Appendix_B_-_Survey_Field_Reports.pdf

PDF 6 MB Posted

Attached to
Repair Backflow Preventers Federal contract opportunity
Solicitation number
FA481918B7005
Issued by
Department of the Air Force Air Combat Command

About this file

This document was requested at the site visit. Additional questions and answers will be posted at a later time

View the file

Other files for this federal contract opportunity

Other files attached to Repair Backflow Preventers, newest first.
File Type Posted
FA481918B7005_Amendment_1.pdf PDF
Q&A.pdf PDF
Attachment_06_AF3065.pdf PDF
Attachment_02_APPENDIX_A_Repair_Backflow_Preventers.pdf PDF
Attachment_04,_AF_Form_3000.pdf PDF
Attachment_01_SOW_Repair_Backflow_Preventers.pdf PDF
Attachment_07_AF_Form_66.pdf PDF
Attachment_03_Wage_Determination.pdf PDF
Attachment_05_AF_3064.pdf PDF
FA481918B7005.pdf PDF
Attachment_1_-_DRAFT_Statement_of_Work.pdf PDF
Pre-Solicitation_Notice_-_Repair_Backflow_Preventers.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

** Install (1) ____ inch domestic RP backflow assembly - ____________ Hazzard

Assembly required on 6" Fire Riser see photo backflow assemblies

Mechanical room at rear of building

Equipment room North West corner N 30°04'23.713" W 085°35'28.546"

Mechanical room right corner of front entrance

Outside of building 486 proper mechanical room

Front planter - fed from hose bibb at side of building

**AMENDED REPORT TO ADD

RECOMMENDATIONS**

Recommend Relocating Backflow Assembly to proper height

*Amended to add recommedation*

Recommend Relocating Backflow Assembly to proper height

*Amended to add recommendation*

Install four Domestic Containment RP Backflow Assembly and three DCVA Fire

(including bypass) See Photo

DCVA

VAQ Dorm not

Right Side of Driveway/Parking Lot

Safety Shower and Eyewash inside unprotected

Assembly required, Hose Bibb at Restroom -HBVB at hose in front. No access Inside

Assembly required: 1/2" Copper line with no valve- No Fixtures outside - No Access to inside

Install one Domestic Containment (1/2" Copper Line) RP Backflow Assembly

Assembly required: Safety Shower and Eyewash inside unprotected

Install three Domestic Containment RP Devices

Assemblies

RECOMMENDATIONS: Install one DCVA Fire Backflow Assembly. Repair required: Domestic Backflow device re-mounted to accessible level.