Appendix_B_-_Survey_Field_Reports.pdf
PDF 6 MB Posted
- Attached to
- Repair Backflow Preventers Federal contract opportunity
- Solicitation number
- FA481918B7005
About this file
This document was requested at the site visit. Additional questions and answers will be posted at a later time
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA481918B7005_Amendment_1.pdf | ||
| Q&A.pdf | ||
| Attachment_06_AF3065.pdf | ||
| Attachment_02_APPENDIX_A_Repair_Backflow_Preventers.pdf | ||
| Attachment_04,_AF_Form_3000.pdf | ||
| Attachment_01_SOW_Repair_Backflow_Preventers.pdf | ||
| Attachment_07_AF_Form_66.pdf | ||
| Attachment_03_Wage_Determination.pdf | ||
| Attachment_05_AF_3064.pdf | ||
| FA481918B7005.pdf | ||
| Attachment_1_-_DRAFT_Statement_of_Work.pdf | ||
| Pre-Solicitation_Notice_-_Repair_Backflow_Preventers.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
** Install (1) ____ inch domestic RP backflow assembly - ____________ Hazzard
Assembly required on 6" Fire Riser see photo backflow assemblies
Mechanical room at rear of building
Equipment room North West corner N 30°04'23.713" W 085°35'28.546"
Mechanical room right corner of front entrance
Outside of building 486 proper mechanical room
Front planter - fed from hose bibb at side of building
**AMENDED REPORT TO ADD
RECOMMENDATIONS**
Recommend Relocating Backflow Assembly to proper height
*Amended to add recommedation*
Recommend Relocating Backflow Assembly to proper height
*Amended to add recommendation*
Install four Domestic Containment RP Backflow Assembly and three DCVA Fire
(including bypass) See Photo
DCVA
VAQ Dorm not
Right Side of Driveway/Parking Lot
Safety Shower and Eyewash inside unprotected
Assembly required, Hose Bibb at Restroom -HBVB at hose in front. No access Inside
Assembly required: 1/2" Copper line with no valve- No Fixtures outside - No Access to inside
Install one Domestic Containment (1/2" Copper Line) RP Backflow Assembly
Assembly required: Safety Shower and Eyewash inside unprotected
Install three Domestic Containment RP Devices
Assemblies
RECOMMENDATIONS: Install one DCVA Fire Backflow Assembly. Repair required: Domestic Backflow device re-mounted to accessible level.