
0 0 ala
ELECTRICAL CONNECTION
NO ELECTRICAL CONNECTION
SOLENOID VALVE
CONTROL/RELAY COIL; X INDICATES TYPE,
Y INDICATES LOOP NO. WHEN USED
1YPES:
CR - CONTROL RELAY
DP - DEFINITE PURPOSE RELAY
LC - LIGHTING CONTACTOR
M - MOTOR STARTER
NORMALLY OPEN CONTACT (N.O.)
NORMALLY CLOSED CONTACT (N.C.)
PC - PHOTOCELL
TC - TIME CLOCK
TR - TIMING RELAY
NORMALLY OPEN TIME DELAY RELAY CONTACT WITH TIME DELAY
ON CLOSING AFTER COIL IS ENERGIZED
NORMALLY CLOSED TIME DELAY RELAY CONTACT WITH TIME
DELAY ON OPENING AFTER COIL IS ENERGIZED
NORMALLY OPEN TIME DELAY RELAY CONTACT WITH TIME
DELAY ON OPENING AFTER COIL IS DE-ENERGIZED
NORMALLY CLOSED TIME DELAY RELAY CONTACT WITH TIME
DELAY ON CLOSING AFTER COIL IS DE-ENERGIZED
NORMALLY OPEN TEMPERATURE SWITCH;
CLOSE ON RISING TEMPERATURE
NORMALLY CLOSED TEMPERATURE SWITCH;
OPEN ON RISING TEMPERATURE
NORMALLY OPEN FLOW SWITCH; CLOSE ON INCREASING FLOW
NORMALLY CLOSED FLOW SWITCH;
OPEN ON INCREASING FLOW
NORMALLY OPEN LEVEL SWITCH, CLOSE ON RISING LEVEL
NORMALLY CLOSED LEVEL SWITCH, OPEN ON RISING LEVEL
NORMALLY OPEN PRESSURE SWITCH, CLOSE ON INCREASING
PRESSURE
NORMALLY CLOSED PRESSURE SWITCH, OPEN ON INCREASING
PRESSURE
NORMALLY OPEN LIMIT SWITCH, CLOSE ON REACHING LIMIT
NORMALLY CLOSED LIMIT SWITCH, OPEN ON REACHING LIMIT
MICROPROCESSOR (PLC, RTU, ETC.) OUTPUT
MICROPROCESSOR (PLC, RTU, ETC.) INPUT
FIELD WIRING EXTERNAL TO CONTROL PANEL
INTERLOCK; X INDICATES TYPE
1YPES:
E - ELECTRICAL
M - MECHANICAL
K - KEY
3 POSITION SELECTOR SWITCH, MAINTAINED CONTACTS;
UNLESS OTHERWISE NOTED, 2-POSITION SIMILAR
NORMALLY OPEN PUSHBUTION, MOMENTARY CONTACT
UNLESS OTHERWISE NOTED
NORMALLY CLOSED PUSHBUTION, MOMENTARY CONTACT
UNLESS OTHERWISE NOTED
CANNON AFB
I
----0---
OL
LLJ CPT
r"l
7 I 8
CONTROL SYMBOLOGY
INDICATING LIGHT, X INDICATES LENS COLOR
PUSH TO TEST INDICATING LIGHT, X INDICATES LENS COLOR
LENS COLORS:
R - RED
G - GREEN
B - BLUE
Y - YELLOW
W - WHITE
A - AMBER
THERMAL OVERLOAD ELEMENT
THERMAL OVERLOAD RELAY CONTACT. WHEN SHOWN X
INDICATES QUANTITY.
CONTROL POWER TRANSFORMER (CPT)
RUN TIME METER
FIRE ALARM SYMBOLOGY
®OR 0
®OR~
@ OR ~
I
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR
FIRE ALARM MANUAL PULL STATION
FLOW SWITCH
TAMPER SWITCH
PRESSURE SWITCH
CDxAND cDx SPOT AND DUCT SMOKE DETECTOR, X INDICATES TYPE
SUBSCRIPT:
I - IONIZATION
P - PHOTOELECTRIC
D - FIRE OR SMOKE DAMPER
HEAT DETECTOR
SUBSCRIPT:
R/C - RATE COMPENSATION
R/F - COMBINATION RATE OF RISE AND FIXED TEMP
R - RATE OF RISE FIXED
F -
FLAME DETECTOR
SUBSCRIPT:
IR - INFRARED
UV - ULTRAVIOLET
DOOR HOLDER
BELL
HORN/SPEAKER
FLASHING LIGHT
HORN/SPEAKER AND FLASHING LIGHT COMBINATION UNIT
BELL/SPEAKER AND FLASHING LIGHT COMBINATION UNIT
UPGRADE PORTALES SUBSTATION ELECTRICAL LEGEND
0 1/2" 1" FILENAME OOG-05.dwg SHEET
NEW MEXICO 2014 --- SCALE NOT TO SCALE OOG-05
D c
B
1 2 3
B 10/9/2015 1003 REVIEW SUBMITIAL
A 9/15/2014 653 DESIGN SUBMITIAL
ISSUE DATE DESCRIPTION
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
PROJECT NUMBER 236097
PORTALES
SUBSTATION
5 6 7 8
D c
B
\ A
CANNON AFB LOCATION PLAN
UPGRADE PORTALES SUBSTATION
NEW MEXICO 2014
O 1/2" 1" FILENAME OOG-06.dwg l"""""iiii~~lllllllllllllll~
SCALE NO SCALE
SHEET
OOG-06
SEAL GEAR BOX BASE AS
ON DETAIL 1/00A-01
INSTALL PEMKO 321SSN
NEOPRENE DOOR BOTIOM
SWEEP
EXISTING DOOR
ADD PEMKO 332SSR NEOPRENE
PERIMETER GASKETING AT INDOOR
FACE OF DOOR JAMB AND HEAD
i:, I
CJ) 0
I r---
WITH STAINLESS STEEL RETAINER-+-+-
1 '-4" w w
18'-o"
I I
EJISTING
SWITCHGEAR
I
I I I I
3 I 4-15 I 6/"1
CJ_ --J_ --J /
EXISTING
SWITCHGEAR
ACCESS ROOM
1 '-1"
INSTALL FOAM OR NEOPRENE
DECK VOID PLUGS AT THE
INTERIOR OF THE ROOF DECK
FACIA AND COPING
CLOSE THE GAP AT THE JOINT
BETWEEN THE SWITCH
GEAR ENCLOSURE AND THE STEEL
FRAME AS SHOWN ON DETAIL
A/OOA01
I ~INSTALL PEMKO 321 SSN NOPRENE v ~ DOOR BOTIOM SWEEP
EXISTING DOOR
NOTE:
~A~~-~~~~~~··~····~····~-
ADD PEMKO 332SSR NEOPRENE
PERIMETER GASKETING AT INDOOR
FACE OF DOOR JAMB AND HEAD
WITH STAINLESS STEEL RETAINER
TYPICAL SEAL ALL JOINTS AT
CORNERS, CONNECTIONS, SIDING
LAPS, HEAD AND SILL JOINTS,
DOOR FRAMES, ETC. WITH
POLYURETHANE BASED SEALANT;
SEE SPECIFICATIONS
INSTALL RETRO FIT BATI INSULATION
SYSTEM AT WALLS, R-18 MIN WITH
POLYPROPELYNE FACING
20' -5"
A
INSTALL FOAM OR NEOPRENE
DECK VOID PLUGS AT THE
INTERIOR OF THE ROOF DECK
FACIA AND COPING EXISTING BUILDING PLAN
EXTERIOR
EXISTING SWITCH
GEAR BOX--~
CONTINUOUS
POL YU RETHAN E
SEALANT @ UNIT
ANCHOR BASE
CONCRETE PAD
1/4" = 1'-0"
INTERIOR
..•. ·. . .... , .i·-.- ... ~4-.. ···~-~-- •.· .... __ .• .. , -~ ..
:·-. -~- ·.: .. . .... . •.. .;• . • . . .. ..d. '-~ .• • ..
DETAIL
1 1/2" = 1 '-0"
INSTALL FOAM OR NEOPRENE
DECK VOID PLUGS AT THE
INTERIOR OF THE ROOF DECK
FACIA AND COPING; FIELD VERIFY
PROFILE
4 5
EXISTING PRE-FINISHED FASCIA
DECK VOID PLUG-~
NEW 1 8 GAUGE BREAK METAL
CLOSURE, ANCHOR TO SWITCH
GEAR ROOF WITH SELF TAPPING
SCREWS --------~
POLYURETHANE SEALANT
BELOW CLOSURE PANEL ---~
EXISTING
SWITCHGEAR
.•.#!·.:·"'•' :111.• •.o1"~-
.. ~!' ''!.".:4·.·.:··"··.··,; .. _'·-~· .. : .. · ...... ~. 4-•
.. :4 ........ -. :
OOA-01
EXISTING BUILDING SECTION
3/4" = 1'-0"
EXISTING STRUCTURAL GIRTS,
TYP
METAL ROOF DECK, EXISTING
EXISTING
SWITCHGEAR
MAINTENANCE
ROOM
. _: .• -~ ·._ .: : :4 ' ...
R-30 BATI INSULATION
WITH STANDARD WHITE
FACING
DECK VOID PLUG
EXISTING VERTICAL
METAL SIDING
R-18 BATI INSULATION
WITH HEAVY DUTY WHITE
FACING TYP
. ·.• .· . : ~ • ·4
'.- .• i • .. ·• ·:
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
B 10/9/2015 100% REVIEW SUBMITIAL
A 9/15/2014 65% DESIGN SUBMITIAL
ISSUE DATE DESCRIPTION PROJECT NUMBER 236097
CANNON AFB
UPGRADE PORTALES SUBSTATION
NEW MEXICO 2014
0 1/2" - -
ARCHTECTURAL
PLAN AND SECTION
1" FILENAME OOA-01.dwg --- SCALE AS NOTED
SHEET
OOA-01
D c
I I
I (/) I I w a::
I I w m I I
T
T
1 2 I I
_l _l
I,,_\ I ,.j SSC-1 I ~fs\ V I ,......__\:V-.<11/ 1 E> I y '---'
I lo olo olo o I I I T-
I l
I I I
T I l
I
I
I -T--
5 6 I
_l
FACTORY PROVIDED
REMOTE THERMOSTAT "cd
J • ,,.,@
MECHHANICAL - HVAC PLAN
1I4" = 1 • -o·
I 3 I
GENERAL NOTES
1. FOR LEGEND, SYMBOLS, AND ADDITIONAL GENERAL NOTES SEE DRAWING
00-G03.
2. COORDINATE ALL WORK WITH EXISTING FIELD CONDITIONS.
3. SEE ARCHITECTURAL PLANS AND SPECIFICATIONS FOR PATCHING, PAINTING, AND
SEALANT REQUIREMENTS.
KEY NOTES
0 MOUNT UNIT AS RECOMMENDED BY MANUFACTURER TO WALL 50 INCHES
ABOVE FINISH FLOOR. PROVIDE UNISTRUT MOUNTING TO EXISTING METAL
BUILDING Z CHANNELS.
0 REFRIGERANT LINE SET THROUGH WALL. SEAL PENETRATION IN ACCORDANCE
WITH ARCHITECTURAL SPECIFICATIONS.
0 3/4" CONDENSATE LINE FROM SS-1 THROUGH WALL. ROUTE LINE DOWN TO
GROUND LEVEL. TERMINATE IN GRAVEL AREA.
© PROVIDE 4B"x48"x4" INCH SQUARE SOLID FLAT PRECAST CONCRETE SLAB WITH
#4 REINFORCING BARS 12 INCHES ON CENTER EACH WAY. SLOPE SLAB 1/4
INCH PER FOOT AWAY FROM SUBSTATION.
® MOUNT SSC-1 TO CONCRETE SLAB PER MANUFACTURER REQUIREMENTS.
VRV CONDENSING UNIT SCHEDULE
NOMINAL
#OF
CONDENSER PERFORMANCE ELECTRICAL 'PER UNIT* ENERGY EFFICIENCY BASIS OF DESIGN
MARK SERVES CAPACITY COOLING HEA11NG AIRFLOW AMB. TEMP. NOTES
(TONS)
UNITS
(MBH) (MBH) (CFM) (DEG F. DB)
MCA MOCP V/PH SEER IEER COP MANUF. MODEL
SSC-1 SS-1 2.5 1 30 34.8 2627.0 95 - 0 19.5 20 208/1 19.3 - - DAIKIN AC RXS30LVJU 1,2,3,4,5
NOTES:
1. SINGLE POINT POWER BLOCK CONNECTION REFER TO DIVISION 16 FOR DISCONNECT.
2. MOUNT UNIT ON AND SECURED TO 4" HIGH CONCRETE PAD THAT EXTENDS 4" BEYOND UNIT F0011PRINT.
3. PROVIDE LOW-AMBIENT KIT FOR EXTENDED RANGE COOLING OPERATION AND FILTER DRYER (BASED ON MANUFACTURER RECOMMENDATION).
4. PROVIDE UNIT WITH INVERTER COMPRESSOR AND R-410A REFRIGERANT.
5. PROVIDE REFRIGERANT PIPING IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS BASED ON INSTALLED DISTANCES BETWEEN OUIDOOR AND INDOOR UNITS.
VRV FAN COIL UNIT SCHEDULE
MARK
SS-1
NOTES:
SERVES UNIT TYPE AIRFLOW
(CFM)
SUBSTATION WALL MOUNT 600
MOTOR
HP
1. PROVIDE UNIT WITH FACTORY HIGH EFFICIENCY FILTER.
SPEED
SETIING
3 SPEED
FAN
MINOA
(CFM)
E.S.P. ELECTRICAL
(IN WG) VI PH I HZ MCA
208/1/60
2 PROVIDE MANUFACTURER RECOMMENDED PIPING AND CONNECTIONS FROM CONDENSER TO INDOOR FAN COIL
3. PROVIDE UNIT WITH ECM FAN AND FACTORY CONTROLLER.
4. PROVIDE UNIT WITH INTERGRAL CONDENSATE PUMP, FACTORY WIRED TO FAN COIL UNIT.
5. PROVIDE UNIT WITH WIRED WALL MOUNT THERMOSTAT FROM FACTORY.
B 10/9/2015 100% REVIEW SUBMITIAL
A 9/15/2014 65% DESIGN SUBMITIAL
ISSUE DATE DESCRIPTION
HEATING CAPACITY COOLING CAPACITY WEIGHT BASIS OF DESIGN
TOTAL BACK UP HEAT TOTAL SENS. (LBS) MANUFACTURER MODEL
(MBH) (kW) (MBH) (MBH)
34.8 - 30 19.9 38 DAIKIN AC FTXS30LVJU
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
PROJECT NUMBER 236097
I 5 I 6 I
NOTES
1,2,3,4,5
CANNON AFB
UPGRADE PORTALES SUBSTATION
NEW MEXICO 2014
0 1/2" - -
I
MECHANICAL
HVAC PLAN
1" FILENAME OOM-01.dwg --- SCALE AS NOTED
D c
B
A
OOM-01
1 2 3
OOE-07 OOE-07
TYP.
B 10/9/2015 100% REVIEW SUBMITIAL
A 9/15/2014 65% DESIGN SUBMITIAL
ISSUE DATE DESCRIPTION
SWITCH X
3-5"C
2-5"C
3-5"C
4-5"C
SEE SHEET OOE-02
FOR REQUIREMENTS
r I
I
SEC X01
SEC Y01
SEC Y02
D
2-5"C
4-4"C
PORTALES
SUB
ANTENNA POLE
SEE SHEET OOE-05
8-5"C
CONTROL l"' HOUSE
VAULT
-----r--1 1/2"C 240V STATION
POWER TO SWGR
w C) ::::l
2-5"C
CKT 12
w C) ::::l
N
2-5"C
CKT 13
1--~~---.l- UGE ---l.-fl-~~~~--cJ--~~~~-+-uGE~\--~~~.C:::J.~~~~~~~~~~uGE~~~~~~~---,±,-~-
SWITCH Y SEC 1202 SEC 1201 SEC 1301 =_____.:_~
SEC 1302
S GUNSHIP ROAD
SUBSTATION SITE PLAN
1" = 30'-o"
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES CANNON AFB
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN UPGRADE PORTALES SUBSTATION
ELECTRICAL KEVIN THERNES
PROJECT NUMBER 236097 NEW MEXICO 2014
0 1/2" - -
ELECTRICAL
SUBSTATION SITE PLAN
1" FILENAME OOE-01.dwg --- SCALE AS NOTED
D c
B
A
OOE-01
B
C
2 3 4 5 6 7 8
D
ISSUE DATE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1/2" 1"
FILENAME
SCALE
SHEET
PROJECT ENGINEER
ELECTRICAL
CANNON AFB
UPGRADE PORTALES SUBSTATION
00E-03
SWITCHGEAR ONE-LINE DIAGRAM
C p w w o r k i n g o m a d
E d w g
P
M c q u e e n
B
C
2 3 4 5 6 7 8
D
ISSUE DATE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1/2" 1"
FILENAME
SCALE
SHEET
PROJECT ENGINEER
ELECTRICAL
CANNON AFB
UPGRADE PORTALES SUBSTATION
00E-04
COMMUNICATION WIRING
SWITCHGEAR ELEVATIONS
C p w w o r k i n g o m a d
E d w g
P
M c q u e e n
SSC-1
1 2
A C/l I I I w
( "/T l l - 1 I I
_r_ 0 0
I
I
EXIST 500KCMIL
GROUND RING.
VERIFY LOCATION
GENERAL NOTE:
REPLACE ROCK GRADING AT LOCATIONS
OF NEW ELECTRICAL WORK. LEVEL
ROCK TO MATCH EXISTING.
4 5
©~ rn I 0 I I I I ,------li---1:::(} - I CJ T -- T T ,-----rr---1 -1 ACP i- , ·I' 4 5 l~~IB~ =
I T
KEY NOTES:
r;\ COOPER METALUX, DUAL BULB, \..}._/ T5,28W PART NO 4SSF2 28T5
ROOM ~
"11
WW EBT1 -U.
;;;'--. SEL-3031 RADIOS. SEE SHEET
\!:../ ODE -04.
0 1 1/2"C BELOW GRADE.
/;\ NEMA 4 PULLBOX FOR ANTENNA
\21 CABLE. BOX SIZE 16"x14"x 6"
0 WOOD POLE WITH ANTENNA.
"' 2'-0"
®" r-I'm -; ACP: 1 5 VIA PULLBOX i--Jr---ri41'{...=_:G:;,...F ACP:1,3 VIA PULLi"B;;.;;O;.;..;X __ .....,,~ SS-1
("";;\ THOROUGHLY CLEAN INSIDE OF
\'::../ SWITCHGEAR AFTER CONSTRUCTION I "" ~..-d'.
L " ~ I
1 1/2 c I I I I I 11
IS COMPLETE.
3-#14, 1 #14G
5' -0" 4'-0"
SWITCHGEAR BUILDING PLAN SECTION
1/4" = 1 '-0" 1I4" = 1 • -o"
PANELBOARD NO: AC PANEL (ACP) PANELBOARD NO: DC PANEL (DCP)
VOLTAGE: 240/120 BUS RATING (A): 100 ENCLOSURE: NEMA1 VOLTAGE: 125VDC BUS RATING (A): 100 ENCLOSURE: NEMA 1 PHASE: 1 MAIN OC DEVICE: MLO MOUNTING: SWGR PHASE: 2 MAIN OC DEVICE: 100 MOUNTING: SWGR WIRE: 3+GND INTERRUPTING RATING (KA): 10 LOCATION: PORTALES SUBSTATION WIRE: 2 INTERRUPT RA TING (KA): 10 LOCATION: PORTALES SUB
200% NEUTRAL: NO SERVICE ENTRANCE LABEL: NO
LOAD (W) OCP OCP LOAD (W)
CKT CONNECTED LOAD "'Al OCP OCP CONNECTED LOAD VAl CKT NO. DESCRIPTION LTS REC MECH MISC AMPS p AMPS P LTS REC MECH MISC DESCRIPTION NO.
CKT DESCRIPTION CONT. MAX. AMPS p AMPS P CONT. MAX. DESCRIPTION CKT
NO. DUTY DUTY DUTY DUTY NO.
1 CONDENSING UNIT 2,172 20 2 A 20 2 125VDC BAITER 2
3 SSC-1 2,172 B CHARGER 4
5 SPARE 20 1 A 20 1 1,750 SECTION 2-4 HEATERS 6
7 SECTION 1 HEATERS 500 20 1 B 20 1 1,260 SWGR RECEPTS 8
1 FROMBATIERY 30 2 A 30 2 SEL-551 CONTROL PWR
3 CHARGER B 4
5 A 6
7 52-MAIN CONTROL CKT 30 2 ~ 30 2 52-C12 CONTROL CKT -
B 8
9 SECTION 5-6 HEATERS 1,500 20 1 A 20 1 SPARE 10
11 SWGR LTS 175 15 1 B 20 1 SPARE 12
52-C 11 CONTROL CKT 30 2 ~ 30 2 52-C13 CONTROL CKT
11 B 12
13 SPARE 20 1 A 20 1 SPARE 14
15 BLDG RECEPT 360 20 1 B 20 1 SPARE 16
GE MUL TILIN A60
A
SEL-735 PQM
30 2 B 30 2
17 BLDG LTS 90 20 1 A 20 1 SPARE 18
19 SPARE 15 1 B 15 1 SPARE 20
17 A 18
SPARE 20 2 B 30 2 SEL-3530 AND SEL-3031
21 SPARE 15 1 A 15 1 SPARE 22
23 SPARE 20 1 B 15 1 SPARE 24
SPACE
A
SPACE
23 B 24
LOAD SUMMARY LOAD SUMMARY
LTS REC MECH MISC SPARE TOTAL PHASE BALANCE
CONNECTED LOAD (KVA) 0.3 1.6 4.3 3.8 --- 10.0 240 LINE-TO-LINE VOLTS PHASE A (KVA)
I
DEMAND FACTOR 1.25 NEC 1.00 1.00 20o/o --- 42 CONNECTED AMPS PHASE B (KV A) 4
DESIGN LOAD (KVA) 0.3 1.6 4.3 3.8 2.0 12.0 50 DESIGN AMPS
CONT. MAX. VOLTS
TOTAL LOAD IWl 0 0 125
TOTAL LOAD (A) 0 0
NOTES:
NOTES: 1. EXISTING LOADS TO BE FIELD VERIFIED.
1. FIELD VERIFY ALL EXISTING CONDITIONS. 2. ALL INDICATED BREAKERS ARE EXISTING.
2. ALL INDICATED BREAKERS ARE EXISTING.
PROJECT MANAGER TOM FURNE
PROJECT ENGINEER KEVIN THERNES
ARCHITECTURAL RICHARD McKINLEY
MECHANICAL RYAN ADRIAN
ELECTRICAL KEVIN THERNES
B 10/9/2015 100% REVIEW SUBMITIAL
A 9/15/2014 65% DESIGN SUBMITIAL
ISSUE DATE DESCRIPTION PROJECT NUMBER 236097
ANTENNA
35 ' WOOD POLE
KEY NOTES:
r;\ HVAC DISCONNECT, 240V, 2 POLE, \..}._/ 30A, 42" AFG
;;;'--. DUPLEX GFCI RECEPTACLE, WITH
\!:../ IN USE COVER. MOUNT 18" ABOVE
GRADE
/;"\ 2" CONDUIT TO CONTAIN ALL
\:::_/ BUILDING CIRCUITS
/;\ PROTECT BEND RADIUS OF
\21 ANTENNA CABLE BY WRAPPING
AROUND THE INSIDE OF THE
PULLBOX.
CANNON AFB
UPGRADE PORTALES SUBSTATION
NEW MEXICO 2014
I
I I
2---~------1 2--- ------
BATIERY
ROOM DRESS, SUPPORT ITWO
RADIO CABLES ALONG
BACK PANEL I
RADIOS
I
I --
--1
I ACP
I _L - -
PULLBOX 1O"x12"x6"
MIN
3/ 4"C TO LOADS
DETAIL
1/2" = 1 '-0"
SURGE I
ARRESTORS I
_L - --
SWITCHGEAR BUILDING ELECTRICAL PLAN
0 1/2" 1" FILENAME OOE-05.dwg
SHEET
- ---- SCALE AS NOTED OOE-05
D c
B
RTSP
EQUIPMENT STATUS INPUT TABLE
STATUS TO BE TRANSFERRED TO SCADA
INPUT SEL-3530 SEL-735 MAIN SEL-735 FDR C11 SEL-735 FDR C12 SEL-735 FDR C13
IN1 BATTER CHARGER FAULT SEL-551 FDR C12 FAULT
IN2 SEL-3031 FAULT
IN3 SEL-3031 FAULT
SEL-551 FDR C11 FAULT
SEL-751A FDR C11 FAULT
52C11 MOC
SEL-751A FDR C12 FAULT
52C12 MOC
SEL-551 FDR C13 FAULT
SEL-751A FDR C13 FAULT
52C13 MOC
IN4 SPARE FDR C11 L/R SWITCH IN REMOTE FDR C12 L/R SWITCH IN REMOTE FDR C13 L/R SWITCH IN REMOTE
IN5 SPARE SPARE SPARE SPARE
IN6 SPARE
SEL-551 MAIN FAULT
SEL-751A FDR MAIN FAULT
52M MOC
MAIN L/R SWITCH IN REMOTE
SPARE
SPARE SPARE SPARE SPARE
IN7 SPARE
IN8 SPARE
IN9 SPARE
IN10 SPARE
IN11 SPARE
IN12 SPARE
IN13 SPARE
IN14 SPARE
IN15 SPARE
IN16 SPARE
IN17 SPARE
IN18 SPARE
IN19 SPARE
IN20 SPARE
IN21 SPARE
IN22 SPARE
IN23 SPARE
IN24 SPARE
NOTE: FOR EXISTING RELAYS SEL-551 AND SEL-751A. COORDINATE WITH CAFB FOR DATA TO BE COMMUNICATED TO SCADA.
EQUIPMENT STATUS OUTPUT TABLE
STATUS TO BE TRANSFERRED TO SCADA
OUTPUT SEL-3530 SEL-735 MAIN SEL-735 FDR C11 SEL-735 FDR C12 SEL-735 FDR C13
OUT1 SPARE REMOTE TRIP MAIN REMOTE TRIP C11 REMOTE TRIP C12 REMOTE TRIP C13
OUT2 SPARE REMOTE CLOSE MAIN REMOTE CLOSE C11 REMOTE CLOSE C12 REMOTE CLOSE C13
OUT3 SPARE SPARE SPARE SPARE SPARE
OUT4 SPARE SPARE SPARE SPARE SPARE
OUT5 SPARE SPARE SPARE SPARE SPARE
OUT6 SPARE SPARE SPARE SPARE SPARE
OUT7 SPARE SPARE SPARE SPARE SPARE
OUT8 SPARE
A
B
C
2 3 4 5 6 7 8
D
ISSUE DATE DESCRIPTION
PROJECT MANAGER
PROJECT NUMBER
0 1/2" 1"
FILENAME
SCALE
SHEET
PROJECT ENGINEER
ELECTRICAL
CANNON AFB
UPGRADE PORTALES SUBSTATION
MECHANICAL
ARCHITECTURAL
00E-06
RELAY DIAGRAMS
TYPICAL BREAKER CONTROL AND
SEL -751A
SEL -751A
| 100% 1 |
| 100% 2 |
| 100% 3 |
| 100% 4 |
| 100% 5 |
| 100% 6 |
| 100% 7 |
| 100% 8 |
| 100% 9 |
| 100% 10 |
| 100% 11 |
| 100% 12 |
| 100% 13 |
| 100% 14 |
File details come from the government source that posted it. Updated .