This Statement of Work (SOW) details a fire system leak detection and repair project at Seymour Johnson Air Force Base in Goldsboro, NC. The project involves locating and repairing a leak in a 2,900-foot, 12-inch fire main line constructed of C900 and Ductile Iron, buried 3-6 feet deep and traversing grass, roads, parking lots, hangars, and aircraft taxiways. The system is pressurized at 175 psi and supplied by two 30 gpm jockey pumps and three 2,000 gpm pumps, with two buried isolation valves and five post-indicator valves (PIVs) located at various buildings. The contractor must be a professional company experienced in water system leak detection, provide all necessary materials, complete the work within the specified timeframe, and guarantee workmanship for one year, with a minimum bond requirement of $10,000.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CUI
STATEMENT OF WORK
Bldg 4511 Fire System leak
SCOPE: The work covered by the provisions of this Agreement consists of furnishing all labor, tools, equipment, and transportation necessary to find the leak and repair it in the fire system main.
Upon notification to proceed, coordinate installation/repair time with authorized Government personnel. Collecting materials from the authorized Government representative. Completing the job in accordance with all federal, state, and local codes. Prove functional operations prior to payment.
Detection and repair services specs:
- Length= 2900’
- Size = 12” line
- Line material is C900 and Ductile Iron
- Bury depth is 3’ - 6’ deep & traverses under grass/roads/parking lots/hanger/aircraft taxiways
- 175 psi line, supplied by 2ea 30 gpm jockey pumps & 3ea 2000 gpm pumps
- 2ea buried Isolation valves, 1ea near B4511and 1ea near B4535
- 5ea PIVs located at: 1ea B4535, 1ea B2151, 3ea B4522
- 1ea fire hydrant located at NE end of Bldg 4522
Repairs include but are not limited to: pipes, connectors, valves and/or all associated parts to complete the project.
OUALI FICATIONS: The contractor will be a professional company adept in finding/locating leaks in water systems.
M AT ERI AL S: The Contractor will be responsible for providing all materials for the job.
LOCATION: Work to be accomplished is at Seymour Johnson Air Force Base, Goldsboro, NC
SECURITY: All personnel will have a clean record to gain access to SJAFB.
WORK WEEK: The contractor will be required to work during normal duty hours, 0700-1600, Monday-Friday unless quite hours are required. These hours will be negotiated to be performed during a designated timeframe. After hour work can be approved by Government representative.
WORKMANSHIP: All workmanship will comply with standard trade practices. The contractor shall provide all qualified personnel, equipment, and services required to install find and repair the leak.
CLEAN UP: The contractor is responsible to return all work sites back to their original condition before the project is finished.
TIME OF PERFORMANCE: The contractor will be shown the job site and informed of the requirements. The contractor and the inspector shall agree on an estimated number of hours that it should take to complete the job. The contractor shall be available to begin work within two
(2) days from the award of contract. The government will not pay for travel time to and from the base.
WARR ANTY: The contractor will guarantee all workmanship for a period of one year from
CUI
completion of work. The contractor will be responsible for any damage to government facilities resulting from his or her work. If damages are incurred, the contractor will supply skilled craftsmen and materials to make repairs. The contractor must be bonded for a minimum of $10,000.